Algorithm
Algorithm
Research Article
ISSN 1751-8687
Algorithm for transformer differential Received on 21st September 2015
Revised on 25th April 2016
protection based on wavelet correlation Accepted on 12th May 2016
doi: 10.1049/iet-gtd.2015.1147
modes www.ietdl.org
Abstract: In this study, a new algorithm for discrimination between internal faults and inrush current conditions in power
transformers is presented. First, the proposed algorithm removes the pre-fault conditions of the fault currents. Then, those
currents are processed using the discrete wavelet transform to obtain the wavelet matrix. The correlation matrix is
computed from wavelet matrix to know the eigenvalues associated with each frequency scale and to reduce the
analysed information. This algorithm, which the authors are going to call wavelet correlation modes, is used to identify
inrush and internal fault currents in power transformer. To validate the proposed algorithm, simulations are carried out
in power systems computer-aided design software, and the obtained signals are analysed in order to evaluate its
performance and sensitivity.
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
& The Institution of Engineering and Technology 2016 2871
4 Wavelet correlation modes
If a signal f (n) is scaled up to a defined decomposition level, then, it
will be producing a wavelet matrix M(J + 1, n), this matrix is
analysed using its correlation matrix defined by [20]
M × MT
Y= (5)
n
In this way, all information will be contained into the total wavelet
3 Wavelet transform correlation matrix, so as its modes associated with each frequency
scale. Moreover, the modes are defined by the eigenvalues of the
WT is very useful for processing signals and this powerful technique wavelet correlation matrix as follows [21]
is able to provide time–frequency information about signals at
specific applications. WT has a continuous version defined by [18]
Y T = LLT (7)
1
1 t−b where L and T are the left and right eigenvector matrices,
WT(a, b) = √ t(t)c∗ dt (3)
a −1 a respectively, and Λ is the eigenvalues diagonal matrix
⎛ ⎞
l1 0 0 ··· 0
where a is the scale parameter regarding frequency, b is the ⎜0 l2 0 ··· 0⎟
translation parameter in time to the signal f (t) and ca,b(t) is the ⎜ ⎟
⎜ .. ⎟
chosen mother wavelet and * represents the operation of complex L=⎜
⎜0 0 . ··· 0⎟ ⎟ (8)
conjugate. For discrete signals, a and b parameters take discrete ⎜ . .. .. .. ⎟
values 2j and i2j, respectively. Therefore, the WT in its discrete ⎝ .. . . lr−1 . ⎠
form is defined as follows 0 0 0 0 lr
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
2872 & The Institution of Engineering and Technology 2016
Table 1 Wavelet correlation matrices produced by internal fault and inrush current
Internal fault Inrush current
3.94 × 10−1 1.05 × 10−2 −1.83 × 10−3 1.32 × 10−1 2.77 × 10−3 5.94 × 10−5 8.67 × 10−7 −4.63 × 10−4
1.05 × 10−2 1.47 × 100 −1.12 × 100 −2.12 × 101 5.94 × 10−5 6.01 × 10−2 −1.27 × 10−3 2.24 × 10−1
−1.83 × 10−3 −1.12 × 100 9.96 × 100 1.21 × 102 8.67 × 10−7 −1.27 × 10−3 8.77 × 10−1 2.21 × 10−1
1.32 × 10−1 −2.12 × 101 1.21 × 102 1.35 × 104 −4.63 × 10−4 2.24 × 10−1 2.21 × 10−1 5.17 × 102
are acquired from CTs and these are used to obtain incremental transformer ratings due to the proposed normalisation. In this
differential currents. At the second stage, incremental differential sense, the maximum inrush current can be computed as follows [23]
currents are normalised and their wavelet matrices are computed
using the DWT. At the last stage, for each incremental differential √
2U (2BN ) + BR − BS
current the wavelet correlation matrix is computed using (5), so as I pk = (9)
the total wavelet correlation matrix (6). Finally, the eigenvalues (v L )2 + R2 BN
are calculated using (7) and (8), such that the maximum
eigenvalue defines WCM value. This procedure is independent of where U is the applied voltage, L represents the air-core inductance
any frequency variation in the power network. Hence, a minimum of the transformer, R is the DC resistance of the windings, BR is the
threshold is used to detect any transient conditions; when it is remanent flux density of the core, BS represents the saturation flux
done, a second threshold must be verified with the aim to know if density of the core material and BN is the normal rated flux density
the event is an inrush or fault current. of the core.
5.2 Thresholds
5.1 Normalised signals
Energisation and fault conditions produce transient information which
In general, inrush current plays an important role during energisation is analysed for identifying the occurred transient phenomenon.
and it is related with relay settings. This current can be computed Therefore, the proposed algorithm requires a minimum threshold in
using a simplified equation [23] or estimated according to its rated order to detect a transient condition. So, the minimum threshold
current, since an inrush current may reach up to eight times the defines when there is a normal condition into the differential
rated current [24]. By this reason, incremental differential currents protection scheme. In this sense, the proposed algorithm uses a
are normalised regarding the maximum expected inrush current. minimum threshold of 0.0001 (empirical value obtained by
Therefore, the proposed algorithm can be applied to different simulation) and this is used to activate the differential protection.
Hence, to discriminate between inrush currents and internal faults,
the algorithm must be verified a second threshold. To avoid a
mis-operation into the differential protection scheme, and taken into
account that the major DC hysteresis loop of the transformer core
can reach 1.5 times its nominal flux [25]. The second threshold is
adjusted to 2, since the incremental differential currents were
normalised regarding the maximum expected inrush current.
6 Test system
7 Results
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
& The Institution of Engineering and Technology 2016 2873
Fig. 4 Test system
the studied transient phenomena. By this reason, in this paper, only analysed sceneries, the inrush currents are correctly identified by
the greatest eigenvalue produced by the total wavelet correlation the proposed algorithm, allowing the blocking of the differential
matrix is used. protection operation. In fact, seven cases are presented to evaluate
A total of 108 simulations were made considering different the performance of the proposed algorithm.
transient conditions, organised as follows: 32 transformer
energisation, 32 internal faults, 16 external faults, 16
overexcitations and 12 combined cases (modification of power 7.1 Transformer energisation
system parameters). In the whole cases, the proposed algorithm
clearly distinguishes between inrush and fault currents. The Fig. 5 presents the waveforms and algorithm performance for an
internal faults were simulated as phase-to-ground fault in wye side energisation. The saturation effects in CT’s are clearly shown at
using the transformer model of used PSCAD software. In all the primary and secondary currents of Figs. 5a and b, respectively.
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
2874 & The Institution of Engineering and Technology 2016
Fig. 6 Internal fault
a Primary currents
b Secondary currents
c Incremental differential currents
d WCM results and traditional differential protection response
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
& The Institution of Engineering and Technology 2016 2875
The incremental differential currents are shown in Fig 5c. Finally, 7.5 Change in X/R ratio of the system
the proposed algorithm results are presented in Fig. 5d, the event
is an inrush current due to the greatest eigenvalue is lower than 2. The magnitude and duration of inrush currents are affected by the
X/R ratio. In this case, the X/R ratio is modified in the Thevenin
equivalent of 115 kV. Fig. 9 shows the obtained results for a
transformer energisation with a modification on X/R ratio of 50
7.2 Internal fault over its base value. In this case, the greatest eigenvalue produces
values lower than 2; this is clearly shown in Fig. 9d, so the event
An internal fault in transformer is described in Fig. 6, where a is identified as an inrush current.
line-to-ground fault at 20% of the winding is simulated. In this
case, primary currents have higher current values than rated
current, such as it is shown in Figs. 6a and b. This condition is 7.6 Overexciting
correctly detected since the greatest eigenvalue is higher than 2
(established threshold). When the power transformer primary winding is overexciting flows
more power to the primary than the secondary side, meaning to
differential protection scheme a fault condition. This condition is
7.3 Internal fault after energisation considerated a mis-operation because the fault is not produced by
an internal fault [27]. To evaluate the algorithm performance in
In this case, a three-phase fault is simulated into the differential zone this scenario, in 200 ms was energised the power transformer and
at the secondary side 13.8 kV and one cycle after the energisation in 500 ms occurs the primary winding overexciting. It was
(200 ms). The proposed algorithm results are shown in Fig. 7, the considerate a 150% excitation value. To the traditional differential
algorithm is able to identify an internal fault under this condition; protection, when the overexciting was incepted occurs a
the fault is detected at 1.33 ms after fault inception. mis-operation as is shown in Fig. 10. By another hand, the
algorithm response is below to the threshold and the event is
identified as not fault condition as is shown in Fig. 10d.
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
2876 & The Institution of Engineering and Technology 2016
Fig. 9 Change in X/R ratio of the system
a Primary currents
b Secondary currents
c Incremental differential currents
d WCM results and traditional differential protection response
Fig. 10 Overexciting
a Primary currents
b Secondary currents
c Incremental differential currents
d WCM results and traditional differential protection response
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
& The Institution of Engineering and Technology 2016 2877
Fig. 11 Energisation and internal B-phase-fault to ground limiting the magnitude current
a Primary currents
b Secondary currents
c Incremental differential currents
d WCM results and traditional differential protection response
below than the threshold. However when the fault occurs, the results, the WCM algorithm is able to identify internal faults from
algorithm identified the event as an internal fault though the fault inrush current in a quarter of cycle and can be implemented with
magnitude was lower than the inrush current magnitude as is different transformer ratings.
shown in Fig. 11.
All simulations are analysed and it is concluded that the proposed The authors acknowledge the financial support given by the
algorithm is able to identify internal faults from inrush currents. In CONACYT (Mexico)/CONICET (Argentina) through the bilateral
this sense, inrush currents at different time of occurrence are cooperation project 189382.
analysed, so that WCM algorithm produces values of 0.1–0.8, due
to that the incremental differential currents were normalised
regarding the maximum expected inrush current.
In the same way, several internal faults are analysed and their 11 References
results are evaluated, producing higher values than the established
threshold. On the other hand, the proposed algorithm is evaluated 1 Zheng, T., Gu, J., Huang, S.F., et al.: ‘A new algorithm to avoid maloperation of
transformer differential protection in substations with an inner bridge connection’,
with external faults at both sides of the transformer; in these cases, IEEE Trans. Power Deliv., 2012, 27, (3), pp. 1178–1185
the WCM algorithm produces lower values than 0.1. Finally, the 2 Chiesa, N., Mork, B.A., Høidalen, H.K.: ‘Transformer model for inrush current
mean time detection for internal faults is equal to 3.5 ms. In calculations: simulations, measurements and sensitivity analysis’, IEEE Trans.
addition, the proposed algorithm is independent to any frequency Power Deliv., 2010, 25, (4), pp. 2599–2608
3 Lin, X., Huang, J., Zeng, L., et al.: ‘Analysis of electromagnetic transient and
variation in the power system. By this, the authors conclude that adaptability of second-harmonic restraint based differential protection of UHV
the proposed algorithm is able to identify inrush current in a power transformer’, IEEE Trans. Power Deliv., 2010, 25, (4), pp. 2299–2307
quarter of cycle and only requires a half cycle window. 4 Vazquez, E., Mijares, I.I., Chacon, O.L., et al.: ‘Transformer differential protection
using principal component analysis’, IEEE Trans. Power Deliv., 2008, 23, (1),
pp. 67–72
5 Tripathy, M., Maheshwari, R.P., Verma, H.K.: ‘Power transformer differential
9 Conclusions protection based on optimal probabilistic neural network’, IEEE Trans. Power
Deliv., 2010, 25, (1), pp. 102–112
6 Negreiros Alencara, R.J., Holanda Bezerra, U., Damasceno Ferreira, A.M.: ‘A
A new algorithm for differential protection is proposed. The method to identify inrush currents in power transformers protection based on the
algorithm uses the highest eigenvalue produced by the total differential current gradient’, Electr. Power Syst. Res., 2014, 111, pp. 78–84
wavelet correlation matrix and its results are validated in 7 Bi, D.Q., Zhang, X.A., Yang, H.H., et al.: ‘Correlation analysis of waveforms in
simulations through a test system. Furthermore, different scenarios nonsaturation zone-based method to identify the magnetizing inrush in
transformer’, IEEE Trans. Power Deliv., 2007, 22, (3), pp. 1380–1385
are analysed in order to avoid a mis-operation during inrush 8 Barbosa, D., Netto, U.C., Coury, D.V., et al.: ‘Power transformer differential
current. The algorithm takes a sliding window of half cycle and protection based on Clarke’s transform and fuzzy systems’, IEEE Trans. Power
produces good results in all simulated cases. On the basis of the Deliv., 2011, 26, (2), pp. 1212–1220
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
2878 & The Institution of Engineering and Technology 2016
9 Bejmert, D., Rebizant, W., Schiel, L.: ‘Transformer differential protection with 19 Gaouda, A.M., Salama, M.M.A.: ‘DSP wavelet-based tool for monitoring
fuzzy logic based inrush stabilization’, Electr. Power Energy Syst., 2014, 63, transformer inrush currents and internal faults’, IEEE Trans. Power Deliv., 2010,
pp. 51–63 25, (3), pp. 1258–1267
10 Saleh, S.A., Scaplen, B., Rahman, M.A.: ‘A new implementation method of 20 Hendriks, R.C., Gerkmann, T.: ‘Noise correlation matrix estimation for
wavelet-packet-transform differential protection for power transformers’, IEEE multi-microphone speech enhancement’, IEEE Trans. Audio Speech Lang.
Trans. Ind. Appl., 2011, 47, (2), pp. 1003–1012 Process., 2012, 20, (1), pp. 223–233
11 Hossam Eldin, A.A., Refaey, M.A.: ‘A novel algorithm for discrimination between 21 Hu, H., He, Z., Zhang, Y., et al.: ‘Modal frequency sensitivity analysis and
inrush current and internal faults in power transformer differential protection based application using complex nodal matrix’, IEEE Trans. Power Deliv., 2014, 29,
on discrete wavelet transform’, Electr. Power Syst. Res., 2011, 81, pp. 19–24 (2), pp. 969–971
12 Vahidi, B., Ghaffarzadeh, N., Hosseinian, S.H.: ‘A wavelet-based method to 22 Taniguchi, T., Sha, S., Karasawa, Y.: ‘Statistical distribution of eigenvalues of
discriminate internal faults from inrush currents using correlation coefficient’, correlation matrices in i.i.d MIMO channels under Rayleigh fading’. IEEE 16th
Electr. Power Energy Syst., 2010, 32, pp. 788–793 Int. Symp. on Personal, Indoor and Mobile Radio Communications, 11–14
13 Rasoulpoor, M., Banejad, M.: ‘A correlation based method for discrimination September 2005, pp. 537–541
between inrush and short circuit currents in differential protection of power 23 Girgis, R.S., teNyenhuis, E.G.: ‘Characteristics of inrush current of present designs
transformer using discrete wavelet transform: theory, simulation and of power transformers’. IEEE General Meeting Power Engineering Society, 24–28
experimental validation’, Electr. Power Energy Syst., 2013, 51, pp. 168–177 June 2007, pp. 1–6
14 Benmouyal, G., Roberts, J.: ‘Superimposed quantities: their true nature and 24 Gong, M., Zhang, X., Gong, Z., et al.: ‘Study on a new method to identify inrush
application relays’. Proc. of the 26th Annual Western Protective Relay Conf., current of transformer based on wavelet neural network’. Int. Conf. on Electrical
Spokane, WA, 26–28 October 1999 and Control Engineering (ICECE), 16–18 September 2011, pp. 848–852
15 Claude, F., Navarro, G., Ordóñez, A.: ‘The wavelet matrix: an efficient wavelet tree 25 Faiz, J., Saffari, S.: ‘Inrush current modeling in a single-phase transformer’, IEEE
for large alphabets’, Inf. Syst., 2015, 47, pp. 15–32 Trans. Magn., 2010, 46, (2), pp. 578–581
16 Zhang, W., Tan, Q., Miao, S., et al.: ‘Self-adaptive transformer differential 26 Abniki, H., Majzoobi, A., Monsef, H., et al.: ‘Identifying inrush currents from
protection’, IET Gener. Transm. Distrib., 2013, 7, (1), pp. 61–68 internal faults using symmetrical components in power transformers’. 2010 Proc.
17 Hosny, A., Sood, V.K.: ‘Transformer differential protection with phase angle of the Int. Symp. Modern Electric Power Systems (MEPS), 20–22 September
difference based inrush restraint’, Electr. Power Syst. Res., 2014, 115, pp. 57–64 2010, pp. 1–6
18 Ozgonenel, O., Karagol, S.: ‘Transformer differential protection using wavelet 27 ‘IEEE guide for protective relay applications to power transformers’, in IEEE Std.
transform’, Electr. Power Syst. Res., 2014, 114, pp. 60–67 C37.91-2000 (Revision of IEEE Std. C37.91-1985, pp. 1–85
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 12, pp. 2871–2879
& The Institution of Engineering and Technology 2016 2879