DI-M9301 Digital Single Input and Output Module

This document summarizes the features and installation of the DI-M9301 Digital Single Input and Output Module. The module has an input port that can be programmed for normally open or closed dry contacts and also as self-answering. It has an addressable design and utilizes AD sampling for input testing. The module connects to GST-M200 and GST-IFP4M fire alarm panels and has a dry contact output. It is installed using screw terminals in an electrical box or enclosure and can be mounted on a guide rail. Programming sets the input type and address using a handheld programmer.

Uploaded by

dalanruhuna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
777 views

DI-M9301 Digital Single Input and Output Module

This document summarizes the features and installation of the DI-M9301 Digital Single Input and Output Module. The module has an input port that can be programmed for normally open or closed dry contacts and also as self-answering. It has an addressable design and utilizes AD sampling for input testing. The module connects to GST-M200 and GST-IFP4M fire alarm panels and has a dry contact output. It is installed using screw terminals in an electrical box or enclosure and can be mounted on a guide rail. Programming sets the input type and address using a handheld programmer.

Uploaded by

dalanruhuna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

DI-M9301

Digital Single Input and Output Module

Features
 Input port is provided with Class B pathway Fire Alarm
supervision when connects with 4.7KΩ EOLR Equipment
47AU
(Part Number 3010786).
 Input port can be programmed to monitor either
normally open or normally closed dry contact
input.
 Input can also be programmed as
“self-answering”, which means that the Input port
monitoring is disabled, and the module will
directly send a “status” signal to FACP when the
dry-contact output changes state. Installation
 Addressable unit. Address can be programmed
in field. Warning:
 Input port utilizes AD sampling technology for Before installing the module, disconnect power
precise testing. from the loop.
 Compatible with GST-M200 and GST-IFP4M Fire 1) Before installation, make sure the enclosure is in
Alarm Control Panels (FACP). good condition and markings are complete.
 Guide rail for easy installation. 2) The module shall either be installed in a North
America standard metal electrical box. Minimum
 Standard: UL864, NFPA [70, 72]. size is 4 in. square, 2-1/8 in depth (in this case,
Description standard box cover is required), or in a UL
Signaling Listed enclosure that provides
With a microprocessor, DI-M9301 Digital Single Input minimum wiring entries and spacing as shown on
and Output Module can communicate with fire alarm Fig 2 and Fig 3. Minimum mounting space is
control panel (FACP). On receiving start command 67×40.5mm.
from the FACP, it will close the output relay and
illuminate the Active indicator.

Connection and Cabling


Terminals of the module are shown in Fig. 1.

Fig 2

Fig. 1
 (Z1, Z2) IN & OUT: Connecting with the Signaling
Line Circuit (SLC) loop of FACP, polarity
insensitive.
 I, G: Connecting with normally open dry contact
of an input device that closes when the device is
in alarm or changes state. It may also be set to
normally closed input by hand held programmer.
 COM, NO, NC: Dry contact output terminals.
 CODE: Connecting with the programmer.
Recommended Wiring: minimum 17 AWG. Subject to
local codes.

30310199 Issue 1.06


Application
The module connects with fire control devices which
are activated by the FACP.
The address and operating mode of the module can
be programmed by a programmer in field. Please refer
to P-9910B Hand Held Programmer Installation and
Operation Manual for details.
Programming Parameters:
In standby state of the programmer, press Fn and then
number 3, “—“will be popped up on the screen to
indicate it is in programming mode. Write a parameter
and then pressing “Program”, a “P” will show on the
screen meaning the parameter is programmed.
Press Fn and then number 3, input checking methods
can be set.
Parameters Setting Input
1 Self-answering
2 normally-closed
Any other normally-open
Fig. 3 numbers(Default)
Pressing Fn and 4 can set the number of addresses.
3) The module can be mounted on a guide rail as
Parameters Setting points
shown on Fig 4.
2 occupies two addresses,
4) The module can also be installed in the
one for the input and one
enclosure by 4 mounting screws as shown in
for output
Fig.5.
Any other one address for both input
numbers(Default) and output
Note: “Normally-closed” opinion can only be used for
trouble circuit, or Class E non-fire, non-emergency
input, e.g. door status sensor.

 Connection of the module to field devices with


normally open dry contact is shown in Fig. 6(line
detection is provided by the controlled device).
 Connection of the module to devices controlled
by 24VDC is shown in Fig.7 (line detection is
provided by the controlled equipment).
FACP

FACP

Z1 Z1
Fig. 4 Z2 Z2

Z1 Z2 Z1 Z2

DI-M9301 DI-M9301
I G NO COM NC I G NO COM NC
Control Control
Feedback 4.7kΩ Input Feedback 4.7kΩ Input

Controlled Device Controlled Device

a b

Fig. 6
Power +24V Power +24V
Fig. 5 GND GND
Z1
FACP Z1 FACP
Z2 Z2

Z1 Z2 Z1 Z2
DI-M9301 DI-M9301
I G NO COM NC I G NO COM NC

4.7kΩ 4.7kΩ

Controlled Device Controlled Device

a b

Fig. 7

30310199 Issue 1.06


Specification Accessories and Tools
Operating Loop 24VDC(16VDC - 28VDC) Model Name Remark
Voltage Power Limited
Standby Current ≤ 0.28mA P-9910B Hand Held Supplied
Programme separately
Action Current Loop ≤ 0.7mA r
Output Capacity: 2A @ 30 VDC, 0.35PF. RY-1W-4.7k±5% End-of-Line Provided
Output Control Relay normally open/normally Resistor
Way closed contact input
Programming Electronically addressing Limited Warranty
Initiating circuit 25Ω each wire
maximum line GST warrants that the product will be free from defects
impedance in design, materials and workmanship during the
Address Range Two options preset by warranty period. This warranty shall not apply to any
manufacturer: product that is found to have been improperly installed
or used in any way not in accordance with the
Option 1: Both Input and Output instructions supplied with the product. Anybody,
occupy one address that ranges including the agents, distributors or employees, is not
from 1 to 242. in the position to amend the contents of this warranty.
Please contact your local distributor for products not
Option 2: Occupy two addresses covered by this warranty.
representing Input and Output.
Input address range is 1 to 241.
Output address is automatically
programmed as input address
plus 1.
LED Input LED: Red. It lights in
receiving feedbacks, lights 0.5s
on, 0.5s off in input faults, and
flashes in other states.
Output LED: Red. It lights in
relay action, turns off in other
states.
Ingress IP30 (not tested by UL)
Protection Rating
Operating 0℃ - +49℃
Temperature
Relative Humidity ≤ 93%,Non Condensing
Materials of the ABS, white(RAL9016)
Enclosure
Dimension 85.3mm×78mm×33mm ( with
((L×W×H) base)
Weight About 66.5g (with base)

This Data Sheet is subject to change without notice. Please contact GST for more information or questions.

Gulf Security Technology Co., Ltd.


No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
[email protected] www.gst.com.cn

30310199 Issue 1.06