Conventional Reflective Beam Detector: Technical Specifications

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Conventional

Reflective Beam
Detector C-9105R
With built-in intelligent microprocessor, the
detector has strong ability of analysis and
judgment. The detector is ideally suited to
historical buildings, warehouses, large
storages, shopping malls, leisure centers,
exhibition halls, hotel lobbies, printing
houses, clothing factories, museums and
prisons, as well as places where slight
smoke particles or corrosive gas exist.

Technical Specifications
• Standards: BS EN54 Part-12
• Protection Rating: IP20*
(IP 66 thru glue seal)
• Operating Voltage
Power Voltage: 24Vdc (±10%)
Loop Voltage: 24Vdc
• Operating Current
Features and Benefits Standby current: 12mA
Alarm current: 22mA
1. Wide monitoring area, range 8-100 • Length of Optical Pathway:
metres o 8-100meter
2. Combination of the emitting and • Monitoring width: 14m
receiving parts makes mounting easy • Monitoring Area: 1400m²
and optical pathway accurate • Commissioning Tools: Magnet
3. Simple and cost effective to install • Operating Temperature:
transmitter and reflective ‘honey -10°C to +50°C
comb’ mirror. • Relative humidity: 95%
4. Quick and easy to set up visual • Application: Indoor use
strength indication. • Material and Colour: ABS, Gray
5. Build-in microprocessor • Wiring: 1 pair -24Vdc, 1pair- loop
6. Self-diagnosis function can monitor • Dimensions:206mmX95mmX95mm
the inner fault.
7. Automatic compensation for factors
weakening received signals, such as
dust contamination, positional
excursion and ageing transmitter.
8. SMT processing technology Indication of Detector State:
9. Attractive and decent appearance
Commission: Green LED and Yellow LED
are lit or flash in a certain way.
Description
Normal monitoring state: Red LED
C-9105R Conventional Reflective Beam flashes periodically (with loop connected)
Detector is an addressable reflective infrared Fire: Red LED constantly illuminates, and
beam smoke detector that can be directly Yellow LED turns off. The fire signal has
connected to a fire alarm controller, by to be cleared by the controller
transmitting status information via bus Fault: Yellow LED constantly illuminates.
between the detector and controller. The
detector must be used together with a
reflector. The number of reflector(s) to be
used (one or four) depends on the distance
from the detector.
Conventional
Reflective Beam
Detector C-9105R

Wiring and Connection


Connect the wires to the required terminal
according to the wire diagram. The D1,D2
is for 24VDC power supply. The K11,k12 for
fire alarm output contact (passive). The
cable must be fire rated and the size
depends on the distance and application.
The minimum size gauge 1.0mm²

FIRE ALARM
OUTPUT
CONTACT
(TO FACP) TO POWER SUPPLY
24VDC

K22 K21K12 K11 D1 D2

Mounting the Detector


Selection of compatible Control Panels
The detector can be mounted in 2 ways: the
installed onto standard two gang electrical Compatible with all GST Intelligent Fire
box, or directly by drilling the holes and Alarm Panels GST 200, GST 5000, GST
fixing with plugs. 9000 with interface module. Compatible
with all GST Conventional Fire Alarm
Control panel

Ordering Information:
Part No Description Weight Pack
/Kg Qty
per
Box
C-9105R Conventional 1.3 10
Reflector Beam
Detector

MANUFACTURED IN ACCORDANCE WITH

Note: Specifications are subject to change without notice.