Lab 3
Lab 3
Power, P (W) 54 53 50
Table 1
1) Calculate the average value of Z, R and X (Zmean, Rmean, Xmean). These values are the model
value.
Phase 1.
𝑉𝑘 19.0
Z= = 4.98 = 3.82 Ω
𝐼𝑘
𝑃 54
R = 𝐼² = = 2.18 Ω
4.98²
Phase 2.
𝑉𝑘 17.8
Z= = 4.98 = 3.57 Ω
𝐼𝑘
𝑃 53
R = 𝐼² = = 2.14 Ω
4.98²
𝑉𝑘 18.5
Z= = 4.99 = 3.71 Ω
𝐼𝑘
𝑃 50
R = 𝐼² = = 2.01 Ω
4.99²
Thus,
2) Determine the real line length, L in km by the aid of the calculated XMODEL in (1) and the
predetermined impedance scale stated in the theory previously. Then, compare with the
transmission length the Line Model MV 1420 is representing. (Given the real line reactance, X is
0.40 Ω/phase/km)
(3.04)(17.5)
L= = 133 𝑘𝑚
0.4
From real line specification the ‘Long’ length is 136km, but the measurement we got is L = 133km.
The large difference in them is due to the line impedance and load impedance. If the load
impedance is equal to the line impedance, then given any signal source connected will produce the
exact impedance and will have the exact amount of current drawn from it regardless the line length.
So, in conclusion we could not get the right amount is due to different value of impedance.
3) Determine the cross-section area of the copper for the real line by the aid of the calculated
RMODEL in (1), calculated line length, L in (2) and the predetermined impedance scale in the theory
previously. (Given the copper resistivity of the real line, ρ is 0.0017 Ω mm2/m or 17 Ω mm2/km).
Then, round off to the nearest standard value and choose a suitable area from the series:
16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400 mm2.
𝜌𝐿 (17)(133)
A =17.5𝑅𝑚𝑜𝑑𝑒𝑙 = (17.5)(2.11)
= 61.23𝑚𝑚²
Table 2
∑ 𝐼𝑐𝑚
Mean of 𝐼𝑐𝑚 = 3
1.58+1.56+1.58
𝐼𝑐𝑚 = 3
𝐼𝑐𝑚 = 1.57𝐴
∑ 𝐼𝑐𝑒
Mean of 𝐼𝑐𝑒 = 3
0.61+0.60+0.61
𝐼𝑐𝑒 = 3
𝐼𝑐𝑒 = 0.61𝐴
2) Calculate the mutual capacitance of the real line by using the following equation if the rated
voltage is 77kV.
Also calculate the mutual inductance per kilometre, cm and compare with the value previously
mentioned in the theory.
1.57(20)
𝐶𝑚 = 77𝑥103 (2𝜋)(50)
𝐶𝑚 = 1.298𝜇𝐹
𝐶𝑚
𝑐𝑚 =
𝐿
1.298𝑥10−6
𝑐𝑚 =
136
𝑐𝑚 = 9.544𝑛𝐹/𝑘𝑚
The value 9.544nF/km is slightly bigger than the theoretical value given of 9.5nF/km probably due
to the approximation method used by the transmission model for simplicity of depicting the
transmission line.
3) Calculate the earth capacitance of the real line by using the following equation if the rated
voltage is 77kV.
0.61(20)
𝐶𝑒 = 77𝑥103 (2𝜋)(50)
𝐶𝑒 = 504.335𝑛𝐹
Experiment 2: Voltage Drop of the Line.
pf = 1.0 IT, A 1A 2A 3A
Table Part A
Table Part B
Table Part C
Discussion.
1) Based on Graph 1, VR in part B is decreasing while VR in part C is the only one increasing
compare to the other part resulting in a maximum charging current at that instant in time.
VR vs IT
135
130
125
Voltage (V)
120
Resistive
115
Capacitive
110 Inductive
105
100
0 0.5 1 1.5 2 2.5 3 3.5 4
Current (A)
Graph 1
2) Based on Graph 2, voltage regulator in part A is between 2.5 to 7.5 while voltage regulator in
part B is between 3.8 to 11.5 and voltage regulator for part C is between 0.7 to 2.0 which is closer
to zero hence is more stable the secondary voltage and the better the regulation it will provide.
%VR vs IT
14
12
10
Voltage regulation (%)
6
Resistive
4
Capacitive
2
Inductive
0
0 0.5 1 1.5 2 2.5 3 3.5 4
-2
-4
-6
Current (A)
Graph 2
4)
a) When XL is larger XC, the circuit turned inductive which the voltage lead current by 90°.
b) When XC is larger than XL, the circuit become capacitive which the current leads voltage by
90°.
c) When XC is equal to XL, the point at which this occurs is called the Resonant Frequency point
where a series RLC circuit this resonance frequency produces a Series Resonance.