Design Calculation of Precast Wall
Design Calculation of Precast Wall
A. Wind Pressure
Kz 1.56
Kzt 1.0
Kd 0.85
V 200
Iw 1.0
q 47.3 10
6 Kz KztKd V2 Iw
q 2.509
P q GCp q i GCpi
GCp1 0.75
GCp2 0.75
GCpi1 0.18
GCpi2 0.18
P1 q GCp1 q GCpi1
P1 0.749
P2 q GCp1 q GCpi2
P2 3.015
P3 q GCp2 q GCpi1
P3 3.015
P4 q GCp2 q GCpi2
P4 0.749
Use
P max P1 P2 P3 P4
P 3.015
B. Design of Wall Thickness
For members subject to shear and failure:
Panelwidth 2550
Panelheight 8400
Dbeam 4200
Lunsupported Panelheight Dbeam
Lunsupported 4200
fc 27.58
fy60 414
fy40 276
b 1000
t 150
t
d
2
1 fc b d
Vc
3
6 10
Vcallowable
Vc 65.646
Shear due to gravity:
Vg 24
t Panelwidth
1000 Lunsupported 10
3
1000
Vg 38.556
Since Vcg < Vc, shear design is okay.
Shear due to wind:
Vcw 0.75P Lunsupported 10 3
Vcw 9.496
Since Vcw < Vc, shear design is okay.
Thickness of precast wall is t = 150 mm
C. Design of Wall Reinforcement Due to Wind
wu P Panelwidth 10 3
wu 7.687
Vertical Bar:
wu Lunsupported2
Mu 1.6
8
7
M u 2.712 10
Mu
Rn
2
0.9 Panelwidth d
Rn 2.101
fy60
m
0.85 fc
m 17.66
1 2 m Rn
rho 1 1
m fy60
rho 0.00532
A s rho Panelwidth d
3
A s 1.018 10
rho min 0.001
A smin rho min Panelwidth t
A smin 382.5
Therefore
A srequired max A s A smin
3
A srequired 1.018 10
diav 12
s v 275
Panelwidth
diav
2
Asprovided
4 sv
A sprovided 1048.721
Since As(provided) > As(required), vertical bars provided are adequate.
Horizontal Bar:
rho m 0.001
A shorizontal rho m 1000 t
A shorizontal 150
diah 10
s h 300
1000
diah
2
A sprov
4 sh
A sprov 261.799
Since As(provided) > As(required), horizontal bars provided are adequate.
D. Design for Wall Connection (Wind)
Shear on Dowel
Precast wall panel area
Ac 10.725
Vrequired P Ac
Vrequired 32.331
d v 16
s v 1255
2
Vprovided 0.40 d v fy60
Panelwidth
10
3
4 sv
Vprovided 67.653
Since V(provided) > V(required), shear design is okay.
Steel Anchor Plate due to Bending:
Fpanel 1000
Pu 1.2
D
N
3
Pu 9.969 10
M Pu d
N - mm
5
M 7.477 10
fb 0.60Fysteel
Mpa
fb 148.8
thickness check,
1
3
Thickness
M 12
fb Lweld
mm
Thickness 7.011
Panelwidth 24
Vcweight Panelheight t
2 1000
10001000
KN
Vcweight 38.556
Design Moment,
t Panelheight Panelheight
24
1000
10001000
Mu 1.4
8
KN - m
Mu 44.453
Mu 1000 1000
Rn
tt
0.9 Panelwidth
4
Rn 3.443
fy40
mLift
0.85 fc
mLift 11.773
1
2 mLift Rn
2
1 1
1
rhoLift
mLift fy40
mm
rhoLift 0.014
t
As1 rhoLift Panelwidth
2
mm2
3
As1 2.593 10
rhomin 0.001
diameter 12
spacing 300
2 Panelwidth
Asprovided ( diameter)
4 spacing
mm2
Asprovided 961.327
Parameters:
Mpa
fc 20.7
Mpa
fy 276
mm
Width 5100
mm
Length 4200
mm
Thk 125
mm
Vertbar 12
mm
Horbar 10
Thk
UDL 24
1000
KN/m
UDL 3
Mx:
Mx 0.0107UDL
Width 2 Length
10001000 1000
KN-m
Mx 3.507
Resisting Section:
mm
3
15Thk 1.875 10
mm
Width 3
2.55 10
2
A min 15Thk
Width
2
mm
3
A 1.875 10
A
Mx1 Mx
1000
KN-mm
Mx1 6.575
2
MxperM Mx
Width
1000
KN-m
MxperM 1.375
My:
My 0.0107UDL
Length
2 Width
1000
10001000
KN-m
My 2.888
Resisting Section:
mm
Thk
62.5
2
Thk
My1 My
2 1000
KN-m
My1 0.18
2
MyperM My
Length
1000
KN - m
MyperM 1.375
1
fc 2
Allow 5 1 0.0069
0.0069
Mpa
Allow 1.89
2 1
Sx Width Thk
6
mm3
7
Sx 1.328 10
2 1
Sy Length Thk
6
mm3
7
Sy 1.094 10
Capacity Check:
0.001
acty MyC
Sy
3
1000
Mpa
acty 0.126
WeightX:
Length
Wtx 24 Thk
10001000
KN/m
Wtx 12.6
P due to Weightx:
Width
P1 Wtx
2 1000
KN
P1 32.13
( 0.207Width
Wtx )
Vax
1000
KN
Vax 13.302
Vbx P1 Vax
KN
Vbx 18.828
( 0.586Width Wtx )
Vcx Vbx
1000
KN
Vcx 18.828
Vdx Vcx P1
KN
Vdx 13.302
OBTAIN MAXIMUM:
KN
VmaxX 18.828
Width
Max 0.5 Vax 0.207
1000
KN-m
Max 7.021
KN-m
Mbx 7.046
KN-m
Mcx 7.021
KN-m
MmaxX 7.046
Weight due to y:
Width
Wty 24 Thk
10001000
KN/m
Wty 15.3
P due to Weightx:
Length
P2 Wty
2 1000
KN
P2 32.13
( 0.207Length
Wty )
Vay
1000
KN
Vay 13.302
Vby P2 Vay
KN
Vby 18.828
( 0.586Length Wty )
Vcy Vby
1000
KN
Vcy 18.828
Vdy Vcy P2
KN
Vdy 13.302
VmaxY max( Vay Vby Vcy Vdy )
KN
VmaxY 18.828
Length
May 0.5 Vay 0.207
1000
KN-m
May 5.782
KN-m
MmaxY 5.803
mm Concrete cover
cc 40
Sling Angle:
s 60
( Thk cc Horbar)
ecc
2
mm
ecc 37.5
ds ecc
mm
ds 37.5
VmaxX
Px
tan s
180
KN
Px 10.87
VmaxY
Py
tan s
180
KN
Py 10.87
Moment:
ecc
Mxs Px
1000
KN-m
Mxs 0.408
ecc
Mys Py
1000
KN-m
Mys 0.408
Total Moment:
Check Stresses:
MxT 0.001
xtotal
Sx
3
1000
Mpa
xtotal 0.561
MyT 0.001
ytotal
Sy
3
1000
Mpa
ytotal 0.568
allowable>x or y
Reinforcement:
Prod 1.5
6
MxUlt MxT Prod 1.7 10
Nmm
7
MxUlt 1.901 10
6
MyUlt MyT Prod 1.7 10
Nmm
7
MyUlt 1.584 10
Nmm
7
MaxUlt 1.901 10
Get k:
1
2
2 MaxUlt
0.9
Ksteel 1 1
2
0.85 fc ecc 1000
Ksteel 1 0.841i
Zone
Ca 0.4
ap 1.0
Ip 1.0
Rp 3.0
Bottom Elevation:
m
hb 239.63
Top Elevation:
m
ht 243.63
Roof Height:
m
HR 248.025
Hu ht 0.305
m
Hu 243.325
Hb hb 0.305
m
Hb 239.935
1 3
Ca ap Ip Hu
Fpu
Rp HR
Fpu 0.526
1 3
Ca ap Ip Hb
Fpb
Rp HR
Fpb 0.52
KN
Fpseismic 33.609