Building Code2
Building Code2
MYANMAR
NATIONAL
BUILDING
CODE
2012
PART2
ARCHITECTURE AND URBAN DESIGN
MYANMAR NATIONAL BUILDING CODE 2012
PART 1 ARCHITECTURE AND URBAN DESIGN
TABLE OF CONTENTS
Gymnasiums
Indoor swimming pools
Indoor tennis courts
Lecture halls
Libraries
Museums
Places of religious worship: Pagodas, Temples, Churches, Mosques, etc.
Pool and billiard parlours
Waiting areas in transportation terminals, etc.
A-4 Assembly uses intended for viewing of indoor sporting events and activities with
spectator seating including:
Arenas
Skating rinks
Swimming pools
Tennis courts, etc.
A-5 Assembly uses intended for participation in or viewing outdoor activities including:
Amusement park structures
Grandstands
Stadiums, etc.
2.1.4 Business (Group B)
2.1.4.1 General
Business occupancy includes, among others, the use of a building or structure, or a portion
thereof, for office, professional or service-type transactions, including storage of records and
accounts. Business occupancies shall include the following:
Airport traffic control towers
Ambulatory health care facilities
Veterinary
Banks
Barber and beauty shops
Car wash
Clinic-outpatient
Dry cleaning and laundries: pick-up and delivery stations and self-service
Electronic data processing: public internet access centre
Laboratories: testing and research
Motor vehicle showrooms
Post offices
Print shops
Professional services (architects, attorneys, dentists, physicians, engineers, etc.)
Radio and television stations
Telephone exchanges
Training and skill development not within a school or academic program, etc.
2.1.4.1 Definitions
The following words and terms shall, for the purposes of this section and as used elsewhere in
this code, have the meanings shown herein.
CLINIC, OUTPATIENT. Buildings or portions thereof used to provide medical care on less
than a 24-hour basis to individuals who are not rendered incapable of self-preservation by the
services provided.
2.1.5 Educational (Group E)
Educational occupancy includes, among others, the use of a building or structure, or a portion
thereof, by six or more persons at any time for educational purposes of the basic education
and higher education. Assembly areas of Group E occupancy having more than 50 occupant
loads are considered as Group A-3 occupancy. Religious educational rooms and religious
auditoriums, which are accessory to places of religious worship in accordance with assembly
portion and have occupant loads of less than 50, shall be classified as A-3 occupancies.
Educational occupancies shall include the following:
Basic Education Schools
Day care
Universities and Colleges
Vocational Training Centres, etc.
2.1.5.1 Definitions
The following words and terms shall, for the purposes of this section and as used elsewhere in
this code, have the meanings shown herein.
DAY CARE: The use of a building or structure, or portion thereof, for educational,
supervision or personal care services for more than five children older than 2 1/ 2 years of age
shall be classified as a Group E occupancy.
2.1.6 Factory and Industrial (Group F)
2.1.6.1 General
Factory Industrial occupancy includes, among others, the use of a building or structure, or a
portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing,
packaging, repair or processing operations that are not classified as a Group H hazardous or
Group S storage occupancy.
2.1.6.2 Factory industrial F-1 moderate-hazard occupancy
Factory industrial uses which are not classified as Factory Industrial F-2 Low Hazard shall be
classified as F-1 Moderate Hazard and shall include the following:
Aircraft (manufacturing, not to include repair)
Appliances
Athletic equipment
Automobiles and other motor vehicles
Bakeries
Beverages: over 16-percent alcohol content
Bicycles
Boats
Brooms or brushes
Business machines
Cameras and photo equipment
Canvas or similar fabric
Carpets and rugs (includes cleaning)
Clothing
Construction and agricultural machinery
Disinfectants
Dry cleaning and dyeing
Electric generation plants
Electronics
Engines (including rebuilding)
Food processing
Furniture
Fibrous products
Jute products
Laundries
Leather products
Machinery
Metals
Millwork (sash and door)
Motion pictures and television filming (without spectators)
Musical instruments
Optical goods
Paper mills or products
Photographic film
Plastic products
Printing or publishing
Recreational vehicles
Refuse incineration
Shoes
Soaps and detergents
Textiles
Tobacco
Trailers
Upholstering
Woodworking (cabinet, etc.)
Wood; distillation, etc.
2.1.6.3 Factory industrial F-2 low-hazard occupancy
Factory industrial uses that involve the fabrication or manufacturing of non combustible
materials which during finishing, packing or processing do not involve a significant fire
hazard shall be classified as F-2 occupancies and shall include the following:
Beverages: up to and including 16-percent alcohol content
Brick and masonry
Ceramic products
Cottage industries
Foundries
Glass products
Gypsum
Ice
Metal products (fabrication and assembly), etc.
2.1.6.4 Myanmar private industrial enterprises
As for classification of Myanmar private Industrial enterprises, shall be limited to the 1990
Private Industrial Enterprises Law for small, medium and large industries are shown in
Appendix (2.1.6.4).
2.1.7 High Hazardous (Group H)
The architectural aspects in designing of hazardous building should be referred to Part 5 Building
Services, Fire Protection of this building code.
2.1.8 Institutional (Group I)
2.1.8.1 General
Institutional Group I occupancy includes, among others, the use of a building or structure, or
a portion thereof, in which people are provided for public service facilities and cared for or
live in a supervised environment, having physical limitations because of health or age are
harboured for medical treatment or other care or treatment, or in which people are detained
for penal or correctional purposes or in which the liberty of the occupants is restricted.
Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4.
Correctional Centres
Detention Centres
Jails
Prisons, etc.
Buildings of Group I-3 shall be classified as one of the occupancy conditions indicated as
following:
2.1.8.4.1 Condition 1
This occupancy condition shall include buildings in which free movement is allowed
from sleeping areas, and other spaces where access or occupancy is permitted, to the
exterior via means of egress without restraint. A Condition 1 facility is permitted to be
constructed as Group R.
2.1.8.4.2 Condition 2
This occupancy condition shall include buildings in which free movement is allowed
from sleeping areas and any other occupied smoke compartment to one or more other
smoke compartments. Egress to the exterior is impeded by locked exits.
2.1.8.4.3 Condition 3
This occupancy condition shall include buildings in which free movement is allowed
within individual smoke compartments, such as within a residential unit comprised of
individual sleeping units and group activity spaces, where egress is impeded by remote-
controlled release of means of egress from such a smoke compartment to another smoke
compartment.
2.1.8.4.4 Condition 4
This occupancy condition shall include buildings in which free movement is restricted
from an occupied space. Remote-controlled release is provided to permit movement from
sleeping units, activity spaces and other occupied areas within the smoke compartment to
other smoke compartments.
2.1.8.4.5 Condition 5
This occupancy condition shall include buildings in which free movement is restricted
from an occupied space. Staff-controlled manual release is provided to permit movement
from sleeping units, activity spaces and other occupied areas within the smoke
compartment to other smoke compartments.
2.1.8.5 Group I-4 day care facilities under 2 and half years
This group shall include buildings and structures occupied by persons of any age who receive
custodial care for less than 24 hours by individuals other than parents or guardians, relatives
by blood, marriage or adoption and in a place other than the home of the person cared for.
2.1.8.5.1 Adult care facility
A facility that provides accommodations for less than 24 hours for more than five
unrelated adults and provides supervision and personal care services shall be classified as
Group I-4.
Exception: A facility where occupants are capable of responding to an emergency
situation without physical assistance from the staff shall be classified as Group R-3.
Wax candles
2.1.11.3 Low-Hazard storage (Group S-2)
Group S-2 includes, among others, buildings used for the storage of non-combustible
materials such as products on wood pallets or in paper cartons with or without single
thickness divisions; or in paper wrappings. Such products are permitted to have a negligible
amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall
include the following:
Asbestos
Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers
Cement in bags
Chalk and crayons
Dairy products in non waxed coated paper containers
Dry cell batteries
Electrical coils
Electrical motors
Empty cans
Food products
Foods in non-combustible containers
Fresh fruits and vegetables in non plastic trays or containers
Frozen foods
Glass
Glass bottles, empty or filled with non-combustible liquids
Gypsum board
Inert pigments
Ivory
Meats
Metal cabinets
Metal desks with plastic tops and trim
Metal parts
Metals
Mirrors
Oil-filled and other types of distribution transformers
Parking garages open or enclosed
Porcelain and pottery
Stoves
Talc and soap stones
a) There shall be not more than 10 doctors in one joined consultation room.
b) There shall be physical separation between the paediatric clinics and the general
clinics.
c) There shall be physical separation between the gynecological clinics and the general
clinics, however paediatric clinics and the gynecological clinics can be combined.
d) The floor area of waiting room in a consultation unit shall be calculated based on the
number of consultants. This shall be minimum of 200 sq.ft. per consultant.
e) The egress and the escape routes must be in conformity with chapters 6 of this code.
f) There shall be minimum of one toilet for 15 waiting chairs.
2.2.2 Educational Buildings
2.2.2.1 Groupings and class rooms
The number of children in each group for respective ages and levels and required minimum
floor areas must conform to the following norms, unless otherwise define in the concerned
educational authorities.
Table 2.1 Groupings and Floor Area Requirements in the Class Rooms for Respective Levels
Primary classes, first grade to 4th grade 25 children 25 sq-ft per child
Middle classes, fifth grade to eight grade 40 children 20 sq-ft per child
All class rooms must have additional storage space for common properties of the class. For
nurseries and kindergartens: there should be separate space for play areas and rest/sleeping
areas. For all classes: The maximum width of all class rooms should not exceed 35 feet. Class
rooms must have window areas which are not less than 15% of the floor areas and window
sill heights must be not less than 3ft. And the railing height must be inconformity with section
2.5.6.3. Class rooms’ heights must be minimum 9 ft. All class rooms must be connected with
covered corridors or passages.
2.2.2.2 General requirements
All education building must have assembly areas which should hold at least 50% of all
children with minimum floor areas of 7 sq.ft per child. For urban schools, ample parking
space and delivery of children must be considered. There should be rooms for teachers with
maximum eight teachers in one room and at least 80 sq-ft per teacher. There should be
separate toilet facilities for teachers and children and the toilets for the students must be able
to check the misuse of drugs and other illicit activities. All schools must have schools library
and computer facilities. All schools must have space for facilities of physical education,
handicraft and domestic science education for the children. In addition to the open space
requirements of this chapter there should be play ground around 20,000 sq-ft for all schools
with more than 500 children.
2.2.2.3 Open space requirements
The requirements for open spaces of respective norms are as the following table 2.2.2.
Table 2.2 Open Space Requirements for Respective Levels
Primary classes, first grade to 4th grade 15 sq-ft per 10 sq-ft per
child child
Middle classes, fifth grade to eight grade 20 sq-ft per 10 sq-ft per
child child
b) Buildings need not comply with the provisions of this section when they totally
comply with other applicable provisions of this code.
2.2.3.2 Definitions
The following words and terms shall, for the purposes of this chapter and as used elsewhere in
this code, have the meanings shown herein.
ANCHOR BUILDING. An exterior perimeter building of a group other than H having direct
access to a covered mall building but having required means of egress independent of the
mall.
COVERED MALL BUILDING. A single building enclosing a number of tenants and
occupants, such as retail stores, drinking and dining establishments, entertainment and
amusement facilities, passenger transportation terminals, offices and other similar uses
wherein two or more tenants have a main entrance into one or more malls. For the purpose of
this chapter, anchor buildings shall not be considered as a part of the covered mall building.
The term" covered mall building" shall include open mall buildings as defined below.
Mall. A roofed or covered common pedestrian area within a covered mall building that serves
as access for two or more tenants and not to exceed three levels that are open to each other.
The term "mall" shall include open malls as defined below.
Open mall. An unroofed common pedestrian way serving a number of tenants not exceeding
three levels. Circulation at levels above grade shall be permitted to include open exterior
balconies leading to exits discharging at grade.
Open mall building. Several structures housing a number of tenants, such as retail stores,
drinking and dining establishment. entertainment and amusement facilities, offices, and other
similar uses, wherein two or more tenants have a main entrance into one or more open malls.
For the purpose of Chapter 4 of the International Building Code, anchor buildings are not
considered as a part of the open mall building.
FOOD COURT. A public seating area located in the mall that serves adjacent food
preparation tenant spaces.
GROSS LEASABLE AREA. The total floor area designed for tenant occupancy and
exclusive use. The area of tenant occupancy is measured from the center lines of joint
partitions to the outside of the tenant walls. All tenant areas, including areas used for storage,
shall be included in calculating gross leasable area.
2.2.3.3 Lease plan
Each covered mall building owner shall provide both the building and fire departments with a
lease plan showing the location of each occupancy and its exits after the certificate of
occupancy has been issued. No modifications or changes in occupancy or use shall be made
from that shown on the lease plan without prior approval of the building official.
2.2.3.4 Means of egress
Each tenant space and the covered mall building shall be provided with means of egress as
required by Chapter 6, Means of Egress.
2.2.3.5 Mall width
For the purpose of providing required egress, malls are permitted to be considered as
corridors but need not comply with the requirements of Chapter 6, Means of Egress of this
code where the width of the mall is as specified in this section.
a) The automatic sprinkler system shall be complete and operative throughout occupied
space in the covered mall building prior to occupancy of any of the tenant spaces.
Unoccupied tenant spaces shall be similarly protected unless provided with approved
alternative protection.
b) Sprinkler protection for the mall shall be independent from that provided for tenant
spaces or anchors. Where tenant spaces are supplied by the same system, they shall
be independently controlled.
2.2.3.9.1 Standpipe system
The covered mall building shall be equipped throughout with a standpipe system as
required by Part 5, Building Services (Fire).
2.2.3.10 Smoke control
Where a covered mall building contains an atrium, a smoke control system shall be provided.
Exception: A smoke control system is not required in covered mall buildings when an atrium
connects only two stories.
2.2.3.11 Kiosks
Kiosks and similar structures (temporary or permanent) shall meet the following
requirements:
a) Combustible kiosks or other structures shall not be located within the mall unless
permitted by the Part 5, Building Services (Fire).
b) Kiosks or similar structures located within the mall shall be provided with approved
fire suppression detection devices.
c) The minimum horizontal separation between kiosks or groupings thereof and other
structures within the mall shall be 20 feet (6096 mm).
d) Each kiosk or similar structure or groupings thereof shall have a maximum area of
300 square feet (28 m2).
e) There shall be no function in the kiosks with open flame.
2.2.3.12 Children's playground structures
Structures intended as children's playgrounds that exceed 10 feet (3048 mm) in height and
150 square feet (14 m2) in area shall comply with Covered mall and Open mall Buildings
Sections.
2.2.3.12.1 Materials
Children's playground structures shall be constructed of non-combustible materials.
2.2.3.12.2 Fire protection
Children's playground structures located within the mall shall be provided with the same
level of approved fire suppression and detection devices required for kiosks and similar
structures.
2.2.3.12.3 Separation
Children's playground structures shall have a minimum horizontal separation from other
structures within the mall of 20 feet (6090 mm).
Exception: Two connections to the same main shall be permitted provided the main is
valued such that an interruption can be isolated so that the water supply will continue
without interruption through at least one of the connections.
2.2.4.3 Emergency systems
The detection, alarm and emergency systems of high-rise buildings shall comply with Part 5,
Building Services.
2.2.4.3.1 Standby power
A standby power system complying with Part 5, Building Services.
2.2.4.4 Means of egress and evacuation
The means of egress in high-rise buildings shall comply with Chapter 6, Means of egress.
2.2.4.5 Elevators and escalators
Elevator and escalators installation and operation in high-rise buildings shall comply with
Part 5, Building Services.
2.2.4.6 Smoke removal
To facilitate smoke removal in post-fire salvage and overhaul operations, buildings and
structures shall be equipped with natural or mechanical ventilation for removal of products of
combustion in accordance with one of the following:
a) Easily identifiable, manually operable windows or panels shall be distributed around
the perimeter of each floor at not more than 50-foot (15 240 mm) intervals.
b) The area of operable windows or panels shall not be less than 40 square feet (3.7 m2)
per 50 linear feet (15 240 mm) of perimeter.
Exceptions:
1) In Group R occupancies, each sleeping unit or suite having an exterior wall shall
be permitted to be provided with 2 square feet (0.19 m2) of venting area in lieu of
the area specified in Item 1.
2) Windows shall be permitted to be fixed provided that glazing can be cleared by
fire fighters.
3) Mechanical air-handling equipment providing one exhaust air change every 15
minutes for the area involved. Return and exhaust air shall be moved directly to
the outside without recirculation to other portions of the building.
4) Any other approved design that will produce equivalent results.
2.2.4.7 Helipad
Provision of space for helipad on roof top shall be considered if required, and shall comply
with Part 3 structure and part 5 Building Services.
2.2.4.8 Swimming pool and roof garden
Provision of space for swimming pool and roof garden inside the building or roof top shall be
considered if required and shall comply with Part 3 structure and Part 5, Building Services.
2.2.5 Atriums
2.2.5.1 General
The provisions of this section shall apply to buildings or structures containing vertical
openings defined herein as "Atriums."
2.2.5.1.1 Definition
The following word and term shall, for the purposes of this chapter and as used elsewhere
in this code, have the meaning shown herein.
ATRIUM. An opening connecting two or more stories other than enclosed stairways,
elevators, hoist ways, escalators, plumbing, electrical, air-conditioning or other
equipment, which is closed at the top and not defined as a mall. Stories, as used in this
definition, do not include balconies within assembly groups or mezzanines that comply
with Mezzanines Section, Chapter 3, General Building Heights and Areas.
2.2.5.2 Use
The floor of the atrium shall not be used for other than low fire hazard uses and only
approved materials and decorations in accordance with Part 5, Building Services (Fire) shall
be used in the atrium space.
Exception: The atrium floor area is permitted to be used for any approved use where the
individual space is provided with an automatic sprinkler system in accordance with Automatic
Sprinkler Systems, Part 5, Building Services (Fire).
2.2.5.3 Automatic sprinkler protection
An approved automatic sprinkler system shall be installed throughout the entire building.
2.2.5.4 Fire alarm system
A fire alarm system shall be provided in accordance with Part 5, Building Services (Fire).
2.2.5.5 Smoke control
A smoke control system shall be installed in accordance with Part 5, Building Services (Fire).
Exception: Smoke control is not required for atriums that connect only two stories.
2.2.5.6 Enclosure of atriums
Atrium spaces shall be separated from adjacent spaces by a 1-hour fire barrier constructed in
accordance with Part 5, Building Services (Fire).
2.2.5.7 Standby power
Equipment required to provide smoke control shall be connected to a standby power system
in accordance with Part 5, Building Services (Fire).
2.2.6 Underground Buildings
In the third phase, the details of this section will be described depending on the resources’
availability.
2.2.7 Motor-Vehicle-Related Occupancies
In the third phase, the details of this section will be described depending on the resources’
availability.
2.2.8 Motion Picture Projection Rooms
In the third phase, the details of this section will be described depending on the resources’
availability.
Residential 2 (R-2) 5 50 ft
Hostels Walk up Apt,
etc.
Residential 3(R-3) 3 36 ft
Low –rise , detached
houses, single family
(Individual lots/units)
Residential 4(R-4)/ 3 36 ft
Residential care,
assisted living
NOTE:
For purposes of the Code, all buildings proposed for construction shall be classified according
to the following types; and should also link with Part 3, Structure.
a) Type I - shall be of wood construction. The structural elements may be any of the
materials permitted by this Code.
b) Type II - shall be of wood construction with protective fire-resistant materials and
one-hour fire-resistive throughout, except, that permanent non-bearing partitions may
use fire- retardant treated wood within the framing assembly with one-hour
resistivity.
c) Type III - shall be of masonry and wood construction. Structural elements may be
any of the materials permitted by this Code provided, that the building shall be one-
hour fire-resistive throughout. Exterior walls shall be of incombustible fire-resistive
construction.
d) Type IV - shall be steel, iron, concrete, or masonry construction and walls, ceiling
and permanent partitions, shall be of Incombustible fire- resistive construction,
except, that permanent non-bearing partitions of one-hour fire-resistive construction
may use fire- retardant treated wood within the framing assembly. ,
e) Type V - shall be fire-resistive. The structural elements shall be of steel, iron,
concrete, or masonry construction. Walls, ceilings and permanent partitions shall be
of incombustible fire-resistive construction.
Establishing Grade
a) In case of sloping grade where the building footprint running perpendicular to the
Road right of way (RROW) has a difference in elevation of less than 3.00 meters, the
highest adjoining natural grade (ground surface) or finished grade (sidewalk surface)
shall be considered the established grade elevation;
b) In case of sloping grade where the edges of the building footprint turning
perpendicular to the RROW has a difference in elevation of more than 3.00 meters,
the average grade level of the building footprint shall be considered the established
grade elevation ; and
c) The building/structure height shall be measured from the highest adjoining public
sidewalk (finished grade) or ground surface (natural grade); Provided, that the height
measured from the lowest adjoining surface shall not exceed such maximum height
by more than 3.00 meters; Except, that towers, spires and steeples, erected as parts of
the building and not used for habitation or storage are limited as to the height only by
structural design, if completely of incombustible materials, or may extend but not
exceed 6.00 meters above the prescribed building height limit (BHL) for each
occupancy group, if of combustible materials
d) Maximum of sixty (60) storeys (5900 ft or 180.00 meters) for inland areas not close
to airports.
2.3.5 Mixed Use and Occupancy
Buildings or parts of buildings that contain two or more occupancies or uses are classified as
mixed use. This section applies to mixed use occupancy and the buildings that they occupy. The
first subject of this section cover incidental uses that must comply with this section, the only
exceptions are incidental use areas that serve as a dwelling or living space that do not have to
comply with this section. An incidental use area must be classified in accordance with the
occupancy of that portion of the building in which it is located or the building must be classified
as a mixed occupancy and will comply with this section.
Where the code allows an automatic fire-extinguishing system without a fire barrier, the
incidental use area must be separated from the rest of the building by construction that is capable
of resisting smoke from passing through the building. The partitions must extend from the floor to
the underneath of the fire-resistance-rated floor/ceiling assembly or fire-resistance-rated
roof/ceiling assembly above or to the bottom of the floor or roof sheathing or sub deck above.
Doors must be self-closing or automatic closing when the detection of smoke is made. Doors also
must not have any air transfer openings and cannot be undercut in excess of the clearance that is
permitted in Fire Services Department. With some exceptions, no separation is required between
accessory occupancies and the main occupancy. Where an automatic fire-extinguishing system or
automatic sprinkler system is provided, only the incidental use areas need to be equipped with this
system.
2.3.6 Equipment Platforms
Equipment platforms in buildings cannot be considered as a portion of the floor below and must
not contribute to either the building area or the number of stories as regulated by this chapter, and
may also not use the area of the equipment platform to determine the fire area. Equipment
platforms cannot be part of any mezzanine and these platforms and walkways, stairs, and ladders
that provide access to an equipment platform cannot be used as an exit from the building either.
There are some area limitations that you must be aware of.
The total area of all equipment platforms within a room cannot be larger than two-thirds of the
area of the room which they are in. If the equipment platform is located in the same room as a
mezzanine, the area of the mezzanine must be determined by this chapter and the combined total
area of the room that they are in. If a mezzanine is in a building that is required to have an
automatic sprinkler system, equipment platforms must be fully protected by these sprinklers
above and below the platform.
Width must be at least 20 feet. Where the value of width varies along the perimeter of the
building, the calculation performed in accordance with Equation 5.1 must be based on the
weighted average of each part of the exterior wall and open space where the value of “W” is
greater than or equal to 20 feet. When “W” is more than 30 feet, a value of 30 feet must be used in
calculating the weighted average, regardless of the actual width of the open space. The exception
being that the quantity of “W” divided by 30 must be permitted to be a maximum of two when the
building meets all requirements of this chapter except for compliance with the 60-foot public way
or yard requirement, if applicable. These open spaces must be either on the same lot or dedicated
for public use and must be accessed from a street or approved fire lane.
a) The automatic sprinkler system increase cannot apply to buildings with an occupancy in
Group H-1.
b) The automatic sprinkler system increase must not apply to the floor area of occupancy in
Group H-2 or H-3. For mixed-use buildings containing these occupancies, the allowable
area must be calculated in accordance with this book, with the sprinkler increase applying
only to the portions of the buildings not classified as Group H-2 or H-3.
2.3.7 Height Determination for Sky Terrace Floors
For developments with sky terrace floors, the overall height control will be relaxed, based on the
proposed storey height of the development. The additional allowable height over and above the
overall aggregate height for the development is tabulated:
Propose story height of Additional height allowable over the overall aggregate
development height for developments with sky terrace levels
7- 20 10.0m or 32.8 ft
41- 50 25.0m or 82 ft
NOTE:
a) A sky terrace floor refers to a floor where the sky terrace areas within the 45-degree line
occupy at least 60% of the floor plate, and is used for sky terrace and other communal
purposes.
b) This additional height can only be distributed to sky terrace floors within the
development.
c) Spaces for M&E services located directly beneath the sky terrace floor can also be
included under the additional height. Drop-panels are not allowed at the soffit along the
perimeter of sky terrace floors, as the intention is to encourage the provision of high
volume open communal spaces.
Figure 3.1 Illustration on the Relaxation of the Overall Aggregate Heights for
Developments with Sky Terrace Floors
The illustration is shown as a guideline of a typical 12-storey commercial development that has an
overall aggregate height of 60.0m based on 5.0m maximum floor-to-floor height for each floor,
can enjoy an additional height of 10m, if the development includes at least one sky terrace floor.
1) The wall or glass separating the interior ofthe building from the pedestrian
walkway shall be protected by an automatic sprinkler system and the sprinkler
system shall completely wet the entire surface of interior sides of the wall or glass
when actuated;
2) The glass shall be in a gasketed frame and installed in such a manner that the
framing system will deflect without breaking (loading) the glass before the
sprinkler operates; and
3) Obstructions shall not be installed between the sprinkler heads and the wall or
glass.
b) The distance between the connected buildings is more than 10 ft (3048 mm) and both
sidewalls of the pedestrian walkway are at least 50 percent open with the open area
uniformly distributed to prevent the accumulation of smoke and toxic gases.
c) Buildings are on the same lot.
d) Where exterior walls of connected buildings are required to have a fire-resistance rat-
ing greater than 2 hours, the walkway shall be equipped throughout with an automatic
sprinkler system installed.
e) The previous exception shall apply to pedestrian walkways having a maximum height
above grade of three stories or 40 ft (12 192 mm), or five stories or 55 ft (16 764 mm)
where sprinklered.
2.4.4.6 Public way
The installation of a pedestrian walkway over a public right-of-way shall be subject to the
approval of the applicable concerned Authority. The vertical clearance from the public right-
of-way to the lowest part of a pedestrian walkway shall be 15 ft (4572mm) minimum.
2.4.4.7 Egress
Access shall be provided at all times to a pedestrian walkway that serves as a required exit.
2.4.4.8 Width
The unobstructed width of pedestrian walkways shall not be less than 36 inches (914 mm).
The total width shall not exceed 30 ft (9144 mm).
2.4.4.9 Tunneled walkway
Separation between the tunneled walkway and the building to which it is connected shall not
be less than 2 hour fire-resistant construction and openings therein shall be protected.
2.4.5 Awnings and Canopies
2.4.5.1 General
Awnings or canopies shall comply with the requirements of this section and other applicable
sections of this code.
2.4.5.2 Definitions
The following term shall, for the purposes of this section and as used elsewhere in this code,
have the meaning shown herein.
AWNING. An architectural projection that provides weather protection, identity or
decoration and is wholly supported by the building to which it is attached. An awning is
comprised of a lightweight frame structure over which a covering is attached.
2.4.6.6 Construction
A marquee shall be supported entirely from the building and constructed of noncombustible
materials. Marquees shall be designed as required in Part 3, Structural Design. Structural
members shall be protected to prevent deterioration.
2.4.6.7 Public way
If it is allowed to construct in the public right-of-way by the concerned authority, marquees
with less than 15 ft (4572 mm) clearance above the sidewalk shall not extend into or occupy
more than two-thirds the width of the sidewalk measured from the building. Stanchions or
columns that support awnings, canopies, marquees and signs shall be located not less than 2 ft
(610 mm) in from the curb line.
2.4.7 Signs
2.4.7.1 General
A sign shall not be erected in a manner that would confuse or obstruct the view of or interfere
with exit signs required by means of egress or with official traffic signs, signals or devices.
Within Conservation Zones and designated historic areas, signage and materials must comply
with the local planning guidance intended to conserve and enhance the built environment.
Commercial, advertising billboards will not be permitted in Conservation Zones, designated
historic areas and landscape or sites affecting their broader setting. Signs shall not be erected,
constructed or maintained so as to obstruct any fire escape or any window or door or opening
used as a means of egress or so as to prevent free passage from one part of a roof to any other
part thereof. A sign shall not be attached in any form, shape or manner to a fire escape, nor be
placed in such manner as to interfere with any opening required for ventilation. Signs and
sign support structures, together with their supports, braces, guys and anchors, shall be kept in
repair and in proper state of preservation. The display surfaces of signs shall be kept neatly
painted or posted at all times.
Signs which are written in any foreign language shall have a corresponding translation in
English or in Myanmar. No sign or signboard shall be constructed as to unduly obstruct the
natural view of the landscape, distract or obstruct the view of the public as to constitute a
traffic hazard, or otherwise defile, debase or offend aesthetic and cultural values and
traditions. The installation of all kinds of signs shall be such that a harmonious and aesthetic
relationship of all units therein is presented.
2.4.7.2 Definitions
For the purpose of this Section, the following definitions shall apply.
ADVERTISING SIGN. Any surface or structure with characters, letters or illustrations
applied thereto and displayed in any manner whatsoever out of doors for purposes of
advertising or to give information regarding or to attract the public to any place, person,
public performance, article or merchandise whatsoever, and which surface or structure is
attached to, forms part of or is connected with any building, or is fixed to a tree or to the
ground or to any pole, screen, fence or hoarding or displayed in space.
BANNER SIGN. A sign utilizing a banner as its display surface.
CANOPY SIGN. A sign affixed to the visible surface(s) of an attached or freestanding
canopy.
CLOSED SIGN. An advertising sign in which at least more than fifty percent of the area is
solid or tightly enclosed or covered.
COMBINATION SIGN. A sign that is supported partly by a pole and partly by a building
structure.
DIRECTION SIGN. Usually included with an arrow and used for indicating a change in route
or confirmation to a correct direction.
ELECTRIC SIGN. An advertising sign in which electric fittings, which are an integral part of
the signs, are used
FREESTANDING SIGN. A sign principallysupported by a structure affixed to the ground,
and not supported by a building, including signs supported by one or more columns, poles or
braces placed in or upon the ground.
GROUND SIGN. An advertising sign detached from a building, and erected or painted on the
ground or on any pole, screen, fence or hoarding and visible to the public.
IDENTIFICATION SIGN. A sign that gives specific location information, identifies specific
items, for example, Parking Lot B, Building No. 5, First Aid, etc.
ILLUMINATED SIGN. An advertising sign, permanent or otherwise, the functioning of
which depends upon its being illuminated by director indirect light, and other than an electric
sign.
INFORMATIONAL SIGN. Used for overall information for general organization of a series
of elements that is, campus plan, bus route, building layout, shopping mall plan, etc.
MARQUEE SIGN. An advertising sign attached to or hung from a marquee canopy or other
covered structure projecting from and supported by the building and extending beyond the
building wall, building line.
OPEN SIGN. An advertising sign in which at least fifty percent of the enclosed area is
uncovered or open to the transmission of wind.
PORTABLE SIGN. Any sign not permanently attached to the ground or to a building or
building surface.
PROJECTING SIGN. An advertising sign affixed to any building element and projecting
more than 300 mm therefrom.
REGULATORY SIGN. Sign that gives operational requirements, restrictions or gives
warnings, usually used for traffic delineation or control, for example ‘stop’, ‘No parking’,
‘one Way’, etc.
ROOF SIGN. An advertising sign erected or placed on or above the parapet or any portion of
a roof of a building including signs painted on the roof of a building.
SKY SIGN. An advertising sign displayed in space like:
a) a gas filled balloon anchored to a point on the ground and afloat in the air with or
without a streamer of cloth, etc; or
b) sky-writing, that is, a sign or word traced in the atmosphere by smoke discharged
from an aeroplane.
SIGN. Any device visible from a public place that displays either commercial or non-
commercial messages by means of graphic presentation of alphabetic or pictorial symbols or
representations. Noncommercial flags or any flags displayed from flagpoles or staffs shall not
be considered as signs
f) Placement of sign should be avoided where they may conflict with pedestrian
traffic.
g) Sign should be placed to allow safe pedestrian clearance vertically and latterly.
h) Braille strips may be placed along sign edges or raised letters may be used for
readability for the blind and partially sighted.
i) No sign shall be attached in anyway to a tree or shrub.
j) The signs other than pertaining to building shall not be permitted to come in front
of buildings such as hospitals, educational institutions, public offices, museums,
buildings devoted to religious worship and buildings of national importance.
2.4.7.5.4 Materials
Materials for construction of signs or sign structures shall be of the quality and grade as
specified in Part 6, Building Materials. Exceptions will be made in respect of sign in
conservation zones, where they will conform to the planning guidance for each zone.
2.4.7.5.4.1 Use of combustibles
Wood or plastic or other ‘materials of combustible characteristics similar to wood
may be used for mouldings, cap pings, nailing blocks, letters and latticing where
permitted and for other purely ornamental features of signs. Sign facings may be
made of approved combustible materials provided the area of each face is not more
than 108 sq-ft (10 sq-m) and the wiring for electric lighting is entirely enclosed in
metal conduit and installed with a clearance of not less than 2 in (5 cm) from the
facing material.
2.4.7.5.4.2 Glass in signs
All glass used in advertising signs, other than glass tubing used in gas discharge or
similar signs, shall be of safety glass conforming to accepted standards at least 3 mm
thick. Glass panels in advertising signs shall not exceed 64.58 sq-ft (6 sq-m) in area,
each panel being securely fixed in the body of the sign independently of all other
panels. Glass signs shall be properly protected from the possibility of damage by
falling objects by the provisions of suitable protecting metal canopies, or by other
approved means. Use of glass may be discouraged or avoided wherever possible for
signs placed overhead.
2.4.7.5.5 Traffic control interference
No advertising sign shall be erected or maintained which interferes with or is likely to
interfere with any sign or signal for the control of traffic. No advertising sign shall be
placed particularly in bends and curves so as to obstruct the view of traffic at intersecting
streets.
2.4.7.5.6 Draining of signs
Adequate provision for drainage shall be made in every advertising sign, where the
possibility of collection of moisture exists.
2.4.7.5.7 Animated devices
Signs which contain moving section or ornaments shall have fail-safe provisions to
prevent the section or ornaments from releasing and falling or shifting its centre of gravity
more than 18 in (450 mm). The fail-safe device shall be in addition to the mechanism and
its housing which operate the movable section or ornament. The fail-safe device shall be
capable of supporting the full dead weight of the section or ornament when moving
mechanism releases.
2.4.7.6 Electric signs and illuminated signs
2.4.7.6.1 Material for electric signs
Every electric sign shall be constructed of non-combustible material except where the
sign is purely a flood-lit sign.
2.4.7.6.2 Installation of electric signs and illuminated signs
Every electric sign and illuminated sign shall be installed in accordance with Part 5,
Building Services (Electrical and Allied Installations).
2.4.7.6.3 Colour
No illuminated sign in red, amber or green colour shall be erected or maintained within a
horizontal distance of 32.8 ft (10 m) of any illuminated traffic sign.
2.4.7.6.4 Height
All advertising signs illuminated by light other than a white light at height of less than
two storeys or 20 ft (6 m) above the ftpath, whichever be the greater height, shall be
suitably screened so as to satisfactorily prevent any interference with any sign or signal
for the control of traffic.
2.4.7.6.5 Intense illumination
No person shall erect any sign which is of such intense illumination as to disturb the
residents in adjacent or nearby residential buildings. Not with standing any permission
given for such erection, any such sign which after erection is, in the opinion of the
Authority, of such intense illumination as to disturb the occupants of adjacent or nearby
buildings shall, on the order of the Authority, be suitably altered or removed by the owner
of the site concerned within such reasonable period as the Authority may specify.
2.4.7.6.6 Hours of operation
No electric sign, other than those necessary in the opinion of the Authority in the interest
of public amenity, health and safety, shall be operated between midnight and sunrise.
2.4.7.6.7 Flashing, occulting and animated
No flashing, occulting or animated advertising signs, the periodicity of which exceeds 30
flashes to the minute, shall be erected so that the lowest point of such signs is less than 30
ft (9 m) above the ground level.
2.4.7.7 Ground signs
2.4.7.7.1 Material
Every ground sign exceeding 20 ft (6 m) in height together with frames, supports and
braces shall be constructed of non-combustible material except as in 2.4.7.5.4.1.
2.4.7.7.2 Dimensions
No ground sign shall be erected to a height exceeding 30 ft above the ground. Lighting
reflectors may extend beyond the top or face of the sign.
2. Five to eight storeys or exceeding 59 ft (18m) but not exceeding 118 9.84 ft (3 m)
ft (36m)
2.4.7.8.3 Location
a) No roof sign shall be so placed on the roof of any building as to prevent free
passage from one part of the roof to another.
b) No roof sign shall be placed on or over the roof of any building unless the entire
roof construction is of non-combustible material.
2.4.7.8.4 Projection
No roof sign shall project beyond the existing building line of the building of which it is
erected or shall extend beyond the roof in any direction.
2.4.7.8.5 Supports and anchorage
Every roof sign shall be thoroughly secured and anchored to the building on or over
which it is erected. All loads shall be safely distributed to the structural members of the
building.
2.4.7.8.6 Clearance
Roof signs shall be so constructed as to leave a clear space of not less than 6 ft (1829
mm) between the roof level and the lowest part of the sign and shall have at least 5 ft
(1524 mm) clearance between the vertical supports thereof.
2.4.7.9 Verandah signs
2.4.7.9.1 Material
Every verandah sign shall be constructed entirely of non-combustible material except as
in 2.4.7.5.4.1.
2.4.7.9.2 Dimensions
No verandah sign exceed 3.28 ft (1 m) in height. No verandah sign hanging from a
verandah shall exceed 8.2 ft (2.5 m) in length and 50 mm in thickness, except that
verandah box signs measuring not more than 200 mm in thickness, measured between the
principal faces of the sign and constructed entirely of metal wired glass may be erected.
2.4.7.9.3 Alignment
Every verandah sign shall be set parallel to the building line, except that any such sign
hanging from a verandah shall be set at right angles to the building line.
2.4.7.9.4 Location
Verandah signs, other than hanging signs only, shall be placed in the following locations:
a) Immediately above the eaves of the VERANDAH roof in such a manner as not to
project beyond the rear of the roof gutter;
b) Against but not above or below the VERANDAH parapet or balustrade provided
such parapet or balustrade is solid and the sign does not project more than 20 cm
from the outside face of such parapet or balustrade; or
c) On the VERANDAH beams or parapets in the case of painted signs.
2.4.7.9.5 Height of hanging VERANDAH signs
Every VERANDAH sign hanging from a VERANDAH shall be fixed in such a manner
that the lowest point of such sign is not less than 8 .2 ft (2.5 m) above the pavement.
2.4.7.9.6 Projection
Except as provided for in 2.4.7.9.4, no VERANDAH sign shall extend outside the line of
the VERANDAH to which it is attached.
e) Any sign not securely fixed so as to prevent the sign swinging from side to side;
f) Any advertising sign made of cloth, paper mache, or similar or like material but
excluding licensed paper signs on hoardings or fences,
g) Any advertising sign on a plot used or intended to be used exclusively for
residential purposes, other than a brass plate or board preferably not exceeding
600 mm x 450 mm in size, affixed to the fence or entrance door or gate of a
dwelling, and in the case of a block of flats, affixed to the wall of the entrance
hall or entrance door of any flat and
h) Any sign on trees, rocks, hillsides and similar natural features.
2.4.7.14.2 Requirements for temporary signs
All temporary advertising, travelling circus and fair signs and decorations during public
rejoicing shall be subject to the approval of the Authority and shall be subjected to the
approval of the Authority and shall be erected so as not to obstruct any opening and to
minimize fire risk.
The advertisement contained on any such sign shall pertain only to the business, industry
or other pursuit conducted on or within the premises on which such sign is erected or
maintained. Temporary advertising signs shall be removed as soon as tom or damaged
and in any case within 14 days after erection unless extended.
The Authority shall be empowered to order the immediate removal of any temporary
advertising sign or decoration, where, in its opinion such action is necessary in the
interests of public amenity and safety.
2.4.7.14.2.1 Pole signs
Pole signs shall be constructed entirely of non-combustible materials and shall
conform to the requirements for ground or roof signs as the case may be. Such signs
may extend beyond the street line if they comply with the provisions for projecting
signs.
2.4.7.14.2.2 Banner and cloth signs
Temporary signs and banners attached to or suspended from a building, constructed
of cloth or other combustible material shall be strongly constructed and shall be
securely attached to their supports. They shall be removed as soon as torn or
damaged, and in no case later than 14 days after erection; except, that permits for
temporary signs suspended from or attached to a canopy or marquee shall be limited
to a period of 10 days.
2.4.7.14.2.3 Maximum size
Temporary signs shall not exceed 108 sq.ft (10 sq.m) in area.
2.4.7.14.2.4 Projection
Temporary signs of cloth and similar combustible construction shall not extend more
than 300 mm over or into a street or other public space except that such signs when
constructed without a frame may be supported flat against the face of a canopy or
marquee or maybe suspended from the lower fascia thereof but shall not extend closer
to the ftpath than 8.2 ft (2.5 m).
the requirements of Sections 3109.4.1.1 through 3109.4.1.8. When the ladder or steps
are secured, locked or removed, any opening created shall not allow the passage of a
4-inch-diameter (102 mm) sphere.
2.4.9.4.2 Indoor swimming pools
Walls surrounding indoor swimming pools shall not be required to comply with Section
2.4.9.4.1.8.
2.4.9.4.3 Prohibited locations
Barriers shall be located so as to prohibit permanent structures, equipment or similar
objects from being used to climb the barriers.
2.4.10 Automatic Vehicular Gates
2.4.10.1 General
Automatic vehicular gates shall comply with the requirements of this section and other
applicable sections of this code.
2.4.10.2 Definition
The following word and term shall, for the purposes of this section and as used elsewhere in
this code, have the meaning shown herein.
VEHICULAR GATE. A gate that is intended for use at a vehicular entrance or exit to a
facility, building or portion thereof, and that is not intended for use by pedestrian traffic.
h) The headroom of areas meant only for car parking shall be not less than 8 feet.
i) The headroom at stair cases shall not be less than 7 feet and the height of any
covered footway shall be not less than 8 feet.
j) The height of rooms in public areas shall not be less than 11 feet (excluded are
the areas such as water-closets, lavatories, cloakrooms, corridors and rooms).
k) Where a balcony is provided in public resort or public places, the heights between
the finished floor level and the ceiling over such balcony, shall be not less than
9.5 feet.
l) The height of non-habitable rooms on public places, such as water-closets,
lavatories, corridors, etc, shall not be less than 8 feet.
Exception: When the clear room height is considered, the required height for all
electrical and mechanical services such as duct lines, fire extinguishing systems, etc.
should be noticed.
2.5.6.3 Inner connecting space widths
a) Clear minimum width of inner connecting spaces (corridors, passages, etc.) in the
residential units, or units with not more than 10 persons occupancy, shall be
minimum 3 feet 6 inches, and if these are longer than 15 feet, or if these are used by
more than 75 occupants, and number of doors, door widths and width of openings
shall comply with fire safety requirements.
b) Clear minimum width of inner connecting spaces (corridors, passages, etc.) in the
building with public access, must be 6 feet.
2.5.6.4 Doors and openings
All doors entering any habitable room shall have minimum clear height of 6.5 feet and width
of 2.75 feet.
a) All doors entering toilets and kitchens in residential units shall have minimum height
of 6.5 feet and width of 2.75 feet.
b) All exit doors shall open outwards and number of doors, door widths and width of
openings shall comply with section 2.6 Means of Egress.
c) Where the space beneath a roof is enclosed by a ceiling, access to such space shall be
provided for inspection, cleaning and repairs by means of an opening with minimum
2.5 feet width in any direction.
2.5.7 Stairs, Steps, Ramps and Lifts
2.5.7.1 Stairs
Stair in this chapter means only for internal stair whereas, the exit stair is described in chapter
6-Means of Egress of this part and emergency stair is in Part 5- Building Service (Fire) of this
code.
a) All staircases shall be properly lighted and ventilated.
b) All stairs in residential units have a landing after 12 risers maximum, in all other
buildings there shall be not more than 16 risers between each such landing.
c) All stairs shall have non-slip surface.
d) In cases where stairs or steps begin after the doors and other openings, the distance
between such openings and the beginning of stairs/ steps shall normally be the same
as the width of the respective stairs, but minimum of 3 feet shall be required.
e) Timber staircases may be permitted for the following building types, provided these
are not more than three storeys in height:
1) Detached residential buildings; duplex houses and terrace houses;
2) In the upper floors of shop houses other than from the ground floor to the first
floor provided that it is located within the protected area for its full height; and
3) Other similar types of buildings of low fire risk.
2.5.7.1.1 Stair widths
1) Clear minimum width of inner stairs in detached houses, duplex and terrace
houses, meant for use of single families, or units with less than occupancy of 10
people other than shop houses shall be 3 feet, and 3.5 feet from wall to wall.
2) Clear minimum width of stairs in shop houses shall be 4 feet.
3) Clear minimum width of stairs in multi-storeyed residential buildings meant for
usage of less than 10 families and not more than 4 storeys shall be 4.5 feet, and
these must conform to tables 2.5.1 and 2.5.2, as well as these must have approval
from the fire department at the design stage.
4) Clear minimum width of stairs in multi-storeyed residential buildings meant for
usage of more than 10 families and more than 4 storeys, shall be 5 feet and these
must conform to tables 2.5.1 and 2.5.2, as well as these must have approval from
the fire department at the design stage.
5) Clear minimum width of stairs in public buildings with limited access excluding
the shopping centres must be 5 feet and these must conform to tables 2.5.1 and
2.5.2, as well as these must have approval from the fire department at the design
stage.
6) Clear minimum width of stairs of buildings with public access such as offices,
post offices, railway stations, etc. excluding the shopping centres must be 6 feet
and these must conform to tables 2.5.1 and 2.5.2, as well as these must have
approval from the fire department at the design stage.
7) Clear minimum width of stairs in shopping centres with less than 3000 square
feet and more than one storey shall be 6 feet and these must conform to tables
2.5.1 and 2.5.2, as well as these must have approval from the fire department at
the design stage.
8) Clear minimum width of stairs in shopping centres with more than 3000 square
feet shopping area shall be 8 feet and these must conform to tables 2.5.1 and
2.5.2, as well as these must have approval from the fire department at the design
stage.
9) Clear minimum width of stairs in schools, with more than 100 children, shall be 6
feet and these must conform to tables 2.5.1 and 2.5.2.
10) Clear minimum width of hospitals, and the buildings of health care, shall be 6 feet
and these must conform to tables 2.5.1 and 2.5.2.
11) The widths of landings are normally the same as respective stairs, and as
minimum, these shall follow the width and heights given in this paragraph.
e) Net railing height, (measured from floor finishing to the top of railing) of balconies,
large windows reaching to the floor level, terraces, flat roofs and similar structures at
buildings with more than 3 stories or more than 35 feet above the ground level shall
not be lower than 3.5 feet, and the spacing of balustrades or similar openings below
the hand railing level should be less than 6 inches.
f) Net railing height of stairs, balconies, terraces and similar structures at schools shall
not be lower than 4 feet (measured from floor finishing to the top of railing) and there
shall be not horizontal divisions in the railing to avoid children stepping on the
railings.
g) Staircases exceeding 8 feet in width shall be provided with intermediate handrail and
the distances of handrails shall be maximum 8 feet away from each other.
h) All steps with more than 6 risers shall have an intermediate landing of minimum 3
feet in length.
2.5.7.4 Protection at elevated areas
Every flat roof, balcony or other elevated areas located at 4 feet or more above the adjacent
area where normal access is provided shall be protected along the edges with suitable railings,
parapets or similar elements with not less than the height given in the paragraph 38 mentioned
above.
2.5.7.5 Ramps
The design of ramps shall conform to following points:-
a) All ramps meant for wheel chair of handicapped persons must have the slopes less
than 10 %, (Rise: run ratio 1:10).
b) All ramps meant for light motor vehicles less than 2 tons net weight must have the
slopes, less than 16 %, (Rise: run ratio 1: 6.25).
c) All ramps meant for medium heavy vehicles less than 5 tons net weight must have the
slopes less than 14 %, (Rise to run ration 1:7.2).
d) The clear headroom of ramps at the entering points into the buildings, meant for light
vehicles less than 2 tons shall not be lower than 7 feet, and meant for entrance of
heavy vehicles with less than 5 tons shall not be less than 9 feet.
Rise
1'
Run
10 '
Figure 2.5.2 Schematic figure showing gradient of ramps (rise: run ratio)
c) All buildings with public dealing functions like banks, shopping centres, hospitals,
etc., which have more than 3 storeys and higher than 30 feet from ground level to the
topmost floor, shall be equipped with adequate number of lifts or similar facilities.
d) In the shopping centres with more than 3 storeys and more than 5000 square feet
shopping area, shall be equipped with adequate number of additional mechanical
means of vertical transport, such as lifts, escalators, etc.
e) In places where mechanical means of vertical transportation, such as escalators or
lifts are provided, ordinary stairs designed in line with these codes are necessary.
f) The capacity of vertical transportation, size and number of lifts shall follow the norms
and standards based on calculations done by qualified engineers of the respective
field.
2.5.9 Access to Unoccupied Spaces
2.5.9.1 Crawl spaces
Crawl spaces shall be provided with aminimum of one access opening not less than 18 inches
by 24inches (457 mm by 610 mm).
2.5.9.2 Attic spaces
An opening not less than 20 inches by 30inches (559 mmby 762 mm) shall be provided to any
attic areahaving a clear height of over 30 inches (762 mm). A 30-inch(762 mm) minimum
clear headroom in the attic space shall beprovided at or above the access opening.
2.5.10 Surrounding Materials
2.5.10.1 Floors
In other than dwelling units, toilet and bathingroom floors shall have a smooth, hard,
nonabsorbent surfacethat extends upward onto thewalls at least 6 inches (152 mm).
2.5.10.2 Walls
Walls within 2 feet (610 mm) of urinals andwater closets shall have a smooth, hard,
nonabsorbent surface,to a height of 4 feet (1219 mm) above the floor, and except forstructural
elements, the materials used in such walls shall be ofa type that is not adversely affected by
moisture.
Exceptions: Dwelling units, sleeping units and toilet rooms those are not accessible to the
public andwhich have not more than one water closet.
Accessories such as grab bars, towel bars, paper dispensersand soap dishes, provided on or
within walls, shall be installedand sealed to protect structural elements from moisture.
2.5.10.3 Showers
Shower compartments and walls above bathtubswith installed shower heads shall be finished
with asmooth, nonabsorbent surface to a height not less than 70inches (1778 mm) above the
drain inlet.
Airport terminal
Dormitories 50 gross
Educational
Institutional areas
Library
Mercantile
Decks 15 gross
gross = Gross floor area of a building, means the total floor area calculated based on center of
exterior walls, including the circulation area such as stairs , corridors, etc. but excluding
the technical area without floors shafts, ducts, lift wells etc
net = Net floor area of a room or of a units means total floor calculated based on center of the
walls of respective room or of unit.
2.6.3.1 Mixed occupancy
Where building is designed for different types of occupancies or different purposes at the
same time, the exit requirements shall meet the more stringent requirements of each building
section and function of the respective portions.
2.6.3.2 Multiple occupancy or use
Where a building is designed for multiple purposes involving different activities at different
times, the greatest number of occupants shall form the basis for determining the egress
requirements.
A, B, Ea, F, M, U 49
S 29
1-500 2
501-1000 3
Whenever there are two exit doors or two exit access doorways are required, the distance between
the two exits are at least equal to or more than half the furthest distance from one point to another
of that particular room and each exit shall be of equal capacity.
b) The single exit staircase shall serve not more than four apartments or maisonettes
at each storey level, and
d) Travel distance from the most remote exit door to the exit staircase from each
apartment or maisonette shall not exceed 15 m, and
e) Exit staircase shall comply with the requirements of cl.2.6.9 Exit stairs & 2.6.10
Exit discharge.
f) Approach to the exit staircase shall be through cross-ventilated lobby. The
ventilation openings having a minimum width of 2000mm and a minimum height
of 1200mm shall be unobstructed from parapet wall or balustrade level upwards
and be positioned on opposite sides of the lobby such that they provide cross-
ventilation throughout the entire space of the lobby. Where multiple ventilation
openings are provided on opposite sides of the lobby, the minimum width and
height of each opening shall not be less than 1000 mm and 1200mm respectively,
provided the aggregate width of the openings at each opposite side is not less than
2000mm.
g) Fire lift shall be provided to comply with the requirements of fire department, and
h) Wet rising main shall be provided to comply with the requirements of fire
department, and
i) Access to the building for fire fighting appliances shall be provided to comply
with the requirements of fire department.
2.6.7 Exit Access Travel Distance
Exit access travel distances are determined by type of occupancy and shall comply with the table
given below in these codes.
Table 2.6.5 Exit Access Travel Distance
car parks
Detached, semi-detached NR NR NR NR NR NR
& terrace House,
including townhouses
To
Type of Occupancy Other Ramps
outdoors
exit & Stair- Corridors
at ground Stairs Corridor
corridor cases Exits
level
doors Passageways
(inches)
Detached, semi- NR NR NR NR 3 3
detached & terrace
House, including
townhouses
a) Applies to corridors serving classrooms. Other corridors shall have a minimum width of
3ft 6 inches.
b) Applies to corridors serving patients. Other corridors shall have a minimum 3ft 6 inches.
c) Staircase within maisonette serving as an internal access to be at least 3ft width.
The maximum width of exit staircase shall be not more than 6 feet 6 inches. Where staircase
exceed 6 feet 6 inches in width, handrails shall be used to divide the staircase into sections of not
less than 3 feet 6 inches of width or more than 6 feet 6 inches of width.
2.6.9 Exit Stairs
All exit stairs shall be constructed minimum 1 hour rated construction.
All exit stairs (except for R1a, R2, R3 and R5 which are not more than 3 storeys) riser heights
shall be 7 inches maximum and 4 inches minimum.
All stairs in shall be not more than 16 risers between each such landing.
Stair threads and risers shall be of uniform size and shape. The tolerance between the largest and
smallest riser heights or between the largest and smallest tread depth shall not exceed 3/8 inch in
any flight of stairs.
The width of landings shall not be less than the width of stairways they serve.
Winder stairs are not permitted in means of egress stairways except within a dwelling unit. Where
circular/geometric staircases are used as exit staircases, the width of threads measured at the
narrower end shall be not less than 4in in residential buildings and at a distance of 2ft from the
narrower end shall be not less than 9in in residential buildings.
Spiral stair cases as exist stair can be used at residential detached and semi detached buildings not
more than 3 storey.
2.6.9.1 Internal exit stair
An internal exit stair which serves as an exit shall be enclosed.
All services such as pipe/duct installation shall not be located inside protected staircase and
no wash room is allowed to be located inside staircase.
There shall be no unprotected openings of occupancy area within 4ft horizontally and 10 ft
vertically below any part of the ventilation opening in the external wall of internal exit
staircase. Exceptional cases are public and commercial buildings like hotels and offices etc.
which are properly provided and maintained with mechanical ventilation and lighting
facilities as per Building services chapter.
The width of stair case shall be complying with egress width table.
If the stair serves more than 6 storey, smoke stop lobby shall be added.
2.6.9.2 External exit stair
a) An exit stair which serves as an exit must be located outside of the building or at least
one side of staircase must be external wall and the external exit staircase shall be
located so as to lead directly to a street or open space with direct access to street.
b) The stair must be naturally ventilated with a minimum unobstructed opening area,
larger or equal to 20% of area of stair case.
c) There shall be no unprotected openings within 3 m horizontally or within 3 m
vertically below, or adjacent or facing.
Exception: For residential walk apartments which are located in CBD, having back lane and
can’t comply with cl.2.6.9.b, the building can be accessible by fire engine and it shall has one
fireman-stair at the back of flat.
2.6.10 Exits Discharge
All exits shall be discharge at ground level directly into a safe exterior space within its own
property or public space.
Exception: In sprinkler protected building, maximum 50% of the total building exits are allowed
to discharge directly to the ground level circulation space subject to the following:
a) The discharge point shall be at a location in the circulation space at ground level with
direct access and within sight of a safe exterior open space.
b) The maximum distance of the discharge point to exterior open space is 30ft.
The sprinkler system shall conform to the Building services chapter.
2.6.11 Exit Passage Way
Exit passage way can be used as a horizontal extension of a vertical exit viz exit staircase or a
passage leading from a courtyard to an open exterior space, complying with the requirements of
travel distance and exit discharge.
2.6.11.1 Internal exit passage way
a) Exit passageways that serve as a means of escape shall be minimum 1 hour rated
construction.
b) The enclosure walls of an exit passageway shall have not more than two exit
doors opening into the exit passageway
c) Exit doors opening into an exit passageway shall have fire resistance rating as
required for exit doors opening into exit staircases, fitted with automatic self-
closing device.
d) The minimum width and capacity of exit passageway shall comply with
Cl.2.6.8 Egress Width
e) Changes in level along an exit passageway requiring less than two risers shall
be by a ramp complying with the provisions under Cl.2.6.2
f) If the exit staircase which connects to the internal exit passageway is
pressurised, the internal exit passageway shall not be naturally ventilated but
shall be mechanically ventilated.
2.6.11.1 External exit passageway
a) An external exit passageway can be used as a required exit in lieu of an internal exit
passageway. The external wall between the exit passageway and the rest of the floor
space can have ventilation openings of non-combustible construction, fixed at or
above a level 1.8m (7ft), measured from the finished floor level of the passageway to
the sill level of the openings and such ventilation openings shall be located not less
than 3.0 m (10ft) from any opening of an exit staircase, and
b) An external exit passageway may not be subjected to the limitations of a maximum of
two exit doors opening into the exit passageway, and
c) An external exit passageway may be roofed over provided the depth of the roofed
over portion shall not exceed 3m to avoid smoke logging, and
d) An external exit passageway may be enclosed on the open side by only a parapet wall
of not less than 1.0 m or more than 1.1m (3ft 4in) in height and the vertical height of
the
unobstructed ventilation opening measured from the parapet wall up to the top edge
of the opening or eaves of overhang shall not be less than 1.2m (4ft), Exception: if
external passage way is used on ground between building and fence, the farthest edge
of roof or slab above the exit passage shall be 3ft apart from fence and the passage
shall have minimum width of 4 ft.
e) Exit doors opening into an external exit passageway shall have fire resistance for at
least half an hour and fitted with automatic self-closing device.
2.6.12 Exit Doors
2.6.12.1 Exit doors opening
Exit doors opening into exit staircases and exit passageways shall not impede the egress of
occupants when such doors are swung open, and all doors which open into the corridor, shall
not hinder movement of occupants. The corridor's clear width shall at least remain to be half
of the required clear width as stipulated under Table B when such door(s) is swung open.
Exit doors and exit access doors shall open in the direction of exit travel:
a) When leading to an access doors shall open in the direction of exit access way
b) When used in exit enclosure, including smoke stop and fire fighting lobbies in a
building. It shall not apply to doors of individual residential units that open directly
into an exit enclosure, or
c) When serving a high hazard area, or
d) When serving a room or space with more than 50 persons.
2.6.12.2 Locking of staircase and smoke stop/ fire lift lobby doors
One way locking device is allowed to be protected to doors of exit staircase, smoke stop/ fire
lift lobby in the following situations, provided only one-way locking device is used, e g .panic
bolt or thumb turn locking device:
a) Exit door between staircase shaft and occupancy area; and
b) Exit access door between smoke/ fire fighting lobby and occupancy area; and
c) Exit door between staircase shaft and smoke stop lobby; and
d) Exit door between staircase shaft and circulation area; and exit access door between
smoke stop/ fire fighting lobby and circulation area.
2.6.13 Means of Egress Lighting
Emergency lighting system must be provided along Exit Access and Exits, Exits discharge.
2.6.14 Accessible Means of Egress
Accessible egress must be provided if there is "accessible place". Refer to Chapter 7.
2.6.15 Smoke Stop Lobby
A separate lobby adjoining the exit access way and exit stair with a minimum rated 1 hour
construction.
Its area shall be minimum 30sq-ft and if it serves as a fire fighting lobby, floor area shall not be
smaller than 60sq-ft and width no dimension less than 6ft 6 inches.
There shall be permanent fixed ventilation openings in the external wall of lobby, not less than 15
percent of the floor area or mechanical ventilation comply with Building services chapter.
There shall be no unprotected openings of occupancy area within 4ft horizontally and 10 ft
vertically below any part of the ventilation opening.
2.6.16 Exit Sign
All signage showing the emergency exit route must be visible from distance of 100 ft and they
shall not be covered by other elements.
2.6.17 Emergency Escape/ Refuge Area
In the third phase, the details of this section will be described depending on the resources’
availability.
2.6.18 Special Requirements
2.6.18.1 Hospitals
a) All multi-storey hospitals with patients care of more than 24 hours must have all
vertical transportation system (fire escape bed lift) only for the patients if the hospital
is more than 4 storeys and
b) Every storey shall have fire escape lobby or balcony that is designed for 2 hour fire
rating.
2.6.18.2 Definitions
FIREMAN STAIR: The stairs generally meant for usage of fireman in case of emergency.
The fireman stairs must be able to stand minimum 1000 pounds.
FIRE ESCAPE BED LIFT: Lift is to be used for the evacuation of patients in beds including
wheelchairs or physically disabled, in a fire emergency, although it can be use as a passenger
lift during normal time.
2.7 ACCESSIBILITY
2.7.1 Scope
The provisions of this chapter shall control the design and construction of facilities for
accessibility to physically disabled persons.
2.7.2 Scoping Requirements
All public buildings shall be accessible for the meant for handicapped persons and must have
minimum one accessible toilet comply with this chapter. Minimum provision for disabled persons
based on building types shall be as per following table.
Table 2.7.1 Scoping Requirements
Type of Building Minimum provision
All public transportation building At least one space shall be accessible to use
publice transport.
Banks At least one accessible service desk shall be
provided for every 10 service desk.
Hotels At least one guest room shall be provided for
every 250 guestrooms or part and thereof.
Concert halls, Stadium, Cinema At least one wheel chair space shall be
and public resort provided for every 500 seats or part thereof.
Religious Building (If occupancy The main worship shall be made accessible in
load is more than 1000) accordance with this chapter.
Hostels and Halls At least one level, preferably access level,
shall be provided with facilities in accordance
with 2.7.3.
Shopping Mall (if ground floor At least ground floor shall be accessible in
area is more than 10,000sq-ft) accordance with 2.7.3.
2.8.4.3 Wood
Exterior walls of wood construction shall be designed and constructed in accordance with
Part 3- Structural Design.. Wood shall be performed according to the wood section in
Material Chapter. Locally available timber can be used. Treated timber is preferable to
untreated timber. The treatment may be done in a traditional manner.
2.8.4.4 Masonry
Exterior walls of masonry construction shall be designed and constructed in accordance with
Masonry Section in Part 3- Structural Design.. Masonry units, mortar and metal accessories
used in anchored and adhered veneer shall meet the physical requirements of Masonry
Section in Material Chapter. The backing of anchored and adhered veneer shall be of
concrete, masonry, steel framing or wood framing.
2.8.4.5 Metal
Exterior walls of formed steel construction, structural steel or lightweight metal alloys shall
be designed and constructed in accordance with Part 3- Structural Design. and shall be
performed according to Aluminium and Other Light Metals and Their Alloys Section in
Material Chapter.
2.8.4.6 Concrete
Exterior walls of concrete construction shall be designed and constructed in accordance with
Concrete Section in Part 3- Structural Design.. Concrete shall be performed according to
Concrete Section in Material Chapter.
2.8.4.7 Glass-unit masonry
Exterior walls of glass-unit masonry construction shall be designed and constructed in
accordance with Glass-unit masonry Section in Part 3- Structural Design..
2.8.4.8 Stone Venner
Exterior walls of stone venner construction shall be designed and constructed in accordance
with Part 3- Structural Design. Stone shall be performed according to Part 6- Material.
2.8.4.9 Exterior insulation and finish systems
Exterior insulation and finish systems (EIFS) with or without drainage shall govern the
materials, construction and quality for use as exterior wall coverings.
2.8.5 Projections in Brickwork
All projections in brickwork shall be corbelled gradually and no projection shall extend more than
9 inches from the face of any wall.
2.8.6 Recess
Where a recess in the load-bearing building is made in an external wall or a division wall (party
wall):-
a) The wall at the back of the recess shall not be less than 4.5 inches thick at an external wall
and 9 inches thick at a division wall;
b) A sufficiently strong members like lintel or arch of noncombustible material shall be built
over the recess area;
c) If a recess or opening is made at the edge of a division wall or of an external wall, there
shall be a space of not less than 1.5 feet between the beginning of opening and the
extreme end of the wall.
2.8.7 Installation of Wall Coverings
2.8.7.1 Exterior covering materials in brick walls
In all cases where 4.5 inches brick walls or non-load-bearing walls of other materials should
be attached to reinforced concrete frames, or other structural members, such walls shall be
properly secured to the structural members.
2.8.7.2 Cement plaster
Cement plaster applied to exterior walls shall conform to the requirements specified in
Cement and Concrete Section in Part 6- Material.
2.8.7.3 Fastening
Weather boarding and wall coverings shall be securely fastened with aluminum, copper, zinc,
zinc-coated or other approved corrosion-resistant fasteners or the approved manufacturer’s
installation instructions.
2.8.8 Exterior Doors and Windows
The openings of exterior walls shall be provided the overhead sun shade and similar projections
for weather protection. Exterior doors and windows shall be installed in accordance with
approved manufacturer’s instructions and shall be performed according to Part 6- Material..
Fastener size and spacing shall be provided in such instructions and shall be calculated based on
maximum loads and spacing. Any parts of the exterior doors and windows shall be water-proof.
The protective bars and safety glazing are required for any fixed or operable opening extended to
floor finished level. The protective bars or sill height of operable openings shall be 3 feet above
adjacent floor finished level that is more than 30 inches above exterior ground level. The
insulating glass shall be installed if required to give weather protection.
2.8.8.1 Curtain walls
Any parts or members of curtain walls shall be water-proof and installed in accordance with
approved manufacturer’s instructions. The approved flexible fire barrier material that
provides an effective firestop and smoke seal for perimeter voids and accommodates dynamic
movement between the curtain wall and the floor shall be provided.
2.8.9 Balconies and Similar Projections, Bay and Oriel Windows
Balconies and similar projections, bay and oriel windows shall conform to the type of
construction required for the building to which they are attached. Exterior balconies attached to or
supported by wall required to be of masonry, shall have brackets or beams constructed of
incombustible materials. 3 feet height railings shall be provided for balconies, landings, or
porches which are more than 30 inches above exterior ground level.
2.8.10 Metal Composite Materials (MCM)
The provisions of this section shall govern the materials, construction and quality of metal
composite materials (MCM) for use as exterior wall coverings.
2.8.10.1 Exterior wall finish
MCM used as exterior wall finish or as elements of balconies and similar projections and bay
and oriel windows to provide cladding or weather resistance.
POSITIVE ROOF DRAINAGE: The drainage condition in which consideration has been
made for all loading deflections of the roof deck, and additional slope has been provided to
ensure drainage of the roof within 48 hours of precipitation.
ROOF COVERING: Roof covering is a durable exterior surface material that provides
weather protection for the building at the roof.
ROOFING ASSEMBLY: Roofing assembly includes the roof deck, substrate or thermal
barrier, insulation, vapour retarder, underlayment, inter-laymen, base plies, roofing plies, and
roof covering that is assigned a roofing classification.
ROOF VENTILATION: The natural or mechanical process of supplying conditioned or
unconditioned air to, or removing such air from, attics, cathedral ceilings or other enclosed
spaces over which a roof assembly is installed.
SCUPPER: An opening in a wall or parapet that allows water to drain from a roof.
UNDERLAYMENT is one or more layers of felt, sheathing paper, no bituminous saturated
felt or other approved material over which a roofing system is applied.
2.9.2 Roof Covering
Roof covering for all buildings shall be either fire-retardant or ordinary depending upon the fire-
resistive requirements: of the particular type of construction. The use of combustible roof
insulation shall be permitted in all type of construction provided it is covered with approved roof
covering applied directly thereto.
2.9.3 Roof Trusses
All roofs shall be so framed and tied into the framework and supporting walls
so as to form an integral part of the whole building. Roof trusses shall have all joints well fitted
and shall have all tension members well tightened before any load is placed in the truss. Diagonal
and sway bracing shall be used to brace all roof trusses. The allowable working stresses of
materials in trusses shall conform to this Code. Camber shall be provided to prevent sagging.
2.9.3.1 Attics
2.9.3.1.1 Access
An attic access opening shall be provided in the ceiling of the top floor of buildings with
a combustible ceiling or roof construction. The opening shall be located in a corridor or
hallway of buildings of three (3) or more stories in height and readily, accessible in
buildings of any height. An opening shall not be less than 600 millimetres square (23.4")
or 600 millimetres diameter (0.78"). The minimum clear headroom of 800 millimeters
(31.2") shall be provided above the access opening.
2.9.3.1.2 Area separation
Enclosed attic spaces of combustible construction shall be divided into horizontal areas
not exceeding 250 sq. meters (2691 sq.ft) by fire-resistive partitions extending from the
ceiling to the roof. Except, that where the entire attic is equipped with approved
automatic fire-extinguishing system, the attic space may be divided into areas not to
exceed 750 sq. meters (8073 sq.ft). Openings in the partitions shall be protected by self-
closing doors.
if the height of the skylight does not exceed 6.00 meters (19.6 ft) above the grade, but in other
cases metal frames and metal sash bars shall be used.
Glass used for the transmission of light, if placed in floors or sidewalks, shall be supported by
metal or reinforced concrete frames, and such glass shall not be less than 12.5 millimeters (0.5")
in thickness. Any such glass over 100 sq. centimeters (15.5 sq.inches) in area shall have wire
mesh embedded in the same or shall be provided with, a wire screen underneath as specified for
skylights in the Code. All portions of the floor lights or sidewalk lights shall be of the same
strength as required for floor or sidewalk construction, except in cases where the floor is
surrounded by a railing not less 1.10 meters (3.6 ft) in height, in which case the construction
shall be calculated for not less than roof loads.
2.9.7 Penthouses and Roof Top Structures
2.9.7.1 Height
No penthouse or other projection above the roof in structures of other than Type V
construction shall exceed 8.40 meters (28 ft) above the roof when used as an enclosure for
tanks or for elevators which run to the roof and in all other cases shall not extend more than
3.60 meters (12 ft) in height with the roof.
2.9.7.2 Area
The aggregate area of all penthouses and other roof structures shall not exceed 50% of the
area of the supporting roof.
2.9.7.3 Prohibited uses
No penthouse, bulkhead, or any other similar projection above the roof shall be used for
purposes other than shelter of mechanical equipment or shelter of vertical shaft openings in
the roof. A penthouse or bulkhead used for purposes other than that allowed by this Section
shall conform to the requirements of the Code for an additional storey.
2.9.7.4 Construction
Roof structures shall be constructed with walls, floors, and roof as required for the main
portion of the building except in the following cases:
On Types III and IV constructions, the exterior walls and roofs of penthouses which are 1.50
meters (4.5 ft) or more from an adjacent property line may be of one-hour fire-resistive
incombustible construction.
Walls not less than 1.50 meters (4.5 ft) from an exterior wall of a Type IV construction may
be of one-hour fire-resistive incombustible construction. The above restrictions shall not
prohibit the placing of wood flagpoles or similar structures on the roof of any building.
2.9.8 Chimneys
2.9.8.1 Structural design
Chimneys shall be designed, anchored, supported, reinforced constructed, and installed in
accordance with generally accepted principles of engineering. Every chimney shall be
capable of producing a draft at the appliance not less than that required for the safe operation
of the appliance connected thereto. No chimney shall support any structural load other than
its own weight unless it is designed to act as a supporting member. Chimneys in a wood-
framed building shall be anchored laterally at the ceiling line and at each floor line which is
more than 1.80 meters (6 ft) above grade, except when entirely within the framework or
when designed to be free standing.
2.9.8.2 Walls
Every masonry chimney shall have walls of masonry units, bricks, stones, listed masonry
chimney units, reinforced concrete or equivalent solid thickness of hollow masonry and lined
with suitable liners in accordance with the following requirements.
2.9.8.2.1 Masonry chimneys for residential type appliances
Masonry Chimneys shall be constructed of Masonry units or reinforced concrete with
walls not less than 100 millimeters ( 4 in) thick: or rubble stone masonry not less than 300
millimeters ( 12 in) thick. The chimney liner shall be in accordance with the code.
2.9.8.2.2 Masonry chimneys for low heat appliances
Masonry Chimneys shall be constructed of Masonry units or reinforced concrete with
walls not less than 200 millimeters (8 in) thick. Expect that rubble stone masonry not less
than 300 millimeters (12 in) thick. The chimney liner shall be in accordance with the
code.
2.9.8.2.3 Masonry chimneys for medium-heat appliances
Masonry chimneys for medium-heat appliances shall be constructed of solid masonry
units of reinforced concrete not less than 200 millimeters ( 8 in) thick. Except, that stone
masonry shall be not less than 300 millimeters (12 in) thick and, in addition shall be
lined with not less than 100 millimeters ( 4 in) of firebrick laid in a solid bed of fire clay
mortar with solidly filled head, bed, and wall joints, starting not less than 600 millimeters
(24 in) below the chimney connector entrance, Chimneys extending 7.50 meters (22.5 ft)
or less above the chimney connector shall be lined to the tap.
2.9.8.2.4 Masonry chimneys for high-heat appliances
Masonry chimneys for high-heat appliances shall be constructed with double walls of
solid masonry units or reinforced concrete not less than 200 millimeters (8 in) in
thickness, with an air space of not less than 50 millimeters (2 in) between walls. The
inside of this Interior walls shall be of firebrick not less than 100 millimeters (4 in) in
thickness laid in a solid bed of fire clay mortar with solidly filled head, bed, and Wall
joints.
2.9.8.2.5 Masonry chimneys for incinerators installed in multi-storey buildings
(apartment-type incinerators)
Chimneys for incinerators installed in multi-storey buildings using the chimney
passageway as a refuse chute where the horizontal grate area of combustion chamber
does not exceed 0.80 sq. Meters shall have walls of solid masonry or reinforced concrete,
not less than 100 millimeters thick with, a chimney lining as specified in the Code. If the
grate area of such an incinerator exceeds 0.80 sq. meters, the walls shall not be less than
100 millimeters of firebrick except that higher than 9.00 meters ( 27") above the roof of
the combustion chamber, common brick alone 200 millimeters in thickness may be used.
2.9.8.2.6 Masonry chimneys for commercial and industrial type incinerators
Masonry chimneys for commercial and industrial type Incinerators of a size designed for
not more than 110 kilograms of refuse per hour and having a horizontal grate area not
exceeding 0.50 sq. meter shall have walls of solid masonry or reinforced concrete not
less than 100 millimeters thick with lining of not less than 100 millimeters ( 4 in) of
firebrick, which lining shall extend for not less than 12.00 meters (36 ft ) above the roof
of the combustion chamber If the design capacity of grate area of such an
inclneratorexceeds110 kilograms per hour and 0.80 sq. meter ( 80 sq ft) respectively,
walls shall not be less than 200 millimeters (8 in) thick, lined with not less than 1 00
millimeters (4 in) of firebrick extending the full height of the chimney.
2.9.8.3 Linings
Fire clay chimney lining shall not be less than 15 millimeters (1/2 in) thick. The lining shall
extend from 200 millimeters (8 in) below the lowest inlet or, in the case of fireplace, from
the throat of the fireplace to a point above enclosing masonry walls, Fire clay chimney linings
shall be installed ahead of the construction of the chimney as it Is carried up, carefully bedded
one on the other in the fire clay mortar, with close-fitting joints left smooth on the inside.
Firebrick not less than 500 millimeter thick maybe used in place of fireclay chimney.
2.9.8.4 Area
No chimney passageway shall be smaller in area, than the vent connection of the appliance
attached thereto.
2.9.8.5 Height
Every masonry chimney shall extend at least 600 millimeters ( 24 in) above the part of the
roof through which it passes and at least 600 millimeters (24 in) above the highest elevation
of any part of a building within 3.00 meters (9") to the chimney.
2.9.8.6 Corbelling
No masonry chimney shall be corbelled from a wall more than 150 millimeters, (6 in) nor
shall a masonry chimney is corbelled from a wall which is less than300 millimeters (12 in) in
thickness unless it projects equally on each side of the wall. In the second storey of a two-
storey building of Group “R” Occupancy, corbelling of masonry chimneys on the exterior of
the enclosing walls may equal the wall thickness. In every case the corbelling shall not exceed
25 millimeters ( 10 in) projection for each course of brick.
2.9.8.7 Change in size or shape
No change in the size or shape of a masonry chimney shall be made within a distance of 150
millimeters (6 in) above or below the roof joints or rafters where the chimney passes through
the roof.
2.9.8.8 Separation
When more than one passageway is contained in the same chimney, masonry
separation at least 100 millimeters (4 in) thick bonded into the masonry wall of the
chimney shall be provided to separate passageways.
2.9.8.9 Inlets
Every inlet to any masonry chimney shall enter the side thereof and shall be of not
less than millimeters thick metal or 16 millimeters refractory material.
2.9.8.10 Clearance
Combustible materials shall not be placed within 50 millimeters of smoke chamber or
masonry chimney walls when built within a structure or within 25 millimeters (10 in)
when the chimney is built entirely outside the structure.
2.9.8.11 Termination
All incinerator chimneys shall terminate in a substantially constructed spark arrester
having a mesh not exceeding 20 millimeters.
2.9.8.12 Cleanout
Cleanout openings shall be provided at the base of every masonry chimney.
buildings and sites, so that the inherent significance is retained while permitting continued use
and thus maintaining the building and site for future generations.
DANGEROUS. Any building or structure or portion shall be deemed dangerous if each of them
has collapsed, partially collapsed, moved off its foundation or lacks the support of ground
necessary to support it or there exists a significant risk of collapse, detachment or dislodgment of
any portion, member, appurtenance or ornamentation of the building or structure under service
loads.
EXISTING STRUCTURE. A structure erected prior to the date of adoption of this code, or one
for which a legal building permit has been issued.
PRIMARY FUNCTION. A primary function is a major activity for which the facility is intended.
SUBSTANTIAL STRUCTURAL DAMAGE. A condition if in any story, the vertical elements of
the lateral force-resisting system have suffered damage such that the lateral load-carrying capacity
of the structure in any horizontal direction has been reduced by more than 20 percent from its pre-
damage condition; or the capacity of any vertical gravity load-carrying component' or any group
of such components, that supports more than 30 percent of the total area of the structure 's floor(s)
and roof(s) has been reduced more than 20 percent from its pre-damage condition and the
remaining capacity of such affected elements, with respect to all dead and live loads, is less than
75 percent of that required by this code for new buildings of similar structure, purpose and
location.
TECHNICALLY INFEASIBLE. An alteration of a building or a facility that has little likelihood
of being accomplished because the existing structural conditions require the removal or alteration
of a load-bearing member that is an essential part of the structural frame, or because other existing
physical or site constraints prohibit modification or addition of elements, spaces or features which
are in full and strict compliance with the minimum requirements for new construction and which
are necessary to provide accessibility.
2.10.3 Additions
2.10.3.1 General
Additions to any building or structure shall comply with the requirements of this code for new
construction. Alterations to the heritage and existing building or structure shall be made to
ensure that the heritage and existing building or structure together with the addition are no
less conforming with the provisions of this code than the heritage and existing building or
structure was prior to the addition. An existing building together with its additions shall
comply with the height and area provisions of Chapter 3, General Building Heights and
Areas.
2.10.3.2 Flood hazard areas
For buildings and structures in flood hazard areas, any addition that constitutes substantial
improvement (basically having a value of 50% market value of the existing structure) of the
heritage building or existing structure, shall comply with the flood design requirements for
new construction, and all aspects of the existing structure shall be brought into compliance
with the requirements for new construction for flood design. For buildings and structures in
flood hazard areas, any additions that do not constitute substantial improvement or substantial
damage of the heritage existing structure, are not required to comply with the flood design
requirements for new construction.
members and connections required by this rehabilitation design shall comply with the
detailing provisions of this code for new buildings of similar structure, purpose and location.
2.10.5.3.1 Lateral force-resisting elements
Regardless of the level of damage to vertical elements of the lateral force-resisting
system, if substantial structural damage to gravity load-carrying components was caused
primarily by wind or earthquake effects, then the building shall be evaluated in
accordance with Section 2.10.5.2.1.
2.10.5.4 Less than substantial structural damage
For damage less than substantial structural damage, repairs shall be allowed that restore the
building to its predamage state using materials and strengths that existed prior to the damage.
New structural members and connections used for this repair shall comply with the detailing
provisions of this code for new buildings of similar structure, purpose and location.
2.10.5.5 Flood hazard areas
For buildings and structures in flood hazard areas, any repair that constitutes substantial
improvement of the existing structure, shall comply with the flood design requirements for
new construction, and all aspects of the existing structure shall be brought into compliance
with the requirements for new construction for flood design. For buildings and structures in
flood hazard areas, any repairs that do not constitute substantial improvement or substantial
damage of the existing structure, are not required to comply with the flood design
requirements for new construction.
2.10.6 Fire Escapes
2.10.6.1 Where permitted
Fire escapes shall be permitted only as provided for in Chapter 6, Means of Egress.
2.10.6.2 Construction
The fire escape shall be designed to support a live load of 100 pounds per square foot (4788
Pa) and shall be constructed of steel or other approved non-combustible materials.
2.10.7 Glass Replacement
2.10.7.1 Conformance
The installation or replacement of glass shall be as required for new installations.
2.10.8 Change of Occupancy
2.10.8.1 Conformance
No change shall be made in the use or occupancy of any building that would place the
building in a different division of the same group of occupancies or in a different group of
occupancies, unless such building is made to comply with the requirements of this code for
such division or group of occupancies. Subject to the approval of the relevant planning
authority, the use or occupancy of existing buildings shall be permitted to be changed and the
building is allowed to be occupied for purposes in other groups without conforming to all the
requirements of this code for those groups, provided the new or proposed use is less
hazardous, based on life and fire risk, than the existing use.
c) The proportion and location of new buildings must give deference to the heritage
monuments visually and to maintain the silhouette as well as the visual axis in the
environment of heritage monuments.
d) Adaptive reused of listed buildings is encouraged to prevent their deterioration. The
relevant authority must approve a Conservation Management Plan (CMP) for the
building, and oversee compliance with the CMP.
e) Under chapter IV, paragraph 7 of the "Protection and Preservation of Cultural
Heritage Regions Law", The Ministry of Culture may direct the relevant trusts or
institution who are taking care of the ancient monument to do so without altering the
original ancient form and structure and the original ancient workmanship.
f) Under chapter IV, paragraph 6 of the "Protection and Preservation of Cultural
Heritage Regions Law", The Ministry of Culture may direct to be dismantled a
building which is not an ancient monument and which obstructs the view of an
ancient monument or surrounding natural landscape within the cultural heritage
region.
g) The provisions of this code relating to the construction, repair, alteration, addition,
restoration and movement of structures, and change of occupancy shall not be
mandatory for historic buildings where such buildings are judged by the relevant
planning authority to not constitute a distinct life safety hazard.
h) On completion of the development the developer will repair the footways and
carriageways around the building to a standard specified by the authority and, where
appropriate include any necessary tree planting or landscaping as part of the
development cost.
2.10.9.2 Flood hazard areas
Within flood hazard areas, where the work proposed constitutes substantial improvement, the
building shall be brought into compliance with Part 3, Structural Design, Flood Loads
Section.
Exception: Historic buildings that are:
a) Listed or preliminarily determined to be eligible to be listed buildings,
b) Determined by the Concerned Department as contributing to the historical
significance of a registered historic district or a district preliminarily determined to
qualify as an historic district; or
c) Designated as historic under a state or local historic preservation program that is
approved by the Concerned Department.
The historic buildings need not meet new construction requirements for any category of
renovation or reuse, including change in occupancy, when the buildings are not judged by
building official to constitute distinct life-safety hazard.
2.10.10 Accessibility for Existing Buildings
2.10.10.1 Scope
The provisions of Sections 2.10.11.1 through 2.10.11.9 apply to maintenance, change of
occupancy, additions and alterations to existing buildings, including those identified as
historic buildings.
occupancy. The analysis shall demonstrate that the building with the work completed is
capable of resisting the loads specified in Chapter 3, Structural Design.
2.10.11.2 Submittal
The results of the investigation as required in Section 2.10.12.4, along with proposed
compliance alternatives, shall be submitted to the relevant planning authority.
2.10.11.3 Determination of compliance
The relevant planning authority shall determine whether the existing building, with the
proposed addition, alteration or change of occupancy, complies with the provisions of this
section.
2.10.11.2 Application Forms and Submission Requirements
Applications on buildings should be made and the information required should be provided.
In addition to the normal requirements, the following is required for applications within the
urban conservation areas which should comply with part 1 of this code :
1) When an application involves the demolition of a building within an area, A two
streetscape elevations (scale 1:100) are required, one indicating the relationship of the
existing building with adjacent buildings, and another showing the new construction
in the context of the streetscape;
2) When an application involves the opening of a garage or construction of a garage
cluster, a block plan (scale 1:500) is required, indicating the site in relation to the
street network and the street width adjacent to the site access. Proper elevations are to
be submitted of the entrance to the garage cluster along the street alignment,
including drawings of the adjacent facades on either side of he main site entrance;
3) Elevations (scale 1:50) should show in detail all materials and colour schemes
proposed. Any signage and/or advertisements proposed on commercial premises are
to be included in the elevations. In particularly sensitive cases 1:20 detailed drawings
will be required;
4) When an application involves construction in a backyard/garden or courtyard,
photographs showing all sides of the backyard/garden or courtyard are required.
BUILT-UP AREA RATIO: It means the ratio between the built-up area and the total land
area. This is the same as plinth area ratio.
PLINTH AREA RATIO: It means the ratio between the plinth area and the total land area.
This is the same as built-up area ratio.
FLOOR AREA INDEX (FAI) OR FLOOR AREA RATIO (FAR): Floor area index means the
total gross floor area (GFA) divided by the land area belonging to the particular building and
floor area ratio means the ratio of the above mentioned areas. There are zonal FAI indicating
the floor area densities of zones and estates FAI which indicates the floor area densities of
estates.
For the purpose of urban planning, the floors which are only covered but not within the walls,
such as terraces, verandahs, balconies are calculated as 50 % of the floors.
GROSS FLOOR AREA (GFA): It means the total floor area calculated based on centre of
exterior walls, including the circulation area such as stairs, corridors, etc. but excluding the
technical area without floors shafts, ducts, lift wells etc.
CUL-DE-SAC: It means a street or lane closed at one end and can be also called dead-end
street.
CBD OR CENTRAL BUSINESS DISTRICT: It means area or locality in a city or town
having business, cultural and other functions concentrated in that district or locality.
DEPTH: In respect of a building, means the measured distance between the front line of the
building and the back line of the rear main wall which separates the main building from the
open space or in case of row blocks, the side shorter than the longer side.
DETACHED BUILDING: It means any building not attached to any other buildings.
Normally, single family houses are detached building.
DIVISION WALL OR (PARTY WALL) It means a wall forming part of a building and used
or constructed for separation of adjoining buildings belonging to different owners or
occupants or constructed to be occupied by different persons constructed at the abutting
common boundary.
DUPLEX HOUSE: It means any building with two residential units designed to be abutting to
each other separated by a division wall. Each unit has its own separate entrance and each unit
shall have one or more storeys used only by the same people.
EXTERNAL WALL: It means an outer wall of a building and not immediately adjoining a
wall of another building.
FIRE WALL: It means any wall of materials having the fire resistance as required under Part
9 and 10 of these codes and constructed to be used for the separation of adjoining buildings or
premises or separation of parts of building to prevent or reduce the spreading of fire from one
building to another or from one part of a building to another part of that building.
GREEN AREA: It means not occupied by any structures including the traffic and parking
areas and covered only by grass and trees or bear land covered by vegetations.
GROUND STOREY: It means the storey at the ground level of a building to which there is an
entrance from outside on or above the level of the ground.
HUMAN HABITATION: It means usage of people as living, sleeping, studying or other
functions where the people stay more than 6 hours per day.
HUMAN SETTLEMENT: It means areas where human beings reside or occupy to practice
their activities.
INFRASTRUCTURE: It means the systems or part of systems like roads, water supply,
electricity, waste disposal, etc. that are essential for proper functioning of human settlements,
group of buildings or separate buildings.
PARKING AISLE: It means an access lane or driveway with adjacent parking stalls.
PARKING STALL: It means space for a parking of motor vehicle, a car or a motor cycle
parking lot.
PLOT: It means land area defined by the concerned authority with measurements.
POINT BLOCK: It means a building with the lengths less than two times the widths of
respective buildings.
SETBACK DISTANCE: It means the distance, a building or any part of a building has to
maintain from other buildings, boundary line or any other element.
TERRACE HOUSE: It means any building with more than three residential units designed to
be in a row. Each unit has its own separate entrance and each unit may have more than one
storey but used only by the same family and the units are separated by division wall.
LANES FOR MOTOR CYCLES: It shall be provided at the side of pedestrian footways,
where it is possible and are required at motor vehicle free zones such as parks and green
areas.
LANES FOR SLOW-MOVING VEHICLES: Lanes such as bicycles and tricycles shall be
provided at the side of roads where it is possible and are required at motor roads planned
besides the busy streets or as required in the detailed plans of respective settlements.
FIRST CLASS AREA: Area which is defined by authorities of the respective towns and
cities which have basically residential characters with larger plot sizes.
2.11.1.3 Classification of roads
All roads outside the urban areas are classified as follows:
a) UNION HIGHWAY ROADS OR INTER-REGION ROADS:
These are roads planned to connect from one region to others and are free of all
vehicles which are not motorized and which maximum speed 50 miles per hours.
These are roads planned to connect from one region to others must have minimum of
two lanes in one direction in addition to one side lane meant for emergency stopping
or for police and lifesaving vehicles. The lane widths must have minimum 14 feet
each and the side lane width shall be minimum 8 feet.
b) TOWNSHIP ROADS:
Township roads are the roads connecting between the rural settlements or between
the rural settlements or connecting between small urban centres.
Such roads must have the minimum of two lanes and shoulders on each side where
each lane having minimum 12 feet and shoulders minimum 4 feet. For such rural
roads, there shall be pedestrian path at least at one side with minimum of 6 feet width.
c) RURAL ROADS:
Rural roads are the roads connecting between the rural settlements or between the
rural settlements and their urban centres.
Such roads must have the minimum of two lanes and shoulders on each side where
each lane having minimum 10 feet and shoulders minimum 3 feet. For such rural
roads, there shall be pedestrian path at least at one side with minimum of 5 feet width.
d) URBAN ROADS:
All urban roads have the following classifications:
1) Urban Avenues/ Boulevard: Urban Avenues are the roads connecting zones
in the urban areas and are longer than 5 miles. These are roads must have
minimum of two lanes in one direction in addition to paved platforms on each
side. The urban avenues must have a green dividing strip minimum in the
middle and the lane widths must have minimum 14 feet each and the platform
width shall be minimum 6 feet.
2) Urban Main Road: Urban main roads are the roads connecting one the zone
in the urban areas and which are not longer than 5 miles. These are roads
must have minimum of two lanes in one direction in addition to paved
platforms on each side. The lane widths must have minimum 12 feet each and
the platform width shall be minimum 5 feet.
3) Feeder Roads: Feeder roads are the roads connecting collector roads and
urban avenues or the urban main roads where several collector roads are
connected. These are roads which have minimum two lanes in addition to
paved platforms on each side. The lane widths must have minimum 12 feet
each and the platform width shall be minimum 4 feet.
4) Collector Roads: Collector roads are the roads connecting between the feeder
roads and residential areas. These are roads which have minimum two lanes
in addition to paved platforms on each side. The lane widths shall have
minimum 12 feet each and the platform width shall be minimum 4 feet.
5) Residential roads: Residential roads are the roads in the residential areas.
These are roads which have minimum two lanes in addition to paved
platforms on each side. The lane widths shall have minimum 10 feet each and
the platform width shall be minimum 4 feet.
6) Short residential roads: Residential roads serving less than 4 units can be of
one lane unless the roads do not exceed 300 feet in length, and these roads
must be consist of two lanes if these served more than 4 units and longer than
300 feet.
7) Cul-de-sacs: All cul-de-sacs longer than 300 feet in length must have the
minimum width of 20 feet, such cul-de-sacs must be provided turning circle.
8) One Way roads: One way roads can be planned in the residential areas meant
only for one direction. These have minimum lane widths of 14 feet.
9) Service roads: Service roads are the roads where the usage is limited only to
delivery vehicles. These roads shall have minimum road width of 10 feet.
10) All gradient roads longer than 300 feet must have maximum gradient for
10%.
11) The gradients of minor roads adjoining the major roads must have the
maximum gradient of 12%.
2.11.2 Environmental Issues
a) Every building to be erected shall generally be considered as non-disturbing and non-
polluting to the environment, for that reason the first and foremost consideration of all
architects is the “Environmental Issue”.
b) Whenever any building is planned, the architect should first make the environmental
assessments, these include:-
1) The role and position of the planned building in the environment, whether or not
the building to be constructed is disturbing to environment visually or physically.
2) The building to be constructed shall consider the laws concerning the
conservation of heritage in Myanmar.
c) The concepts on sources of infrastructure and waste disposal of the building, during the
construction process and after the completion of building.
d) The expected traffic generated during and after the building completion.
e) The concept of facilities for entering, parking and departing the building
f) The concept for public facilities such as green areas, schools, shopping, social amenities,
etc.
2.11.3 Urban Densities
a) In conservation zones and the CBD areas of cities and towns, or in the areas defined as
high density zones, the densities should be in line with by-laws and zoning plans of
respective towns where available (TWG 1).
b) Outside conservation zones and CBD areas or outside quasi such areas, the following
estate densities should be maintained
1) In multi-storeyed residential estates, estate floor area index should not exceed 1.5
2) In multi-storeyed residential estates, the built-up area ratio shall not be more than
0.7 (total built-up area/open area including traffic area <0.3)
3) In the areas with single family units or duplexes, there shall not be more than 20
units per acre
c) Outside conservation zones and CBD areas or outside quasi CBD areas, the open space
for buildings abutting a street shall be:-
1) In respect of other buildings used for non-residential purposes, not less than one-
tenth of the built-up area of the building lot;
2) In respect of a building with mixed residential and commercial buildings, not less
than one-third of the built-up area of the building lot;
d) The plot sizes in the urban settlements are defined in TWG 1 of this code, and these are to
be followed accordingly.
space measured between external walls of the building and the boundary of the plot;
and 3 feet clear space between the extreme projections of the buildings such as roof
edges, gutters, etc. In cases where the buildings exceed 3 stories, the space mentioned
here shall increase with the rate of 1 foot or one tenth of floor to floor height for
every increase of a story (or floor to floor height, whichever is greater) and the space
shall be up to 10 feet between external walls of the building and boundary.
b) For areas outside conservation zones and Central Business District which are not
defined as first class areas there shall be minimum of 3 feet clear space between
external walls of the building or any elements of the building and one side of the plot
shall have the minimum space of 6 feet clear space, and the boundary of the plot, if
the building does not exceed three stories. In cases where the buildings exceed 3
stories, the space mentioned here shall increase with the rate of 1 foot or one tenth of
floor to floor height for every increase of a story (or floor to floor height, whichever
is greater) and the space shall be up to 6 feet between external walls of the building
and boundary.
c) For duplex houses and terrace houses, clear space of 3 feet must be maintained
between the extreme projections of the buildings (roof edges, balconies, etc.) and the
boundary of the plot.
d) For multi-storeyed residential buildings, in the estates outside CBD areas or quasi
equivalent to such areas, unless otherwise mentioned in the specific bye-laws of some
cities:-
1) For multi-storeyed row blocks with several units parallel and in front to front
position, the wall to wall distance shall be not less than the height of the higher
building, in the cases where the building heights are different, and minimum 50
feet must be maintained for driveway, parking, aprons and platforms
2) For multi-storeyed row blocks with several units parallel to each other and
having back to back position, the wall to wall distance shall be not less than
half the height of the higher building, in the cases where the building heights
are different and minimum of 30 feet must be maintained as service back lane
meant for septic tanks, other infrastructural requirements and as free spaces.
3) For buildings where the gable side abuts the longitudinal side of the building,
the space between the buildings shall be not less than half the height of the
higher building; in the cases the building heights are different and minimum of
30 feet shall be provided for free flow of air and for other infrastructural
requirements. ( the different cases are shown in Figure 1 and 2)
4) For multi-storeyed point blocks with several units facing each other, the
spacing shall be not less than half the height of the higher building, and that
distance shall be minimum 40 feet for residential road and for other
infrastructural requirements.
(Multi-storeyed point blocks in these codes are defined in part I of these codes)
e) For buildings in the CBD areas or quasi equivalent to such areas, the building
spacing rules are to follow the local codes wherever available.
minimum
H
minimum
0.5 H H
Front to front
Back to back position
position
Back lane
minimum
minimum 50'
30'
b) Where buildings abut on a street, there shall not be permanent structures like
verandahs, balconies, sun-shades, canopies, etc. built beyond the property line of
respective buildings.
2.11.5.4 Walkways and covered walkways
a) The width of any covered or uncovered walkway shall not be less than 7 feet if the
walkway is in a confined walls and not less than 4 feet in the open space.
b) Where there is a change in levels along the walkway there shall be steps with risers
not exceeding 7 inches and treads not less than 16 inches or a pedestrian ramp of
gradient not exceeding 10 % or rise: run ratio of 1:10. (see also part 5 of these codes)
c) Where a service road is designed in the residential areas, the walkway is required to
be provided along the street.
2.11.6 Roads and Parking Spaces
a) The width of one lane of the road for motor vehicles is minimum 12 feet, in the
residential areas; the paved area of the road meant for both ways must be at least be
16 feet with 2 feet shoulder at both sides.
b) The internal turning radius of roads in the residential areas shall be 12 feet minimum
and the internal turning radius of parking access way shall be 10 feet minimum.
c) Parking (A parking stall means a space for a parking of motor car and a parking aisle
means an access lane or driveway with adjacent parking stalls.) The general
requirement for parking spaces for cars shall be:
1) Minimum dimensions of parking stalls are 8 feet width and 16 feet in length
when stalls are perpendicular to or with angle to the aisles.
2) Minimum dimensions of parking stalls are 8 feet width and 18 feet in length
when stalls are parallel to the aisles.
Figure 2.11.3 Position of Parking Stalls and Required Dimensions (Above figure)
Figure 2.11.4 Places to Maintain Obstruction Free Zones and Parking Stalls with
Adjacent Obstructions
(For parallel parking, where a car cannot be parked by reversing, the length of stall shall be 24'.)
2.11.6.1 The minimum width of parking aisle
The minimum width of parking aisle shall be as follows:
Table 2.11.1 Minimum Widths of Parking Aisles
Two -way traffic
One -way traffic flow
flow
Parking Angle
Stalls on 1 side Stalls on 2 sides Stalls on 1 or 2 sides
Figure 2.11.7 Dimensions of Parking Aisles with Parking Stalls at Different Angles
c) The clear ramps and access-ways shall have physical separations (with raised
brickwork, concrete blocks, etc.) if these are used in two directions at one level, with
minimum height of 9 inches above the driveway level.
d) There shall be a straight landing of minimum 30 feet in length every after 160 feet of
ramps with gradients given in the table below.
Table 2.11.2 Type of Ramps and Access Ways and Widths
garages. The road and parking areas cannot be counted as play and green areas as
required in part 2, paragraph 6 of these codes.
b) For shopping centres, there shall be minimum one parking space for 1000 square feet
sales floor area, planned separately as parking lots or as parking spaces.
c) For offices in the urban areas, there should be minimum one parking space for 10
employees, planned separately as parking lots or as parking space.
d) For other commercial establishments like banks, restaurants, clubs, hotels, etc. the
additional calculation for parking requirements must be submitted together with
planning and building permit.
2.11.7 Landscaping and Recreation Areas
In the third phase, the details of this section will be described depending on the resources’
availability.
In the third phase, the details of this section will be described depending on the resources’ availability.