GROUP- A
(Multiple choice type questions)
1. Choose the correct alternatives from any five of the followings: 1×5
(i) Circuit breaker usually operates under
(a) Steady-state short- circuit current
(b) Sub-transient state of short-circuit current
(c) Transient state of short circuit- current
(d) None of these
Ans.(c)
ii) A 50 Hz, 3- phase synchronous generator has inductance per phase of 15
mH. The capacitance of generator and circuit breaker is 0.002 µF. Its
frequency of oscillation is
(a) 29 kHz (b) 2.9 kHz (c) 290 kHz (d) 29 MHz
3. The single line diagram of a network is shown in the figure below. The series line
reactance is 0.001 p.u. per km and shunt susceptance is 0.0016 p.u. per km.
Assemble the bus admittance matrix (YBUS) of the network.
GROUP- C
(Long answer type questions)
Answer any one of the following. 1 ×15
4. (a) If the inductance and capacitance of a power system are respectively 1 H and
0.001 µF and the instantaneous value of interrupted current is 10 A, then find the
voltage across the breaker contacts. 3
(a) Two 10 MVA, 50 Hz, 11 kV alternators, each with a 20% reactance, run in
parallel on a section bus-bar A which is connected through a 30 % bus-bar reactor
rated at 20 MVA to a bus-bar B having two generators similar to those of A. A %
MVA feeder having 5 % reactance is connected to bus-bar A. Calculate the steady
value of the fault current if a short-circuit occur between the three conductors at
the far end of the feeder. 6
(b) A 50 Hz, 11 KV, three-phase alternator with earthed neutral has an inductance
per phase 2 mH and is connected to busbar through a circuit breaker. The capacitance to
earth between the alternator and the circuit breaker is 0.02 µF per phase. A fault occurs
just beyond the CB, which opens when the symmetrical SC current is 7000 A
(rms).Ignoring the first pole to clear factor, calculate the following:
(a) Maximum voltage across the contacts of the circuit breaker.
(b) Frequency of oscillations.
(c) Average rate of rise of re-striking voltage up to the first peak. 6
5. a) Discuss the advantages of using Y bus model of power system network for the
load flow analysis. 3
Choosing 200 MVA and 35kV as the base quantities, compute per unit reactances
of the three generators referred to these base quantities. All the generators are
connected to common bus-bars. 5