Fault
Fault
Fault
g
GE Industrial Systems
831776A2.CDR
E83849
T
GIS ERE
RE
GE Multilin ISO9001:2000
LISTED EM I
G
*1601-0081-U2*
Addendum
g
GE Industrial Systems
ADDENDUM
This addendum contains information that relates to the L90 Line Current Differential System, version 5.7x. This adden-
dum lists a number of information items that appear in the instruction manual GEK-113527A (revision U2) but are not
included in the current L90 operations.
The following functions and items are not yet available with the current version of the L90 relay:
• Signal sources SRC 5 and SRC 6.
Version 4.0x and higher releases of the L90 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S.
• The new CT/VT modules are specified with the following order codes: 8F, 8H 8L, 8N.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:
The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S), and
the old CT/VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mis-
matches, the new CPU and CT/VT modules have blue labels and a warning sticker stating “Attn.: Ensure CPU and
DSP module label colors are the same!”. In the event that there is a mismatch between the CPU and CT/VT module,
the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be displayed.
All other input/output modules are compatible with the new hardware.
With respect to the firmware, firmware versions 4.0x and higher are only compatible with the new CPU and CT/VT mod-
ules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older CPU and CT/VT modules.
Table of Contents
TABLE OF CONTENTS
5.7.11 AUTORECLOSE.............................................................................................5-249
5.8 INPUTS/OUTPUTS
5.8.1 CONTACT INPUTS ........................................................................................5-261
5.8.2 VIRTUAL INPUTS ..........................................................................................5-263
5.8.3 CONTACT OUTPUTS ....................................................................................5-264
5.8.4 VIRTUAL OUTPUTS ......................................................................................5-266
5.8.5 REMOTE DEVICES........................................................................................5-267
5.8.6 REMOTE INPUTS ..........................................................................................5-268
5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS ...............................................5-269
5.8.8 REMOTE OUTPUTS ......................................................................................5-270
5.8.9 DIRECT INPUTS/OUTPUTS ..........................................................................5-270
5.8.10 RESETTING ...................................................................................................5-273
5.8.11 IEC 61850 GOOSE ANALOGS ......................................................................5-273
5.8.12 IEC 61850 GOOSE INTEGERS .....................................................................5-274
5.9 TRANSDUCER INPUTS AND OUTPUTS
5.9.1 DCMA INPUTS ...............................................................................................5-275
5.9.2 RTD INPUTS ..................................................................................................5-276
5.9.3 DCMA OUTPUTS ...........................................................................................5-278
5.10 TESTING
5.10.1 TEST MODE ...................................................................................................5-281
5.10.2 FORCE CONTACT INPUTS...........................................................................5-282
5.10.3 FORCE CONTACT OUTPUTS.......................................................................5-283
5.10.4 CHANNEL TESTS ..........................................................................................5-284
5.10.5 PHASOR MEASUREMENT UNIT TEST VALUES .........................................5-284
Before attempting to install or use the relay, it is imperative that all WARNINGS and CAUTIONS
in this manual are reviewed to help prevent personal injury, equipment damage, and/or down-
time.
WARNING CAUTION
1.1.2 INSPECTION CHECKLIST
1. Open the relay packaging and inspect the unit for physical damage.
2. View the rear nameplate and verify that the correct model has been ordered.
Model: L90G00HCHF8AH6AM6BP8BX7A
Technical Support:
Made in
Tel: (905) 294-6222 http://www.GEmultilin.com ®
®
Canada
Fax: (905) 201-2098 - M A A B 9 7 0 0 0 0 9 9 -
831795A1.CDR
1 Historically, substation protection, control, and metering functions were performed with electromechanical equipment. This
first generation of equipment was gradually replaced by analog electronic equipment, most of which emulated the single-
function approach of their electromechanical precursors. Both of these technologies required expensive cabling and auxil-
iary equipment to produce functioning systems.
Recently, digital electronic equipment has begun to provide protection, control, and metering functions. Initially, this equip-
ment was either single function or had very limited multi-function capability, and did not significantly reduce the cabling and
auxiliary equipment required. However, recent digital relays have become quite multi-functional, reducing cabling and aux-
iliaries significantly. These devices also transfer data to central control facilities and Human Machine Interfaces using elec-
tronic communications. The functions performed by these products have become so broad that many users now prefer the
term IED (Intelligent Electronic Device).
It is obvious to station designers that the amount of cabling and auxiliary equipment installed in stations can be even further
reduced, to 20% to 70% of the levels common in 1990, to achieve large cost reductions. This requires placing even more
functions within the IEDs.
Users of power equipment are also interested in reducing cost by improving power quality and personnel productivity, and
as always, in increasing system reliability and efficiency. These objectives are realized through software which is used to
perform functions at both the station and supervisory levels. The use of these systems is growing rapidly.
High speed communications are required to meet the data transfer rates required by modern automatic control and moni-
toring systems. In the near future, very high speed communications will be required to perform protection signaling with a
performance target response time for a command signal between two IEDs, from transmission to reception, of less than 3
milliseconds. This has been established by the IEC 61850 standard.
IEDs with the capabilities outlined above will also provide significantly more power system data than is presently available,
enhance operations and maintenance, and permit the use of adaptive system configuration for protection and control sys-
tems. This new generation of equipment must also be easily incorporated into automation systems, at both the station and
enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals.
a) UR BASIC DESIGN 1
The UR is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output
signals. The UR can communicate over a local area network (LAN) with an operator interface, a programming device, or
another UR device.
LAN
Programming Operator
Device Interface
827822A2.CDR
b) UR SIGNAL TYPES
The contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Both ‘wet’ and ‘dry’
contacts are supported.
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic™ equations used to customize
the device. Virtual outputs can also serve as virtual inputs to FlexLogic™ equations.
The analog inputs and outputs are signals that are associated with transducers, such as Resistance Temperature Detec-
tors (RTDs).
The CT and VT inputs refer to analog current transformer and voltage transformer signals used to monitor AC power lines.
The UR-series relays support 1 A and 5 A CTs.
The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series
devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic™
operands inserted into IEC 61850 GSSE and GOOSE messages.
The direct inputs and outputs provide a means of sharing digital point states between a number of UR-series IEDs over a
dedicated fiber (single or multimode), RS422, or G.703 interface. No switching equipment is required as the IEDs are con-
nected directly in a ring or redundant (dual) ring configuration. This feature is optimized for speed and intended for pilot-
aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis.
c) UR SCAN OPERATION
1 The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the
logic program (FlexLogic™ equation), and then sets each output to the appropriate state in an output status table. Any
resulting task execution is priority interrupt-driven.
Read Inputs
Protection elements
serviced by sub-scan
Protective Elements
PKP
Solve Logic DPO
OP
Set Outputs
827823A1.CDR
The firmware (software embedded in the relay) is designed in functional modules which can be installed in any relay as
required. This is achieved with object-oriented design and programming (OOD/OOP) techniques.
Object-oriented techniques involve the use of objects and classes. An object is defined as “a logical entity that contains
both data and code that manipulates that data”. A class is the generalized form of similar objects. By using this concept,
one can create a protection class with the protection elements as objects of the class, such as time overcurrent, instanta-
neous overcurrent, current differential, undervoltage, overvoltage, underfrequency, and distance. These objects represent
completely self-contained software modules. The same object-class concept can be used for metering, input/output control,
hmi, communications, or any functional entity in the system.
Employing OOD/OOP in the software architecture of the L90 achieves the same features as the hardware architecture:
modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection,
transformer protection, distance protection) is constructed by combining objects from the various functionality classes. This
results in a common look and feel across the entire family of UR-series platform-based applications.
As described above, the architecture of the UR-series relays differ from previous devices. To achieve a general understand-
ing of this device, some sections of Chapter 5 are quite helpful. The most important functions of the relay are contained in
“elements”. A description of the UR-series elements can be found in the Introduction to elements section in chapter 5.
Examples of simple elements, and some of the organization of this manual, can be found in the Control elements section of
chapter 5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A
description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section
in chapter 5.
The faceplate keypad and display or the EnerVista UR Setup software interface can be used to communicate with the relay.
1
The EnerVista UR Setup software interface is the preferred method to edit settings and view actual values because the PC
monitor can display more information in a simple comprehensible format.
The following minimum requirements must be met for the EnerVista UR Setup software to properly operate on a PC.
• Pentium class or higher processor (Pentium II 300 MHz or higher recommended)
• Windows 95, 98, 98SE, ME, NT 4.0 (Service Pack 4 or higher), 2000, XP
• Internet Explorer 4.0 or higher
• 128 MB of RAM (256 MB recommended)
• 200 MB of available space on system drive and 200 MB of available space on installation drive
• Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color)
• RS232 and/or Ethernet port for communications to the relay
The following qualified modems have been tested to be compliant with the L90 and the EnerVista UR Setup software.
• US Robotics external 56K FaxModem 5686
• US Robotics external Sportster 56K X2
• PCTEL 2304WT V.92 MDC internal modem
1.3.2 INSTALLATION
After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following
procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD.
1. Insert the GE EnerVista CD into your CD-ROM drive.
2. Click the Install Now button and follow the installation instructions to install the no-charge EnerVista software.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.
5. In the EnerVista Launch Pad window, click the Add Product button and select the “L90 Line Current Differential Sys-
tem” from the Install Software window as shown below. Select the “Web” option to ensure the most recent software
release, or select “CD” if you do not have a web connection, then click the Add Now button to list software items for
the L90.
1
6. EnerVista Launchpad will obtain the software from the Web or CD and automatically start the installation program.
7. Select the complete path, including the new directory name, where the EnerVista UR Setup will be installed.
8. Click on Next to begin the installation. The files will be installed in the directory indicated and the installation program
will automatically create icons and add EnerVista UR Setup to the Windows start menu.
9. Click Finish to end the installation. The UR-series device will be added to the list of installed IEDs in the EnerVista
Launchpad window, as shown below.
a) OVERVIEW
The user can connect remotely to the L90 through the rear RS485 port or the rear Ethernet port with a PC running the
EnerVista UR Setup software. The L90 can also be accessed locally with a laptop computer through the front panel RS232
port or the rear Ethernet port using the Quick Connect feature.
• To configure the L90 for remote access via the rear RS485 port(s), refer to the Configuring Serial Communications
section.
• To configure the L90 for remote access via the rear Ethernet port, refer to the Configuring Ethernet Communications
1
section. An Ethernet module must be specified at the time of ordering.
• To configure the L90 for local access with a laptop through either the front RS232 port or rear Ethernet port, refer to the
Using the Quick Connect Feature section. An Ethernet module must be specified at the time of ordering for Ethernet
communications.
9. Enter the relay slave address, COM port, baud rate, and parity settings from the SETTINGS Ö PRODUCT SETUP ÖØ COM-
MUNICATIONS ÖØ SERIAL PORTS menu in their respective fields.
1 10. Click the Read Order Code button to connect to the L90 device and upload the order code. If an communications error
occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to
the relay setting values.
11. Click “OK” when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for RS232 communications. Proceed to the Connecting to the L90 section to
begin communications.
9. Enter the relay IP address specified in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP
ADDRESS) in the “IP Address” field.
10. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS Ö PROD-
1
UCT SETUP ÖØ COMMUNICATIONS ÖØ MODBUS PROTOCOL menu.
11. Click the Read Order Code button to connect to the L90 device and upload the order code. If an communications error
occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting
values.
12. Click OK when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the L90 section to
begin communications.
4. Select the Serial interface and the correct COM Port, then click Connect.
5. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the L90 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the L90. This ensures that configuration of the EnerVista UR Setup software matches the L90 model number.
Next, use an Ethernet cross-over cable to connect the laptop to the rear Ethernet port. The pinout for an Ethernet cross-
over cable is shown below.
1 4 5 6
3 END 1 END 2
2 7 Pin Wire color Diagram Pin Wire color Diagram
1 8 1 White/orange 1 White/green
2 Orange 2 Green
3 White/green 3 White/orange
4 Blue 4 Blue
5 White/blue 5 White/blue
6 Green 6 Orange
7 White/brown 7 White/brown
8 Brown 8 Brown
842799A1.CDR
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
1 Request
Request
timed
timed
out.
out.
Request timed out.
Request timed out.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the L90 and the laptop computer, and double-check the programmed IP address in
the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting, then repeat step 2 in the above procedure.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Hardware error.
Hardware error.
Hardware error.
Hardware error.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the L90 and the laptop computer, and double-check the programmed IP address in
the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting, then repeat step 2 in the above procedure.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Destination host unreachable.
Destination host unreachable.
Destination host unreachable.
Destination host unreachable.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the IP address is programmed in the local PC by entering the ipconfig command in the command window.
C:\WINNT>ipconfig
Windows 2000 IP Configuration
Ethernet adapter <F4FE223E-5EB6-4BFB-9E34-1BD7BE7F59FF>:
Connection-specific DNS suffix. . :
IP Address. . . . . . . . . . . . : 0.0.0.0
Subnet Mask . . . . . . . . . . . : 0.0.0.0
Default Gateway . . . . . . . . . :
Ethernet adapter Local Area Connection:
Connection-specific DNS suffix . :
IP Address. . . . . . . . . . . . : 1.1.1.2
Subnet Mask . . . . . . . . . . . : 255.0.0.0
Default Gateway . . . . . . . . . :
C:\WINNT>
It may be necessary to restart the laptop for the change in IP address to take effect (Windows 98 or NT).
Before using the Quick Connect feature through the Ethernet port, it is necessary to disable any configured proxy settings
in Internet Explorer.
1. Start the Internet Explorer software.
1
2. Select the Tools > Internet Options menu item and click on Connections tab.
3. Click on the LAN Settings button to open the following window.
4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon-
nected from the L90 relay.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or
online from http://www.GEmultilin.com). See the Software Installation section for installation details.
2. Start the Internet Explorer software.
3. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
4. Click the Quick Connect button to open the Quick Connect dialog box.
5. Select the Ethernet interface and enter the IP address assigned to the L90, then click Connect.
6. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the L90 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the L90. This ensures that configuration of the EnerVista UR Setup software matches the L90 model number.
When direct communications with the L90 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon-
nected from the L90 relay.
AUTOMATIC DISCOVERY OF ETHERNET DEVICES
The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ether-
net network.
Using the Quick Connect feature, a single click of the mouse will trigger the software to automatically detect any UR-series
relays located on the network. The EnerVista UR Setup software will then proceed to configure all settings and order code
options in the Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to
identify and interrogate, in seconds, all UR-series devices in a particular location.
1. Open the Display Properties window through the Site List tree as shown below:
1
842743A3.CDR
2. The Display Properties window will open with a status indicator on the lower left of the EnerVista UR Setup window.
3. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly setup for communications (steps A and B earlier).
If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4. The Display Properties settings can now be edited, printed, or changed according to user specifications.
Refer to chapter 4 in this manual and the EnerVista UR Setup Help File for more information about the
using the EnerVista UR Setup software interface.
NOTE
1 Please refer to Chapter 3: Hardware for detailed mounting and wiring instructions. Review all WARNINGS and CAUTIONS
carefully.
1.4.2 COMMUNICATIONS
The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ether-
net ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male
end is connected to the relay and the DB-9 or DB-25 female end is connected to the PC COM1 or COM2 port as described
in the CPU communications ports section of chapter 3.
All messages are displayed on a 2 × 20 backlit liquid crystal display (LCD) to make them visible under poor lighting condi-
tions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad
and display are not actively being used, the display will default to user-defined messages. Any high priority event driven
message will automatically override the default message and appear on the display.
Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
1
The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting
values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alterna-
tively, values may also be entered with the numeric keypad.
The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may
be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values.
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
• Actual values.
• Settings.
• Commands.
• Targets.
• User displays (when enabled).
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
SETTINGS
SYSTEM SETUP
The relay is defaulted to the “Not Programmed” state when it leaves the factory. This safeguards against the installation of
a relay whose settings have not been entered. When powered up successfully, the Trouble LED will be on and the In Ser-
vice LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain
until the relay is explicitly put in the “Programmed” state.
Select the menu message SETTINGS Ö PRODUCT SETUP ÖØ INSTALLATION Ö RELAY SETTINGS
RELAY SETTINGS:
Not Programmed
To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The faceplate
Trouble LED will turn off and the In Service LED will turn on. The settings for the relay can be programmed manually (refer
1 to Chapter 5) via the faceplate keypad or remotely (refer to the EnerVista UR Setup help file) via the EnerVista UR Setup
software interface.
It is recommended that passwords be set up for each security level and assigned to specific personnel. There are two user
password security access levels, COMMAND and SETTING:
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol-
lowing operations:
• operate breakers via faceplate keypad
• change state of virtual inputs
• clear event records
• clear oscillography records
• operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level
passwords.
NOTE
FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex-
Logic™ section in Chapter 5 for additional details.
1.5.7 COMMISSIONING
The L90 Line Current Differential System is a digital current differential relay system with an integral communications chan-
nel interface.
The L90 is intended to provide complete protection for transmission lines of any voltage level. Both three phase and single
phase tripping schemes are available. Models of the L90 are available for application on both two and three terminal lines.
The L90 uses per phase differential at 64 kbps transmitting two phaselets per cycle. The current differential scheme is
based on innovative patented techniques developed by GE. The L90 algorithms are based on the Fourier transform– 2
phaselet approach and an adaptive statistical restraint. The restraint is similar to a traditional percentage differential
scheme, but is adaptive based on relay measurements. When used with a 64 kbps channel, the innovative phaselets
approach yields an operating time of 1.0 to 1.5 cycles (typical). The adaptive statistical restraint approach provides both
more sensitive and more accurate fault sensing. This allows the L90 to detect relatively higher impedance single line to
ground faults that existing systems may not. The basic current differential element operates on current input only. Long
lines with significant capacitance can benefit from charging current compensation if terminal voltage measurements are
applied to the relay. The voltage input is also used for some protection and monitoring features such as directional ele-
ments, fault locator, metering, and distance backup.
The L90 is designed to operate over different communications links with various degrees of noise encountered in power
systems and communications environments. Since correct operation of the relay is completely dependent on data received
from the remote end, special attention must be paid to information validation. The L90 incorporates a high degree of secu-
rity by using a 32-bit CRC (cyclic redundancy code) inter-relay communications packet.
In addition to current differential protection, the relay provides multiple backup protection for phase and ground faults. For
overcurrent protection, the time overcurrent curves may be selected from a selection of standard curve shapes or a custom
FlexCurve™ for optimum co-ordination. Additionally, three zones of phase and ground distance protection with power
swing blocking, out-of-step tripping, line pickup, load encroachment, and permissive overreaching transfer trip (POTT) fea-
tures are included.
The L90 incorporates charging current compensation for applications on very long transmission lines without loss of sensi-
tivity. The line capacitive current is removed from the terminal phasors.
For breaker-and-a-half or ring applications, the L90 design provides secure operation during external faults with possible
CT saturation.
Voltage, current, and power metering is built into the relay as a standard feature. Current parameters are available as total
waveform RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
52
Monitoring 79
21G
Close Trip
2 50DD 50P
(2)
50_2
(2)
51P
(2)
51_2
(2)
50BF
(2)
87L 87LG
67P
(2)
68 78 21P
50N
(2)
51N
(2) 67N/Q
32N
(2)
Transducer inputs
Metering
FlexElementTM
27P
(2)
50G 51G
(2) (2)
59N
59X 27X
25
(2)
L90 Line Differential Protection System
831706AU.CDR
2.1.2 FEATURES
MONITORING:
• Oscillography of current, voltage, FlexLogic™ operands, and digital signals (1 × 128 cycles to 31 × 8 cycles configu-
rable).
• Events recorder: 1024 events.
• Fault locator.
METERING:
2 • Actual 87L remote phasors, differential current, channel delay, and channel asymmetry at all line terminals of line cur-
rent differential protection.
• Line current, voltage, real power, reactive power, apparent power, power factor, and frequency.
COMMUNICATIONS:
• Front panel RS232 port: 19.2 kbps.
• One or two rear RS485 ports: up to 115 kbps.
• 10Base-F Ethernet port supporting the IEC 61850 protocol.
2.1.3 ORDERING
a) OVERVIEW
The L90 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod-
ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information
required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules).
Order codes are subject to change without notice. Refer to the GE Multilin ordering page at
http://www.GEindustrial.com/multilin/order.htm for the latest details concerning L90 ordering options.
NOTE
The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regu-
lar CT/VT modules or the HardFiber modules). The order code options are described in the following sub-sections.
The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below.
2 SOFTWARE
N
P
R
|
|
|
00
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 and 10/100Base-T
RS485 and single mode ST 100Base-FX
RS485 and single mode ST redundant 100Base-FX
No software options
(IEC 61850 options 02 | | | | | | | | Breaker-and-a-half software
not available with 03 | | | | | | | | IEC 61850
type E CPUs) 05 | | | | | | | | Breaker-and-a-half software and IEC 61850
06 | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | IEC 61850 and phasor measurement unit (PMU)
08 | | | | | | | | Breaker-and-a-half and phasor measurement unit (PMU)
09 | | | | | | | | Breaker-and-a-half, IEC 61850, and phasor measurement unit (PMU)
MOUNT/COATING V | | | | | | | Vertical (3/4 rack)
B | | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | English display
D | | | | | | French display
R | | | | | | Russian display
A | | | | | | Chinese display
K | | | | | | Enhanced front panel with English display
M | | | | | | Enhanced front panel with French display
Q | | | | | | Enhanced front panel with Russian display
U | | | | | | Enhanced front panel with Chinese display
L | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | | 125 / 250 V AC/DC power supply
L | | | | | 24 to 48 V (DC only) power supply
CT/VT MODULES 8F | 8F | | Standard 4CT/4VT
8H | 8H | | Standard 8CT
8L | 8L | | Standard 4CT/4VT with enhanced diagnostics (required for PMU option)
8N | 8N | | Standard 8CT with enhanced diagnostics (required for PMU option)
DIGITAL INPUTS/OUTPUTS XX XX XX | No Module
4A 4A 4A | 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D | 16 digital inputs with Auto-Burnishing
4L 4L 4L | 14 Form-A (no monitoring) Latching outputs
67 67 67 | 8 Form-A (no monitoring) outputs
6A 6A 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C 6C | 8 Form-C outputs
6D 6D 6D | 16 digital inputs
6E 6E 6E | 4 Form-C outputs, 8 digital inputs
6F 6F 6F | 8 Fast Form-C outputs
6G 6G 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K 6K | 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
TRANSDUCER 5A 5A 5A | 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C | 8 RTD inputs
(select a maximum of 3 per unit) 5D 5D 5D | 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E 5E 5E | 4 RTD inputs, 4 dcmA inputs
5F 5F 5F | 8 dcmA inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7V RS422, 2 Channels, 2 Clock Inputs
7W RS422, 2 Channels
Table 2–5: L90 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS)
L90 - * ** - * * * - F ** - H ** - L ** - N ** - S ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT L90 | | | | | | | | | | | | Base Unit
CPU E | | | | | | | | | | | RS485 and RS485
G | | | | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | | | | RS485 and multi-mode ST 100Base-FX
K
L
M
N
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 and multi-mode ST redundant 100Base-FX
RS485 and single mode SC 100Base-FX
RS485 and single mode SC redundant 100Base-FX
RS485 and 10/100Base-T
2
P | | | | | | | | | | | RS485 and single mode ST 100Base-FX
R | | | | | | | | | | | RS485 and single mode ST redundant 100Base-FX
SOFTWARE 00 | | | | | | | | | | No software options
(IEC 61850 options 03 | | | | | | | | | | IEC 61850
not available with 06 | | | | | | | | | | One phasor measurement unit (PMU)
type E CPUs) 07 | | | | | | | | | | IEC 61850 and one phasor measurement unit (PMU)
MOUNT/COATING H | | | | | | | | | Horizontal (19” rack)
A | | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | | English display
D | | | | | | | | French display
R | | | | | | | | Russian display
A | | | | | | | | Chinese display
P | | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | | Enhanced front panel with English display
M | | | | | | | | Enhanced front panel with French display
Q | | | | | | | | Enhanced front panel with Russian display
U | | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | | 24 to 48 V (DC only) power supply
L | | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
PROCESS BUS MODULE | 81 | | | | | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX XX XX XX No Module
4A 4A | | 4 Solid-State (no monitoring) MOSFET outputs
4B 4B | | 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C | | 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D | | 16 digital inputs with Auto-Burnishing
4L 4L | | 14 Form-A (no monitoring) Latching outputs
67 67 | | 8 Form-A (no monitoring) outputs
6A 6A | | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B | | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C | | 8 Form-C outputs
6D 6D | | 16 digital inputs
6E 6E | | 4 Form-C outputs, 8 digital inputs
6F 6F | | 8 Fast Form-C outputs
6G 6G | | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H | | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K | | 4 Form-C and 4 Fast Form-C outputs
6L 6L | | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M | | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N | | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P | | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R | | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S | | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T | | 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U | | 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V | | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E 2E Bi-phase, single channel
2F 2F Bi-phase, dual channel
2G 2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
72 72 1550 nm, single-mode, LASER, 1 Channel
73 73 1550 nm, single-mode, LASER, 2 Channel
74 74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 7A 820 nm, multi-mode, LED, 1 Channel
7B 7B 1300 nm, multi-mode, LED, 1 Channel
7C 7C 1300 nm, single-mode, ELED, 1 Channel
7D 7D 1300 nm, single-mode, LASER, 1 Channel
7E 7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F 7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G 7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 7H 820 nm, multi-mode, LED, 2 Channels
7I 7I 1300 nm, multi-mode, LED, 2 Channels
7J 7J 1300 nm, single-mode, ELED, 2 Channels
7K 7K 1300 nm, single-mode, LASER, 2 Channels
7L 7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M 7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N 7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P 7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R 7R G.703, 1 Channel
7S 7S G.703, 2 Channels
7T 7T RS422, 1 Channel
7V 7V RS422, 2 Channels, 2 Clock Inputs
7W 7W RS422, 2 Channels
The order codes for the reduced size vertical mount units with the process bus module are shown below.
Table 2–6: L90 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS)
L90 - * ** - * * * - F ** - H ** - L ** - N ** - R ** Reduced Size Vertical Mount
BASE UNIT L90 | | | | | | | | | | Base Unit
CPU E | | | | | | | | | RS485 and RS485
G | | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | | RS485 and multi-mode ST 100Base-FX
K | | | | | | | | | RS485 and multi-mode ST redundant 100Base-FX
L | | | | | | | | | RS485 and single mode SC 100Base-FX
M | | | | | | | | | RS485 and single mode SC redundant 100Base-FX
2 SOFTWARE
N
P
R
|
|
|
00
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 and 10/100Base-T
RS485 and single mode ST 100Base-FX
RS485 and single mode ST redundant 100Base-FX
No software options
(IEC 61850 options 03 | | | | | | | | IEC 61850
not available with 06 | | | | | | | | Phasor measurement unit (PMU)
type E CPUs) 07 | | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING V | | | | | | | Vertical (3/4 rack)
B | | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | English display
D | | | | | | French display
R | | | | | | Russian display
A | | | | | | Chinese display
K | | | | | | Enhanced front panel with English display
M | | | | | | Enhanced front panel with French display
Q | | | | | | Enhanced front panel with Russian display
U | | | | | | Enhanced front panel with Chinese display
L | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | | 125 / 250 V AC/DC power supply
L | | | | | 24 to 48 V (DC only) power supply
PROCESS BUS MODULE | 81 | | | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX XX No Module
4A | 4 Solid-State (no monitoring) MOSFET outputs
4B | 4 Solid-State (voltage with optional current) MOSFET outputs
4C | 4 Solid-State (current with optional voltage) MOSFET outputs
4D | 16 digital inputs with Auto-Burnishing
4L | 14 Form-A (no monitoring) Latching outputs
67 | 8 Form-A (no monitoring) outputs
6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C | 8 Form-C outputs
6D | 16 digital inputs
6E | 4 Form-C outputs, 8 digital inputs
6F | 8 Fast Form-C outputs
6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K | 4 Form-C and 4 Fast Form-C outputs
6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7V RS422, 2 Channels, 2 Clock Inputs
7W RS422, 2 Channels
Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face-
plate, please provide the serial number of your existing unit.
Not all replacement modules may be applicable to the L90 relay. Only the modules specified in the order codes are
available as replacement modules.
NOTE
Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http://
www.GEindustrial.com/multilin/order.htm for the latest details concerning L90 ordering options.
NOTE
The replacement module order codes for the horizontal mount units are shown below.
The replacement module order codes for the reduced-size vertical mount units are shown below.
2 |
|
|
|
9M
9N
9P
9R
|
|
|
|
RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and 10/100Base-T (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and single mode ST 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and single mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
FACEPLATE/DISPLAY | 3F | Vertical faceplate with keypad and English display
| 3D | Vertical faceplate with keypad and French display
| 3R | Vertical faceplate with keypad and Russian display
| 3K | Vertical faceplate with keypad and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
DIGITAL | 4A | 4 Solid-State (no monitoring) MOSFET outputs
INPUTS/OUTPUTS | 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 digital inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
| 6C | 8 Form-C outputs
| 6D | 16 digital inputs
| 6E | 4 Form-C outputs, 8 digital inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
CT/VT | 8F | Standard 4CT/4VT
MODULES | 8G | Sensitive Ground 4CT/4VT
(NOT AVAILABLE FOR THE C30) | 8H | Standard 8CT
| 8J | Sensitive Ground 8CT
| 8L | Standard 4CT/4VT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8N | Standard 8CT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 72 | 1550 nm, single-mode, LASER, 1 Channel
| 73 | 1550 nm, single-mode, LASER, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
| 76 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
| 7A | 820 nm, multi-mode, LED, 1 Channel
| 7B | 1300 nm, multi-mode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, LASER, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multi-mode, LED, 2 Channels
| 7I | 1300 nm, multi-mode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, LASER, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7V | RS422, 2 Channels, 2 Clock Inputs
| 7W | RS422, 2 Channels
TRANSDUCER | 5A | 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS | 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
| 5E | 4 dcmA inputs, 4 RTD inputs
| 5F | 8 dcmA inputs
Dedicated inter-relay communications may operate over 64 kbps digital channels or dedicated fiber optic channels. Avail-
able interfaces include:
• RS422 at 64 kbps
• G.703 at 64 kbps
• Dedicated fiber optics at 64 kbps. The fiber optic options include: 2
– 820 nm multi-mode fiber with an LED transmitter.
– 1300 nm multi-mode fiber with an LED transmitter.
– 1300 nm single-mode fiber with an ELED transmitter.
– 1300 nm single-mode fiber with a laser transmitter.
– 1550 nm single-mode fiber with a laser transmitter.
– IEEE C37.94 820 nm multi-mode fiber with an LED transmitter.
All fiber optic options use an ST connector. L90 models are available for use on two or three terminal lines. A two terminal
line application requires one bidirectional channel. However, in two terminal line applications, it is also possible to use an
L90 relay with two bidirectional channels. The second bidirectional channel will provide a redundant backup channel with
automatic switchover if the first channel fails.
The L90 current differential relay is designed to function in a peer-to-peer or master-to-master architecture. In the peer-to-
peer architecture, all relays in the system are identical and perform identical functions in the current differential scheme. In
order for every relay on the line to be a peer, each relay must be able to communicate with all of the other relays. If there is
a failure in communications among the relays, the relays will revert to a master-to-peer architecture on a three-terminal sys-
tem, with the master as the relay that has current phasors from all terminals. Using two different operational modes
increases the dependability of the current differential scheme on a three-terminal system by reducing reliance on communi-
cations.
The main difference between a master and a slave L90 is that only a master relay performs the actual current differential
calculation, and only a master relay communicates with the relays at all other terminals of the protected line.
At least one master L90 relay must have live communications to all other terminals in the current differential scheme; the
other L90 relays on that line may operate as slave relays. All master relays in the scheme will be equal, and each will per-
form all functions. Each L90 relay in the scheme will determine if it is a master by comparing the number of terminals on the
line to the number of active communication channels.
The slave terminals only communicate with the master; there is no slave-to-slave communications path. As a result, a slave
L90 relay cannot calculate the differential current. When a master L90 relay issues a local trip signal, it also sends a direct
transfer trip (DTT) signal to all of the other L90 relays on the protected line.
If a slave L90 relay issues a trip from one of its backup functions, it can send a transfer trip signal to its master and other
slave relays if such option is designated. Because a slave cannot communicate with all the relays in the differential
scheme, the master will then “broadcast” the direct transfer trip (DTT) signal to all other terminals.
The slave L90 Relay performs the following functions:
• Samples currents and voltages.
• Removes DC offset from the current via the mimic algorithm.
• Creates phaselets.
• Calculates sum of squares data.
• Transmits current data to all master L90 relays.
• Performs all local relaying functions.
• Receives current differential DTT and Direct Input signals from all other L90 relays.
• Transmits direct output signals to all communicating relays.
• Sends synchronization information of local clock to all other L90 clocks.
Tx Rx
CHn
CHn
Rx Tx
IED-1 IED-2
Tx Rx
CHn
CHn
Optional redundant channel
Rx Tx
Tx Rx
CHn
CHn
Rx Tx
IED-1 IED-2
Tx Rx
CHn
CHn
Rx Tx
Tx Rx Tx Rx
CHn CHn
IED-3
The L90 has logic to detect that the communications channel is deteriorating or has failed completely. This can provide an
alarm indication and disable the current differential protection. Note that a failure of the communications from the master to
a slave does not prevent the master from performing the current differential algorithm; failure of the communications from a
slave to the master will prevent the master from performing the correct current differential logic. Channel propagation delay
is being continuously measured and adjusted according to changes in the communications path. Every relay on the protec-
tion system can assigned an unique ID to prevent advertent loopbacks at multiplexed channels.
This option allows the user to test the relay at one terminal of the line by looping the transmitter output to the receiver input;
at the same time, the signal sent to the remote will not change. A local loopback feature is included in the relay to simplify
single ended testing.
• Current differential protection: The current differential algorithms used in the L90 Line Current Differential System
are based on the Fourier transform phaselet approach and an adaptive statistical restraint. The L90 uses per-phase
differential at 64 kbps with two phaselets per cycle. A detailed description of the current differential algorithms is found
in chapter 8. The current differential protection can be set in a percentage differential scheme with a single or dual
slope.
2 • Backup protection: In addition to the primary current differential protection, the L90 Line Current Differential System
incorporates backup functions that operate on the local relay current only, such as directional phase overcurrent, direc-
tional neutral overcurrent, negative-sequence overcurrent, undervoltage, overvoltage, and distance protection.
• Multiple setting groups: The relay can store six groups of settings. They may be selected by user command, a con-
figurable contact input or a FlexLogic™ equation to allow the relay to respond to changing conditions.
• User-programmable logic: In addition to the built-in protection logic, the relay may be programmed by the user via
FlexLogic™ equations.
• Configurable inputs and outputs: All of the contact converter inputs (digital inputs) to the relay may be assigned by
the user to directly block a protection element, operate an output relay or serve as an input to FlexLogic™ equations.
All of the outputs, except for the self test critical alarm contacts, may also be assigned by the user.
• Metering: The relay measures all input currents and calculates both phasors and symmetrical components. When AC
potential is applied to the relay via the optional voltage inputs, metering data includes phase and neutral current, phase
voltage, three phase and per phase W, VA, and var, and power factor. Frequency is measured on either current or volt-
age inputs. They may be called onto the local display or accessed via a computer. All terminal current phasors and dif-
ferential currents are also displayed at all relays, allowing the user opportunity to analyze correct polarization of
currents at all terminals.
• Event records: The relay has a sequence of events recorder which combines the recording of snapshot data and
oscillography data. Events consist of a broad range of change of state occurrences, including input contact changes,
measuring-element pickup and operation, FlexLogic™ equation changes, and self-test status. The relay stores up to
1024 events with the date and time stamped to the nearest microsecond. This provides the information needed to
determine a sequence of events, which can reduce troubleshooting time and simplify report generation after system
events.
• Oscillography: The relay stores oscillography data at a sampling rate of 64 times per cycle. The relay can store a
maximum of 64 records. Each oscillography file includes a sampled data report consisting of:
– Instantaneous sample of the selected currents and voltages (if AC potential is used),
– The status of each selected contact input.
– The status of each selected contact output.
– The status of each selected measuring function.
– The status of various selected logic signals, including virtual inputs and outputs.
The captured oscillography data files can be accessed via the remote communications ports on the relay.
• CT failure and current unbalance alarm: The relay has current unbalance alarm logic. The unbalance alarm may be
supervised by a zero-sequence voltage detector. The user may block the relay from tripping when the current unbal-
ance alarm operates.
• Trip circuit monitor: On those outputs designed for trip duty, a trip voltage monitor will continuously measure the DC
voltage across output contacts to determine if the associated trip circuit is intact. If the voltage dips below the minimum
voltage or the breaker fails to open or close after a trip command, an alarm can be activated.
• Self-test: The most comprehensive self testing of the relay is performed during a power-up. Because the system is not
performing any protection activities at power-up, tests that would be disruptive to protection processing may be per-
formed. The processors in the CPU and all CT/VT modules participate in startup self-testing. Self-testing checks
approximately 85 to 90% of the hardware, and CRC/check-sum verification of all PROMs is performed. The proces-
sors communicate their results to each other so that if any failures are detected, they can be reported to the user. Each
processor must successfully complete its self tests before the relay begins protection activities.
During both startup and normal operation, the CPU polls all plug-in modules and checks that every one answers the
poll. The CPU compares the module types that identify themselves to the relay order code stored in memory and
declares an alarm if a module is either non-responding or the wrong type for the specific slot. When running under nor-
mal power system conditions, the relay processors will have idle time. During this time, each processor performs back-
ground self-tests that are not disruptive to the foreground processing.
c) TIME SYNCHRONIZATION
The relay includes a clock which can run freely from the internal oscillator or be synchronized from an external IRIG-B sig-
nal. With the external signal, all relays wired to the same synchronizing signal will be synchronized to within 0.1 millisecond.
d) FUNCTION DIAGRAMS
Disturbance
Detector
UR Platform 51P,N&G
Phasors Trip Output
dV Configurable
Computations
dt Logic
27P
V Sample Raw Compute
Filter
Value Phaselets
59P
21P&G
Sample
Hold
87L
PFLL Status Algorithm
Frequency
Deviation
Master Phase and Frequency
Clock Locked Loop (PFLL)
Phase
Deviation
PHASELETS TO REMOTE
Communications
Remote Relay
Interface PHASELETS FROM REMOTE
Peer Peer
Channel
Communication Control
Time
Stamps
Ping-pong Estimate
Time Stamp
Clock Algorithm Phase Angle
2 Phase
Deviation
Uncertainties
Estimate Phase
Clock Angle Correction
Control Phase Deviation
from GPS signal
Sampling
Control Frequency
Deviation
Sample Compute
Currents and Frequency
Voltages Deviation
Raw
Sample
Remove Decaying Compute Positive
Offset and Sequence
Charging Current Currents
Phaselets Compute
Phaselets Phasors
Phaselets
Align Phaselets
Phaselets
Compute Phasors and
Variance Parameters
Fault
Detector Trip Output
Disturbance
Logic
Detector
831749A1.CDR
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
NOTE FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE DISTANCE GROUND DISTANCE
Characteristic: mho (memory polarized or offset) or Characteristic: Mho (memory polarized or offset) or 2
quad (memory polarized or non-direc- Quad (memory polarized or non-direc-
tional), selectable individually per zone tional)
Number of zones: 3 Reactance polarization: negative-sequence or zero-sequence
Directionality: forward, reverse, or non-directional current
Reach (secondary Ω): 0.02 to 500.00 Ω in steps of 0.01 Non-homogeneity angle: –40 to 40° in steps of 1
Reach accuracy: ±5% including the effect of CVT tran- Number of zones: 3
sients up to an SIR of 30 Directionality: forward, reverse, or non-directional
Distance: Reach (secondary Ω): 0.02 to 500.00 Ω in steps of 0.01
Characteristic angle: 30 to 90° in steps of 1 Reach accuracy: ±5% including the effect of CVT tran-
Comparator limit angle: 30 to 90° in steps of 1 sients up to an SIR of 30
Directional supervision: Distance characteristic angle: 30 to 90° in steps of 1
Characteristic angle: 30 to 90° in steps of 1 Distance comparator limit angle: 30 to 90° in steps of 1
Limit angle: 30 to 90° in steps of 1 Directional supervision:
Right blinder (Quad only): Characteristic angle: 30 to 90° in steps of 1
Reach: 0.02 to 500 Ω in steps of 0.01 Limit angle: 30 to 90° in steps of 1
Characteristic angle: 60 to 90° in steps of 1 Zero-sequence compensation
Left Blinder (Quad only): Z0/Z1 magnitude: 0.00 to 10.00 in steps of 0.01
Reach: 0.02 to 500 Ω in steps of 0.01 Z0/Z1 angle: –90 to 90° in steps of 1
Characteristic angle: 60 to 90° in steps of 1 Zero-sequence mutual compensation
Time delay: 0.000 to 65.535 s in steps of 0.001 Z0M/Z1 magnitude: 0.00 to 7.00 in steps of 0.01
Timing accuracy: ±3% or 4 ms, whichever is greater Z0M/Z1 angle: –90 to 90° in steps of 1
Current supervision: Right blinder (Quad only):
Level: line-to-line current Reach: 0.02 to 500 Ω in steps of 0.01
Pickup: 0.050 to 30.000 pu in steps of 0.001 Characteristic angle: 60 to 90° in steps of 1
Dropout: 97 to 98% Left blinder (Quad only):
Memory duration: 5 to 25 cycles in steps of 1 Reach: 0.02 to 500 Ω in steps of 0.01
VT location: all delta-wye and wye-delta transformers Characteristic angle: 60 to 90° in steps of 1
CT location: all delta-wye and wye-delta transformers Time delay: 0.000 to 65.535 s in steps of 0.001
Voltage supervision pickup (series compensation applications): Timing accuracy: ±3% or 4 ms, whichever is greater
0 to 5.000 pu in steps of 0.001 Current supervision:
Operation time: 1 to 1.5 cycles (typical) Level: neutral current (3I_0)
Reset time: 1 power cycle (typical) Pickup: 0.050 to 30.000 pu in steps of 0.001
Dropout: 97 to 98%
Memory duration: 5 to 25 cycles in steps of 1
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
Operation time: 1 to 1.5 cycles (typical)
Reset time: 1 power cycle (typical)
LINE PICKUP
Phase instantaneous overcurrent: 0.000 to 30.000 pu
Undervoltage pickup: 0.000 to 3.000 pu
Overvoltage delay: 0.000 to 65.535 s
2 Slope # 2: 1 to 70%
Breakpoint between slopes: 0.0 to 20.0 pu in steps of 0.1
Overreach:
Pickup delay:
<2%
0.00 to 600.00 s in steps of 0.01
Zero-sequence current differential (87LG): Reset delay: 0.00 to 600.00 s in steps of 0.01
87LG pickup level: 0.05 to 1.00 pu in steps of 0.01 Operate time: <16 ms at 3 × pickup at 60 Hz
87LG slope: 1 to 50% (Phase/Ground IOC)
87LG pickup delay: 0.00 to 5.00 s in steps of 0.01 <20 ms at 3 × pickup at 60 Hz
DTT: Direct Transfer Trip (1 and 3 pole) to (Neutral IOC)
remote L90 Timing accuracy: Operate at 1.5 × pickup
±3% or ±4 ms (whichever is greater)
Operating Time: 1.0 to 1.5 power cycles duration
Asymmetrical channel delay compensation using GPS: NEGATIVE SEQUENCE TOC
asymmetry up to 10 ms Current: Phasor
LINE CURRENT DIFFERENTIAL TRIP LOGIC Pickup level: 0.000 to 30.000 pu in steps of 0.001
87L trip: Adds security for trip decision; creates 1 Dropout level: 97% to 98% of pickup
and 3 pole trip logic Level accuracy: ±0.5% of reading or ±0.4% of rated
DTT: Engaged Direct Transfer Trip (1 and 3 (whichever is greater)
pole) from remote L90 from 0.1 to 2.0 x CT rating
±1.5% of reading > 2.0 x CT rating
DD: Sensitive Disturbance Detector to detect
fault occurrence Curve shapes: IEEE Moderately/Very/Extremely
Stub bus protection: Security for ring bus and 1½ breaker Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
configurations
Extremely Inverse; I2t; FlexCurves™
Open pole detector: Security for sequential and evolving
(programmable); Definite Time (0.01 s
faults base curve)
PHASE/NEUTRAL/GROUND TOC Curve multiplier (Time dial): 0.00 to 600.00 in steps of 0.01
Current: Phasor or RMS Reset type: Instantaneous/Timed (per IEEE) and Lin-
Pickup level: 0.000 to 30.000 pu in steps of 0.001 ear
Dropout level: 97% to 98% of pickup Timing accuracy: Operate at > 1.03 × actual pickup
Level accuracy: ±3.5% of operate time or ±½ cycle
(whichever is greater)
for 0.1 to 2.0 × CT: ±0.5% of reading or ±0.4% of rated
(whichever is greater) NEGATIVE SEQUENCE IOC
for > 2.0 × CT: ±1.5% of reading > 2.0 × CT rating Current: Phasor
Curve shapes: IEEE Moderately/Very/Extremely Pickup level: 0.000 to 30.000 pu in steps of 0.001
Inverse; IEC (and BS) A/B/C and Short Dropout level: 97 to 98% of pickup
Inverse; GE IAC Inverse, Short/Very/
Level accuracy: 0.1 to 2.0 × CT rating: ±0.5% of reading
Extremely Inverse; I2t; FlexCurves™ or ±0.4% of rated (whichever is greater);
(programmable); Definite Time (0.01 s
> 2.0 × CT rating: ±1.5% of reading
base curve)
Overreach: < 2%
Curve multiplier: Time Dial = 0.00 to 600.00 in steps of
Pickup delay: 0.00 to 600.00 s in steps of 0.01
0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Reset type: Instantaneous/Timed (per IEEE)
Operate time: < 20 ms at 3 × pickup at 60 Hz
Timing accuracy: Operate at > 1.03 × actual pickup
±3.5% of operate time or ±½ cycle Timing accuracy: Operate at 1.5 × pickup
(whichever is greater) ±3% or ±4 ms (whichever is greater)
Programmability: any logical variable, contact, or virtual Operation: drive FlexLogic™ operands
input USER-PROGRAMMABLE PUSHBUTTONS (OPTIONAL)
FLEXELEMENTS™ Number of pushbuttons: 12 (standard faceplate);
Number of elements: 8 16 (enhanced faceplate)
Operating signal: any analog actual value, or two values in Mode: self-reset, latched
differential mode Display message: 2 lines of 20 characters each
Operating signal mode: signed or absolute value Drop-out timer: 0.00 to 60.00 s in steps of 0.05
Operating mode: level, delta Autoreset timer: 0.2 to 600.0 s in steps of 0.1
Comparator direction: over, under Hold timer: 0.0 to 10.0 s in steps of 0.1
Pickup Level: –90.000 to 90.000 pu in steps of 0.001 SELECTOR SWITCH
Hysteresis: 0.1 to 50.0% in steps of 0.1 Number of elements: 2
Delta dt: 20 ms to 60 days Upper position limit: 1 to 7 in steps of 1
Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001 Selecting mode: time-out or acknowledge
NON-VOLATILE LATCHES Time-out timer: 3.0 to 60.0 s in steps of 0.1
Type: set-dominant or reset-dominant Control inputs: step-up and 3-bit
Number: 16 (individually programmed) Power-up mode: restore from non-volatile memory or syn-
Output: stored in non-volatile memory chronize to a 3-bit control input or synch/
restore mode
Execution sequence: as input prior to protection, control, and
FlexLogic™ DIGITAL ELEMENTS
Number of elements: 48
Operating signal: any FlexLogic™ operand
Pickup delay: 0.000 to 999999.999 s in steps of 0.001
Dropout delay: 0.000 to 999999.999 s in steps of 0.001
Timing accuracy: ±3% or ±4 ms, whichever is greater
2.4.3 MONITORING
2.4.4 METERING
FREQUENCY DEMAND
Accuracy at Measurements: Phases A, B, and C present and maxi-
V = 0.8 to 1.2 pu: ±0.001 Hz (when voltage signal is used mum measured currents
for frequency measurement) 3-Phase Power (P, Q, and S) present
I = 0.1 to 0.25 pu: ±0.05 Hz and maximum measured currents
I > 0.25 pu: ±0.001 Hz (when current signal is used Accuracy: ±2.0%
for frequency measurement)
2.4.5 INPUTS 2
AC CURRENT CONTACT INPUTS WITH AUTO-BURNISHING
CT rated primary: 1 to 50000 A Dry contacts: 1000 Ω maximum
CT rated secondary: 1 A or 5 A by connection Wet contacts: 300 V DC maximum
Nominal frequency: 20 to 65 Hz Selectable thresholds: 17 V, 33 V, 84 V, 166 V
Relay burden: < 0.2 VA at rated secondary Tolerance: ±10%
Conversion range: Contacts per common return: 2
Standard CT: 0.02 to 46 × CT rating RMS symmetrical Recognition time: < 1 ms
Sensitive Ground CT module:
Debounce time: 0.0 to 16.0 ms in steps of 0.5
0.002 to 4.6 × CT rating RMS symmetrical
Continuous current draw:3 mA (when energized)
Current withstand: 20 ms at 250 times rated
Auto-burnish impulse current: 50 to 70 mA
1 sec. at 100 times rated
continuous at 3 times rated Duration of auto-burnish impulse: 25 to 50 ms
Short circuit rating: 150000 RMS symmetrical amperes, 250 DCMA INPUTS
V maximum (primary current to external Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10,
CT) 0 to 20, 4 to 20 (programmable)
AC VOLTAGE Input impedance: 379 Ω ±10%
VT rated secondary: 50.0 to 240.0 V Conversion range: –1 to + 20 mA DC
VT ratio: 1.00 to 24000.00 Accuracy: ±0.2% of full scale
Nominal frequency: 20 to 65 Hz; the nominal system fre- Type: Passive
quency should be chosen as 50 Hz or
60 Hz only.
RTD INPUTS
Types (3-wire): 100 Ω Platinum, 100 & 120 Ω Nickel, 10
Relay burden: < 0.25 VA at 120 V Ω Copper
Conversion range: 1 to 275 V Sensing current: 5 mA
Voltage withstand: continuous at 260 V to neutral Range: –50 to +250°C
1 min./hr at 420 V to neutral
Accuracy: ±2°C
CONTACT INPUTS Isolation: 36 V pk-pk
Dry contacts: 1000 Ω maximum
Wet contacts: 300 V DC maximum
IRIG-B INPUT
Amplitude modulation: 1 to 10 V pk-pk
Selectable thresholds: 17 V, 33 V, 84 V, 166 V
DC shift: TTL
Tolerance: ±10%
Input impedance: 22 kΩ
Contacts per common return: 4
Isolation: 2 kV
Recognition time: < 1 ms
Debounce time: 0.0 to 16.0 ms in steps of 0.5 REMOTE INPUTS (IEC 61850 GSSE/GOOSE)
Number of input points: 32, configured from 64 incoming bit pairs
Continuous current draw:3 mA (when energized)
Number of remote devices: 16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Number of remote DPS inputs: 5
HIGH RANGE
RATINGS
Nominal DC voltage: 125 to 250 V
Low range power supply: 8 A / 250 V
Minimum DC voltage: 88 V High range power supply: 4 A / 250 V
Maximum DC voltage: 300 V INTERRUPTING CAPACITY
Nominal AC voltage: 100 to 240 V at 50/60 Hz AC: 100 000 A RMS symmetrical
Minimum AC voltage: 88 V at 25 to 100 Hz DC: 10 000 A
Maximum AC voltage: 265 V at 25 to 100 Hz
Voltage loss hold-up: 200 ms duration at nominal
2.4.7 OUTPUTS
Break (DC inductive, L/R = 40 ms): Break (DC inductive, L/R = 40 ms):
VOLTAGE CURRENT
VOLTAGE CURRENT
24 V 1A
24 V 1A
48 V 0.5 A
48 V 0.5 A
125 V 0.3 A
125 V 0.3 A
250 V 0.2 A
250 V 0.2 A
Operate time: < 8 ms
Operate time: < 4 ms
Contact material: silver alloy
Contact material: silver alloy
LATCHING RELAY FAST FORM-C RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90 Make and carry: 0.1 A max. (resistive load)
2.4.8 COMMUNICATIONS
2.4.10 ENVIRONMENTAL
TYPE TESTS
TEST REFERENCE STANDARD TEST LEVEL
Dielectric voltage withstand EN60255-5 2.3 kV
Impulse voltage withstand EN60255-5 5 kV
2 Damped oscillatory
Electrostatic discharge
IEC61000-4-18 / IEC60255-22-1
EN61000-4-2 / IEC60255-22-2
2.5 kV CM, 1 kV DM
Level 3
RF immunity EN61000-4-3 / IEC60255-22-3 Level 3
Fast transient disturbance EN61000-4-4 / IEC60255-22-4 Class A and B
Surge immunity EN61000-4-5 / IEC60255-22-5 Level 3 and 4
Conducted RF immunity EN61000-4-6 / IEC60255-22-6 Level 3
Power frequency immunity EN61000-4-7 / IEC60255-22-7 Class A and B
Voltage interruption and ripple DC IEC60255-11 12% ripple, 200 ms interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC60255-25 Class A
Sinusoidal vibration IEC60255-21-1 Class 1
Shock and bump IEC60255-21-2 Class 1
Seismic IEC60255-21-3 Class 1
Power magnetic immunity IEC61000-4-8 Level 5
Pulse magnetic immunity IEC61000-4-9 Level 4
Damped magnetic immunity IEC61000-4-10 Level 4
Voltage dip and interruption IEC61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory IEC61000-4-12 2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC61000-4-16 Level 4
Voltage ripple IEC61000-4-17 15% ripple
Ingress protection IEC60529 IP40 front, IP10 back
Cold IEC60068-2-1 –40°C for 16 hours
Hot IEC60068-2-2 85°C for 16 hours
Humidity IEC60068-2-30 6 day, variant 1
Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz
RF immunity IEEE/ANSIC37.90.2 20 V/m, 80 MHz to 1 GHz
Safety UL508 e83849 NKCR
Safety UL C22.2-14 e83849 NKCR7
Safety UL1053 e83849 NKCR
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
2.4.13 APPROVALS
APPROVALS
COMPLIANCE APPLICABLE ACCORDING TO
COUNCIL DIRECTIVE
CE compliance Low voltage directive EN60255-5
EMC directive EN60255-26 / EN50263
EN61000-6-5 2
North America --- UL508
--- UL1053
--- C22.2 No. 14
2.4.14 MAINTENANCE
MOUNTING CLEANING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) Normally, cleaning is not required; but for situations where dust
of torque. has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be
powered up once per year, for one hour continuously, to
NOTE avoid deterioration of electrolytic capacitors.
a) HORIZONTAL UNITS
The L90 Line Current Differential System is available as a 19-inch rack horizontal mount unit with a removable faceplate.
The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains
additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
3
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
11.016”
[279,81 mm]
9.687”
[246,05 mm]
17.56”
[446,02 mm]
7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
19.040”
[483,62 mm]
842807A1.CDR
18.370”
[466,60 mm]
0.280”
[7,11 mm]
Typ. x 4
CUT-OUT
4.000”
[101,60 mm]
17.750”
[450,85 mm] 842808A1.CDR
b) VERTICAL UNITS
The L90 Line Current Differential System is available as a reduced size (¾) vertical mount unit, with a removable faceplate.
The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains
additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
7.482” 11.015”
1.329”
13.560”
3
15.000” 14.025”
4.000”
9.780”
843809A1.CDR
e UR SERIES
Figure 3–7: L90 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL)
Module withdrawal and insertion may only be performed when control power has been removed from the
unit. Inserting an incorrect module type into a slot may result in personal injury, damage to the unit or con-
WARNING
nected equipment, or undesired operation!
Proper electrostatic discharge protection (for example, a static strap) must be used when coming in con-
tact with modules while the relay is energized!
WARNING
The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules must only be replaced with
like modules in their original factory configured slots.
The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows
for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens
completely and allows easy access to all modules in the L90.
842812A1.CDR
The 4.0x release of the L90 relay includes new hardware modules.The new CPU modules are specified with codes
9E and higher. The new CT/VT modules are specified with the codes 8F and higher.
NOTE
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. To prevent hardware mismatches, the new modules have blue labels and a warning sticker stating “Attn.:
Ensure CPU and DSP module label colors are the same!”. In the event that there is a mismatch between the
CPU and CT/VT module, the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be dis-
played.
All other input and output modules are compatible with the new hardware. Firmware versions 4.0x and higher are
only compatible with the new hardware modules. Previous versions of the firmware (3.4x and earlier) are only com-
patible with the older hardware modules.
3
L90 RATINGS: Model: L90D00HCHF8AH6AM6BP8BX7A
000
Line Differential Relay
Mods:
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA Wiring Diagram: ZZZZZZ
Contact Inputs: 300V DC Max 10mA Inst. Manual: D
Contact Outputs: Standard Pilot Duty / 250V AC 7.5A Serial Number: MAZB98000029
360V A Resistive / 125V DC Break Firmware: D
GE Multilin 4A @ L/R = 40mS / 300W Mfg. Date: 1998/01/05
Technical Support:
Made in
Tel: (905) 294-6222 http://www.GEIndustrial.com/Multilin ®
®
Canada
Fax: (905) 201-2098 - M A A B 9 7 0 0 0 0 9 9 -
X W V U T S R P N M L K J H G F D B
c b a c b a c b a c b a c b a
b a b a
Tx1 1 1
1 1
2 2
Rx1 2 2
3 Tx1 3
3 3
Tx1
4 4
CH1
4 4
Rx1 5
Tx2 CH1 5
Tx 6
Rx 6
CH2
Rx2 IN 7
Tx2
7
8
CH2
Tx2 8
OUT
Rx2
Optional Optional Optional Optional Optional Optional CT/VT CPU module Power
Ethernet direct contact contact CT/VT or contact module (Ethernet not supply
switch input/output input/ input/output contact input/output available when module
module output module input/output module ordered with
module module Ethernet switch)
831781A4.CDR
WARNING
The relay follows a convention with respect to terminal number assignments which are three characters long assigned in
order by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from the
first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following
figure for an example of rear terminal assignments.
TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
TRIPPING DIRECTION
A B C (5 Amp)
52
OPTIONAL
3
F1a
F1b
F2a
F2b
F3a
F3b
F4a
F4b
F5a
F6a
F7a
F8a
F1c
F2c
F3c
F4c
F5c
F6c
F7c
F8c
VX
VB
VC
VA
VX
IG5
IG1
VB
VC
IG
VA
IA5
IA1
IB
IC
IA
IC5
IC1
IB5
IB1
CURRENT SUPERVISION
VOLTAGE AND
CURRENT INPUTS VOLTAGE INPUTS
8F
This diagram is based on the following order code: H5a CONTACT INPUT H5a DIGITAL INPUTS/OUTPUTS 6G I H1a TC 1
L90-E00-HCL-F8F-H6G-L6D-N6K-S6C-U6H-W7A H5c CONTACT INPUT H5c H1
V
H1b
This diagram provides an example of how the device H6a CONTACT INPUT H6a H1c
is wired, not specifically how to wire the device. Please H6c CONTACT INPUT H6c I H2a
refer to the Instruction Manual for additional details on H5b COMMON H5b H2 H2b
VOLTAGE SUPERVISION
V
wiring based on various configurations. H2c
H7a CONTACT INPUT H7a
I H3a
H7c CONTACT INPUT H7c
H3 H3b TC 2
H8a CONTACT INPUT H8a V
H3c
H8c CONTACT INPUT H8c
I H4a
H7b COMMON H7b
H4 H4b
V
H8b SURGE H4c
U7a CONTACT INPUT U7a DIGITAL INPUTS/OUTPUTS 6H I U1a
U7c CONTACT INPUT U7c U1 U1b
V
U8a CONTACT INPUT U8a U1c
U8c CONTACT INPUT U8c I U2a
U7b COMMON U7b U2 U2b
V
U2c
U8b SURGE
I U3a
U3 U3b
V
U3c
I U4a
U4 U4b
V
GE Consumer & Industrial U4c
Multilin I U5a
U5 U5b
V
U5c
L90 LINE DIFFERENTIAL RELAY U6
I U6a
U6b
V
U6c
N1a
( DC ONLY )
6K
N1 N1b
L1a CONTACT INPUT L1a
6D
N1c
L1c CONTACT INPUT L1c
N2a
L2a CONTACT INPUT L2a N2 N2b
L2c CONTACT INPUT L2c
N2c
L1b COMMON L1b
N3a
L3a CONTACT INPUT L3a N3 N3b
L3c CONTACT INPUT L3c N3c
L4a CONTACT INPUT L4a N4a
L4c CONTACT INPUT L4c UR COMPUTER
N4 N4b
L3b COMMON L3b 1 1 8
N4c
TXD 2 2 3 RXD
L5a CONTACT INPUT L5a N5a
N5 N5b RXD 3 3 2 TXD
L5c CONTACT INPUT L5c
N5c 4 4 20
L6a CONTACT INPUT L6a
SGND 5 5 7 SGND
DIGITAL INPUTS/OUTPUTS
N6 N6b 6 6 6
L5b COMMON L5b
N6c 7 7 4
L7a CONTACT INPUT L7a 8 8 5
N7a
L7c CONTACT INPUT L7c 9 9 22
N7 N7b
L8a CONTACT INPUT L8a
L8c CONTACT INPUT L8c N7c
N8a 9 PIN 25 PIN
L7b COMMON L7b CONNECTOR CONNECTOR
N8 N8b
L8b SURGE
N8c
INTER-RELAY
FIBER
Tx1 Rx1
COMMS.
TO CHANNEL 1
W7A
REMOTE S1a
6C
CRITICAL
B1a FAILURE S2c
B2b
S3a
B3a 48 V DC S3 S3b
DC OUTPUT
B3b
POWER SUPPLY
S3c
B5b HI S4a
AC or DC CONTROL
B6b LO S4 S4b
POWER
B6a S4c
B8a SURGE S5a
B8b FILTER S5 S5b
S5c
S6a
DIGITAL INPUTS/OUTPUTS
S6 S6b
S6c
Shielded
S7a
twisted pairs
CONTACTS SHOWN S7 S7b
WITH NO
S7c
D1b CONTROL POWER
S8a
9E
RS485
D2b COM 1 S8 S8b
Ground at com
Remote
D3b S8c
Device D1a
RS485
D2a COM 2
D3a com
Co-axial *
D4b
D4a IRIG-B
Input
Co-axial BNC
IRIG-B
CPU
The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE MODULE FUNCTION TERMINALS DIELECTRIC STRENGTH
TYPE (AC)
FROM TO
1 Power supply High (+); Low (+); (–) Chassis 2000 V AC for 1 minute
1 Power supply 48 V DC (+) and (–) Chassis 2000 V AC for 1 minute
1 Power supply Relay terminals Chassis 2000 V AC for 1 minute
2 Reserved N/A N/A N/A
3 Reserved N/A N/A N/A
4
5
Reserved
Analog inputs/outputs
N/A
All except 8b
N/A
Chassis
N/A
< 50 V DC
3
6 Digital inputs/outputs All Chassis 2000 V AC for 1 minute
G.703 All except 2b, 3a, 7b, 8a Chassis 2000 V AC for 1 minute
7
RS422 All except 6a, 7b, 8a Chassis < 50 V DC
8 CT/VT All Chassis 2000 V AC for 1 minute
9 CPU All Chassis 2000 V AC for 1 minute
Filter networks and transient protection clamps are used in the hardware to prevent damage caused by high peak voltage
transients, radio frequency interference (RFI), and electromagnetic interference (EMI). These protective components can
be damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one min-
ute.
CONTROL POWER SUPPLIED TO THE RELAY MUST BE CONNECTED TO THE MATCHING POWER SUPPLY
RANGE OF THE RELAY. IF THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY
CAUTION
OCCUR!
The L90 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well
known to be subject to deterioration over time if voltage is not applied periodically. Deterioration can be
NOTE
avoided by powering the relays up once a year.
The power supply module can be ordered for two possible voltage ranges, with or without a redundant power option. Each
range has a dedicated input connection for proper operation. The ranges are as shown below (see the Technical specifica-
tions section of chapter 2 for additional details):
• Low (LO) range: 24 to 48 V (DC only) nominal.
• High (HI) range: 125 to 250 V nominal.
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical wiring diagram earlier). The critical failure relay is a form-C device that will be energized once control power is
applied and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks
detect a critical failure (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize.
For high reliability systems, the L90 has a redundant option in which two L90 power supplies are placed in parallel on the
bus. If one of the power supplies become faulted, the second power supply will assume the full load of the relay without any
interruptions. Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay
of the module will also indicate a faulted power supply.
An LED on the front of the control power module shows the status of the power supply:
LED INDICATION POWER SUPPLY
CONTINUOUS ON OK
ON / OFF CYCLING Failure
OFF Failure
NOTE:
AC or DC 14 gauge stranded AC or DC
wire with suitable
disconnect devices
is recommended.
Heavy copper conductor
or braided wire
3
GND
+ +
+ —
– LOW HIGH
FILTER SURGE
CONTROL OPTIONAL
POWER ETHERNET SWITCH
Switchgear UR-series
ground bus protection system
827759AA.CDR
A CT/VT module may have voltage inputs on channels 1 through 4 inclusive, or channels 5 through 8 inclusive. Channels 1
and 5 are intended for connection to phase A, and are labeled as such in the relay. Likewise, channels 2 and 6 are intended
for connection to phase B, and channels 3 and 7 are intended for connection to phase C.
Channels 4 and 8 are intended for connection to a single-phase source. For voltage inputs, these channel are labelled as
auxiliary voltage (VX). For current inputs, these channels are intended for connection to a CT between system neutral and
ground, and are labelled as ground current (IG).
Verify that the connection made to the relay nominal current of 1 A or 5 A matches the secondary rating of
the connected CTs. Unmatched CTs may result in equipment damage or inadequate protection.
CAUTION
CT/VT modules may be ordered with a standard ground current input that is the same as the phase current input. Each AC
current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is
withdrawn from the chassis. There are no internal ground connections on the current inputs. Current transformers with 1 to
50000 A primaries and 1 A or 5 A secondaries may be used.
The above modules are available with enhanced diagnostics. These modules can automatically detect CT/VT hardware
failure and take the relay out of service.
CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram.
The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair
cabling on the zero-sequence CT is recommended.
Ground
outside CT
3
To ground;
LOAD must be on
load side
LOAD 996630A5
NOTE
~ 1a
~ 1b
~ 2a
~ 2b
~ 3a
~ 3b
~ 4a
~ 4b
~ 5a
~ 6a
~ 7a
~ 8a
~ 1c
~ 2c
~ 3c
~ 4c
~ 5c
~ 6c
~ 7c
~ 8c
VC
VB
VA
VX
IG
IG1
IA
IC
IA1
IC1
IB
IB1
IG5
VC
VB
VA
IA5
VX
IC5
IB5
~ 1b
~ 2a
~ 2b
~ 3a
~ 3b
~ 4a
~ 4b
~ 5a
~ 5b
~ 6a
~ 6b
~ 7a
~ 7b
~ 8a
~ 8b
~ 1c
~ 2c
~ 3c
~ 4c
~ 5c
~ 6c
~ 7c
~ 8c
IG
IG
IG1
IG1
IA
IC
IA
IC
IA1
IA1
IC1
IB
IC1
IB
IB1
IB1
IG5
IG5
IA5
IC5
IA5
IC5
IB5
IB5
Current inputs
8H, 8J, 8N, and 8R modules (8 CTs)
842766A3.CDR
The L90 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin
HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units,
known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applica-
tions, including protection functions, FlexLogic™, metering, and communications.
The IEC 61850 process bus system offers the following benefits.
• Drastically reduces labor associated with design, installation, and testing of protection and control applications using
the L90 by reducing the number of individual copper terminations.
• Integrates seamlessly with existing L90 applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules.
Every contact input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight
rows in total. A given row of three terminals may be used for the outputs of one relay. For example, for form-C relay outputs,
the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A
output, there are options of using current or voltage detection for feature supervision, depending on the module ordered.
The terminal configuration for contact inputs is different for the two applications.
The contact inputs are grouped with a common return. The L90 has two versions of grouping: four inputs per common
return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
The four inputs per common allows for high-density inputs in combination with outputs, with a compromise of four inputs
sharing one common. If the inputs must be isolated per row, then two inputs per common return should be selected (4D
module).
The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that may
be ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open,
and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose out-
put is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is set to “On =
1” when the current is above about 1 to 2.5 mA, and the current monitor is set to “On = 1” when the current exceeds about
80 to 100 mA. The voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be
used to seal-in the output contact until an external contact has interrupted current flow.
Block diagrams are shown below for form-A and solid-state relay outputs with optional voltage monitor, optional current
monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact outputs.
~#a
~#b
Load
~#c +
c) No monitoring 827862A3.CDR
Figure 3–16: FORM-A AND SOLID-STATE CONTACT OUTPUTS WITH VOLTAGE AND CURRENT MONITORING
The operation of voltage and current monitors is reflected with the corresponding FlexLogic™ operands (CONT OP # VON,
CONT OP # VOFF, and CONT OP # ION) which can be used in protection, control, and alarm logic. The typical application of
the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the
control command.
Refer to the Digital elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be
applied for breaker trip circuit integrity monitoring.
Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to
be used for low voltage accessible applications, it is the customer’s responsibility to ensure proper insula-
WARNING
tion levels!
USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH IMPEDANCE CIRCUITS
NOTE For form-A and solid-state relay output contacts internally equipped with a voltage measuring cIrcuit across the
contact, the circuit has an impedance that can cause a problem when used in conjunction with external high input
impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may con-
tinue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as
an impedance.
The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the form-
A contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is
used as a source, a 500 Ω, 10 W resistor is appropriate. In this configuration, the voltage across either the form-A
contact or the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number
sign “#” appears, substitute the contact number
NOTE
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the Flex-
Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of
NOTE
the output contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
3 ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-C ~8a, ~8c 2 Inputs
3
~4B MODULE ~4C MODULE ~4D MODULE ~4L MODULE
TERMINAL OUTPUT TERMINAL OUTPUT TERMINAL OUTPUT TERMINAL OUTPUT
ASSIGNMENT ASSIGNMENT ASSIGNMENT ASSIGNMENT
~1 Not Used ~1 Not Used ~1a, ~1c 2 Inputs ~1 2 Outputs
~2 Solid-State ~2 Solid-State ~2a, ~2c 2 Inputs ~2 2 Outputs
~3 Not Used ~3 Not Used ~3a, ~3c 2 Inputs ~3 2 Outputs
~4 Solid-State ~4 Solid-State ~4a, ~4c 2 Inputs ~4 2 Outputs
~5 Not Used ~5 Not Used ~5a, ~5c 2 Inputs ~5 2 Outputs
~6 Solid-State ~6 Solid-State ~6a, ~6c 2 Inputs ~6 2 Outputs
~7 Not Used ~7 Not Used ~7a, ~7c 2 Inputs ~7 2 Outputs
~8 Solid-State ~8 Solid-State ~8a, ~8c 2 Inputs ~8 Not Used
842762A2.CDR
6K
I I
~ 1b ~1 ~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 1c ~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 2a ~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 2b ~2 ~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
~ 3a ~ 3a ~ 3a
~ 7c CONTACT IN ~ 7c
~ 3b ~3 ~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a ~ 4a ~ 4a
~ 7b COMMON ~ 7b
~ 4b ~4 ~4 ~ 4b ~4 ~ 4b
~ 4c ~ 8b SURGE ~ 4c ~ 4c
~ 5a ~ 5a
~ 5b ~5 ~5 ~ 5b
~ 5c ~ 5c
~ 6a ~ 6a
~ 6b ~6 ~6 ~ 6b
~ 6c ~ 6c
~ 7a
3
DIGITAL I/O
~ 7b ~7
~ 7c
~ 8a
~ 8b ~8
~ 8c
842763A2.CDR
CONTACT INPUTS:
A dry contact has one side connected to terminal B3b. This is the positive 48 V DC voltage rail supplied by the power sup-
ply module. The other side of the dry contact is connected to the required contact input terminal. Each contact input group
has its own common (negative) terminal which must be connected to the DC negative terminal (B3a) of the power supply
module. When a dry contact closes, a current of 1 to 3 mA will flow through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this contact
is connected to the required contact input terminal. If a wet contact is used, then the negative side of the external source
must be connected to the relay common (negative) terminal of each contact group. The maximum external source voltage
for this arrangement is 300 V DC.
The voltage threshold at which each group of four contact inputs will detect a closed contact input is programmable as
17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.
B 1b
1
B 1a CRITICAL
FAILURE
B 2b
B 3a -
POWER SUPPLY
48 VDC
B 3b + OUTPUT
B 5b HI+
CONTROL
B 6b LO+
POWER
B 6a -
B 8a SURGE
B 8b FILTER
827741A4.CDR
NOTE
Contact outputs may be ordered as form-a or form-C. The form-A contacts may be connected for external circuit supervi-
sion. These contacts are provided with voltage and current monitoring circuits used to detect the loss of DC voltage in the
circuit, and the presence of DC current flowing through the contacts when the form-A contact closes. If enabled, the current
monitoring can be used as a seal-in signal to ensure that the form-A contact does not attempt to break the energized induc-
tive coil circuit and weld the output contacts.
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We
recommend using an external DC supply.
NOTE
50 to 70 mA
3 mA
time
25 to 50 ms 842749A1.CDR
842751A1.CDR
Transducer input modules can receive input signals from external dcmA output transducers (dcmA In) or resistance tem-
perature detectors (RTD). Hardware and software is provided to receive signals from these external transducers and con-
vert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard dcmA ranges. Software is provided to configure
virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three ter-
minals per row with a total of eight rows. A given row may be used for either inputs or outputs, with terminals in column "a"
having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/
output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
3 require a twisted-pair shielded cable, where the shield is grounded at one end only. The figure below illustrates the trans-
ducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module.
NOTE
A 9-pin RS232C serial port is located on the L90 faceplate for programming with a personal computer. All that is required to
use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the
RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at 19200 bps.
NOTE
a) OPTIONS
In addition to the faceplate RS232 port, the L90 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
NOTE
SM fiber
9L
Shielded twisted-pairs optic cable 100Base-FL NORMAL COM1
D1b +
9E
RS485 D1a +
D2b — RS485
COM1 D2a —
Ground at D3b COMMON COM2
remote
Ground at D3a COMMON
D1a + remote
device RS485 D4b +
D2a — device
— IRIG-B
COM2 D4a
D3a COMMON input
D4b + BNC
D4a — IRIG-B Co-axial cable
CPU
input BNC IRIG-B output
BNC Co-axial cable
Co-axial cable
CPU
BNC IRIG-B output
Co-axial cable
9M
NORMAL
COM1
100Base-FL
MM fiber
Tx1 100Base-F ALTERNATE
9G
NORMAL
COM1
optic cable Rx1 10Base-FL
Shielded twisted-pairs
D1a +
10Base-T RS485
Shielded twisted-pairs D2a —
D1a + COM2
RS485 Ground at D3a COMMON
3
D2a — remote D4b
COM2 +
Ground at D3a COMMON device
D4a — IRIG-B
remote D4b +
device
input
D4a — IRIG-B BNC
input Co-axial cable
CPU
BNC BNC IRIG-B output
Co-axial cable
Co-axial cable
CPU
BNC IRIG-B output
Co-axial cable
Shielded
9N
10/100Base-T NORMAL COM1
MM fiber twisted-pairs
+
9H
D2a —
Tx2
Rx2 10Base-F ALTERNATE COM2
Ground at D3a COMMON
Shielded remote D4b
10Base-T +
twisted-pairs device
D1a + D4a — IRIG-B
RS485 input
D2a —
COM2 BNC
Ground at D3a COMMON Co-axial cable
CPU
remote D4b +
device BNC IRIG-B output
D4a — IRIG-B Co-axial cable
input
BNC
Co-axial cable
CPU
SM fiber
Tx1
9P
NORMAL
COM1
optic cable Rx1 100Base-FL
10/100Base-T
Shielded twisted-pairs
MM fiber D1a +
Tx1 100Base-FL NORMAL COM1 RS485
9J
CPU
BNC BNC IRIG-B output
Co-axial cable Co-axial cable
CPU
9R
Rx1 100Base-FL
COM1
MM fiber optic cable Tx1 Tx2 100Base-F ALTERNATE
9K
NORMAL
COM1
Rx1 100Base-FX
MM fiber optic cable Tx2 100Base-FX
Rx2 Fiber
MM fiber optic cable Tx1 100Base-FX ports
Rx1
W1a GROUND
842765A5.CDR
b) RS485 PORTS
RS485 data transmission and reception are accomplished over a single twisted pair with transmit and receive data alternat-
ing over the same two wires. Through the use of these ports, continuous monitoring and control from a remote computer,
SCADA system or PLC is possible.
To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be
observed. For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–”
terminals connected together. The COM terminal should be connected to the common wire inside the shield, when pro-
vided. To avoid loop currents, the shield should be grounded at one point only. Each relay should also be daisy chained to
the next one in the link. A maximum of 32 relays can be connected in this manner without exceeding driver capability. For
larger systems, additional serial channels must be added. It is also possible to use commercially available repeaters to
increase the number of relays on a single channel to more than 32. Star or stub connections should be avoided entirely.
Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are internally provided at both communication ports. An iso-
lated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum reliability, all
3
equipment should have similar transient protection devices installed.
Both ends of the RS485 circuit should also be terminated with an impedance as shown below.
CAUTION
The fiber optic communication ports allow for fast and efficient communications between relays at 10 Mbps or 100 Mbps.
Optical fiber may be connected to the relay supporting a wavelength of 820 nm in multi-mode or 1310 nm in multi-mode
and single-mode. The 10 Mbps rate is available for CPU modules 9G and 9H; 100Mbps is available for modules 9H, 9J, 9K,
9L, 9M, 9N, 9P, and 9R. The 9H, 9K, 9M, and 9R modules have a second pair of identical optical fiber transmitter and
receiver for redundancy.
The optical fiber sizes supported include 50/125 µm, 62.5/125 µm and 100/140 µm for 10 Mbps. The fiber optic port is
3 designed such that the response times will not vary for any core that is 100 µm or less in diameter, 62.5 µm for 100 Mbps.
For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers,
the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connec-
tor, only a quarter turn of the coupling is required.
3.2.10 IRIG-B
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within
1 millisecond. The IRIG time code formats are serial, width-modulated codes which can be either DC level shifted or ampli-
tude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS
satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized.
TO OTHER DEVICES
(DC-SHIFT ONLY)
827756A5.CDR
The IRIG-B repeater provides an amplified DC-shift IRIG-B signal to other equipment. By using one IRIG-B serial connec-
tion, several UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal
even when a relay in the series is powered down.
NOTE
Using an amplitude modulated receiver will also cause errors of up to 1 ms in metered synchrophasor values.
Using the IRIG-B repeater function in conjunction with synchrophasors is not recommended, as the repeater adds
NOTE a 40 μs delay to the IRIG-B signal. This results in a 1° error for each consecutive device in the string as reported in
synchrophasors.
A special inter-relay communications module is available for the L90. This module is plugged into slot “W” in horizontally
mounted units and slot “R” in vertically mounted units. Inter-relay channel communications is not the same as 10/100Base-
F interface communications (available as an option with the CPU module). Channel communication is used for sharing data
among relays.
The inter-relay communications modules are available with several interfaces as shown in the table below.
All of the fiber modules use ST type connectors. For two-terminal applications, each L90 relay requires at least one com-
munications channel.
The current differential function must be “Enabled” for the communications module to properly operate.
Refer to SETTINGS ÖØ GROUPED ELEMENTS Ö LINE DIFFERENTIAL Ö CURRENT DIFFERENTIAL menu.
NOTE
The fiber optic modules (7A to 7W) are designed for back-to-back connections of UR-series relays only. For
connections to higher-order systems, use the 72 to 77 modules or the 2A and 2B modules.
NOTE
OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.
CAUTION
3.3.2 FIBER: LED AND ELED TRANSMITTERS
The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules.
Module: 7A / 7B / 7C 7H / 7I / 7J
Connection Location: Slot X Slot X 3
RX1 RX1
TX1 TX1
RX2
TX2
The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module.
TX1 TX1
RX1 RX1
TX2
RX2
a) DESCRIPTION
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps. The SETTINGS Ö PRODUCT SETUP ÖØ DIRECT I/O ÖØ DIRECT I/O DATA RATE
setting is not applicable to this module.
NOTE
AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Con-
necting the shield to pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if pin X1a
or X6a is used, do not ground at the other end. This interface module is protected by surge suppression devices.
Shield X 1a
3
7S
Tx – X 1b
G.703
channel 1 Rx – X 2a
Inter-relay communications Tx + X 2b
Rx + X 3a
Surge X 3b
Shield X 6a
Tx – X 6b
G.703
channel 2
Rx – X 7a
Tx + X 7b
Rx + X 8a
Surge X 8b
842773A2.CDR
7S
Tx - X 1b X 1b Tx -
G.703 G.703
CHANNEL 1
Rx - X 2a X 2a Rx -
CHANNEL 1
Tx + X 2b X 2b Tx +
Rx + X 3a X 3a Rx +
SURGE X 3b X 3b SURGE
Shld. X 6a X 6a Shld.
Tx - X 6b X 6b Tx -
G.703 G.703
Rx - X 7a X 7a Rx -
COMM.
COMM.
CHANNEL 2 CHANNEL 2
Tx + X 7b X 7b Tx +
Rx + X 8a X 8a Rx +
SURGE X 8b X 8b SURGE
831727A3.CDR
6. Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position.
The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as
the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the
clips simultaneously. When the clips have locked into position, the module will be fully inserted.
The switch settings for the internal and loop timing modes are shown below:
842752A1.CDR
3 In minimum remote loopback mode, the multiplexer is enabled to return the data from the external interface without any
processing to assist in diagnosing G.703 line-side problems irrespective of clock rate. Data enters from the G.703 inputs,
passes through the data stabilization latch which also restores the proper signal polarity, passes through the multiplexer
and then returns to the transmitter. The differential received data is processed and passed to the G.703 transmitter module
after which point the data is discarded. The G.703 receiver module is fully functional and continues to process data and
passes it to the differential Manchester transmitter module. Since timing is returned as it is received, the timing source is
expected to be from the G.703 line side of the interface.
DMX G7R
842774A1.CDR
DMX G7R
842775A1.CDR
a) DESCRIPTION
There are three RS422 inter-relay communications modules available: single-channel RS422 (module 7T), dual-channel
RS422 (module 7W), and dual-channel dual-clock RS422 (module 7V). The modules can be configured to run at 64 or
128 kbps. AWG 24 twisted shielded pair cable is recommended for external connections. These modules are protected by
optically-isolated surge suppression devices.
The two-channel two-clock RS422 interface (module 7V) is intended for use with two independent channel banks
with two independent clocks. It is intended for situations where a single clock for both channels is not acceptable.
NOTE
The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows:
• Site 1: Terminate shield to pins 6a or 7b or both.
• Site 2: Terminate shield to COM pin 2b. 3
The clock terminating impedance should match the impedance of the line.
Single-channel RS422 module Dual-channel RS422 module
~ 3b Tx – ~ 3b Tx –
7W
7T
~ 3a Rx – ~ 3a Rx –
RS422
~ 2a Tx + RS422 Inter-relay comms. ~ 2a Tx +
channel 1
~ 4b Rx + ~ 4b Rx +
~ 6a Shield ~ 6a Shield
Inter-relay communications
~ 7a ~ 5b Tx –
Clock
~ 8b ~ 5a Rx –
RS422
~ 2b COM ~ 4a Tx +
channel 2
~ 8a Surge ~ 6b Rx +
~ 7b Shield
~ 7a
Clock
~ 8b
~ 2b COM
Tx– W 3b W 3b Tx–
7T
7T
Rx– W 3a W 3a Rx–
RS422 RS422
CHANNEL 1 Tx– W 2a W 2a Tx+
CHANNEL 1
Rx+ W 4b W 4b Rx+
COMMUNICATIONS
COMMUNICATIONS
Shld. W 6a W 6a Shld.
+ W 7a W 7a +
CLOCK CLOCK
– W 8b W 8b –
COM W 2b + W 2b COM
SURGE W 8a W 8a SURGE
64 kHz 831809A1.CDR
By using this configuration, the timing for both data modules and both UR–RS422 channels will be derived from a single
clock source. As a result, data sampling for both of the UR–RS422 channels will be synchronized via the send timing leads
on data module 1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the
G.703 interface is a viable option that does not impose timing restrictions.
Data module 1
Signal name
Tx1(+) W 2a SD(A) - Send data
7W
Tx1(-) W 3b SD(B) - Send data
RS422
CHANNEL 1
Rx1(+) W 4b RD(A) - Received data
Rx1(-) W 3a RD(B) - Received data
Shld. W 6a RS(A) - Request to send (RTS)
INTER-RELAY COMMUNICATIONS
3 RS422
CHANNEL 2
Rx2(+)
Rx2(-)
W 6b
W 5a
CS(B) - Clear To send
Local loopback
Shld. W 7b Remote loopback
com W 2b Signal ground
SURGE W 8a ST(A) - Send timing
ST(B) - Send timing
Data module 2
Signal name
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(A) - Send data
SD(B) - Send data
RD(A) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(B) - Request to send (RTS)
CS(A) - Clear To send
CS(B) - Clear To send
Local loopback
Remote loopback
Signal ground
ST(A) - Send timing
ST(B) - Send timing
831022A3.CDR
c) TRANSMIT TIMING
The RS422 interface accepts one clock input for transmit timing. It is important that the rising edge of the 64 kHz transmit
timing clock of the multiplexer interface is sampling the data in the center of the transmit data window. Therefore, it is impor-
tant to confirm clock and data transitions to ensure proper system operation. For example, the following figure shows the
positive edge of the Tx clock in the center of the Tx data bit.
Tx Clock
Tx Data
d) RECEIVE TIMING
The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data.
NRZI-MARK is an edge-type, invertible, self-clocking code.
To recover the Rx clock from the data-stream, an integrated DPLL (digital phase lock loop) circuit is utilized. The DPLL is
driven by an internal clock, which is 16-times over-sampled, and uses this clock along with the data-stream to generate a
data clock that can be used as the SCC (serial communication controller) receive clock.
The two-channel two-clock RS422 interface (module 7V) is intended for use with the synchrophasor feature. The module
connections are illustrated below.
Tx – ~3b
7V
RS422
Rx –
Tx +
~3a
~2a
3
channel 1
Rx + ~4b
Shield ~6a
Tx – ~5b
Rx – ~5a
RS422 Tx + ~4a
channel 2
Rx + ~6b
RS422 communications
Shield ~7b
Channel 1 Tx – ~7a
clock Rx – ~8b
Channel 2 Tx – ~1b
clock Rx – ~1a
Common COM ~2b
Surge ~8a
842802A2.CDR
The following figure shows the combined RS422 plus Fiber interface configuration at 64K baud. The 7L, 7M, 7N, 7P, and 74
modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is employed
via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber.
AWG 24 twisted shielded pair is recommended for external RS422 connections and the shield should be grounded only at
one end. For the direct fiber channel, power budget issues should be addressed properly.
When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed maximum
optical input power to the receiver.
WARNING
~ 1a Clock
7L, 7M, 7N, 7P, 74
~ 1b (channel 1)
~ 2b COM
~ 2a Tx1 +
~ 3a Rx1 –
RS422
~ 3b Tx1 –
channel 1
Inter-relay comms.
~ 4b Rx1 +
~ 6a Shield
Fiber
Tx2 Rx2 channel 2
~ 8a Surge
842777A1.CDR
The figure below shows the combined G.703 plus fiber interface configuration at 64 kbps. The 7E, 7F, 7G, 7Q, and 75 mod-
ules are used in configurations where channel 1 is employed via the G.703 interface (possibly with a multiplexer) and chan-
nel 2 via direct fiber. AWG 24 twisted shielded pair is recommended for external G.703 connections connecting the shield to
pin 1a at one end only. For the direct fiber channel, power budget issues should be addressed properly. See previous sec-
tions for additional details on the G.703 and fiber interfaces.
When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi-
mum optical input power to the receiver.
WARNING
~ 1a
communications
~ 3a Rx +
~ 3b Surge
Inter-relay
Tx2 Fiber
Rx2 channel 2
842778A1.CDR
The UR-series IEEE C37.94 communication modules (modules types 2G, 2H, 76, and 77) are designed to interface with
IEEE C37.94 compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input and
output applications for firmware revisions 3.30 and higher. The IEEE C37.94 standard defines a point-to-point optical link
for synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard
provides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94 communication modules are either
64 kbps (with n fixed at 1) for 128 kbps (with n fixed at 2). The frame is a valid International Telecommunications Union
(ITU-T) recommended G.704 pattern from the standpoint of framing and data rate. The frame is 256 bits and is repeated at
a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps.
The specifications for the module are as follows:.
• IEEE standard: C37.94 for 1 × 128 kbps optical fiber interface (for 2G and 2H modules) or C37.94 for 2 × 64 kbps opti-
cal fiber interface (for 76 and 77 modules).
• Fiber optic cable type: 50 mm or 62.5 mm core diameter optical fiber.
• Fiber optic mode: multi-mode.
• Fiber optic cable length: up to 2 km.
• Fiber optic connector: type ST.
• Wavelength: 830 ±40 nm.
• Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports
the IEEE C37.94 standard as shown below.
The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a
non-compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard, as
shown below.
The UR-series C37.94 communication module has six (6) switches that are used to set the clock configuration. The func-
tions of these control switches is shown below.
3
842753A1.CDR
For the internal timing mode, the system clock is generated internally. therefore, the timing switch selection should be inter-
nal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1. Remove the IEEE C37.94 module (type 2G, 2H, 76, or 77 module):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2. Remove the module cover screw.
3. Remove the top cover by sliding it towards the rear and then lift it upwards.
4. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
5. Replace the top cover and the cover screw.
6. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
The UR-series C37.94SM communication modules (2A and 2B) are designed to interface with modified IEEE C37.94 com-
pliant digital multiplexers or IEEE C37.94 compliant interface converters that have been converted from 820 nm multi-mode
fiber optics to 1300 nm ELED single-mode fiber optics. The IEEE C37.94 standard defines a point-to-point optical link for
synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard pro-
vides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94SM communication module is 64 kbps only
with n fixed at 1. The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from
the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit
rate of 2048 kbps.
The specifications for the module are as follows:
• Emulated IEEE standard: emulates C37.94 for 1 × 64 kbps optical fiber interface (modules set to n = 1 or 64 kbps).
• Fiber optic cable type: 9/125 μm core diameter optical fiber. 3
• Fiber optic mode: single-mode, ELED compatible with HP HFBR-1315T transmitter and HP HFBR-2316T receiver.
• Fiber optic cable length: up to 10 km.
• Fiber optic connector: type ST.
• Wavelength: 1300 ±40 nm.
• Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that sup-
ports C37.94SM as shown below.
It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below.
The UR-series C37.94SM communication module has six (6) switches that are used to set the clock configuration. The
functions of these control switches is shown below.
842753A1.CDR
For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be
internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The C37.94SM communications module cover removal procedure is as follows:
1. Remove the C37.94SM module (modules 2A or 2B):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2. Remove the module cover screw.
3. Remove the top cover by sliding it towards the rear and then lift it upwards.
4. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
3 5. Replace the top cover and the cover screw.
6. Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU mod-
ules with revisions 5.5x and higher. The modules communicate to the L90 through an internal Ethernet port (referred to as
the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST
100Base-FX ports.
The Ethernet switch module should be powered up before or at the same time as the L90. Otherwise, the switch
module will not be detected on power up and the EQUIPMENT MISMATCH: ORDERCODE XXX self-test warning will be
NOTE issued.
The type 2S and 2T managed Ethernet switch modules provide two 10/100Base-T and four multimode ST 100Base-FX
external Ethernet ports accessible through the rear of the module. In addition, a serial console port is accessible from the 3
front of the module (requires the front panel faceplate to be open).
The pin assignment for the console port signals is shown in the following table.
Two 10/100Base-T
ports
Four 100Base-FX
multimode ports
with ST connectors
RS232
console port
Independent power
supply. Options:
2S: high-voltage
2T: low-voltage
The 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.
The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FX
ports have one LED to indicate linkup and activity.
842868A2.CDR
A suitable IP/gateway and subnet mask must be assigned to both the switch and the UR relay for correct operation. The
Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net-
work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified.
Do not connect to network while configuring the switch module.
CAUTION
2. Enter “3.94.247.229” in the IP Address field and “255.255.252.0” in the Subnet Mask field, then click OK.
The software will send the new settings to the L90 and prompt as follows when complete.
3. Cycle power to the L90 and switch module to activate the new settings.
1. Select the desired device from site tree in the online window.
2. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File >
Transfer Settings File item from the device settings tree.
The system will request the name and destination path for the settings file.
3. Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open.
The settings file will be transferred to the Ethernet switch and the settings uploaded to the device.
a) DESCRIPTION
This section describes the process for upgrading firmware on a UR-2S or UR-2T switch module.
There are several ways of updating firmware on a switch module:
• Using the EnerVista UR Setup software.
• Serially using the L90 switch module console port.
• Using FTP or TFTP through the L90 switch module console port.
It is highly recommended to use the EnerVista UR Setup software to upgrade firmware on a L90 switch module.
Firmware upgrades using the serial port, TFTP, and FTP are described in detail in the switch module manual.
NOTE
NOTE
The firmware version installed on the switch will appear on the lower left corner of the screen.
2. Using the EnerVista UR Setup program, select the Settings > Product Setup > Communications > Ethernet Switch
> Firmware Upload menu item.
The following popup screen will appear warning that the settings will be lost when the firmware is upgraded.
It is highly recommended that you save the switch settings before upgrading the firmware.
NOTE
3. After saving the settings file, proceed with the firmware upload by selecting Yes to the above warning.
Another window will open, asking you to point to the location of the firmware file to be uploaded.
4. Select the firmware file to be loaded on to the Switch, and select the Open option.
The following window will pop up, indicating that the firmware file transfer is in progress.
If the firmware load was successful, the following window will appear:
Note
The switch will automatically reboot after a successful firmware file transfer.
NOTE
5. Once the firmware has been successfully uploaded to the switch module, load the settings file using the procedure
described earlier.
The following table provides details about Ethernet module self-test errors.
Be sure to enable the ETHERNET SWITCH FAIL setting in the PRODUCT SETUP ÖØ USER-PROGRAMMABLE SELF-TESTS menu
and the relevant PORT 1 EVENTS through PORT 6 EVENTS settings under the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ ETH-
ERNET SWITCH menu.
The EnerVista UR Setup software provides a graphical user interface (GUI) as one of two human interfaces to a UR device.
The alternate human interface is implemented via the device’s faceplate keypad and display (refer to the Faceplate inter-
face section in this chapter).
The EnerVista UR Setup software provides a single facility to configure, monitor, maintain, and trouble-shoot the operation
of relay functions, connected over local or wide area communication networks. It can be used while disconnected (off-line)
or connected (on-line) to a UR device. In off-line mode, settings files can be created for eventual downloading to the device.
In on-line mode, you can communicate with the device in real-time.
The EnerVista UR Setup software, provided with every L90 relay, can be run from any computer supporting Microsoft Win-
dows® 95, 98, NT, 2000, ME, and XP. This chapter provides a summary of the basic EnerVista UR Setup software interface
features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software
interface.
To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV-
ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the L90 section in Chapter 1 for details.
f) FILE SUPPORT
• Execution: Any EnerVista UR Setup file which is double clicked or opened will launch the application, or provide focus
to the already opened application. If the file was a settings file (has a URS extension) which had been removed from
the Settings List tree menu, it will be added back to the Settings List tree menu.
• Drag and Drop: The Site List and Settings List control bar windows are each mutually a drag source and a drop target
for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and any
Windows Explorer directory folder are each mutually a file drag source and drop target.
New files which are dropped into the Settings List window are added to the tree which is automatically sorted alphabet-
ically with respect to settings file names. Files or individual menu items which are dropped in the selected device menu
in the Site List window will automatically be sent to the on-line communicating device.
g) FIRMWARE UPGRADES
The firmware of a L90 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond-
ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default
values, minimum/maximum values, data type, and item size) may change slightly from version to version of firm-
NOTE
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable, self-test
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.
The EnerVista UR Setup software main window supports the following primary display components:
1. Title bar which shows the pathname of the active data view.
2. Main window menu bar.
3. Main window tool bar.
4. Site list control bar window.
5. Settings list control bar window.
6. Device data view windows, with common tool bar.
7. Settings file data view windows, with common tool bar.
8. Workspace area with data view tabs.
9. Status bar.
10. Quick action hot links.
2 1 6 7 4
10
4
9 8 842786A2.CDR
Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam-
ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows
engineers to configure and test these common settings, then lock them so they are not available to users. For example,
these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate
on the specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers install-
ing the devices. These will be settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings tem-
plates can be applied to both settings files (settings file templates) and online devices (online settings templates). The func-
tionality is identical for both purposes.
The settings template feature requires that both the EnerVista UR Setup software and the L90 firmware are at ver-
sions 5.40 or higher.
NOTE
The software will prompt for a template password. This password is required to use the template feature and must be
at least four characters in length.
3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.
By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the
phase time overcurrent settings window in edit mode.
The software will prompt for a template password. This password must be at least four characters in length.
Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND
Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings tree view is shown below.
Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR
Figure 4–5: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND
Use the following procedure to display settings available for editing and settings locked by the template. 4
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View All Settings option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings
will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR
Figure 4–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND
4. Verify one more time that you wish to remove the template by clicking Yes.
The EnerVista software will remove all template information and all settings will be available.
The UR allows users to secure parts or all of a FlexLogic™ equation, preventing unauthorized viewing or modification of
critical FlexLogic™ applications. This is accomplished using the settings template feature to lock individual entries within
FlexLogic™ equations.
Secured FlexLogic™ equations will remain secure when files are sent to and retrieved from any UR-series device.
4 The following procedure describes how to lock individual entries of a FlexLogic™ equation.
1. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the set-
tings template feature.
2. Select the FlexLogic > FlexLogic Equation Editor settings menu item.
By default, all FlexLogic™ entries are specified as viewable and displayed against a yellow background. The icon on
the upper right of the window will also indicate that EnerVista UR Setup is in EDIT mode.
3. Specify which entries to lock by clicking on them.
The locked entries will be displayed against a grey background as shown in the example below.
Once the template has been applied, users will only be able to view and edit the FlexLogic™ entries not locked by the tem-
plate. The effect of applying the template to the FlexLogic™ entries in the above procedure is shown below.
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
4 3. Enter the serial number of the L90 device to lock to the settings file in the Serial # Lock field.
The settings file and corresponding secure FlexLogic™ equations are now locked to the L90 device specified by the serial
number.
A traceability feature for settings files allows the user to quickly determine if the settings in a L90 device have been
changed since the time of installation from a settings file. When a settings file is transfered to a L90 device, the date, time,
and serial number of the L90 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the L90 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the L90
device or obtained from the L90 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
The serial number of the UR-series device and the file transfer
date are added to the settings file when settings files
are transferred to the device.
1. The transfer date of a setting file written to a L90 is logged in the relay and can be viewed via EnerVista UR Setup or
the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
2. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes
have been made to the relay configuration since the settings file was saved.
4
842863A1.CDR
Traceability data
in settings report
842862A1.CDR
842865A1.CDR
a) ENHANCED FACEPLATE
The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The
front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules.
Display
Keypad
4
Front panel
RS232 port
b) STANDARD FACEPLATE
The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The
front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over
the faceplate which must be removed in order to access the keypad panel. The following figure shows the horizontal
arrangement of the faceplate panels.
Display
Front panel
RS232 port
The following figure shows the vertical arrangement of the faceplate panels for relays ordered with the vertical option.
DISPLAY
MENU 7 8 9
HELP MESSAGE 4 5 6
ESCAPE 1 2 3 KEYPAD
ENTER VALUE 0 . +/-
LED PANEL 3
4 LED PANEL 2
USER 2
LED PANEL 1
827830A1.CDR
PHASE C
NEUTRAL/GROUND USER 3
a) ENHANCED FACEPLATE
The enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event
cause LEDs, and the next four columns contain the 48 user-programmable LEDs.
The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these
latched conditions can also be reset via the SETTINGS ÖØ INPUT/OUTPUTS ÖØ RESETTING menu). The RS232 port is
intended for connection to a portable PC.
The USER keys are used by the breaker control feature.
842811A1.CDR
• TROUBLE: This LED indicates that the relay has detected an internal problem.
• TEST MODE: This LED indicates that the relay is in test mode.
• TRIP: This LED indicates that the FlexLogic™ operand serving as a trip switch has operated. This indicator always
latches; as such, a reset command must be initiated to allow the latch to be reset.
• ALARM: This LED indicates that the FlexLogic™ operand serving as an alarm switch has operated. This indicator is
never latched.
• PICKUP: This LED indicates that an element is picked up. This indicator is never latched.
The event cause indicators in the first column are described below.
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: This LED indicates voltage was involved. 4
• CURRENT: This LED indicates current was involved.
• FREQUENCY: This LED indicates frequency was involved.
• OTHER: This LED indicates a composite function was involved.
• PHASE A: This LED indicates phase A was involved.
• PHASE B: This LED indicates phase B was involved.
• PHASE C: This LED indicates phase C was involved.
• NEUTRAL/GROUND: This LED indicates that neutral or ground was involved.
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack-
age of every L90, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
b) STANDARD FACEPLATE
The standard faceplate consists of three panels with LED indicators, keys, and a communications port. The RESET key is
used to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions
can also be reset via the SETTINGS ÖØ INPUT/OUTPUTS ÖØ RESETTING menu). The RS232 port is intended for connection
to a portable PC.
The USER keys are used by the breaker control feature.
842781A1.CDR
STATUS INDICATORS:
• IN SERVICE: Indicates that control power is applied; all monitored inputs/outputs and internal systems are OK; the
relay has been programmed.
• TROUBLE: Indicates that the relay has detected an internal problem.
• TEST MODE: Indicates that the relay is in test mode.
• TRIP: Indicates that the selected FlexLogic™ operand serving as a Trip switch has operated. This indicator always
latches; the reset command must be initiated to allow the latch to be reset.
• ALARM: Indicates that the selected FlexLogic™ operand serving as an Alarm switch has operated. This indicator is
never latched.
• PICKUP: Indicates that an element is picked up. This indicator is never latched.
EVENT CAUSE INDICATORS:
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
4 All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: Indicates voltage was involved.
• CURRENT: Indicates current was involved.
• FREQUENCY: Indicates frequency was involved.
• OTHER: Indicates a composite function was involved.
• PHASE A: Indicates phase A was involved.
• PHASE B: Indicates phase B was involved.
• PHASE C: Indicates phase C was involved.
• NEUTRAL/GROUND: Indicates that neutral or ground was involved.
USER-PROGRAMMABLE INDICATORS:
The second and third provide 48 amber LED indicators whose operation is controlled by the user. Support for applying a
customized label beside every LED is provided.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
842782A1.CDR
842784A1.CDR
a) ENHANCED FACEPLATE
The following procedure requires the pre-requisites listed below.
• EnerVista UR Setup software is installed and operational.
• The L90 settings have been saved to a settings file.
• The L90 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://
www.GEindustrial.com/multilin/support/ur and printed.
• Small-bladed knife.
This procedure describes how to create custom LED labels for the enhanced front panel display.
1. Start the EnerVista UR Setup software.
2. Select the Front Panel Report item at the bottom of the menu tree for the settings file. The front panel report window
will be displayed.
4
Figure 4–22: FRONT PANEL REPORT WINDOW
3. Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided.
4. Feed the L90 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
5. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
6. Remove the L90 label insert tool from the package and bend the tabs as described in the following procedures. These
tabs will be used for removal of the default and custom LED labels.
It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part
number facing the user.
NOTE
The label package shipped with every L90 contains the three default labels shown below, the custom label template sheet,
and the label removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, follow the procedures below to remove the original labels and insert the new ones.
The following procedure describes how to setup and use the label removal tool.
1. Bend the tabs at the left end of the tool upwards as shown below.
2. Bend the tab at the center of the tool tail as shown below.
The following procedure describes how to remove the LED labels from the L90 enhanced front panel and insert the custom
labels.
1. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from
the relay.
4
2. Slide the label tool under the LED label until the tabs snap out as shown below. This will attach the label tool to the LED
label.
4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below.
The following procedure describes how to remove the user-programmable pushbutton labels from the L90 enhanced front
panel and insert the custom labels.
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the
bent tab is pointing away from the relay.
2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will
attach the label tool to the user-programmable pushbutton label.
3. Remove the tool and attached user-programmable pushbutton label as shown below.
4
4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the buttons,
as shown below.
b) STANDARD FACEPLATE
Custom labeling of an LED-only panel is facilitated through a Microsoft Word file available from the following URL:
http://www.GEindustrial.com/multilin/support/ur/
This file provides templates and instructions for creating appropriate labeling for the LED panel. The following procedures
are contained in the downloadable file. The panel templates provide relative LED locations and located example text (x)
edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling.
1. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014).
Push in
and gently lift
up the cover.
842771A1.CDR
2. Pop out the LED module and/or the blank module with a screwdriver as shown below. Be careful not to damage the
plastic covers.
F60
R
842722A1.CDR
3. Place the left side of the customized module back to the front panel frame, then snap back the right side.
4. Put the clear Lexan front cover back into place.
The following items are required to customize the L90 display module:
• Black and white or color printer (color preferred).
• Microsoft Word 97 or later software for editing the template.
• 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069),
and a custom module cover (GE Multilin Part Number: 1502-0015).
The following procedure describes how to customize the L90 display module:
1. Open the LED panel customization template with Microsoft Word. Add text in places of the LED x text placeholders on
the template(s). Delete unused place holders as required.
2. When complete, save the Word file to your local PC for future use.
3. Print the template(s) to a local printer.
4. From the printout, cut-out the Background Template from the three windows, using the cropmarks as a guide.
5. Put the Background Template on top of the custom display module (GE Multilin Part Number: 1513-0069) and snap the
clear custom module cover (GE Multilin Part Number: 1502-0015) over it and the templates.
4.3.4 DISPLAY
All messages are displayed on a 2 × 20 backlit liquid crystal display (LCD) to make them visible under poor lighting condi-
4
tions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad
and display are not actively being used, the display will default to user-defined messages. Any high priority event driven
message will automatically override the default message and appear on the display.
4.3.5 KEYPAD
Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting
values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alterna-
tively, values may also be entered with the numeric keypad.
The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may
be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values.
a) INTRODUCTION
The L90 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker,
which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually
initiated from faceplate keypad or automatically initiated from a FlexLogic™ operand. A setting is provided to assign names
to each breaker; this user-assigned name is used for the display of related flash messages. These features are provided for
two breakers; the user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
For the following discussion it is assumed the SETTINGS ÖØ SYSTEM SETUP ÖØ BREAKERS Ö BREAKER 1(2) Ö BREAKER
FUNCTION setting is "Enabled" for each breaker.
ENTER COMMAND This message appears when the USER 1, USER 2, or USER 3 key is pressed and a
PASSWORD COMMAND PASSWORD is required; i.e. if COMMAND PASSWORD is enabled and no com-
mands have been issued within the last 30 minutes.
Press USER 1 This message appears if the correct password is entered or if none is required. This mes-
To Select Breaker sage will be maintained for 30 seconds or until the USER 1 key is pressed again.
BKR1-(Name) SELECTED This message is displayed after the USER 1 key is pressed for the second time. Three
4 USER 2=CLS/USER 3=OP possible actions can be performed from this state within 30 seconds as per items (1), (2)
and (3) below:
(1)
USER 2 OFF/ON If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is
To Close BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to close breaker 1.
(2)
USER 3 OFF/ON If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is
To Open BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to open breaker 1.
(3)
BKR2-(Name) SELECTED If the USER 1 key is pressed at this step, this message appears showing that a different
USER 2=CLS/USER 3=OP breaker is selected. Three possible actions can be performed from this state as per (1),
(2) and (3). Repeatedly pressing the USER 1 key alternates between available breakers.
Pressing keys other than USER 1, 2 or 3 at any time aborts the breaker control function.
4.3.7 MENUS
a) NAVIGATION
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
• Actual values.
• Settings.
• Commands.
• Targets.
• User displays (when enabled).
b) HIERARCHY
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
SETTINGS
SYSTEM SETUP
Ø
SETTINGS Press the MESSAGE DOWN key to move to the next Settings page. This page con-
SYSTEM SETUP tains settings for System Setup. Repeatedly press the MESSAGE UP and DOWN
keys to display the other setting headers and then back to the first Settings page
header.
Ø
PASSWORD From the Settings page one header (Product Setup), press the MESSAGE RIGHT
SECURITY key once to display the first sub-header (Password Security).
Ø
ACCESS LEVEL: Press the MESSAGE RIGHT key once more and this will display the first setting for
Restricted Password Security. Pressing the MESSAGE DOWN key repeatedly will display the
Ø remaining setting messages for this sub-header.
PASSWORD Press the MESSAGE LEFT key once to move back to the first sub-header message.
SECURITY
Ø
DISPLAY Pressing the MESSAGE DOWN key will display the second setting sub-header asso-
PROPERTIES ciated with the Product Setup header.
Ø
FLASH MESSAGE Press the MESSAGE RIGHT key once more and this will display the first setting for
TIME: 1.0 s Display Properties.
Ø
DEFAULT MESSAGE To view the remaining settings associated with the Display Properties subheader,
INTENSITY: 25% repeatedly press the MESSAGE DOWN key. The last message appears as shown.
FLASH MESSAGE For example, select the SETTINGS Ö PRODUCT SETUP ÖØ DISPLAY PROPERTIES Ö FLASH
TIME: 1.0 s MESSAGE TIME setting.
Ø
MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the HELP key
MAXIMUM: 10.0 again to view the next context sensitive help message.
Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point: The relay numeric keypad works the same as that of any electronic calculator. A number is
entered one digit at a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MES-
SAGE LEFT key or pressing the ESCAPE key, returns the original value to the display.
• VALUE keys: The VALUE UP key increments the displayed value by the step value, up to the maximum value allowed.
4 While at the maximum value, pressing the VALUE UP key again will allow the setting selection to continue upward
from the minimum value. The VALUE DOWN key decrements the displayed value by the step value, down to the mini-
mum value. While at the minimum value, pressing the VALUE DOWN key again will allow the setting selection to con-
tinue downward from the maximum value.
FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate
TIME: 2.5 s numeric keys in the sequence “2 . 5". The display message will change as the digits are
Ø being entered.
NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Therefore, press
HAS BEEN STORED ENTER to store the new value in memory. This flash message will momentarily appear
as confirmation of the storing process. Numerical values which contain decimal places
will be rounded-off if more decimal place digits are entered than specified by the step
value.
ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted", "Command",
Restricted "Setting", and "Factory Service".
Enumeration type values are changed using the VALUE keys. The VALUE UP key displays the next selection while the
VALUE DOWN key displays the previous selection.
ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting", press the VALUE keys until the proper selec-
Setting tion is displayed. Press HELP at any time for the context sensitive help messages.
Ø
NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing
HAS BEEN STORED ENTER stores the new value in memory. This flash message momentarily appears as
confirmation of the storing process.
There are several places where text messages may be programmed to allow the relay to be customized for specific appli-
cations. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example: to enter the text, “Breaker #1”.
1. Press the decimal to enter text edit mode.
2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4. Press ENTER to store the text.
5. If you have any problem, press HELP to view context sensitive help. Flash messages will sequentially appear for sev-
eral seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.
RELAY SETTINGS: When the relay is powered up, the Trouble LED will be on, the In Service LED off, and
Not Programmed this message displayed, indicating the relay is in the "Not Programmed" state and is safe-
guarding (output relays blocked) against the installation of a relay whose settings have
not been entered. This message remains until the relay is explicitly put in the "Pro-
grammed" state.
4
To change the RELAY SETTINGS: "Not Programmed" mode to "Programmed", proceed as follows:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE RIGHT key until the PASSWORD SECURITY message appears on the display.
3. Press the MESSAGE DOWN key until the INSTALLATION message appears on the display.
4. Press the MESSAGE RIGHT key until the RELAY SETTINGS: Not Programmed message is displayed.
SETTINGS
Ø
SETTINGS PASSWORD
PRODUCT SETUP SECURITY
DISPLAY
PROPERTIES
↓
5. After the RELAY SETTINGS: Not Programmed message appears on the display, press the VALUE keys change the
selection to "Programmed".
6. Press the ENTER key.
7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the
In Service LED will turn on.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the faceplate RS232 connection. Remote access is defined as any access to settings or commands via any rear com-
munications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
To enter the initial setting (or command) password, proceed as follows:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE RIGHT key until the ACCESS LEVEL message appears on the display.
3. Press the MESSAGE DOWN key until the CHANGE LOCAL PASSWORDS message appears on the display.
4. Press the MESSAGE RIGHT key until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD message
appears on the display.
PASSWORD ACCESS LEVEL:
SECURITY Restricted
CHANGE LOCAL CHANGE COMMAND
PASSWORDS PASSWORD: No
CHANGE SETTING
4 PASSWORD: No
ENCRYPTED COMMAND
PASSWORD: ---------
ENCRYPTED SETTING
PASSWORD: ---------
5. After the CHANGE...PASSWORD message appears on the display, press the VALUE UP or DOWN key to change the
selection to “Yes”.
6. Press the ENTER key and the display will prompt you to ENTER NEW PASSWORD.
7. Type in a numerical password (up to 10 characters) and press the ENTER key.
8. When the VERIFY NEW PASSWORD is displayed, re-type in the same password and press ENTER.
CHANGE SETTING
PASSWORD: No
NEW PASSWORD
HAS BEEN STORED
9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) Password will be
active.
FOR 10 MIN! flash message will appear upon activation of the ten minute timeout or any other time a user attempts any
change to the defined tier during the ten minute timeout. The LOCAL ACCESS DENIED FlexLogic™ operand will be set to
“Off” after the expiration of the ten-minute timeout.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and
the L90 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The REMOTE ACCESS DENIED FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.
SETTINGS SECURITY
See page 5-8.
PRODUCT SETUP
DISPLAY
See page 5-12.
PROPERTIES
CLEAR RELAY
See page 5-14.
RECORDS
COMMUNICATIONS
See page 5-15.
MODBUS USER MAP
See page 5-34.
REAL TIME
See page 5-35.
CLOCK
FAULT REPORTS
See page 5-36.
OSCILLOGRAPHY
See page 5-38.
DATA LOGGER
See page 5-40.
5
DEMAND
See page 5-42.
USER-PROGRAMMABLE
See page 5-43.
LEDS
USER-PROGRAMMABLE
See page 5-46.
SELF TESTS
CONTROL
See page 5-47.
PUSHBUTTONS
USER-PROGRAMMABLE
See page 5-49.
PUSHBUTTONS
FLEX STATE
See page 5-54.
PARAMETERS
USER-DEFINABLE
See page 5-55.
DISPLAYS
INSTALLATION
See page 5-57.
SETTINGS AC INPUTS
See page 5-59.
SYSTEM SETUP
POWER SYSTEM
See page 5-60.
SIGNAL SOURCES
See page 5-61.
L90 POWER SYSTEM
See page 5-64.
BREAKERS
See page 5-69.
SWITCHES
See page 5-73.
FLEXCURVES
See page 5-76.
PHASOR MEASUREMENT
See page 5-83.
UNIT
SETTINGS FLEXLOGIC
See page 5-115.
FLEXLOGIC EQUATION EDITOR
FLEXLOGIC
See page 5-115.
TIMERS
FLEXELEMENTS
See page 5-116.
NON-VOLATILE
See page 5-120.
LATCHES
5 SETTING GROUP 2
↓
SETTING GROUP 6
AUTORECLOSE
See page 5-249.
RTD INPUTS
See page 5-276.
DCMA OUTPUTS
See page 5-278.
CHANNEL TESTS
See page 5-284.
PMU
See page 5-284.
TEST VALUES
In the design of UR relays, the term element is used to describe a feature that is based around a comparator. The compar-
ator is provided with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to deter-
mine if the input is within the defined range that will set the output to logic 1, also referred to as “setting the flag”. A single
comparator may make multiple tests and provide multiple outputs; for example, the time overcurrent comparator sets a
pickup flag when the current input is above the setting and sets an operate flag when the input current has been at a level
above the pickup setting for the time specified by the time-current curve settings. All comparators use analog parameter
actual values as the input.
The exception to the above rule are the digital elements, which use logic states as inputs.
NOTE
Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on the element logic diagram. This includes the inputs, settings, fixed
logic, and the output operands generated (abbreviations used on scheme logic diagrams are defined in Appendix F).
5 Some settings for current and voltage elements are specified in per-unit (pu) calculated quantities:
pu quantity = (actual quantity) / (base quantity)
For current elements, the ‘base quantity’ is the nominal secondary or primary current of the CT.
Where the current source is the sum of two CTs with different ratios, the ‘base quantity’ will be the common secondary or
primary current to which the sum is scaled (that is, normalized to the larger of the two rated CT inputs). For example, if CT1
= 300 / 5 A and CT2 = 100 / 5 A, then in order to sum these, CT2 is scaled to the CT1 ratio. In this case, the base quantity
will be 5 A secondary or 300 A primary.
For voltage elements the ‘base quantity’ is the nominal primary voltage of the protected system which corresponds (based
on VT ratio and connection) to secondary VT voltage applied to the relay.
For example, on a system with a 13.8 kV nominal primary voltage and with 14400:120 V delta-connected VTs, the second-
ary nominal voltage (1 pu) would be:
13800
---------------- × 120 = 115 V (EQ 5.1)
14400
For Wye-connected VTs, the secondary nominal voltage (1 pu) would be:
13800
---------------- × 120
---------- = 66.4 V (EQ 5.2)
14400 3
Many settings are common to most elements and are discussed below:
• FUNCTION setting: This setting programs the element to be operational when selected as “Enabled”. The factory
default is “Disabled”. Once programmed to “Enabled”, any element associated with the function becomes active and all
options become available.
• NAME setting: This setting is used to uniquely identify the element.
• SOURCE setting: This setting is used to select the parameter or set of parameters to be monitored.
• PICKUP setting: For simple elements, this setting is used to program the level of the measured parameter above or
below which the pickup state is established. In more complex elements, a set of settings may be provided to define the
range of the measured parameters which will cause the element to pickup.
• PICKUP DELAY setting: This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup
and operate output states.
• RESET DELAY setting: This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the
Operate output state and the return to logic 0 after the input transits outside the defined pickup range.
• BLOCK setting: The default output operand state of all comparators is a logic 0 or “flag not set”. The comparator
remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN
input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise
the comparator. The BLOCK input is used as one of the inputs to RUN control.
• TARGET setting: This setting is used to define the operation of an element target message. When set to Disabled, no
target message or illumination of a faceplate LED indicator is issued upon operation of the element. When set to Self-
Reset, the target message and LED indication follow the Operate state of the element, and self-resets once the oper-
ate element condition clears. When set to Latched, the target message and LED indication will remain visible after the
element output returns to logic 0 - until a RESET command is received by the relay.
• EVENTS setting: This setting is used to control whether the Pickup, Dropout or Operate states are recorded by the
event recorder. When set to Disabled, element pickup, dropout or operate are not recorded as events. When set to
Enabled, events are created for:
(Element) PKP (pickup)
(Element) DPO (dropout)
(Element) OP (operate)
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not ‘0’.
a) BACKGROUND
5
The L90 may be used on systems with breaker-and-a-half or ring bus configurations.
In these applications, each of the two three-phase sets of individual phase currents (one associated with each breaker) can
be used as an input to a breaker failure element. The sum of both breaker phase currents and 3I_0 residual currents may
be required for the circuit relaying and metering functions. Two separate synchrocheck elements can be programmed to
check synchronization between two different buses VT and the line VT. These requirements can be satisfied with a single
L90, equipped with sufficient CT and VT input channels, by selecting proper parameter to measure. A mechanism is pro-
vided to specify the AC parameter (or group of parameters) used as the input to protection/control comparators and some
metering elements. Selection of the measured parameter(s) is partially performed by the design of a measuring element or
protection/control comparator by identifying the measured parameter type (fundamental frequency phasor, harmonic pha-
sor, symmetrical component, total waveform RMS magnitude, phase-phase or phase-ground voltage, etc.). The user com-
pletes the process by selecting the instrument transformer input channels to use and some parameters calculated from
these channels. The input parameters available include the summation of currents from multiple input channels. For the
summed currents of phase, 3I_0, and ground current, current from CTs with different ratios are adjusted to a single ratio
before summation. A mechanism called a “Source” configures the routing of CT and VT input channels to measurement
sub-systems.
Sources, in the context of L90 series relays, refer to the logical grouping of current and voltage signals such that one
source contains all the signals required to measure the load or fault in a particular power apparatus. A given source may
contain all or some of the following signals: three-phase currents, single-phase ground current, three-phase voltages and
an auxiliary voltages from a single-phase VT for checking for synchronism.
To illustrate the concept of Sources, as applied to current inputs only, consider the breaker-and-a-half scheme below. Some
protection elements, like breaker failure, require individual CT current as an input. Other elements, like distance, require the
sum of both current as an input. The line differential function requires the CT currents to be processed individually to cope
with a possible CT saturation of one CT during an external fault on the upper bus. The current into protected line is the pha-
sor sum (or difference) of the currents in CT1 and CT2, depending on the current distribution on the upper bus.
Banks are ordered sequentially from the block of lower-numbered channels to the block of higher-numbered channels, and
from the CT/VT module with the lowest slot position letter to the module with the highest slot position letter, as follows:
INCREASING SLOT POSITION LETTER -->
CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3
< bank 1 > < bank 3 > < bank 5 >
< bank 2 > < bank 4 > < bank 6 >
The UR platform allows for a maximum of three sets of three-phase voltages and six sets of three-phase currents. The
result of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is shown below.
ITEM MAXIMUM NUMBER
CT/VT Module 2
CT Bank (3 phase channels, 1 ground channel) 8
VT Bank (3 phase channels, 1 auxiliary channel) 4
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY
CHANGE LOCAL
MESSAGE See page 5–9.
PASSWORDS
ACCESS
MESSAGE See page 5–10.
SUPERVISION
DUAL PERMISSION
MESSAGE See page 5–11.
SECURITY ACCESS
PASSWORD ACCESS Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level
is not available and intended for factory use only.
The following operations are under command password supervision:
• Operating the breakers via faceplate keypad.
• Changing the state of virtual inputs.
• Clearing the event records.
5 • Clearing the oscillography records.
• Clearing fault reports.
• Changing the date and time.
• Clearing the breaker arcing current.
• Clearing energy records.
• Clearing the data logger.
• Clearing the user-programmable pushbutton states.
The following operations are under setting password supervision:
• Changing any setting.
• Test mode operation.
The command and setting passwords are defaulted to “0” when the relay is shipped from the factory. When a password is
set to “0”, the password security feature is disabled.
The L90 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the L90, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic™ operands.
• ACCESS LOC SETG OFF: Asserted when local setting access is disabled.
• ACCESS LOC SETG ON: Asserted when local setting access is enabled.
• ACCESS LOC CMND OFF: Asserted when local command access is disabled.
• ACCESS LOC CMND ON: Asserted when local command access is enabled.
• ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
• ACCESS REM SETG ON: Asserted when remote setting access is enabled.
• ACCESS REM CMND OFF: Asserted when remote command access is disabled.
• ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
NOTE
b) LOCAL PASSWORDS
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ CHANGE LOCAL PASSWORDS
Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to “Yes” via the front panel
interface, the following message sequence is invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD.
If the setting and command passwords are identical, then this one password allows access to both com-
mands and settings.
NOTE
c) REMOTE PASSWORDS
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.
5. The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.
If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password
value.
d) ACCESS SUPERVISION
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION
• INVALID ATTEMPTS BEFORE LOCKOUT: This setting specifies the number of times an incorrect password can be
entered within a three-minute time span before lockout occurs. When lockout occurs, the LOCAL ACCESS DENIED and
REMOTE ACCESS DENIED FlexLogic™ operands are set to “On”. These operands are returned to the “Off” state upon
expiration of the lockout.
• PASSWORD LOCKOUT DURATION: This setting specifies the time that the L90 will lockout password access after
the number of invalid password entries specified by the INVALID ATTEMPS BEFORE LOCKOUT setting has occurred.
The L90 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic™ operand is
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
The UNAUTHORIZED ACCESS operand is reset with the COMMANDS ÖØ CLEAR RECORDS ÖØ RESET UNAUTHORIZED
ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The
operand does not generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed
with event logs or targets enabled.
The access level timeout settings are shown below.
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION Ö ACCESS LEVEL TIMEOUTS
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note 5
that the access level will set as restricted if control power is cycled.
• COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
• SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
DUAL PERMISSION LOCAL SETTING AUTH: Range: selected FlexLogic™ operands (see below)
SECURITY ACCESS On
REMOTE SETTING AUTH: Range: FlexLogic™ operand
MESSAGE
On
ACCESS AUTH Range: 5 to 480 minutes in steps of 1
MESSAGE
TIMEOUT: 30 min.
The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic™ operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing
the local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel.
• REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to pro-
viding the remote setting password to gain setting access.
• ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On”. The state of the FlexLogic™ oper-
and is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time-
out is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
5 The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable
when the Remote Settings Authorization setting is programmed to any operand except “On” or “Off”. The state of the
FlexLogic™ operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is per-
mitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer
expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™
operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
• LANGUAGE: This setting selects the language used to display settings, actual values, and targets. The range is
dependent on the order code of the relay.
• FLASH MESSAGE TIME: Flash messages are status, warning, error, or information messages displayed for several
seconds in response to certain key presses during setting programming. These messages override any normal mes-
sages. The duration of a flash message on the display can be changed to accommodate different reading rates.
• DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a
default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough
during programming or reading of actual values.
• DEFAULT MESSAGE INTENSITY: To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
• SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME: These settings are only visible if the L90 has a liquid
crystal display (LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled”, the LCD backlighting
is turned off after the DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, providing that no keys
have been pressed and no target messages are active. When a keypress occurs or a target becomes active, the LCD
backlighting is turned on.
• CURRENT CUT-OFF LEVEL: This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the
rated value) are very susceptible to noise. Some customers prefer very low currents to display as zero, while others
prefer the current be displayed even when the value reflects noise rather than the actual signal. The L90 applies a cut-
off value to the magnitudes and angles of the measured currents. If the magnitude is below the cut-off level, it is substi-
tuted with zero. This applies to phase and ground current phasors as well as true RMS values and symmetrical compo-
nents. The cut-off operation applies to quantities used for metering, protection, and control, as well as those used by
communications protocols. Note that the cut-off level for the sensitive ground input is 10 times lower that the CURRENT
CUT-OFF LEVEL setting value. Raw current samples available via oscillography are not subject to cut-off. 5
This setting does not affect the 87L metering cutoff, which is constantly at 0.02 pu.
• VOLTAGE CUT-OFF LEVEL: This setting modifies the voltage cut-off threshold. Very low secondary voltage measure-
ments (at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed
as zero, while others prefer the voltage to be displayed even when the value reflects noise rather than the actual sig-
nal. The L90 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below
the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical
components. The cut-off operation applies to quantities used for metering, protection, and control, as well as those
used by communications protocols. Raw samples of the voltages available via oscillography are not subject cut-off.
The CURRENT CUT-OFF LEVEL and the VOLTAGE CUT-OFF LEVEL are used to determine the metered power cut-off levels. The
power cut-off level is calculated as shown below. For Delta connections:
We have:
CT primary = “100 A”, and
VT primary = PHASE VT SECONDARY x PHASE VT RATIO = 66.4 V x 208 = 13811.2 V
The power cut-off is therefore:
power cut-off = (CURRENT CUT-OFF LEVEL × VOLTAGE CUT-OFF LEVEL × CT primary × VT primary)/VT secondary
= ( 3 × 0.02 pu × 1.0 V × 100 A × 13811.2 V) / 66.4 V
= 720.5 watts
Any calculated power value below this cut-off will not be displayed. As well, the three-phase energy data will not accumu-
late if the total power from all three phases does not exceed the power cut-off.
Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals
as valid measurements. Unless dictated otherwise by a specific application, the default settings of “0.02
NOTE
pu” for CURRENT CUT-OFF LEVEL and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.
Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program-
mable pushbuttons to clear specific records are typical applications for these commands. Since the L90 responds to rising
edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign User-Programmable Pushbutton 1 to clear demand records, the following settings should be
applied.
1. Assign the clear demand function to Pushbutton 1 by making the following change in the SETTINGS Ö PRODUCT SETUP
ÖØ CLEAR RELAY RECORDS menu:
CLEAR DEMAND: “PUSHBUTTON 1 ON”
2. Set the properties for User-Programmable Pushbutton 1 by making the following changes in the SETTINGS Ö PRODUCT
SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.20 s”
5.2.4 COMMUNICATIONS
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS
MESSAGE
WEB SERVER
See page 5–32.
5
HTTP PROTOCOL
TFTP PROTOCOL
MESSAGE See page 5–32.
IEC 60870-5-104
MESSAGE See page 5–32.
PROTOCOL
SNTP PROTOCOL
MESSAGE See page 5–33.
ETHERNET SWITCH
MESSAGE See page 5–34.
b) SERIAL PORTS
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS Ö SERIAL PORTS
SERIAL PORTS RS485 COM1 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
RATE: 19200 28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
RS485 COM1 PARITY: Range: None, Odd, Even
MESSAGE Only active if CPU Type E is ordered
None
RS485 COM1 RESPONSE Range: 0 to 1000 ms in steps of 10
MESSAGE Only active if CPU Type E is ordered
MIN TIME: 0 ms
RS485 COM2 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
MESSAGE 28800, 33600, 38400, 57600, 115200
RATE: 19200
RS485 COM2 PARITY: Range: None, Odd, Even
MESSAGE
None
RS485 COM2 RESPONSE Range: 0 to 1000 ms in steps of 10
MESSAGE
MIN TIME: 0 ms
The L90 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for
local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet
or RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that
these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of
these ports may be connected to a computer running EnerVista UR Setup. This software can download and upload setting
files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and con-
nected to a DCS, PLC or PC using the RS485 ports.
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
NOTE
each transmission.
c) NETWORK
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK
These messages appear only if the L90 is ordered with an Ethernet card.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The
NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a set-
ting for the TCP/UDP port number. These settings are used only in advanced network configurations and should normally
be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays
behind a router). By setting a different TCP/UDP PORT NUMBER for a given protocol on each UR-series relay, the router can
map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured
to use the correct port number if these settings are used.
When the NSAP address, any TCP/UDP port number, or any user map setting (when used with DNP) is changed, it
will not become active until power to the relay has been cycled (off-on).
NOTE
Do not set more than one protocol to the same TCP/UDP PORT NUMBER, as this will result in unreliable opera-
tion of those protocols.
WARNING
d) MODBUS PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ MODBUS PROTOCOL
The serial communication ports utilize the Modbus protocol, unless configured for DNP or IEC 60870-5-104 operation (see
descriptions below). This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device
only. When using Modbus protocol on the RS232 port, the L90 will respond regardless of the MODBUS SLAVE ADDRESS pro-
grammed. For the RS485 ports each L90 must have a unique address from 1 to 254. Address 0 is the broadcast address
which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same
address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher
address starting at 1. Refer to Appendix B for more information on the Modbus protocol.
Changes to the MODBUS TCP PORT NUMBER setting will not take effect until the L90 is restarted.
NOTE
e) DNP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL
The L90 supports the Distributed Network Protocol (DNP) version 3.0. The L90 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the L90 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the L90 at one time.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the IEC 60870-5-104 FUNCTION set-
ting is set to “Enabled”, the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL Ö DNP CHANNELS
DNP CHANNELS DNP CHANNEL 1 PORT: Range: NONE, COM1 - RS485, COM2 - RS485,
NETWORK FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
DNP CHANNEL 2 PORT: Range: NONE, COM1 - RS485, COM2 - RS485,
MESSAGE FRONT PANEL - RS232, NETWORK - TCP,
COM2 - RS485
NETWORK - UDP
The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, the Modbus protocol is disabled on that port. Note that COM1 can
be used only in non-Ethernet UR relays. When this setting is set to “Network - TCP”, the DNP protocol can be used over
TCP/IP on channels 1 or 2. When this value is set to “Network - UDP”, the DNP protocol can be used over UDP/IP on chan-
nel 1 only. Refer to Appendix E for additional information on the DNP protocol.
Changes to the DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings will take effect only after power has
been cycled to the relay.
NOTE
The DNP NETWORK CLIENT ADDRESS settings can force the L90 to respond to a maximum of five specific DNP masters. The
settings in this sub-menu are shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL Ö DNP NETWORK CLIENT ADDRESSES
The DNP UNSOL RESPONSE FUNCTION should be “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the L90 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the L90 retransmits an unsolic-
ited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP UNSOL
RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which unsolic-
ited responses are sent is determined by the L90 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the L90 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000”,
all DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000
V on the L90 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer-
tain ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value will be 10
5
times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the L90 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger unsolic-
ited responses from the L90 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting should
be set to “15”. Note that these settings are the deadband default values. DNP object 34 points can be used to change dead-
band values, from the default, for each individual DNP analog input point. Whenever power is removed and re-applied to
the L90, the default deadbands will be in effect.
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the L90.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays,
check the “DNP Points Lists” L90 web page to view the points lists. This page can be viewed with a web
NOTE
browser by entering the L90 IP address to access the L90 “Main Menu”, then by selecting the “Device Infor-
mation Menu” > “DNP Points Lists” menu item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings allow the user to select the DNP
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the L90 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The L90 can be configured to sup-
port paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED CONTROL
POINTS setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on
a one-to-one basis.
The DNP ADDRESS setting is the DNP slave address. This number identifies the L90 on a DNP communications link. Each
DNP slave should be assigned a unique address.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the L90. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the DNP TCP CONNECTION TIMEOUT setting for the changes to take
effect.
NOTE
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
5 PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT LISTS Ö BINARY INPUT / MSP POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT LISTS ÖØ ANALOG INPUT / MME POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP /
IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point
NOTE are ignored.
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the L90 is restarted.
NOTE
MESSAGE
GGIO4 ANALOG 5
CONFIGURATION
GGIO5 UINTEGER
MESSAGE
CONFIGURATION
REPORT CONTROL
MESSAGE
CONFIGURATION
XCBR
MESSAGE
CONFIGURATION
XSWI
MESSAGE
CONFIGURATION
The L90 Line Current Differential System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The L90 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The L90 operates as an IEC 61850
server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE... Ö TRANSMISSION
TRANSMISSION GENERAL
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
MESSAGE
GOOSE
The DEFAULT GSSE/GOOSE UPDATE TIME sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The DEFAULT GSSE/GOOSE UPDATE TIME setting is applicable to GSSE, fixed L90 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850... Ö GSSE/GOOSE... Ö TRANSMISSION ÖØ GSEE
5 GSSE GSSE FUNCTION: Range: Enabled, Disabled
Enabled
GSSE ID: Range: 65-character ASCII string
MESSAGE
GSSEOut
DESTINATION MAC: Range: standard MAC address
MESSAGE
000000000000
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The GSSE ID setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In L90 releases previous to 5.0x, this name string was repre-
sented by the RELAY NAME setting.
The fixed GOOSE settings are shown below:
PATH: SETTINGS Ö PRODUCT... ÖØ COMMUNICATIONS ÖØ IEC 61850... Ö GSSE/GOOSE... Ö TRANSMISSION ÖØ FIXED GOOSE
The configurable GOOSE settings allow the L90 to be configured to transmit a number of different datasets within IEC
61850 GOOSE messages. Up to eight different configurable datasets can be configured and transmitted. This is useful for
intercommunication between L90 IEDs and devices from other manufacturers that support IEC 61850.
The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the L90.
The L90 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data
transfer between devices.
Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.
Datasets 1 and 2 should be used for high-speed transmission of data that is required for applications such as transfer trip-
ping, blocking, and breaker fail initiate. At least one digital status value needs to be configured in the required dataset to
enable transmission of configured data. Configuring analog data only to dataset 1 or 2 will not activate transmission.
Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every
100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any
changes have been made. If any changes in the data items are detected, these changes will be transmitted through a
GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.
For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no
changes in the data items are detected.
The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes-
sages due to an oscillation being created that is triggering a message.
The L90 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be
caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station
components. If erroneously oscillation is detected, the L90 will stop sending GOOSE messages from the dataset for a min-
imum period of one second. Should the oscillation persist after the one second time-out period, the L90 will continue to
block transmission of the dataset. The L90 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error mes-
sage on the front panel display, where XXX denotes the data item detected as oscillating.
For versions 5.70 and higher, the L90 supports four retransmission schemes: aggressive, medium, relaxed, and heartbeat.
The aggressive scheme is only supported in fast type 1A GOOSE messages (GOOSEOut 1 and GOOSEOut 2). For slow
GOOSE messages (GOOSEOut 3 to GOOSEOut 8) the aggressive scheme is the same as the medium scheme.
The details about each scheme are shown in the following table.
The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception
dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION
ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGU-
RABLE GOOSE 1 settings menu:
– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE DEVICES
ÖØ REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
– Set REMOTE DEVICE 1 ETYPE APPID to match the ETHERTYPE application ID from the transmitting device. This is
“0” in the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the data by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE INPUTS ÖØ REMOTE INPUT 1
settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The L90 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between L90 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains
the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the L90
(DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN sup-
port).
Set the CONFIG GSE 1 FUNCTION function to “Disabled” when configuration changes are required. Once changes are
entered, return the CONFIG GSE 1 FUNCTION to “Enabled” and restart the unit for changes to take effect.
NOTE
PATH:...TRANSMISSION ÖØ CONFIGURABLE GOOSE 1(8) ÖØ CONIFIG GSE 1(64) DATA TIMES Ö ITEM 1(64)
5 CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
DATASET ITEMS GGIO1.ST.Ind1.stVal transmitted data
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: “GGIO1.ST.Ind1.stVal” and “GGIO1.ST.Ind1.q”. The L90 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH:...RECEPTION ÖØ CONFIGURABLE GOOSE 1(8) ÖØ CONIFIG GSE 1(64) DATA ITEMS
CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
DATASET ITEMS GGIO1.ST.Ind1.stVal transmitted data
The configurable GOOSE settings allow the L90 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to eight different configurable datasets can be configured for reception. This is useful for
intercommunication between L90 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between L90 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains
the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a L90 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and
“GGIO3.ST.Ind2.stVal”. The L90 will then create a dataset containing these two data items. The Boolean status values from
these data items can be utilized as remote input FlexLogic™ operands. First, the REMOTE DEVICE 1(16) DATASET setting
must be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then REMOTE IN 1(16) ITEM settings
must be set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic™ operands will then change state in
accordance with the status values of the data items in the configured dataset.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.XM.AnIn1 and higher items.
Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up).
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ SERVER CONFIGURATION
The IED NAME and LD INST settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The LOCATION is a
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS connections. The INCLUDE
NON-IEC DATA setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC 5
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
“Disabled”.
The SERVER SCANNING feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta-
tus values in the L90. Clients will still be able to connect to the server (L90 relay), but most data values will not be updated.
This setting does not affect GOOSE/GSSE operation.
Changes to the IED NAME setting, LD INST setting, and GOOSE dataset will not take effect until the L90 is restarted.
NOTE
The main menu for the IEC 61850 logical node name prefixes is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850... ÖØ IEC 61850 LOGICAL NODE NAME PREFIXES
The IEC 61850 logical node name prefix settings are used to create name prefixes to uniquely identify each logical node.
For example, the logical node “PTOC1” may have the name prefix “abc”. The full logical node name will then be
“abcMMXU1”. Valid characters for the logical node name prefixes are upper and lowercase letters, numbers, and the
underscore (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard.
Changes to the logical node prefixes will not take effect until the L90 is restarted.
The main menu for the IEC 61850 MMXU deadbands is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ MMXU DEADBANDS
MMXU2 DEADBANDS
MESSAGE
MMXU3 DEADBANDS
MESSAGE
MMXU4 DEADBANDS
MESSAGE
The MMXU deadband settings represent the deadband values used to determine when the update the MMXU “mag” and
“cVal” values from the associated “instmag” and “instcVal” values. The “mag” and “cVal” values are used for the IEC 61850
buffered and unbuffered reports. These settings correspond to the associated “db” data items in the CF functional con-
straint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value “shall repre-
sent the percentage of difference between the maximum and minimum in units of 0.001%”. Thus, it is important to know the
maximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband.
The minimum value for all quantities is 0; the maximum values are as follows:
• phase current: 46 × phase CT primary setting
• neutral current: 46 × ground CT primary setting
• voltage: 275 × VT ratio setting
5 • power (real, reactive, and apparent): 46 × phase CT primary setting × 275 × VT ratio setting
• frequency: 90 Hz
• power factor: 2
The GGIO1 status configuration points are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850... ÖØ GGIO1 STATUS CONFIGURATION
The NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect until
the L90 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850... ÖØ GGIO2 CONTROL... Ö GGIO2 CF SPSCO 1(64)
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the L90
virtual inputs.
GGIO4 ANALOG 1
MESSAGE
MEASURED VALUE
GGIO4 ANALOG 2
MESSAGE
MEASURED VALUE
↓
GGIO4 ANALOG 32
MESSAGE
MEASURED VALUE
The NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4. When this value is
changed, the L90 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
The measured value settings for each of the 32 analog values are shown below.
PATH: SETTINGS Ö PRODUCT... ÖØ COMMUNICATIONS ÖØ IEC 61850... ÖØ GGIO4... Ö GGIO4 ANALOG 1(32) MEASURED VALUE
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the L90. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
• GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger™ value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850... ÖØ REPORT... Ö REPORT 1(6) CONFIGURATION
REPORT 1
5 CONFIGURATION
REPORT 1
RptID:
Range: up to 66 alphanumeric characters
Changes to the report configuration will not take effect until the L90 is restarted.
Please disconnect any IEC 61850 client connection to the L90 prior to making setting changes to the report config-
uration. Disconnecting the rear Ethernet connection from the L90 will disconnect the IEC 61850 client connection.
NOTE
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ XCBR CONFIGURATION
The CLEAR XCBR1 OpCnt setting represents the breaker operating counter. As breakers operate by opening and closing, the
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1.
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is 5
restarted:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ XSWI CONFIGURATION
The CLEAR XSWI1 OpCnt setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
NOTE functionality.
The L90 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Mozilla Firefox. This feature is available only if the L90 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the L90 “Main Menu”. Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be
accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web
browser on the computer simply by entering the IP address of the L90 into the “Address” box on the web browser.
i) TFTP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ TFTP PROTOCOL
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the L90 over a network. The L90 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
5 obtained from the L90 contains a list and description of all available files (event records, oscillography, etc.).
The L90 supports the IEC 60870-5-104 protocol. The L90 can be used as an IEC 60870-5-104 slave device connected to a
maximum of two masters (usually either an RTU or a SCADA master station). Since the L90 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the L90 at one time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the L90 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the L90 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD set-
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the L90, the default thresholds will be in effect.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to “Enabled”, the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
k) SNTP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ SNTP PROTOCOL
The L90 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the L90 can obtain clock time over 5
an Ethernet network. The L90 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a dedicated
product using a GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported.
If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the L90 clock for
as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained from the SNTP server is used. If
either SNTP or IRIG-B is enabled, the L90 clock value cannot be changed using the front panel keypad.
To use SNTP in unicast mode, SNTP SERVER IP ADDR must be set to the SNTP/NTP server IP address. Once this address is
set and SNTP FUNCTION is “Enabled”, the L90 attempts to obtain time values from the SNTP/NTP server. Since many time
values are obtained and averaged, it generally takes three to four minutes until the L90 clock is closely synchronized with
the SNTP/NTP server. It may take up to two minutes for the L90 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the SNTP SERVER IP ADDR setting to “0.0.0.0” and SNTP FUNCTION to “Enabled”. The
L90 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The L90 waits up to eighteen
minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The UR-series relays do not support the multicast or anycast SNTP functionality.
l) ETHERNET SWITCH
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ ETHERNET SWITCH
These settings appear only if the L90 is ordered with an Ethernet switch module (type 2S or 2T).
The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings
are used in advanced network configurations. Please consult the network administrator before making changes to these
settings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings.
The PORT 1 EVENTS through PORT 6 EVENTS settings allow Ethernet switch module events to be logged in the event
recorder.
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the ADDRESS line (this value must be converted from hex to decimal format). The corresponding value is dis-
played in the VALUE line. A value of “0” in subsequent register ADDRESS lines automatically returns values for the previous
ADDRESS lines incremented by “1”. An address value of “0” in the initial register means “none” and values of “0” will be dis-
played for all registers. Different ADDRESS values can be entered as required in any of the register positions.
REAL TIME IRIG-B SIGNAL TYPE: Range: None, DC Shift, Amplitude Modulated
CLOCK None
REAL TIME CLOCK Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
LOCAL TIME OFFSET Range: –24.0 to 24.0 hrs in steps of 0.5
MESSAGE
FROM UTC: 0.0 hrs
DAYLIGHT SAVINGS Range: Disabled, Enabled
MESSAGE
TIME: Disabled
DST START MONTH: Range: January to December (all months)
MESSAGE
April
DST START DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST START DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST START HOUR: Range: 0:00 to 23:00
MESSAGE
2:00
DST STOP MONTH: Range: January to December (all months)
MESSAGE
April 5
DST STOP DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST STOP DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST STOP HOUR: Range: 0:00 to 23:00
MESSAGE
2:00
If the L90 channel asymmetry function is enabled, the IRIG-B input must be connected to the GPS receiver
and the proper receiver signal type assigned.
NOTE
The date and time can be synchronized a known time base and to other relays using an IRIG-B signal. It has the same
accuracy as an electronic watch, approximately ±1 minute per month. If an IRIG-B signal is connected to the relay, only the
current year needs to be entered. See the COMMANDS ÖØ SET DATE AND TIME menu to manually set the relay clock.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record.
The LOCAL TIME OFFSET FROM UTC setting is used to specify the local time zone offset from Universal Coordinated Time
(Greenwich Mean Time) in hours. This setting has two uses. When the L90 is time synchronized with IRIG-B, or has no per-
manent time synchronization, the offset is used to calculate UTC time for IEC 61850 features. When the L90 is time syn-
chronized with SNTP, the offset is used to determine the local time for the L90 clock, since SNTP provides UTC time.
The daylight savings time (DST) settings can be used to allow the L90 clock can follow the DST rules of the local time zone.
Note that when IRIG-B time synchronization is active, the DST settings are ignored. The DST settings are used when the
L90 is synchronized with SNTP, or when neither SNTP nor IRIG-B is used.
Only timestamps in the event recorder and communications protocols are affected by the daylight savings time set-
tings. The reported real-time clock value does not change.
NOTE
5 MESSAGE
Z1 MAG: 3.00 Ω
FAULT REP 1 REM1-TAP Range: 25 to 90° in steps of 1
MESSAGE
Z1 ANG: 75°
FAULT REP 1 REM1-TAP Range: 0.0 to 2000.0 in steps of 0.1
MESSAGE
LENGTH (km ): 100.0
FAULT REP 1 REM2-TAP Range: 0.01 to 250.00 ohms in steps of 0.01
MESSAGE
Z1 MAG: 3.00 Ω
FAULT REP 1 REM2-TAP Range: 25 to 90° in steps of 1
MESSAGE
Z1 ANG: 75°
FAULT REP 1 REM2-TAP Range: 0.0 to 2000.0 in steps of 0.1
MESSAGE
LENGTH (km ): 100.0
FAULT REPORT 1 VT Range: None, I0, V0
MESSAGE
SUBSTITUTION: None
FAULT REP 1 SYSTEM Range: 0.01 to 650.00 ohms in steps of 0.01
MESSAGE
Z0 MAG: 2.00 Ω
FAULT REP 1 SYSTEM Range: 25 to 90° in steps of 1
MESSAGE
Z0 ANGLE: 75°
The L90 incorporates a multi-ended fault locator method based on the synchronized voltage and current measurements at
all ends of the transmission line. This makes it possible to compute the fault location without assumptions or approxima-
tions. This fault locator method is applicable on both two-terminal and three-terminal applications, with results computed
independently at each terminal. For three-terminal line applications, the fault locator is reports the exact line segment at
which the fault occurred and the distance to the fault from the terminal adjacent to the fault.
if charging current compensation is configured and enabled, the line charging current is removed at each terminal for
improved accuracy.
During communication channel failures, the L90 uses the single-ended algorithm to calculate and report fault location.
When the single-ended algorithm is used for three-terminal line applications, the faulted segment of the line is not deter-
mined and reported.
The L90 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as
the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
• Fault report number.
• Name of the relay, programmed by the user.
• Firmware revision of the relay.
• Date and time of trigger.
• Name of trigger (specific operand).
• Line or feeder ID via the name of a configured signal source.
• Active setting group at the time of trigger.
• Pre-fault current and voltage phasors (two cycles before either a 50DD disturbance associated with fault report source
or the trigger operate). Once a disturbance is detected, pre-fault phasors hold for 3 seconds waiting for the fault report
trigger. If trigger does not occur within this time, the values are cleared to prepare for the next disturbance.
• Fault current and voltage phasors (one cycle after the trigger).
• Elements operated at the time of triggering.
• Events: 9 before trigger and 7 after trigger (only available via the relay webpage).
• Fault duration times for each breaker (created by the breaker arcing current feature).
5
The captured data also includes the fault type and the distance to the fault location, as well as the reclose shot number
(when applicable) To include fault duration times in the fault report, the user must enable and configure breaker arcing cur-
rent feature for each of the breakers. Fault duration is reported on a per-phase basis.
The relay allows locating faults, including ground faults, from delta-connected VTs. In this case, the missing zero-sequence
voltage is substituted either by the externally provided neutral voltage (broken delta VT) connected to the auxiliary voltage
channel of a VT bank, or by the zero-sequence voltage approximated as a voltage drop developed by the zero-sequence
current, and user-provided zero-sequence equivalent impedance of the system behind the relay.
The trigger can be any FlexLogic™ operand, but in most applications it is expected to be the same operand, usually a vir-
tual output, that is used to drive an output relay to trip a breaker. To prevent the overwriting of fault events, the disturbance
detector should not be used to trigger a fault report. A FAULT RPT TRIG event is automatically created when the report is
triggered.
If a number of protection elements are ORed to create a fault report trigger, the first operation of any element causing the
OR gate output to become high triggers a fault report. However, If other elements operate during the fault and the first oper-
ated element has not been reset (the OR gate output is still high), the fault report is not triggered again. Considering the
reset time of protection elements, there is very little chance that fault report can be triggered twice in this manner. As the
fault report must capture a usable amount of pre and post-fault data, it can not be triggered faster than every 20 ms.
Each fault report is stored as a file; the relay capacity is fifteen (15) files. An sixteenth (16th) trigger overwrites the oldest
file.
The EnerVista UR Setup software is required to view all captured data. The relay faceplate display can be used to view the
date and time of trigger, the fault type, the distance location of the fault, and the reclose shot number.
The FAULT REPORT 1 SOURCE setting selects the source for input currents and voltages and disturbance detection. For dual-
breaker applications where the line current is supplied individually from two breaker CTs, the fault locator source should
include the sum of currents from both CTs as well as the line voltage.
The FAULT 1 REPORT TRIG setting assigns the FlexLogic™ operand representing the protection element/elements requiring
operational fault location calculations. The distance to fault calculations are initiated by this signal. The FAULT REPORT 1 Z1
MAG and FAULT REPORT 1 Z0 MAG impedances are entered in secondary ohms.
For a two-terminal line application, the FAULT REPORT 1 Z1 MAG, FAULT REPORT 1 Z1 ANG, FAULT REPORT 1 Z0 MAG, FAULT
REPORT 1 Z0 ANG and FAULT REPORT 1 LENGTH settings for the entire line must to be entered for fault location calculations.
For a three-terminal application, these settings are used to enter the line segment impedance and length from the local ter-
minal to the tap point only.
The FAULT REP 1 REM1-TAP Z1 MAG and FAULT REP 1 REM1-TAP Z1 ANG settings are used for three-terminal applications to
enter positive sequence section impedances (in secondary ohms) for the line segment from remote terminal 1 to the tap
point. The length of the line section from remote terminal 1 to the tap point is entered in the FAULT REP 1 REM1-TAP LENGTH
setting.
The FAULT REP 1 REM2-TAP Z1 MAG, FAULT REP 1 REM2-TAP Z1 ANG, and FAULT REP 1 REM2-TAP LENGTH settings are used as
above, but for the line segment from remote terminal 2 to the tap point.
The FAULT REPORT 1 VT SUBSTITUTION setting shall be set to “None” if the relay is fed from wye-connected VTs. If delta-con-
nected VTs are used, and the relay is supplied with the neutral (3V0) voltage, this setting shall be set to “V0”. The method is
still exact, as the fault locator would combine the line-to-line voltage measurements with the neutral voltage measurement
to re-create the line-to-ground voltages. See the ACTUAL VALUES ÖØ RECORDS Ö FAULT REPORTS menu for additional
details. It required to configure the delta and neutral voltages under the source indicated as input for the fault report. Also,
the relay will check if the auxiliary signal configured is marked as “Vn” by the user (under VT setup), and inhibit the fault
location if the auxiliary signal is labeled differently.
If the broken-delta neutral voltage is not available to the relay, an approximation is possible by assuming the missing zero-
sequence voltage to be an inverted voltage drop produced by the zero-sequence current and the user-specified equivalent
zero-sequence system impedance behind the relay: V0 = –Z0 × I0. In order to enable this mode of operation, the FAULT
REPORT 1 VT SUBSTITUTION setting shall be set to “I0”.
The FAULT REP 1 SYSTEM Z0 MAG and FAULT REP 1 SYSTEM Z0 ANGLE settings are used only when the VT SUBSTITUTION set-
ting value is “I0”. The magnitude is to be entered in secondary ohms. This impedance is an average system equivalent
5 behind the relay. It can be calculated as zero-sequence Thevenin impedance at the local bus with the protected line/feeder
disconnected. The method is accurate only if this setting matches perfectly the actual system impedance during the fault. If
the system exhibits too much variability, this approach is questionable and the fault location results for single-line-to-ground
faults shall be trusted with accordingly. It should be kept in mind that grounding points in vicinity of the installation impact
the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.).
For proper operation of the multi-ended fault locator, the nominal primary voltage is expected to appear identical at
all line terminals as seen from the nominal secondary voltage, VT ratio, and VT connection settings of the first 87L
NOTE source.
5.2.8 OSCILLOGRAPHY
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic™ operand. Multiple oscillography records may be cap-
tured simultaneously.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscil-
lography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES ÖØ
RECORDS ÖØ OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sam-
ple configurations with corresponding cycles/record.
A new record may automatically overwrite an older record if TRIGGER MODE is set to “Automatic Overwrite”.
Set the TRIGGER POSITION to a percentage of the total buffer size (for example, 10%, 50%, 75%, etc.). A trigger position of 5
25% consists of 25% pre- and 75% post-trigger data. The TRIGGER SOURCE is always captured in oscillography and may be
any FlexLogic™ parameter (element state, contact input, virtual output, etc.). The relay sampling rate is 64 samples per
cycle.
The AC INPUT WAVEFORMS setting determines the sampling rate at which AC input signals (that is, current and voltage) are
stored. Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling
rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device.
When changes are made to the oscillography settings, all existing oscillography records will be CLEARED.
WARNING
b) DIGITAL CHANNELS
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY ÖØ DIGITAL CHANNELS
A DIGITAL 1(63) CHANNEL setting selects the FlexLogic™ operand state recorded in an oscillography trace. The length of
each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.
Upon startup, the relay will automatically prepare the parameter list.
c) ANALOG CHANNELS
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY ÖØ ANALOG CHANNELS
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay are dependent on:
• The type of relay,
• The type and number of CT/VT hardware modules installed, and
• The type and number of analog input hardware modules installed.
Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value
parameters is presented in Appendix A: FlexAnalog parameters. The parameter index number shown in any of the tables is
used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list
of parameters via the relay keypad and display - entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
5 All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-
nates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will
appear.
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Changing any setting affecting data logger operation will clear any data that is currently in the log.
NOTE
• DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to “Continu-
ous”, the data logger will actively record any configured channels at the rate as defined by the DATA LOGGER RATE. The
data logger will be idle in this mode if no channels are configured. When set to “Trigger”, the data logger will begin to
record any configured channels at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic™
operand. The data logger will ignore all subsequent triggers and will continue to record data until the active record is
full. Once the data logger is full a CLEAR DATA LOGGER command is required to clear the data logger record before a
new record can be started. Performing the CLEAR DATA LOGGER command will also stop the current record and reset
the data logger to be ready for the next trigger.
• DATA LOGGER TRIGGER: This setting selects the signal used to trigger the start of a new data logger record. Any
FlexLogic™ operand can be used as the trigger source. The DATA LOGGER TRIGGER setting only applies when the
mode is set to “Trigger”.
• DATA LOGGER RATE: This setting selects the time interval at which the actual value data will be recorded.
• DATA LOGGER CHNL 1(16): This setting selects the metering actual value that is to be recorded in Channel 1(16) of
the data log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/
VT hardware modules installed, and the type and number of Analog Input hardware modules installed. Upon startup,
the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is
shown in Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to
expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of
parameters via the relay keypad/display – entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
• DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not
selected to “Off” without over-writing old data.
5.2.10 DEMAND
The relay measures current demand on each phase, and three-phase demand for real, reactive, and apparent power. Cur-
rent and Power methods can be chosen separately for the convenience of the user. Settings are provided to allow the user
to emulate some common electrical utility demand measuring techniques, for statistical or control purposes. If the CRNT
DEMAND METHOD is set to "Block Interval" and the DEMAND TRIGGER is set to “Off”, Method 2 is used (see below). If
DEMAND TRIGGER is assigned to any other FlexLogic™ operand, Method 2a is used (see below).
The relay can be set to calculate demand by any of three methods as described below:
CALCULATION METHOD 1: THERMAL EXPONENTIAL
This method emulates the action of an analog peak recording thermal demand meter. The relay measures the quantity
(RMS current, real power, reactive power, or apparent power) on each phase every second, and assumes the circuit quan-
tity remains at this value until updated by the next measurement. It calculates the 'thermal demand equivalent' based on the
5 following equation:
– kt
d(t) = D( 1 – e ) (EQ 5.6)
where: d = demand value after applying input quantity for time t (in minutes)
D = input quantity (constant), and k = 2.3 / thermal 90% response time.
The 90% thermal response time characteristic of 15 minutes is illustrated below. A setpoint establishes the time to reach
90% of a steady-state value, just as the response time of an analog instrument. A steady state value applied for twice the
response time will indicate 99% of the value.
Demand (%)
If no trigger is assigned in the DEMAND TRIGGER setting and the CRNT DEMAND METHOD is "Block Interval", use cal-
culating method #2. If a trigger is assigned, the maximum allowed time between 2 trigger signals is 60 minutes. If
NOTE
no trigger signal appears within 60 minutes, demand calculations are performed and available and the algorithm
resets and starts the new cycle of calculations. The minimum required time for trigger contact closure is 20 μs.
CALCULATION METHOD 3: ROLLING DEMAND
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the programmed demand time interval, in the same way as Block Interval. The value is updated every minute and indicates
the demand over the time interval just preceding the time of update.
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS
b) LED TEST
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS Ö LED TEST
When enabled, the LED test can be initiated from any digital input or user-programmable condition such as user-program-
mable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all LEDs,
including the LEDs of the optional user-programmable pushbuttons.
The test consists of three stages.
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned”. This stage lasts as
long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test will end.
2. All the LEDs are turned off, and then one LED at a time turns on for 1 second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left
panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more
than one LED being turned off from a single logic point. This stage can be interrupted at any time.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and monitor-
ing features. However, the LED control mechanism accepts all the changes to LED states generated by the relay and
stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from
relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress.
A dedicated FlexLogic™ operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is ini-
tiated, the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL set-
ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed.
READY TO TEST
Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input
Set the
LED TEST IN PROGRESS
operand
control input is on
STAGE 1 time-out
(all LEDs on) (1 minute)
5 Wait 1 second
control input
rising edge
STAGE 3
of the control
(one LED off at a time) input
842011A1.CDR
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS Ö
PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS Ö LED TEST menu:
The test will be initiated when the user-programmable pushbutton 1 is pressed. The pushbutton should remain pressed for
as long as the LEDs are being visually inspected. When finished, the pushbutton should be released. The relay will then
automatically start stage 2. At this point forward, test may be aborted by pressing the pushbutton.
APPLICATION EXAMPLE 2:
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. Next,
release the pushbutton to automatically start stage 2. Once stage 2 has started, the pushbutton can be released. When
stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton.
TRIP & ALARM LEDS TRIP LED INPUT: Range: FlexLogic™ operand
Off
ALARM LED INPUT: Range: FlexLogic™ operand
MESSAGE
Off
The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic™ operand is in the logic 1 state.
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows.
5
• LED Panel 2: user-programmable LEDs 1 through 24
• LED Panel 3: user programmable LEDs 25 through 48
For the enhanced faceplate, the LEDs are located as follows.
• LED column 2: user-programmable LEDs 1 through 12
• LED column 3: user-programmable LEDs 13 through 24
• LED column 4: user-programmable LEDs 25 through 36
• LED column 5: user-programmable LEDs 37 through 48
Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic™ operands that control the LEDs. If the LED 1 TYPE setting is
“Self-Reset” (the default setting), the LED illumination will track the state of the selected LED operand. If the LED 1 TYPE set-
ting is “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com-
munications channel, or from any programmed operand, even if the LED operand state de-asserts.
Refer to the Control of setting groups example in the Control elements section of this chapter for group activation.
USER-PROGRAMMABLE REMOTE DEVICE OFF Range: Disabled, Enabled. Valid for units that contain a
SELF TESTS FUNCTION: Enabled CPU with Ethernet capability.
5 PRI. ETHERNET FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with a primary fiber port.
FUNCTION: Disabled
SEC. ETHERNET FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with a redundant fiber port.
FUNCTION: Disabled
BATTERY FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
SNTP FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with Ethernet capability.
FUNCTION: Enabled
IRIG-B FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
ETHERNET SWITCH FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Disabled
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in the “Enabled”
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
To enable the Ethernet switch failure function, ensure that the ETHERNET SWITCH FAIL FUNCTION is “Enabled” in this
menu.
NOTE
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained – if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-program-
mable control pushbuttons.
The location of the control pushbuttons are shown in the following figures.
Control pushbuttons 5
842813A1.CDR
USER 4
842733A2.CDR
The control pushbuttons become user-programmable only if the breaker control feature is not configured for manual control
via the USER 1 through 3 pushbuttons as shown below. If configured for manual control, breaker control typically uses the
larger, optional user-programmable pushbuttons, making the control pushbuttons available for other user applications.
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL:
When applicable
AND RUN
Enabled=1
OFF TIMER
SYSTEM SETUP/ FLEXLOGIC OPERAND
BREAKERS/BREAKER 2/ ON 0 CONTROL PUSHBTN 1 ON
BREAKER 2 PUSHBUTTON 100 msec
CONTROL:
842010A2.CDR
Enabled=1
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
• Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
• Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic™ oper-
ands) into FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER
LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6 LABEL 7 LABEL 8 LABEL 9 LABEL 10 LABEL 11 LABEL 12 LABEL 13 LABEL 14 LABEL 15 LABEL 16
842814A1.CDR
1 3 5 7 9 11
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
842779A1.CDR
The pushbuttons can be automatically controlled by activating the operands assigned to the PUSHBTN 1 SET (for latched and
self-reset mode) and PUSHBTN 1 RESET (for latched mode only) settings. The pushbutton reset status is declared when the
PUSHBUTTON 1 OFF operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent
on whether latched or self-reset mode is programmed.
• Latched mode: In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the PUSH-
BTN 1 SET setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set state
until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is stored in
non-volatile memory and maintained through a loss of control power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET set-
ting or by directly pressing the associated active front panel pushbutton.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY set-
tings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if con-
trol is not executed within a specified time period.
• Self-reset mode: In self-reset mode, a pushbutton will remain active for the time it is pressed (the pulse duration) plus
the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via FlexLogic™, the
pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand remains assigned to the PUSH-
BTN 1 SET setting has no effect on the pulse duration.
The pushbutton is reset (deactivated) in self-reset mode when the dropout delay specified in the PUSHBTN 1 DROP-OUT
TIMEsetting expires.
The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push-
button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari-
NOTE ous system disturbances that may cause transient assertion of the operating signals.
The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL and
PUSHBTN 1 REMOTE settings, respectively. If local locking is applied, the pushbutton will ignore set and reset commands
executed through the front panel pushbuttons. If remote locking is applied, the pushbutton will ignore set and reset com-
mands executed through FlexLogic™ operands.
The locking functions are not applied to the autorestart feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate
inhibit of the local and remote operation simplifies the implementation of local/remote control supervision.
Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined
messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off.
• PUSHBUTTON 1 FUNCTION: This setting selects the characteristic of the pushbutton. If set to “Disabled”, the push-
button is not active and the corresponding FlexLogic™ operands (both “On” and “Off”) are de-asserted. If set to “Self-
Reset”, the control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically
pressed or virtually pressed via a FlexLogic™ operand assigned to the PUSHBTN 1 SET setting.
When in “Self-Reset” mode and activated locally, the pushbutton control logic asserts the “On” corresponding Flex-
Logic™ operand as long as the pushbutton is being physically pressed, and after being released the deactivation of
the operand is delayed by the drop out timer. The “Off” operand is asserted when the pushbutton element is deacti-
vated. If the pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding “On” Flex-
Logic™ operand only for the time period specified by the PUSHBTN 1 DROP-OUT TIME setting.
If set to “Latched”, the control logic alternates the state of the corresponding FlexLogic™ operand between “On” and
“Off” on each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the
“Latched” mode, the states of the FlexLogic™ operands are stored in a non-volatile memory. Should the power supply
be lost, the correct state of the pushbutton is retained upon subsequent power up of the relay.
• PUSHBTN 1 ID TEXT: This setting specifies the top 20-character line of the user-programmable message and is 5
intended to provide ID information of the pushbutton. Refer to the User-definable displays section for instructions on
how to enter alphanumeric characters from the keypad.
• PUSHBTN 1 ON TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is in the “on” position. Refer to the User-definable displays section for instructions on
entering alphanumeric characters from the keypad.
• PUSHBTN 1 OFF TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is activated from the on to the off position and the PUSHBUTTON 1 FUNCTION is
“Latched”. This message is not displayed when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand
status is implied to be “Off” upon its release. The length of the “Off” message is configured with the PRODUCT SETUP
ÖØ DISPLAY PROPERTIES Ö FLASH MESSAGE TIME setting.
• PUSHBTN 1 HOLD: This setting specifies the time required for a pushbutton to be pressed before it is deemed active.
This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be
pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.
• PUSHBTN 1 SET: This setting assigns the FlexLogic™ operand serving to operate the pushbutton element and to
assert PUSHBUTTON 1 ON operand. The duration of the incoming set signal must be at least 100 ms.
• PUSHBTN 1 RESET: This setting assigns the FlexLogic™ operand serving to reset pushbutton element and to assert
PUSHBUTTON 1 OFF operand. This setting is applicable only if pushbutton is in latched mode. The duration of the
incoming reset signal must be at least 50 ms.
• PUSHBTN 1 AUTORST: This setting enables the user-programmable pushbutton autoreset feature. This setting is
applicable only if the pushbutton is in the “Latched” mode.
• PUSHBTN 1 AUTORST DELAY: This setting specifies the time delay for automatic reset of the pushbutton when in
the latched mode.
• PUSHBTN 1 REMOTE: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the
operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
• PUSHBTN 1 LOCAL: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the
front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
• PUSHBTN 1 DROP-OUT TIME: This setting applies only to “Self-Reset” mode and specifies the duration of the push-
button active status after the pushbutton has been released. When activated remotely, this setting specifies the entire
activation time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration.
This setting is required to set the duration of the pushbutton operating pulse.
• PUSHBTN 1 LED CTL: This setting assigns the FlexLogic™ operand serving to drive pushbutton LED. If this setting is
“Off”, then LED operation is directly linked to PUSHBUTTON 1 ON operand.
• PUSHBTN 1 MESSAGE: If pushbutton message is set to “High Priority”, the message programmed in the PUSHBTN 1
IDand PUSHBTN 1 ON TEXT settings will be displayed undisturbed as long as PUSHBUTTON 1 ON operand is asserted.
The high priority option is not applicable to the PUSHBTN 1 OFF TEXT setting.
This message can be temporary removed if any front panel keypad button is pressed. However, ten seconds of keypad
inactivity will restore the message if the PUSHBUTTON 1 ON operand is still active.
If the PUSHBTN 1 MESSAGE is set to “Normal”, the message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT
settings will be displayed as long as PUSHBUTTON 1 ON operand is asserted, but not longer than time period specified
by FLASH MESSAGE TIME setting. After the flash time is expired, the default message or other active target message is
displayed. The instantaneous reset of the flash message will be executed if any relay front panel button is pressed or
any new target or message becomes active.
The PUSHBTN 1 OFF TEXT setting is linked to PUSHBUTTON 1 OFF operand and will be displayed in conjunction with
PUSHBTN 1 ID only if pushbutton element is in the “Latched” mode. The PUSHBTN 1 OFF TEXT message will be displayed
as “Normal” if the PUSHBTN 1 MESSAGE setting is “High Priority” or “Normal”.
• PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into
event recorder.
SETTING
Function
LATCHED To user-programmable
= Enabled
pushbuttons logic
= Latched sheet 2, 842024A2
OR LATCHED/SELF-RESET
= Self-Reset
SETTING
Local Lock
Off = 0
Non-volatile latch
AND
S
TIMER
SETTING Latch
50 ms
Remote Lock R
Off = 0 AND
0
SETTING TIMER
OR
Hold 50 ms
TPKP
0
0
OR
SETTING
Set AND
Off = 0
To user-programmable
OR PUSHBUTTON ON pushbuttons logic
OR
sheet 2, 842024A2
SETTING
Reset AND
Off = 0
AND
5
SETTING
SETTING
Autoreset Delay
Autoreset Function
TPKP
= Enabled
AND
= Disabled
0
AND
SETTING
Drop-Out Timer
TIMER 0
FLEXLOGIC OPERAND 200 ms OR
TRST
PUSHBUTTON 1 ON
0
842021A3.CDR
AND
LCD MESSAGE
ENGAGE MESSAGE
SETTING
Flash Message Time
LATCHED SETTINGS
0 Top Text
AND
OR TRST = XXXXXXXXXX
On Text
= XXXXXXXXXX
Instantaneous
From user-programmable reset *
pushbuttons logic
sheet 1, 842021A3
FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON
Instantaneous
Instantaneous reset will be executed if any reset *
front panel button is pressed or any new
target or message becomes active.
This feature provides a mechanism where any of 256 selected FlexLogic™ operand states can be used for efficient moni-
toring. The feature allows user-customized access to the FlexLogic™ operand states in the relay. The state bits are packed
so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states
which are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-DEFINABLE DISPLAYS
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the USER DISPLAYS menu (between the TARGETS and ACTUAL VALUES top-level menus). The sub-menus facili-
tate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
• KEYPAD: Use the MENU key to select the USER DISPLAYS menu item to access the first user-definable display (note 5
that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The
display disappears after the default message time-out period specified by the PRODUCT SETUP ÖØ DISPLAY PROPER-
TIES ÖØ DEFAULT MESSAGE TIMEOUT setting.
• USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL
setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi-
gate the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The INVOKE AND SCROLL input and the DOWN key operate concurrently.
When the default timer expires (set by the DEFAULT MESSAGE TIMEOUT setting), the relay will start to cycle through the
user displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user dis-
play, not at the first user-defined display. The INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.
Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display will then prompt ADD TO USER DISPLAY LIST?. After selecting “Yes”, a message indi-
cates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus are
automatically configured with the proper content – this content may subsequently be edited.
5 This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user dis-
play. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the start
of a data field - the length of the data field needs to be accounted for. Up to five separate data fields can be entered in a
user display - the nth tilde (~) refers to the nth item.
A User Display may be entered from the faceplate keypad or the EnerVista UR Setup interface (preferred for convenience).
The following procedure shows how to enter text characters in the top and bottom lines from the faceplate keypad:
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. The HELP key may be pressed at any time for context sensitive help information.
7. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the faceplate
keypad, use the number keypad. Use the value of ‘0’ for any items not being used. Use the HELP key at any selected sys-
tem display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus
address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this
conversion).
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays will show in
sequence, changing every 4 seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option
to remove the display from the user display list. Use the MENU key again to exit the user displays menu.
USER DISPLAY 1 DISP 1 TOP LINE: Shows user-defined text with first Tilde marker.
Current X ~ A
DISP 1 BOTTOM LINE: Shows user-defined text with second Tilde marker.
MESSAGE
Current Y ~ A
DISP 1 ITEM 1: Shows decimal form of user-selected Modbus Register
MESSAGE Address, corresponding to first Tilde marker.
6016
DISP 1 ITEM 2: Shows decimal form of user-selected Modbus
MESSAGE Register Address, corresponding to 2nd Tilde marker.
6357
DISP 1 ITEM 3: This item is not being used - there is no corresponding
MESSAGE Tilde marker in Top or Bottom lines.
0
DISP 1 ITEM 4: This item is not being used - there is no corresponding
MESSAGE Tilde marker in Top or Bottom lines.
0
DISP 1 ITEM 5: This item is not being used - there is no corresponding
MESSAGE
0 Tilde marker in Top or Bottom lines.
5.2.17 INSTALLATION
5
PATH: SETTINGS Ö PRODUCT SETUP ÖØ INSTALLATION
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until RELAY SETTINGS is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
UNIT NOT PROGRAMMED self-test error message is displayed until the relay is put into the "Programmed" state.
The RELAY NAME setting allows the user to uniquely identify a relay. This name will appear on generated reports. This name
is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com-
munications channel using the IEC 61850 protocol.
When L90 is ordered with a process card module as a part of HardFiber system, then an additional Remote Resources
menu tree is available in EnerVista UR Setup software to allow configuring HardFiber system.
a) CURRENT BANKS
PATH: SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS Ö CURRENT BANK F1(L5)
Because energy parameters are accumulated, these values should be recorded and then reset immediately
prior to changing CT characteristics.
NOTE
Four banks of phase and ground CTs can be set, where the current banks are denoted in the following format (X represents
the module slot position letter):
Xa, where X = {F, L} and a = {1, 5}.
See the Introduction to AC Sources section at the beginning of this chapter for additional details.
These settings are critical for all features that have settings dependent on current measurements. When the relay is
ordered, the CT module must be specified to include a standard or sensitive ground input. As the phase CTs are connected
in wye (star), the calculated phasor sum of the three phase currents (IA + IB + IC = neutral current = 3Io) is used as the
5
input for the neutral overcurrent elements. In addition, a zero-sequence (core balance) CT which senses current in all of the
circuit primary conductors, or a CT in a neutral grounding conductor may also be used. For this configuration, the ground
CT primary rating must be entered. To detect low level ground fault currents, the sensitive ground input may be used. In this
case, the sensitive ground CT primary rating must be entered. Refer to chapter 3 for more details on CT connections.
Enter the rated CT primary current values. For both 1000:5 and 1000:1 CTs, the entry would be 1000. For correct opera-
tion, the CT secondary rating must match the setting (which must also correspond to the specific CT connections used).
The following example illustrates how multiple CT inputs (current banks) are summed as one source current. Given If the
following current banks:
• F1: CT bank with 500:1 ratio.
• F5: CT bank with 1000: ratio.
• L1: CT bank with 800:1 ratio.
The following rule applies:
SRC 1 = F1 + F5 + L1 (EQ 5.7)
1 pu is the highest primary current. In this case, 1000 is entered and the secondary current from the 500:1 ratio CT will be
adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then
a pickup level of 1 pu will operate on 1000 A primary.
The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A).
b) VOLTAGE BANKS
PATH: SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK F5(L5)
Because energy parameters are accumulated, these values should be recorded and then reset immediately
prior to changing VT characteristics.
CAUTION
Two banks of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, L} and a = {5}.
5 See the Introduction to AC sources section at the beginning of this chapter for additional details.
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5 CON-
NECTION made to the system as “Wye” or “Delta”. An open-delta source VT connection would be entered as “Delta”.
The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominal
voltage is applied to the VT primary.
NOTE
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta connec-
tion, the secondary voltage would be 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage value
entered must be the phase to neutral voltage which would be 115 / 3 = 66.4.
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage
value entered would be 120; that is, 14400 / 120.
The power system NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if the system frequency
cannot be measured from available signals. This may happen if the signals are not present or are heavily distorted. Before
reverting to the nominal frequency, the frequency tracking algorithm holds the last valid frequency measurement for a safe
period of time while waiting for the signals to reappear or for the distortions to decay.
The phase sequence of the power system is required to properly calculate sequence components and power parameters.
The PHASE ROTATION setting matches the power system phase sequence. Note that this setting informs the relay of the
actual system phase sequence, either ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con-
nected to system phases A, B, and C for correct operation.
The FREQUENCY AND PHASE REFERENCE setting determines which signal source is used (and hence which AC signal) for
phase angle reference. The AC signal used is prioritized based on the AC inputs that are configured for the signal source:
phase voltages takes precedence, followed by auxiliary voltage, then phase currents, and finally ground current.
For three phase selection, phase A is used for angle referencing ( V ANGLE REF = V A ), while Clarke transformation of the
phase signals is used for frequency metering and tracking ( V FREQUENCY = ( 2V A – V B – V C ) ⁄ 3 ) for better performance dur-
ing fault, open pole, and VT and CT fail conditions.
The phase reference and frequency tracking AC signals are selected based upon the Source configuration, regardless of
whether or not a particular signal is actually applied to the relay.
Phase angle of the reference signal will always display zero degrees and all other phase angles will be relative to this sig-
nal. If the pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
have the same AC signal reference. These results in very precise correlation of time tagging in the event recorder between
different UR-series relays provided the relays have an IRIG-B connection.
FREQUENCY TRACKING should only be set to “Disabled” in very unusual circumstances; consult the factory for spe-
cial variable-frequency applications.
NOTE
The frequency tracking feature will function only when the L90 is in the “Programmed” mode. If the L90 is “Not Pro-
grammed”, then metering values will be available but may exhibit significant errors.
NOTE
5
The nominal system frequency should be selected as 50 Hz or 60 Hz only. The FREQUENCY AND PHASE REFERENCE
setting, used as a reference for calculating all angles, must be identical for all terminals. Whenever the 87L function
NOTE
is “Enabled”, the frequency tracking function is disabled, and frequency tracking is driven by the L90 algorithm (see
the Theory of operation chapter). Whenever the 87L function is “Disabled”, the frequency tracking mechanism
reverts to the UR-series mechanism which uses the FREQUENCY TRACKING setting to provide frequency tracking for
all other elements and functions.
Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter repre-
sents either the first bank of four channels (1, 2, 3, 4) called “1” or the second bank of four channels (5, 6, 7, 8) called “5” in
a particular CT/VT module. Refer to the Introduction to AC sources section at the beginning of this chapter for additional
details on this concept.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others will be
referred. For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5”, scaled to
whichever CT has the higher ratio. Selecting “None” hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type,
ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs will be summed together.
User selection of AC parameters for comparator elements:
CT/VT modules automatically calculate all current and voltage parameters from the available inputs. Users must select the
specific input parameters to be measured by every element in the relevant settings menu. The internal design of the ele-
ment specifies which type of parameter to use and provides a setting for source selection. In elements where the parameter
may be either fundamental or RMS magnitude, such as phase time overcurrent, two settings are provided. One setting
specifies the source, the second setting selects between fundamental phasor and RMS.
AC input actual values:
The calculated parameters associated with the configured voltage and current inputs are displayed in the current and volt-
age sections of actual values. Only the phasor quantities associated with the actual AC physical input channels will be dis-
played here. All parameters contained within a configured source are displayed in the sources section of the actual values.
DISTURBANCE DETECTORS (INTERNAL):
The disturbance detector (ANSI 50DD) element is a sensitive current disturbance detector that detects any disturbance on
the protected system. The 50DD function is intended for use in conjunction with measuring elements, blocking of current
based elements (to prevent maloperation as a result of the wrong settings), and starting oscillography data capture. A dis-
turbance detector is provided for each source.
5 The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector scheme
logic is as follows:
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 1 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 1 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 2 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 2 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 6 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 6 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old 827092A3.CDR
This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.
F1 DSP Bank
F5
Source 1 Source 2
Amps Amps
Source 3
51BF-1 51BF-2
U1 Volts Amps
A W Var 87T
A W Var 51P
Volts Amps
M1
M1
Source 4
5
UR Relay
M5
5 MESSAGE
NUMBER: 0
CHNL ASYM COMP: Range: FlexLogic™ operand
MESSAGE
Off
BLOCK GPS TIME REF: Range: FlexLogic™ operand
MESSAGE
Off
MAX CHNL ASYMMETRY: Range: 0.0 to 10.0 ms in steps of 0.1
MESSAGE
1.5 ms
ROUND TRIP TIME Range: 0.0 to 10.0 ms in steps of 0.1
MESSAGE
CHANGE: 1.5 ms
Any changes to the L90 power system settings will change the protection system configuration. As such,
the 87L protection at all L90 protection system terminals must be temporarily disabled to allow the relays
NOTE
to acknowledge the new settings.
• NUMBER OF TERMINALS: This setting is the number of the terminals of the associated protected line.
• NUMBER OF CHANNELS: This setting should correspond to the type of communications module installed. If the relay
is applied on two terminal lines with a single communications channel, this setting should be selected as "1". For a two
terminal line with a second redundant channel for increased dependability, or for three terminal line applications, this
setting should be selected as "2".
• CHARGING CURRENT COMPENSATION: This setting enables and disables the charging current calculations and
corrections of current phasors. The voltage signals used for charging current compensation are taken from the source
assigned with the CURRENT DIFF SIGNAL SOURCE 1 setting. As such, it's critical to ensure that three-phase line voltage is
assigned to this source. The following diagram shows possible configurations.
Xreact Xreact
Xreact_n
X1line_capac
X0line_capac 831731A3.CDR
2. Four-reactor arrangement: three identical line reactors (Xreact) wye-connected with the fourth reactor (Xreact_n)
connected between reactor-bank neutral and the ground.
X 1line_capac ⋅ X react X 0line_capac ⋅ ( X react + 3 X react_n )
X C1 = ------------------------------------------------ , X C0 = --------------------------------------------------------------------------------
- (EQ 5.9)
X react – X 1line_capac X react + 3 X react_n – X 0line_capac
= 1 ⁄ ⎛ ---------------------------------- -⎞
1 1 1
2. For 3 terminal line: X react - + ----------------------------------
- + ----------------------------------
⎝X X X ⎠
react_terminal1 react_terminal2 react_terminal3
Xreact_n = the total neutral reactor inductive reactance. If identical reactors are installed at both line ends, the
value of the inductive reactance is divided by 2 (or 3 for a three-terminal line) before using in the above
equations. If the reactors installed at both ends of the line are different, the following equations apply:
1. For 2 terminal line: X react_n = 1 ⁄ ⎛ ---------------------------------------
1 1 -⎞
- + ---------------------------------------
⎝X ⎠
react_n_terminal1 X react_n_terminal2
Charging current compensation calculations should be performed for an arrangement where the VTs are con-
nected to the line side of the circuit; otherwise, opening the breaker at one end of the line will cause a calcula-
NOTE
tion error.
Differential current is significantly decreased when CHARGING CURRENT COMPENSATION is “Enabled” and the
proper reactance values are entered. The effect of charging current compensation is viewed in the METERING
NOTE
ÖØ 87L DIFFERENTIAL CURRENT actual values menu. This effect is very dependent on CT and VT accuracy.
• ZERO-SEQUENCE CURRENT REMOVAL: This setting facilitates application of the L90 to transmission lines with one
or more tapped transformers without current measurement at the taps. If the tapped transformer is connected in a
grounded wye on the line side, it becomes a source of the zero-sequence current for external ground faults. As the
transformer current is not measured by the L90 protection system, the zero-sequence current would create a spurious
differential signal and may cause a false trip.
If enabled, this setting forces the L90 to remove zero-sequence current from the phase currents prior to forming their
differential signals, ensuring protection stability on external ground faults. However, zero-sequence current removal
may cause all three phases to trip for internal ground faults. Consequently, a phase selective operation of the L90 is
not retained if the setting is enabled. This does not impose any limitation, as single-pole tripping is not recommended
for lines with tapped transformers. Refer to chapter 9 for guidelines.
• LOCAL (TERMINAL 1 and TERMINAL 2) ID NUMBER: In installations using multiplexers or modems for communica-
tion, it is desirable to ensure the data used by the relays protecting a given line comes from the correct relays. The L90
performs this check by reading the ID number contained in the messages sent by transmitting relays and comparing
this ID to the programmed correct ID numbers by the receiving relays. This check is used to block the differential ele-
ment of a relay, if the channel is inadvertently set to loopback mode, by recognizing its own ID on a received channel.
If an incorrect ID is found on a either channel during normal operation, the FlexLogic™ operand 87 CH1(2) ID FAIL is
set, driving the event with the same name. The result of channel identification is also available in ACTUAL VALUES Ö
STATUS ÖØ CHANNEL TESTS ÖØ VALIDITY OF CHANNEL CONFIGURATION for commissioning purposes. The default value
“0” at local relay ID setting indicates that the channel ID number is not to be checked. Refer to the Current differential
section in this chapter for additional information.
For two-terminal applications, only the LOCAL ID NUMBER and TERMINAL 1 ID NUMBER should be used. The TERMINAL 2
ID NUMBER is used for three-terminal applications.
• CHNL ASYM COMP: This setting enables/disables channel asymmetry compensation. The compensation is based on
absolute time referencing provided by GPS-based clocks via the L90 IRIG-B inputs. This feature should be used on
5 multiplexed channels where channel asymmetry can be expected and would otherwise cause errors in current differ-
ential calculations. The feature takes effect if all terminals are provided with reliable IRIG-B signals. If the IRIG-B signal
is lost at any terminal of the L90 protection system, or the real time clock not configured, then the compensation is not
calculated. If the compensation is in place prior to losing the GPS time reference, the last (memorized) correction is
applied as long as the value of CHNL ASYM COMP is “On”. See chapter 9 for additional information.
The GPS-based compensation for channel asymmetry can take three different effects:
• If CHNL ASYM COMP (GPS) is “Off”, compensation is not applied and the L90 uses only the ping-pong technique.
• If CHNL ASYM COMP (GPS) is “On” and all L90 terminals have a valid time reference (BLOCK GPS TIME REF not set),
then compensation is applied and the L90 effectively uses GPS time referencing tracking channel asymmetry if
the latter fluctuates.
• If CHNL ASYM COMP (GPS) is “On” and not all L90 terminals have a valid time reference (BLOCK GPS TIME REF not
set or IRIG-B FAILURE operand is not asserted), then compensation is not applied (if the system was not compen-
sated prior to the problem), or the memorized (last valid) compensation is used if compensation was in effect prior
to the problem.
The CHNL ASYM COMP setting dynamically turns the GPS compensation on and off. A FlexLogic™ operand that com-
bines several factors is typically used. The L90 protection system does not incorporate any pre-defined way of treating
certain conditions, such as failure of the GPS receiver, loss of satellite signal, channel asymmetry prior to the loss of
reference time, or change of the round trip time prior to loss of the time reference. Virtually any philosophy can be pro-
grammed by selecting the CHNL ASYM COMP setting. Factors to consider are:
• Fail-safe output of the GPS receiver. Some receivers may be equipped with the fail-safe output relay. The L90 sys-
tem requires a maximum error of 250 μs. The fail-safe output of the GPS receiver may be connected to the local
L90 via an input contact. In the case of GPS receiver fail, the channel compensation function can be effectively
disabled by using the input contact in conjunction with the BLOCK GPS TIME REF (GPS) setting.
• Channel asymmetry prior to losing the GPS time reference. This value is measured by the L90 and a user-pro-
grammable threshold is applied to it. The corresponding FlexLogic™ operands are produced if the asymmetry is
above the threshold (87L DIFF MAX 1 ASYM and 87L DIFF 2 MAX ASYM). These operands can be latched in Flex-
Logic™ and combined with other factors to decide, upon GPS loss, if the relays continue to compensate using the
memorized correction. Typically, one may decide to keep compensating if the pre-existing asymmetry was low.
• Change in the round trip travel time. This value is measured by the L90 and a user-programmable threshold
applied to it. The corresponding FlexLogic™ operands are produced if the delta change is above the threshold
(87L DIFF 1 TIME CHNG and 87L DIFF 2 TIME CHNG). These operands can be latched in FlexLogic™ and combined
with other factors to decide, upon GPS loss, if the relays continue to compensate using the memorized correction.
Typically, one may decide to disable compensation if the round trip time changes.
• BLOCK GPS TIME REF: This setting signals to the L90 that the time reference is not valid. The time reference may be
not accurate due to problems with the GPS receiver. The user must to be aware of the case when a GPS satellite
receiver loses its satellite signal and reverts to its own calibrated crystal oscillator. In this case, accuracy degrades in
time and may eventually cause relay misoperation. Verification from the manufacturer of receiver accuracy not worse
than 250 μs and the presence of an alarm contact indicating loss of the satellite signal is strongly recommended. If the
time reference accuracy cannot be guaranteed, it should be relayed to the L90 via contact inputs and GPS compensa-
tion effectively blocked using the contact position in conjunction with the BLOCK GPS TIME REF setting. This setting is
typically a signal from the GPS receiver signaling problems or time inaccuracy.
Some GPS receivers can supply erroneous IRIG-B signals during power-up and before locking to satellites. If the
receiver’s failsafe contact opens during power-up (allowing for an erroneous IRIG-B signal), then set a dropout delay
up to 15 minutes (depending on GPS receiver specifications) to the failsafe contact via FlexLogic™ to prevent incor-
rect relay response.
• MAX CHNL ASYMMETRY: This setting detects excessive channel asymmetry. The same threshold is applied to both
the channels, while the following per-channel FlexLogic™ operands are generated: 87L DIFF 1 MAX ASYM and 87L DIFF
2 MAX ASYM. These operands can be used to alarm on problems with communication equipment and/or to decide
whether channel asymmetry compensation remains in operation should the GPS-based time reference be lost. Chan-
nel asymmetry is measured if both terminals of a given channel have valid time reference.
If the memorized asymmetry value is much greater than expected (indicating a significant problem with IRIG-B timing),
then this operand can be also used to block GPS compensation, forcing the relay to use the memorized asymmetry
value. 5
• ROUND TRIP TIME CHANGE: This setting detects changes in round trip time. This threshold is applied to both chan-
nels, while the 87L DIFF 1 TIME CHNG and 87L DIFF 2 TIME CHNG ASYM per-channel FlexLogic™ operands are gener-
ated. These operands can be used to alarm on problems with communication equipment and/or to decide whether
channel asymmetry compensation remains in operation should the GPS-based time reference be lost.
IRIG-B FAILURE
DETECTED
FLEXLOGIC OPERAND
ACTUAL VALUE Ch2 Asymmetry > MAX 87L DIFF 2 MAX ASYM
Ch2 Asymmetry
RUN
831025A4.CDR
5.4.5 BREAKERS
A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Only informa-
tion concerning programming of the associated settings is covered here. These features are provided for two or more
breakers; a user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
The number of breaker control elements is dependent on the number of CT/VT modules specified with the L90. The follow-
ing settings are available for each breaker control element.
• BREAKER 1 FUNCTION: This setting enables and disables the operation of the breaker control feature.
• BREAKER1 PUSH BUTTON CONTROL: Set to “Enable” to allow faceplate push button operations.
• BREAKER 1 NAME: Assign a user-defined name (up to six characters) to the breaker. This name will be used in flash
messages related to breaker 1.
• BREAKER 1 MODE: This setting selects “3-pole” mode, where all breaker poles are operated simultaneously, or “1-
pole” mode where all breaker poles are operated either independently or simultaneously.
• BREAKER 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to
open breaker 1.
• BREAKER 1 BLK OPEN: This setting selects an operand that prevents opening of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay
to close breaker 1.
• BREAKER 1 BLK CLOSE: This setting selects an operand that prevents closing of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 ΦA/3P CLOSED: This setting selects an operand, usually a contact input connected to a breaker auxil-
iary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when the
5 breaker is closed. If the BREAKER 1 MODE setting is selected as “3-Pole”, this setting selects a single input as the oper-
and used to track the breaker open or closed position. If the mode is selected as “1-Pole”, the input mentioned above
is used to track phase A and the BREAKER 1 ΦB and BREAKER 1 ΦC settings select operands to track phases B and C,
respectively.
• BREAKER 1 ΦA/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the
inverted BREAKER 1 CLOSED status signal can be used.
• BREAKER 1 ΦB CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B closed position as above for phase A.
• BREAKER 1 ΦB OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B opened position as above for phase A.
• BREAKER 1 ΦC CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C closed position as above for phase A.
• BREAKER 1 ΦC OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C opened position as above for phase A.
• BREAKER 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the
52/a and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has
expired, the BREAKER 1 BAD STATUS FlexLogic™ operand is asserted from alarm or blocking purposes.
• BREAKER 1 EXT ALARM: This setting selects an operand, usually an external contact input, connected to a breaker
alarm reporting contact.
• BREAKER 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among
the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous oper-
ation of the poles.
If single-pole tripping and reclosing is used, the breaker may trip unsymmetrically for faults. In this case, the minimum
alarm delay setting must exceed the maximum time required for fault clearing and reclosing by a suitable margin.
• MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after
an operator has initiated a manual close command to operate a circuit breaker.
• BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service.
SETTING
BREAKER 1 FUNCTION
FLEXLOGIC OPERANDS
= Enabled
AND BREAKER 1 OFF CMD
= Disabled
BREAKER 1 TRIP A
BREAKER 1 TRIP B
AND
SETTING BREAKER 1 TRIP C
BREAKER 1 BLOCK OPEN
Off = 0 AND
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP 3-POLE
SETTING
BREAKER 1 OPEN
Off = 0
OR
SETTING
BREAKER 1 PUSHBUTTON
CONTROL
= Enabled
AND
USER 2 OFF/ON
To open BRK1-(Name)
OR
SETTING AND
BREAKER 1 CLOSE
Off = 0
OR
5
FLEXLOGIC OPERAND
AND BREAKER 1 MNL CLS
61850 Select & Close SETTING
MANUAL CLOSE RECAL1 TIME AND
FLEXLOGIC OPERAND
SETTING
OR AND BREAKER 1 ON CMD
BREAKER 1 BLOCK CLOSE
Off = 0 827061AS.CDR
NOTE
from breaker
control logic
sheet 1, BKR ENABLED
827061AR
SETTING
BREAKER 1 MODE
= 3-Pole FLEXLOGIC OPERAND BREAKER 1
= 1-Pole AND AND BREAKER 1 CLOSED CLOSED
OR (DEFAULT)
= Off
0
FLEXLOGIC OPERAND BREAKER 1
OR AND BREAKER 1 TROUBLE TROUBLE
SETTING Note: the BREAKER 1 TROUBLE LED
(DEFAULT)
BREAKER 1 ΦC CLSD AND can be latched using FlexLogic™
= Off
FLEXLOGIC OPERAND
SETTING
SETTING OR BREAKER 1 BAD STATUS
BREAKER 1 EXT ALARM
BREAKER 1 Toperate
= Off
FLEXLOGIC OPERANDS
AND BREAKER 1 ΦA BAD ST
XOR 0 BREAKER 1 ΦA CLSD
SETTING
AND BREAKER 1 ΦA OPEN
BREAKER 1 ΦA/3P OPND
AND BREAKER 1 ΦA INTERM
5 = Off
AND
AND
AND
SETTING
BREAKER 1 Toperate
FLEXLOGIC OPERANDS
AND BREAKER 1 ΦB BAD ST
XOR 0 BREAKER 1 ΦB CLSD
SETTING
AND BREAKER 1 ΦB OPEN
BREAKER 1 ΦB OPENED
AND BREAKER 1 ΦB INTERM
= Off
AND
AND
SETTING AND
BREAKER 1 Toperate
FLEXLOGIC OPERANDS
AND BREAKER 1 ΦC BAD ST
XOR 0 BREAKER 1 ΦC CLSD
SETTING
AND BREAKER 1 ΦC OPEN
BREAKER 1 ΦC OPENED
AND BREAKER 1 ΦC INTERM
= Off
AND
AND
AND
FLEXLOGIC OPERANDS
AND BREAKER 1 ANY P OPEN
AND BREAKER 1 1P OPEN
BREAKER 1 OOS
SETTING AND
XOR
BREAKER 1 OUT OF SV
= Off
AND
842025A1.CDR
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to cre-
ate an interlocking functionality. For greater security in determination of the switch pole position, both the 52/a and 52/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the L90.
• SWITCH 1 FUNCTION: This setting enables and disables the operation of the disconnect switch element.
• SWITCH 1 NAME: Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used
in flash messages related to disconnect switch 1.
• SWITCH 1 MODE: This setting selects “3-pole” mode, where all disconnect switch poles are operated simultaneously,
or “1-pole” mode where all disconnect switch poles are operated either independently or simultaneously.
• SWITCH 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to
open disconnect switch 1.
• SWITCH 1 BLK OPEN: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWITCH 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay to
close disconnect switch 1.
• SWITCH 1 BLK CLOSE: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWTCH 1 ΦA/3P CLSD: This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when
the disconnect switch is closed. If the SWITCH 1 MODE setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the SWITCH 1 ΦB and SWITCH 1 ΦC settings select operands to
track phases B and C, respectively.
• SWITCH 1 ΦA/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the disconnect switch is open. If a separate 52/b contact input is not avail-
able, then the inverted SWITCH 1 CLOSED status signal can be used.
• SWITCH 1 ΦB CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
• SWITCH 1 ΦB OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
• SWITCH 1 ΦC CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
5 single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
• SWITCH 1 ΦC OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
• SWITCH 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the SWITCH 1 BAD STATUS FlexLogic™ operand is asserted from alarm or blocking purposes.
• SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the L90 is in “Programmed” mode and not in the local control mode.
NOTE
SETTING
SWITCH 1 FUNCTION
= Disabled
= Enabled
SETTING
SWITCH 1 OPEN FLEXLOGIC OPERAND
= Off AND SWITCH 1 OFF CMD
OR
SETTING 61850 Select & Open
SWITCH 1 BLK OPEN
= Off
SETTING
SWITCH 1 CLOSE
= Off FLEXLOGIC OPERAND
OR AND SWITCH 1 ON CMD
SETTING 61850 Select & Close
SWITCH 1 BLK CLOSE
= Off
SETTING
SWITCH 1 MODE
= 3-Pole FLEXLOGIC OPERAND
= 1-Pole AND AND SWITCH 1 CLOSED
OR
FLEXLOGIC OPERAND
AND AND SWITCH 1 OPEN
OR
SETTING
SWTCH 1 ΦA/3P CLSD
FLEXLOGIC OPERAND
= Off
AND SWITCH 1 DISCREP
AND
SETTING
SETTING SWITCH 1 ALARM DELAY
SWITCH 1 ΦB CLOSED
= Off
AND
0
5
FLEXLOGIC OPERAND
OR AND SWITCH 1 TROUBLE
SETTING
SWITCH 1 ΦC CLOSED AND
= Off
FLEXLOGIC OPERAND
SETTING OR SWITCH 1 BAD STATUS
SWITCH 1 Toperate
FLEXLOGIC OPERANDS
AND SWITCH 1 ΦA BAD ST
XOR 0 SWITCH 1 ΦA CLSD
SETTING
AND SWITCH 1 ΦA OPEN
SWTCH 1 ΦA/3P OPND
AND SWITCH 1 ΦA INTERM
= Off
AND
AND
AND
SETTING
SWITCH 1 Toperate
FLEXLOGIC OPERANDS
AND SWITCH 1 ΦB BAD ST
XOR 0 SWITCH 1 ΦB CLSD
SETTING
AND SWITCH 1 ΦB OPEN
SWITCH 1 ΦB OPENED
AND SWITCH 1 ΦB INTERM
= Off
AND
AND
SETTING AND
SWITCH 1 Toperate
FLEXLOGIC OPERANDS
AND SWITCH 1 ΦC BAD ST
XOR 0 SWITCH 1 ΦC CLSD
SETTING
AND SWITCH 1 ΦC OPEN
SWITCH 1 ΦC OPENED
AND SWITCH 1 ΦC INTERM
= Off
AND
AND
AND
842026A3.CDR
5.4.7 FLEXCURVES™
a) SETTINGS
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ FLEXCURVES Ö FLEXCURVE A(D)
FlexCurves™ A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve™, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
The relay using a given FlexCurve™ applies linear approximation for times between the user-entered
points. Special care must be applied when setting the two points that are close to the multiple of pickup of
NOTE
1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin-
ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu.
Addr: Adds the time specified in this field (in ms) to each
curve operating time value.
d) EXAMPLE
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight (8) times pickup with an operating time of 30 ms. At approximately four (4) times pickup, the curve operat-
ing time is equal to the MRT and from then onwards the operating time remains at 200 ms (see below).
842719A1.CDR
842720A1.CDR
1 GE106
0.5
0.2
TIME (sec)
GE103
GE104 GE105
0.1
0.05
GE101 GE102
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842723A1.CDR
5
Figure 5–23: RECLOSER CURVES GE101 TO GE106
50
20 GE142
10
5
GE138
TIME (sec)
1 GE120
GE113
0.5
0.2
0.1
0.05
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842725A1.CDR
50
20
10
GE201
TIME (sec)
GE151
2
GE134 GE140
1
GE137
0.5
50
GE152
20
TIME (sec)
GE141
10
GE131
5
GE200
2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842728A1.CDR
50
20
GE164
10
2
TIME (sec)
GE162
1
0.5
GE133
0.2
GE165
0.1
0.05
GE161
0.02 GE163
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842729A1.CDR
Figure 5–27: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 5
20
GE132
10
1
TIME (sec)
0.5 GE139
0.2
GE136
0.1
GE116
0.05
GE118 GE117
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842726A1.CDR
Figure 5–28: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139
20
10
5
GE122
2
1
TIME (sec)
0.5
GE114
0.2
GE111
GE121
0.1
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842724A1.CDR
5 Figure 5–29: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122
50
20
GE202
10
TIME (sec)
GE135
2 GE119
0.5
0.2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842727A1.CDR
a) MAIN MENU
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT UNIT
The L90 Line Current Differential System is provided with an optional phasor measurement unit feature.
This feature is specified as a software option at the time of ordering. The number of phasor measurement
units available is also dependent on this option. Refer to the Ordering section of chapter 2 for additional
details.
The PHASOR MEASUREMENT UNIT menu allows specifying basic parameters of the measurements process such as signal
source, ID and station name, calibration data, triggering, recording, and content for transmission on each of the supported
ports. The reporting ports menus allow specifying the content and rate of reporting on each of the supported ports.
Precise IRIG-B input is vital for correct synchrophasor measurement and reporting. A DC level shift IRIG-B receiver
must be used for the phasor measurement unit to output proper synchrophasor values.
NOTE
b) BASIC CONFIGURATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1 Ö PMU 1 BASIC CONFIGURATION
This section contains basic phasor measurement unit (PMU) data, such as functions, source settings, and names.
• PMU 1 FUNCTION: This setting enables the PMU 1 functionality. Any associated functions (such as the recorder or
triggering comparators) will not function if this setting is “Disabled”. Use the command frame to force the communica-
tion portion of the feature to start/stop transmission of data. When the transmission is turned off, the PMU is fully oper-
ational in terms of calculating and recording the phasors.
• PMU 1 IDCODE: This setting assigns a numerical ID to the PMU. It corresponds to the IDCODE field of the data, con-
figuration, header, and command frames of the C37.118 protocol. The PMU uses this value when sending data, config-
uration, and header frames and responds to this value when receiving the command frame.
5 • PMU 1 STN: This setting assigns an alphanumeric ID to the PMU station. It corresponds to the STN field of the config-
uration frame of the C37.118 protocol. This value is a 16-character ASCII string as per the C37.118 standard.
• PMU 1 SIGNAL SOURCE: This setting specifies one of the available L90 signal sources for processing in the PMU.
Note that any combination of voltages and currents can be configured as a source. The current channels could be con-
figured as sums of physically connected currents. This facilitates PMU applications in breaker-and-a-half, ring-bus, and
similar arrangements. The PMU feature calculates voltage phasors for actual voltage (A, B, C, and auxiliary) and cur-
rent (A, B, C, and ground) channels of the source, as well as symmetrical components (0, 1, and 2) of both voltages
and currents. When configuring communication and recording features of the PMU, the user could select – from the
above superset – the content to be sent out or recorded.
• PMU 1 POST-FILTER: This setting specifies amount of post-filtering applied to raw synchrophasor measurements.
The raw measurements are produced at the rate of nominal system frequency using one-cycle data windows. This set-
ting is provided to deal with interfering frequencies and to balance speed and accuracy of synchrophasor measure-
ments for different applications. The following filtering choices are available:
This setting applies to all channels of the PMU. It is effectively for recording and transmission on all ports configured to
use data of this PMU.
c) CALIBRATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1(4) ÖØ PMU 1 CALIBRATION
This menu contains user angle calibration data for the phasor measurement unit (PMU). This data is combined with the fac-
tory adjustments to shift the phasors for better accuracy.
• PMU 1 VA... IG CALIBRATION ANGLE: These settings recognize applications with protection class voltage and cur-
rent sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter
a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the
true signal.
• PMU 1 SEQ VOLT SHIFT ANGLE: This setting allows correcting positive- and negative-sequence voltages for vector
groups of power transformers located between the PMU voltage point, and the reference node. This angle is effectively
added to the positive-sequence voltage angle, and subtracted from the negative-sequence voltage angle. Note that:
1. When this setting is not “0°”, the phase and sequence voltages will not agree. Unlike sequence voltages, the
phase voltages cannot be corrected in a general case, and therefore are reported as measured.
2. When receiving synchrophasor date at multiple locations, with possibly different reference nodes, it may be more
beneficial to allow the central locations to perform the compensation of sequence voltages.
3. This setting applies to PMU data only. The L90 calculates symmetrical voltages independently for protection and
control purposes without applying this correction.
4. When connected to line-to-line voltages, the PMU calculates symmetrical voltages with the reference to the AG
voltage, and not to the physically connected AB voltage (see the Metering Conventions section in Chapter 6).
• PMU 1 SEQ CURR SHIFT ANGLE: This setting allows correcting positive and negative-sequence currents for vector
groups of power transformers located between the PMU current point and the reference node. The setting has the
same meaning for currents as the PMU 1 SEQ VOLT SHIFT ANGLE setting has for voltages. Normally, the two correcting
angles are set identically, except rare applications when the voltage and current measuring points are located at differ-
ent windings of a power transformer.
d) PMU COMMUNICATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 COMMUNICATION ÖØ PMU 1 COMM PORT
5 Off
PMU1 PORT A-CH-8 Range: 16 alphanumeric characters
MESSAGE
NM: AnalogChannel8
PMU1 PORT D-CH-1: Range: FlexLogic™ operands
MESSAGE
Off
PMU1 PORT D-CH-1 Range: 16 alphanumeric characters
MESSAGE
NM: DigitalChannel1
PMU1 PORT D-CH-1 Range: On, Off
MESSAGE
NORMAL STATE: Off
↓
This section configures the phasor measurement unit (PMU) communication functions.
• PMU1 COMM PORT: This setting specifies the communication port for transmission of the PMU data.
• PMU1 PORT PHS-1 to PMU1 PORT PHS-14: These settings specify synchrophasors to be transmitted from the
superset of all synchronized measurements. The available synchrophasor values are tabulated below.
SELECTION MEANING
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current
These settings allow for optimizing the frame size and maximizing transmission channel usage, depending on a given
application. Select “Off” to suppress transmission of a given value.
• PMU1 PORT PHS-1 NM to PMU1 PORT PHS-14 NM: These settings allow for custom naming of the synchrophasor
channels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. These names
are typically based on station, bus, or breaker names.
5
• PMU1 PORT A-CH-1 to PMU1 PORT A-CH-8: These settings specify any analog data measured by the relay to be
included as a user-selectable analog channel of the data frame. Up to eight analog channels can be configured to send
any FlexAnalog value from the relay. Examples include active and reactive power, per phase or three-phase power,
power factor, temperature via RTD inputs, and THD. The configured analog values are sampled concurrently with the
synchrophasor instant and sent as 32-bit floating point values.
• PMU1 PORT A-CH-1 NM to PMU1 PORT A-CH-8 NM: These settings allow for custom naming of the analog chan-
nels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 PORT D-CH-1 to PMU1 PORT D-CH-16: These settings specify any digital flag measured by the relay to be
included as a user-selectable digital channel of the data frame. Up to sixteen digital channels can be configured to
send any FlexLogic™ operand from the relay. The configured digital flags are sampled concurrently with the synchro-
phasor instant. The values are mapped into a two-byte integer number, with byte 1 LSB corresponding to the digital
channel 1 and byte 2 MSB corresponding to digital channel 16.
• PMU1 PORT D-CH-1 NM to PMU1 PORT D-CH-16 NM: These settings allow for custom naming of the digital chan-
nels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 PORT D-CH-1 NORMAL STATE to PMU1 PORT D-CH-16 NORMAL STATE: These settings allow for specify-
ing a normal state for each digital channel. These states are transmitted in configuration frames to the data concentra-
tor.
Each logical phasor measurement unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated
PMU recorder, or cross-triggering of other PMUs of the system. They are:
• Overfrequency and underfrequency.
• Overvoltage and undervoltage.
• Overcurrent.
5 • Overpower.
• High rate of change of frequency.
The pre-configured triggers could be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder, and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
SETTING
PMU 1 USER TRIGGER:
Off = 0
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER FLEXLOGIC OPERAND
OR
bit 0
OR
f) USER TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 USER TRIGGER
The user trigger allows customized triggering logic to be constructed from FlexLogic™. The entire triggering logic is
refreshed once every two power system cycles.
g) FREQUENCY TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 FREQUENCY TRIGGER
The trigger responds to the frequency signal of the phasor measurement unit (PMU) source. The frequency is calculated
from either phase voltages, auxiliary voltage, phase currents and ground current, in this hierarchy, depending on the source
configuration as per L90 standards. This element requires the frequency is above the minimum measurable value. If the 5
frequency is below this value, such as when the circuit is de-energized, the trigger will drop out.
• PMU 1 FREQ TRIGGER LOW-FREQ: This setting specifies the low threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
• PMU 1 FREQ TRIGGER HIGH-FREQ: This setting specifies the high threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
• PMU 1 FREQ TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 FREQ TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER
PMU 1 TRIGGERED
PMU 1 FREQ TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND
h) VOLTAGE TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 VOLTAGE TRIGGER
This element responds to abnormal voltage. Separate thresholds are provided for low and high voltage. In terms of signal-
ing its operation, the element does not differentiate between the undervoltage and overvoltage events. The trigger
5 responds to the phase voltage signal of the phasor measurement unit (PMU) source. All voltage channels (A, B, and C or
AB, BC, and CA) are processed independently and could trigger the recorder. A minimum voltage supervision of 0.1 pu is
implemented to prevent pickup on a de-energized circuit, similarly to the undervoltage protection element.
• PMU 1 VOLT TRIGGER LOW-VOLT: This setting specifies the low threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 3% hysteresis.
• PMU 1 VOLT TRIGGER HIGH-VOLT: This setting specifies the high threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 3% hysteresis.
• PMU 1 VOLT TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 VOLT TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
SETTINGS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER PMU 1 CURR TRIGGER
FUNCTION:
PMU 1 POWER TRIGGER
Enabled = 1
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
AND
PMU 1 VOLT TRIG BLK:
OR
PMU 1 TRIGGERED
Off = 0 SETTING
OR
(V > HIGH-VOLT) tPKP
VB VBC PMU 1 VOLT TRIGGER
(0.1pu < V < LOW-VOLT) OR
VC VCA (V > HIGH-VOLT) tDPO
847005A1.CDR
i) CURRENT TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 CURRENT TRIGGER
This element responds to elevated current. The trigger responds to the phase current signal of the phasor measurement
unit (PMU) source. All current channel (A, B, and C) are processed independently and could trigger the recorder.
• PMU 1 CURR TRIGGER PICKUP: This setting specifies the pickup threshold for the overcurrent trigger, in per unit of
the PMU source. A value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis.
• PMU 1 CURR TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 CURR TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
SETTINGS
PMU 1 POWER TRIGGER
PMU 1 CURR TRIGGER
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
FUNCTION:
OR
PMU 1 TRIGGERED
Enabled = 1 SETTING
PMU 1 CURR TRIG BLK: AND PMU 1 USER TRIGGER:
Off = 0 Off = 0
SETTINGS
SETTINGS SETTINGS
PMU 1 CURR TRIGGER PICKUP:
to STAT bits of
PMU 1 SIGNAL PMU 1 CURR TRIGGER PKP TIME: the data frame
RUN
SOURCE:
PMU 1 CURR TRIGGER DPO TIME:
IA I > PICKUP FLEXLOGIC OPERAND
tPKP
OR
IB I > PICKUP PMU 1 CURR TRIGGER
IC I > PICKUP tDPO
847000A1.CDR
j) POWER TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 POWER TRIGGER
This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation the element does not differentiate between the three types of power. The trigger responds to
the single-phase and three-phase power signals of the phasor measurement unit (PMU) source.
• PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. For
single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,
the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase
power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER APPARENT: This setting specifies the pickup threshold for the apparent power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 POWER TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to
normal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the
triggering condition is asserted).
SETTINGS
PMU 1 POWER
TRIGGER FUNCTION: FLEXLOGIC OPERANDS
Enabled = 1 PMU 1 FREQ TRIGGER
AND
OR
PMU 1 TRIGGERED
PMU 1 POWER TRIGGER APPARENT: SETTING
SETTINGS
RUN PMU 1 USER TRIGGER:
PMU 1 SIGNAL SOURCE:
Off = 0
ACTIVE POWER, PA abs(P) > ACTIVE PICKUP
ACTIVE POWER, PB abs(P) > ACTIVE PICKUP
SETTINGS
ACTIVE POWER, PC abs(P) > ACTIVE PICKUP to STAT bits of
PMU 1 POWER TRIGGER PKP TIME: the data frame
3P ACTIVE POWER, P abs(P) > 3*(ACTIVE PICKUP)
REACTIVE POWER, QA
REACTIVE POWER, QB
abs(Q) > REACTIVE PICKUP
abs(Q) > REACTIVE PICKUP
PMU 1 POWER TRIGGER DPO TIME:
tPKP
FLEXLOGIC OPERAND 5
OR
k) DF/DT TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 df/dt TRIGGER
This element responds to frequency rate of change. Separate thresholds are provided for rising and dropping frequency.
The trigger responds to the rate of change of frequency (df/dt) of the phasor measurement unit (PMU) source.
5 • PMU 1 df/dt TRIGGER RAISE: This setting specifies the pickup threshold for the rate of change of frequency in the
raising direction (positive df/dt). The comparator applies a 3% hysteresis.
• PMU 1 df/dt TRIGGER FALL: This setting specifies the pickup threshold for the rate of change of frequency in the fall-
ing direction (negative df/dt). The comparator applies a 3% hysteresis.
• PMU 1 df/dt TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 df/dt TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 TRIGGERED
PMU 1 df/dt TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND
l) PMU RECORDING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1 ÖØ PMU 1 RECORDING
PMU 1 PMU 1 RECORDING Range: 1, 2, 4, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times
RECORDING RATE: 10/sec per second
Each logical phasor measurement unit (PMU) is associated with a recorder. The triggering condition is programmed via the
PMU 1 TRIGGERING menu. The recorder works with polar values using resolution as in the PMU actual values.
TRIGGER
REC
847709A2.CDR
• PMU 1 TIMED TRIGGER POSITION: This setting specifies the amount of pre-trigger data in percent of the entire
record.
• PMU1 PORT 1 PHS-1 to PMU1 PORT 1 PHS-14: These settings specify synchrophasors to be recorded from the
superset of all synchronized measurements as indicated in the following table. These settings allow for optimizing the
record size and content depending on a given application. Select “Off” to suppress recording of a given value.
VALUE DESCRIPTION
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current
• PMU 1 REC PHS-1 NM to PMU 1 REC PHS-14 NM: These settings allow for custom naming of the synchrophasor
channels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. Typically
these names would be based on station, bus, or breaker names.
5
• PMU 1 REC A-CH-1 to PMU 1 REC A-CH-8: These settings specify analog data measured by the relay to be included
as a user-selectable analog channel of the record. Up to eight analog channels can be configured to record any Flex-
Analog value from the relay. Examples include active and reactive power, per phase or three-phase power, power fac-
tor, temperature via RTD inputs, and THD. The configured analogs are sampled concurrently with the synchrophasor
instant.
• PMU 1 REC A-CH-1 NM to PMU 1 REC A-CH-8 NM: These settings allow for custom naming of the analog channels.
Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU 1 REC D-CH-1 to PMU 1 REC D-CH-16: These settings specify any digital flag measured by the relay to be
included as a user-selectable digital channel in the record. Up to digital analog channels can be configured to record
any FlexLogic™ operand from the relay. The configured digital flags are sampled concurrently with the synchrophasor
instant.
• PMU 1 REC D-CH-1 NM to PMU 1 REC D-CH-16 NM: This setting allows custom naming of the digital channels. Six-
teen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
m) NETWORK CONNECTION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1(4) ÖØ REPORTING OVER NETWORK
To provide maximum flexibility to the user, the arrangement of internal digital logic combines fixed and user-programmed
parameters. Logic upon which individual features are designed is fixed, and all other logic, from digital input signals through
elements or combinations of elements to digital outputs, is variable. The user has complete control of all variable logic
through FlexLogic™. In general, the system receives analog and digital inputs which it uses to produce analog and digital
outputs. The major sub-systems of a generic UR-series relay involved in this process are shown below.
The logic that determines the interaction of inputs, elements, schemes and outputs is field programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is available
internally and on the communication ports for other relays to use (distributed FlexLogic™).
FlexLogic™ allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes and outputs. The operators are logic gates, timers and latches (with
set and reset inputs). A system of sequential operations allows any combination of specified operands to be assigned as
inputs to specified operators to create an output. The final output of an equation is a numbered register called a virtual out-
put. Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic™ equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of parame-
ters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, i.e. flag set) or 0 (=OFF, i.e.
flag not set). Each equation is evaluated at least 4 times every power system cycle.
Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper-
ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different
types of operands are listed in the table below.
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–8: L90 FLEXLOGIC™ OPERANDS (Sheet 1 of 9)
OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed
PUSHBUTTONS CONTROL PUSHBTN 2 ON Control pushbutton 2 is being pressed
CONTROL PUSHBTN 3 ON Control pushbutton 3 is being pressed
CONTROL PUSHBTN 4 ON Control pushbutton 4 is being pressed
CONTROL PUSHBTN 5 ON Control pushbutton 5 is being pressed
CONTROL PUSHBTN 6 ON Control pushbutton 6 is being pressed
CONTROL PUSHBTN 7 ON Control pushbutton 7 is being pressed
ELEMENT: 50DD SV Disturbance detector has operated
50DD supervision
ELEMENT: 87L DIFF OP At least one phase of current differential is operated
87L current 87L DIFF OP A Phase A of current differential has operated
differential 87L DIFF OP B Phase B of current differential has operated
87L DIFF OP C Phase C of current differential has operated
87L DIFF RECVD DTT A Direct transfer trip phase A has been received
87L DIFF RECVD DTT B Direct transfer trip phase B has been received
87L DIFF RECVD DTT C Direct transfer trip phase C has been received
87L DIFF KEY DTT Direct transfer trip is keyed
87L DIFF PFLL FAIL Phase and frequency lock loop (PFLL) has failed
87L DIFF CH ASYM DET Channel asymmetry greater than 1.5 ms detected
87L DIFF CH1 FAIL Channel 1 has failed
87L DIFF CH2 FAIL Channel 2 has failed
87L DIFF CH1 LOSTPKT Exceeded maximum lost packet threshold on channel 1
87L DIFF CH2 LOSTPKT Exceeded maximum lost packet threshold on channel 2
87L DIFF CH1 CRCFAIL Exceeded maximum CRC error threshold on channel 1
87L DIFF CH2 CRCFAIL Exceeded maximum CRC error threshold on channel 2
87L DIFF CH1 ID FAIL The ID check for a peer L90 on channel 1 has failed
87L DIFF CH2 ID FAIL The ID check for a peer L90 on channel 2 has failed
87L DIFF GPS FAIL The GPS signal failed or is not configured properly at any terminal
87L DIFF 1 MAX ASYM Asymmetry on channel 1 exceeded preset value
87L DIFF 2 MAX ASYM
87L DIFF 1 TIME CHNG
Asymmetry on channel 2 exceeded preset value
Change in round trip delay on channel 1 exceeded preset value
5
87L DIFF 2 TIME CHNG Change in round trip delay on channel 2 exceeded preset value
87L DIFF GPS 1 FAIL GPS failed at remote terminal 1 (channel 1)
87L DIFF GPS 2 FAIL GPS failed at remote terminal 1 (channel 2)
87L DIFF BLOCKED The 87L function is blocked due to communication problems
ELEMENT: 87L TRIP OP At least one phase of the trip output element has operated
87L differential trip 87L TRIP OP A Phase A of the trip output element has operated
87L TRIP OP B Phase B of the trip output element has operated
87L TRIP OP C Phase C of the trip output element has operated
87L TRIP 1P OP Single-pole trip is initiated
87L TRIP 3P OP Three-pole trip is initiated
ELEMENT: AR ENABLED Autoreclosure is enabled and ready to perform
Autoreclose AR DISABLED Autoreclosure is disabled
(1P/3P) AR RIP Autoreclosure is in “reclose-in-progress” state
AR 1-P RIP A single-pole reclosure is in progress
AR 3-P/1 RIP A three-pole reclosure is in progress, via dead time 1
AR 3-P/2 RIP A three-pole reclosure is in progress, via dead time 2
AR 3-P/3 RIP A three-pole reclosure is in progress, via dead time 3
AR 3-P/4 RIP A three-pole reclosure is in progress, via dead time 4
AR LO Autoreclosure is in lockout state
AR BKR1 BLK Reclosure of breaker 1 is blocked
AR BKR2 BLK Reclosure of breaker 2 is blocked
AR CLOSE BKR1 Reclose breaker 1 signal
AR CLOSE BKR2 Reclose breaker 2 signal
AR FORCE 3-P TRIP Force any trip to a three-phase trip
AR SHOT CNT > 0 The first ‘CLOSE BKR X’ signal has been issued
AR SHOT CNT = 1 Shot count is equal to 1
AR SHOT CNT = 2 Shot count is equal to 2
AR SHOT CNT = 3 Shot count is equal to 3
AR SHOT CNT = 4 Shot count is equal to 4
AR ZONE 1 EXTENT The zone 1 distance function must be set to the extended overreach value
AR INCOMPLETE SEQ The incomplete sequence timer timed out
AR RESET Autoreclose has been reset either manually or by the reset timer
ELEMENT: AUX OV1 PKP Auxiliary overvoltage element has picked up
Auxiliary AUX OV1 DPO Auxiliary overvoltage element has dropped out
overvoltage AUX OV1 OP Auxiliary overvoltage element has operated
AUX OV2 to AUX OV3 Same set of operands as shown for AUX OV1
ELEMENT: SRC1 VT FUSE FAIL OP Source 1 VT fuse failure detector has operated
VTFF (Voltage SRC1 VT FUSE FAIL DPO Source 1 VT fuse failure detector has dropped out
transformer fuse SRC1 VT FUSE FAIL VOL LOSS Source 1 has lost voltage signals (V2 below 15% AND V1 below 5%
failure) of nominal)
SRC2 VT FUSE FAIL to Same set of operands as shown for SRC1 VT FUSE FAIL
SRC4 VT FUSE FAIL
ELEMENT: STUB BUS OP Stub bus is operated
Stub bus
ELEMENT: SWITCH 1 OFF CMD Disconnect switch 1 open command initiated
Disconnect switch SWITCH 1 ON CMD Disconnect switch 1 close command initiated
SWITCH 1 ΦA BAD ST Disconnect switch 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
SWITCH 1 ΦA INTERM Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦA CLSD Disconnect switch 1 phase A is closed
SWITCH 1 ΦA OPEN Disconnect switch 1 phase A is open
SWITCH 1 ΦB BAD ST Disconnect switch 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
SWITCH 1 ΦA INTERM Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦB CLSD Disconnect switch 1 phase B is closed
SWITCH 1 ΦB OPEN Disconnect switch 1 phase B is open
SWITCH 1 ΦC BAD ST Disconnect switch 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
SWITCH 1 ΦA INTERM Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦC CLSD Disconnect switch 1 phase C is closed
SWITCH 1 ΦC OPEN Disconnect switch 1 phase C is open
SWITCH 1 BAD STATUS Disconnect switch 1 bad status is detected on any pole
SWITCH 1 CLOSED Disconnect switch 1 is closed
SWITCH 1 OPEN Disconnect switch 1 is open
SWITCH 1 DISCREP Disconnect switch 1 has discrepancy
SWITCH 1 TROUBLE Disconnect switch 1 trouble alarm
SWITCH 2... Same set of operands as shown for SWITCH 1
FIXED OPERANDS Off Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
5
On Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS: Cont Ip 1 On (will not appear unless ordered)
Contact inputs Cont Ip 2 On (will not appear unless ordered)
↓ ↓
Cont Ip 1 Off (will not appear unless ordered)
Cont Ip 2 Off (will not appear unless ordered)
↓ ↓
INPUTS/OUTPUTS: Cont Op 1 IOn (will not appear unless ordered)
Contact outputs, Cont Op 2 IOn (will not appear unless ordered)
current ↓ ↓
(from detector on
form-A output only)
INPUTS/OUTPUTS: Cont Op 1 VOn (will not appear unless ordered)
Contact outputs, Cont Op 2 VOn (will not appear unless ordered)
voltage ↓ ↓
(from detector on
form-A output only) Cont Op 1 VOff (will not appear unless ordered)
Cont Op 2 VOff (will not appear unless ordered)
↓ ↓
INPUTS/OUTPUTS: Direct I/P 1-1 On (appears only when an inter-relay communications card is used)
Direct input ↓ ↓
Direct I/P 1-8 On (appears only when inter-relay communications card is used)
Direct I/P 2-1 On (appears only when inter-relay communications card is used)
↓ ↓
Direct I/P 2-8 On (appears only when inter-relay communications card is used)
INPUTS/OUTPUTS: RemDPS Ip 1 BAD Asserted while the remote double-point status input is in the bad state.
Remote double- RemDPS Ip 1 INTERM Asserted while the remote double-point status input is in the intermediate
point status inputs state.
RemDPS Ip 1 OFF Asserted while the remote double-point status input is off.
RemDPS Ip 1 ON Asserted while the remote double-point status input is on.
REMDPS Ip 2... Same set of operands as per REMDPS 1 above
INPUTS/OUTPUTS: REMOTE INPUT 1 On Flag is set, logic=1
Remote inputs ↓ ↓
REMOTE INPUT 32 On Flag is set, logic=1
INPUTS/OUTPUTS: Virt Ip 1 On Flag is set, logic=1
Virtual inputs ↓ ↓
Virt Ip 64 On Flag is set, logic=1
PASSWORD ACCESS LOC SETG OFF Asserted when local setting access is disabled.
SECURITY ACCESS LOC SETG ON Asserted when local setting access is enabled.
ACCESS LOC CMND OFF Asserted when local command access is disabled.
ACCESS LOC CMND ON Asserted when local command access is enabled.
ACCESS REM SETG OFF Asserted when remote setting access is disabled.
ACCESS REM SETG ON Asserted when remote setting access is enabled.
ACCESS REM CMND OFF Asserted when remote command access is disabled.
5 ACCESS REM CMND ON
UNAUTHORIZED ACCESS
Asserted when remote command access is enabled.
Asserted when a password entry fails while accessing a password protected
level of the L90.
REMOTE DEVICES REMOTE DEVICE 1 On Flag is set, logic=1
↓ ↓
REMOTE DEVICE 16 On Flag is set, logic=1
REMOTE DEVICE 1 Off Flag is set, logic=1
↓ ↓
REMOTE DEVICE 16 Off Flag is set, logic=1
RESETTING RESET OP Reset command is operated (set by all three operands below).
RESET OP (COMMS) Communications source of the reset command.
RESET OP (OPERAND) Operand (assigned in the INPUTS/OUTPUTS ÖØ RESETTING menu) source
of the reset command.
RESET OP (PUSHBUTTON) Reset key (pushbutton) source of the reset command.
SELF- ANY MAJOR ERROR Any of the major self-test errors generated (major error)
DIAGNOSTICS ANY MINOR ERROR Any of the minor self-test errors generated (minor error)
ANY SELF-TESTS Any self-test errors generated (generic, any error)
BATTERY FAIL See description in Chapter 7: Commands and targets
DIRECT DEVICE OFF See description in Chapter 7: Commands and targets
DIRECT RING BREAK See description in Chapter 7: Commands and targets
EQUIPMENT MISMATCH See description in Chapter 7: Commands and targets
ETHERNET SWITCH FAIL See description in Chapter 7: Commands and targets
FLEXLOGIC ERR TOKEN See description in Chapter 7: Commands and targets
IRIG-B FAILURE See description in Chapter 7: Commands and targets
LATCHING OUT ERROR See description in Chapter 7: Commands and targets
MAINTENANCE ALERT See description in Chapter 7: Commands and targets
PORT 1 OFFLINE See description in Chapter 7: Commands and targets
PORT 2 OFFLINE See description in Chapter 7: Commands and targets
PORT 3 OFFLINE See description in Chapter 7: Commands and targets
PORT 4 OFFLINE See description in Chapter 7: Commands and targets
PORT 5 OFFLINE See description in Chapter 7: Commands and targets
PORT 6 OFFLINE See description in Chapter 7: Commands and targets
PRI ETHERNET FAIL See description in Chapter 7: Commands and targets
PROCESS BUS FAILURE See description in Chapter 7: Commands and targets
REMOTE DEVICE OFF See description in Chapter 7: Commands and targets
RRTD COMM FAIL See description in Chapter 7: Commands and targets
SEC ETHERNET FAIL See description in Chapter 7: Commands and targets
SNTP FAILURE See description in Chapter 7: Commands and targets
SYSTEM EXCEPTION See description in Chapter 7: Commands and targets
TEMP MONITOR See description in Chapter 7: Commands and targets
UNIT NOT PROGRAMMED See description in Chapter 7: Commands and targets
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name
or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic™ operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic™ are listed in the Flex-
Logic™ operators table.
5 LATCH (S,R) Latch (set, reset): reset-dominant The parameter preceding LATCH(S,R) is
the reset input. The parameter preceding
the reset input is the set input.
Timer TIMER 1 Timer set with FlexLogic™ timer 1 settings. The timer is started by the preceding
↓ ↓ parameter. The output of the timer is
TIMER 32 Timer set with FlexLogic™ timer 32 settings. TIMER #.
Assign = Virt Op 1 Assigns previous FlexLogic™ operand to virtual The virtual output is set by the preceding
virtual ↓ output 1. parameter
output = Virt Op 96 ↓
Assigns previous FlexLogic™ operand to virtual
output 96.
When forming a FlexLogic™ equation, the sequence in the linear array of parameters must follow these general rules:
1. Operands must precede the operator which uses the operands as inputs.
2. Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3. Assigning the output of an operator to a virtual output terminates the equation.
4. A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used
once. If this rule is broken, a syntax error will be declared.
Each equation is evaluated in the order in which the parameters have been entered.
FlexLogic™ provides latches which by definition have a memory action, remaining in the set state after the
set input has been asserted. However, they are volatile; that is, they reset on the re-application of control
NOTE power.
When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting
value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during
testing, for example, it is suggested to power the unit down and then back up.
This section provides an example of implementing logic for a typical application. The sequence of the steps is quite impor-
tant as it should minimize the work necessary to develop the relay settings. Note that the example presented in the figure
below is intended to demonstrate the procedure, not to solve a specific application situation.
In the example below, it is assumed that logic has already been programmed to produce virtual outputs 1 and 2, and is only
a part of the full set of equations used. When using FlexLogic™, it is important to make a note of each virtual output used –
a virtual output designation (1 to 96) can only be properly assigned once.
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay Operate Output
OR #2
DIGITAL ELEMENT 1 on Dropout Relay H1
State=Pickup
(200 ms)
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay
OR #2 VIRTUAL OUTPUT 4
DIGITAL ELEMENT 1 on Dropout
State=Pickup (200 ms)
827026A2.VSD
2. Prepare a logic diagram for the equation to produce virtual output 3, as this output will be used as an operand in the
virtual output 4 equation (create the equation for every output that will be used as an operand first, so that when these
operands are required they will already have been evaluated and assigned to a specific virtual output). The logic for
virtual output 3 is shown below with the final output assigned.
DIGITAL ELEMENT 2
State=Operated
827027A2.VSD
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay VIRTUAL
OR #2
DIGITAL ELEMENT 1 on Dropout OUTPUT 4
State=Pickup
(200 ms)
Timer 1
5 VIRTUAL OUTPUT 3
State=ON
Time Delay
on Pickup
(800 ms)
CONTACT INPUT H1c
State=Closed 827028A2.VSD
01
02
03
04
05
.....
97
98
99
827029A1.VSD
98: The gate preceding the output is an AND, which in this case requires two inputs. The operator for this gate is a 2-
input AND so the parameter is “AND(2)”. Note that FlexLogic™ rules require that the number of inputs to most
types of operators must be specified to identify the operands for the gate. As the 2-input AND will operate on the
two operands preceding it, these inputs must be specified, starting with the lower.
97: This lower input to the AND gate must be passed through an inverter (the NOT operator) so the next parameter is
“NOT”. The NOT operator acts upon the operand immediately preceding it, so specify the inverter input next.
96: The input to the NOT gate is to be contact input H1c. The ON state of a contact input can be programmed to be
set when the contact is either open or closed. Assume for this example the state is to be ON for a closed contact.
The operand is therefore “Cont Ip H1c On”.
95: The last step in the procedure is to specify the upper input to the AND gate, the operated state of digital element 2.
This operand is "DIG ELEM 2 OP".
Writing the parameters in numerical order can now form the equation for virtual output 3:
[95] DIG ELEM 2 OP
[96] Cont Ip H1c On
[97] NOT
[98] AND(2)
[99] = Virt Op 3
It is now possible to check that this selection of parameters will produce the required logic by converting the set of parame-
ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 3 dia-
gram as a check.
FLEXLOGIC ENTRY n:
95 DIG ELEM 2 OP VIRTUAL
AND
FLEXLOGIC ENTRY n: OUTPUT 3
96 Cont Ip H1c On
FLEXLOGIC ENTRY n:
5
97 NOT
FLEXLOGIC ENTRY n:
98 AND (2)
FLEXLOGIC ENTRY n:
99 =Virt Op 3
827030A2.VSD
FLEXLOGIC ENTRY n:
85 Virt Op 4 On
FLEXLOGIC ENTRY n:
86 Virt Op 1 On
FLEXLOGIC ENTRY n:
87
5 88
Virt Op 2 On
FLEXLOGIC ENTRY n:
Set
LATCH
Virt Ip 1 On
XOR OR Reset
FLEXLOGIC ENTRY n:
89 DIG ELEM 1 PKP
FLEXLOGIC ENTRY n:
90 XOR
FLEXLOGIC ENTRY n:
91 Virt Op 3 On VIRTUAL
OR T2
FLEXLOGIC ENTRY n: OUTPUT 4
92 OR (4)
FLEXLOGIC ENTRY n:
93 LATCH (S,R)
FLEXLOGIC ENTRY n:
94 Virt Op 3 On T1
FLEXLOGIC ENTRY n:
95 TIMER 1
FLEXLOGIC ENTRY n:
96 Cont Ip H1c On
FLEXLOGIC ENTRY n:
97 OR (3)
FLEXLOGIC ENTRY n:
98 TIMER 2
FLEXLOGIC ENTRY n:
99 =Virt Op 4 827031A2.VSD
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a
form of feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8. The logic should always be tested after it is loaded into the relay, in the same fashion as has been used in the past.
Testing can be simplified by placing an "END" operator within the overall set of FlexLogic™ equations. The equations
will then only be evaluated up to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
There are 512 FlexLogic™ entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" Ele-
ment is selected as a FlexLogic™ entry, the associated state flag will never be set to ‘1’. The ‘+/–‘ key may be used when
editing FlexLogic™ equations from the keypad to quickly scan through the major parameter types.
There are 32 identical FlexLogic™ timers available. These timers can be used as operators for FlexLogic™ equations.
• TIMER 1 TYPE: This setting is used to select the time measuring unit.
• TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0".
• TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".
5.5.7 FLEXELEMENTS™
A FlexElement™ is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a
net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed
number or its absolute value could be used as per user's choice.
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as
per user's choice.
SETTING
SETTINGS
FLEXELEMENT 1
FUNCTION: FLEXELEMENT 1 INPUT
MODE:
Enabled = 1
FLEXELEMENT 1 COMP
MODE:
Disabled = 0
FLEXELEMENT 1
DIRECTION:
SETTING
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 BLK:
FLEXELEMENT 1 INPUT
AND HYSTERESIS:
Off = 0
FLEXELEMENT 1 dt UNIT: SETTINGS
FxE 1 PKP
ACTUAL VALUE
The FLEXELEMENT 1 DIRECTION setting enables the relay to respond to either high or low values of the operating signal. The
following figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP and FLEXELEMENT 1 HYS-
TERESIS settings.
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
842705A1.CDR
FLEXELEMENT 1 PKP
5 FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
842706A2.CDR
The FLEXELEMENT 1 PICKUP setting specifies the operating threshold for the effective operating signal of the element. If set
to “Over”, the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to “Under”, the
element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value.
The FLEXELEMENT 1 HYSTERESIS setting controls the element dropout. It should be noticed that both the operating signal
and the pickup threshold can be negative facilitating applications such as reverse power alarm protection. The FlexEle-
ment™ can be programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP set-
ting is entered in per-unit values using the following definitions of the base units:
The FLEXELEMENT 1 HYSTERESIS setting defines the pickup–dropout relation of the element by specifying the width of the
hysteresis loop as a percentage of the pickup value as shown in the FlexElement™ direction, pickup, and hysteresis dia-
gram.
The FLEXELEMENT 1 DT UNIT setting specifies the time unit for the setting FLEXELEMENT 1 dt. This setting is applicable only if
FLEXELEMENT 1 COMP MODE is set to “Delta”. The FLEXELEMENT 1 DT setting specifies duration of the time interval for the
rate of change mode of operation. This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to “Delta”.
This FLEXELEMENT 1 PKP DELAY setting specifies the pickup delay of the element. The FLEXELEMENT 1 RST DELAY setting
specifies the reset delay of the element.
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
• LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
• LATCH 1 SET: If asserted, the specified FlexLogic™ operands 'sets' Latch 1.
5 • LATCH 1 RESET: If asserted, the specified FlexLogic™ operand 'resets' Latch 1.
SETTING
SETTING
LATCH N LATCH N LATCH N LATCH N LATCH N LATCH 1 FUNCTION:
TYPE SET RESET ON OFF
LATCH 1 TYPE:
Reset ON OFF ON OFF Disabled=0
Dominant Enabled=1 RUN
OFF OFF Previous Previous
State State
ON ON OFF ON SETTING
Each protection element can be assigned up to six different sets of settings according to setting group designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (for example, altered power system config-
uration, season of the year, etc.). The active setting group can be preset or selected via the SETTING GROUPS menu (see the
Control elements section later in this chapter). See also the Introduction to elements section at the beginning of this chap-
ter.
Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if
no other group is active (see the Control elements section for additional details).
a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö LINE DIFFERENTIAL ELEMENTS
b) CURRENT DIFFERENTIAL
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö LINE DIFFERENTIAL... Ö CURRENT DIFFERENTIAL
5-124
VAG
To remote relays
VBG Compute charging current channel 1 and 2
VCG
CALCULATE
SETTINGS RUN
Signal Source 1
CALCULATE IA
= User-selection DATA FROM LOCAL END
CT ratio matching RUN IA Compute IB
Signal Source 2 Charging Current
Process phasor IB phasors and IC
= User-selection IA ΣIA2 at Timestamp variance (local)
Compute sum computations IC I_0
Signal Source 3 of currents IB ΣIB2 at Timestamp
= User-selection IC ΣIC2 at Timestamp
Compute local
Signal Source 4
restraint
= User-selection
CLOCK
5.6 GROUPED ELEMENTS
SYNCHRONIZATION
SETTING SYSTEM SETTINGS
AND SETTING
Number of Terminals Clocks are Ground Pickup
Ground Function
=3 synchronized, phase Ground Restraint
OR = Enbabled
AND and frequency locked AND RUN
SETTING loop PFLL is OK
| IG operate | 2 FLEXLOGIC OPERAND
Number of Channels OR >1 87L DIFF PKP G
| IG restraint | 2
=2 AND
SETTING
DATA FROM REMOTE 1 SETTING
Ground Delay
CT Tap 1 SETTINGS
Channel 1 OK OR TPKP FLEXLOGIC OPERANDS
AND RUN IA Pickup
Channel 1 ID Fail 87L DIFF OP G
IB Restraint 1
ΣIA2 at Timestamp Compute phasors 0
and variance IC Restraint 2
ΣIB2 at Timestamp
(remote 1) I_0 Breakpoint
ΣIC2 at Timestamp
RUN
DTT PHASE A
AND | IA operate | 2 FLEXLOGIC OPERAND
DTT PHASE B FLEXLOGIC OPERAND >1
50DD SV | IA restraint | 2 OR 87L DIFF OP
DTT PHASE C
AND
RUN
| IB operate | 2 FLEXLOGIC OPERANDS
AND >1
AND SETTING | IB restraint | 2 87L DIFF OP A
DATA FROM REMOTE 2 OR CT Tap 2 87L DIFF OP B
Channel 2 OK RUN RUN 87L DIFF OP C
Channel 2 ID Fail IA | IC operate | 2 87L DIFF RECVD DTT A
Compute phasors >1
ΣIA2 at Timestamp IB | IC restraint | 2 87L DIFF RECVD DTT B
and variance IC
ΣIB2 at Timestamp 87L DIFF RECVD DTT C
(remote 2)
ΣIC2 at Timestamp I_0 87L DIFF PFLL FAIL
DTT PHASE A 87L DIFF CH1 FAIL
FLEXLOGIC OPERAND
STUB BUS OP
OR
SETTINGS AND OR
Block AND OR
Off = 0
OR
Function AND
= Enabled To remote relays
OR
DTT channel 1 and 2
OR
= Enabled AND
DTT PHASE A
Key DTT DTT PHASE B
5 SETTINGS
OR DTT PHASE C
Off = 0
827056AB.CDR
GE Multilin
5 SETTINGS 5.6 GROUPED ELEMENTS
c) STUB BUS
PATH: SETTINGS Ö GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö LINE DIFFERENTIAL ELEMENTS ÖØ STUB BUS
The stub bus element protects for faults between two breakers in a breaker-and-a-half or ring bus configuration when the
line disconnect switch is open. At the same time, if the line is still energized through the remote terminal(s), differential pro-
tection is still required (the line may still need to be energized because there is a tapped load on a two terminal line or
because the line is a three terminal line with two of the terminals still connected). Correct operation for this condition is
achieved by the local relay sending zero current values to the remote end(s) so that a local bus fault does not result in trip-
ping the line. At the local end, the differential element is disabled and stub bus protection is provided by a user-selected
overcurrent element. If there is a line fault, the remote end(s) will trip on differential but local differential function and DTT
signal (if enabled) to the local end, will be blocked by the stub bus logic allowing the local breakers to remain closed.
• STUB BUS FUNCTION: There are three requirements for stub bus operation: the element must be enabled, an indica-
tion that the line disconnect is open, and the STUB BUS TRIGGER setting is set as indicated below. There are two meth- 5
ods of setting the stub bus trigger and thus setting up stub bus operation:
1. If STUB BUS TRIGGER is “On”, the STUB BUS OPERATE operand picks up as soon as the disconnect switch opens,
causing zero currents to be transmitted to remote end(s) and DTT receipt from remote end(s) to be permanently
blocked. An overcurrent element, blocked by disconnect switch closed, provides protection for the local bus.
2. An alternate method is to set STUB BUS TRIGGER to be the pickup of an assigned instantaneous overcurrent ele-
ment. The instantaneous overcurrent element must operate quickly enough to pick up the STUB BUS OPERATE
operand, disable the local differential, and send zero currents to the other terminal(s). If the bus minimum fault cur-
rent is above five times the instantaneous overcurrent pickup, tests have confirmed that the STUB BUS OPERATE
operand always pick up correctly for a stub bus fault and prevents tripping of the remote terminal. If minimum stub
bus fault current is below this value, then method 1 should be used. Note also that correct testing of stub bus oper-
ation, when this method is used, requires sudden injection of a fault currents above five times instantaneous over-
current pickup. The assigned current element should be mapped to appropriate output contact(s) to trip the stub
bus breakers. It should be blocked unless disconnect is open. To prevent 87L tripping from remote L90 relays still
protecting the line, the auxiliary contact of line disconnect switch (logic “1” when line switch is open) should be
assigned to block the local 87L function by using the CURRENT DIFF BLOCK setting.
• STUB BUS DISCONNECT: Selects a FlexLogic™ operand to represent the open state of auxiliary contact of line dis-
connect switch (logic “1” when line disconnect switch is open). If necessary, simple logic representing not only line dis-
connect switch but also the closed state of the breakers can be created with FlexLogic™ and assigned to this setting.
• STUB BUS TRIGGER: Selects a FlexLogic™ operand that causes the STUB BUS OPERATE operand to pick up if the
line disconnect is open. It can be set either to “On” or to an instantaneous overcurrent element (see above). If the
instantaneous overcurrent used for the stub bus protection is set with a time delay, then STUB BUS TRIGGER should use
the associated instantaneous overcurrent pickup operand. The source assigned for the current of this element must
cover the stub between CTs of the associated breakers and disconnect switch.
SETTING
STUB BUS
FUNCTION:
Disabled=0
Enabled=1
SETTING
STUB BUS
DISCONNECT: FLEXLOGIC OPERAND
Off=0 AND STUB BUS OP
SETTING
STUB BUS
TRIGGER:
Off=0 831012A3.CDR
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately, the user may assign a FlexLogic™ operand to the TERMINAL OPEN setting that specifies the ter-
minal status. Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been
closed onto a fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high speed automatic reclosure (AR) is
employed. The AR CO-ORD DELAY setting allows the overcurrent setting to be below the expected load current seen after
reclose. Co-ordination is achieved by all of the LINE PICKP UV elements resetting and blocking the trip path before the AR
CO-ORD DELAY times out. The AR CO-ORD BYPASS setting is normally enabled. It is disabled if high speed autoreclosure is
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local ter-
minal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser issues
a close command results in the LINE PICKUP RCL TRIP FlexLogic™ operand. For security, the overcurrent trip is supervised
by an undervoltage condition, which in turn is controlled by the VT FUSE FAIL OP operand with a 10 ms coordination timer. If
a trip from distance in not required, then it can be disabled with the LINE PICKUP DISTANCE TRIP setting. Configure the LINE
PICKUP RCL TRIP operand to perform a trip action if the intent is apply zone 1 extension.
The zone 1 extension philosophy used here normally operates from an under-reaching zone, and uses an overreaching
distance zone when reclosing the line with the other line end open. The AR ACCELERATE setting is provided to achieve
zone 1 extension functionality if external autoreclosure is employed. Another zone 1 extension approach is to permanently
apply an overreaching zone, and reduce the reach when reclosing. This philosophy can be programmed via the autore-
close scheme.
FLEXLOGIC OPERAND
LINE PICKUP UV PKP
SETTING
Terminal Open
SETTING SETTING
Off = 0
Function Overvoltage Pickup Delay
Enabled = 1 TPKP
Disabled = 0 OR
TRST = 0
AND
SETTING
Block
Off = 0 SETTING SETTINGS
Undervoltage Pickup Line End Open Pickup Delay
FLEXLOGIC OPERAND
RUN Line End Open Reset Delay
LINE PICKUP LEO PKP
SETTING VAG or VAB < setting TPKP
(LEO = line end open)
Signal Source VBG or VBC < setting AND OR
TRST
VAG VAB VCG or VCA < setting SETTINGS
VBG VBC AND Autoreclose Coordination
VCG VCA Pickup Delay
RUN
IA IA < 0.05 pu Autoreclose Coordination
Reset Delay
IB IB < 0.05 pu AND
TPKP
IC IC < 0.05 pu
AND
TRST
AND
5 SETTING
Phase IOC Line Pickup
AND OR
10 ms
0
AND
AND
RUN
IA > setting
SETTING IB > setting OR
Autoreclose Coordination IC > setting AND
Bypass FLEXLOGIC OPERANDS
Enabled = 1 OR LINE PICKUP OP
Disabled = 0 LINE PICKUP PKP
LINE PICKUP DPO
FLEXLOGIC OPERANDS
AND
GND DIST Z2 PKP
OR
PH DIST Z2 PKP
AND
OR
FLEXLOGIC OPERAND
SETTING AND LINE PICKUP RCL TRIP
Distance Trip
TIMER
Enabled = 1
0
Disabled = 0
8 cycles FLEXLOGIC OPERANDS
LINE PICKUP I<A
SETTING
LINE PICKUP I<B
Autoreclose Accelerate
LINE PICKUP I<C
Off = 0
FLEXLOGIC OPERANDS OR
AR CLOSE BKR1
AR CLOSE BKR2
D60, L60, and L90 only
FLEXLOGIC OPERAND
SRCX VT FUSE FAIL OP
Source selected in the line pickup element 837000AH.CDR
5.6.5 DISTANCE
a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE
MESSAGE
GROUND DISTANCE Z2
See page 5–139. 5
GROUND DISTANCE Z3
MESSAGE See page 5–139.
Four common settings are available for distance protection. The DISTANCE SOURCE identifies the signal source for all dis-
tance functions. The mho distance functions use a dynamic characteristic: the positive-sequence voltage – either memo-
rized or actual – is used as a polarizing signal. The memory voltage is also used by the built-in directional supervising
functions applied for both the mho and quad characteristics.
The MEMORY DURATION setting specifies the length of time a memorized positive-sequence voltage should be used in the
distance calculations. After this interval expires, the relay checks the magnitude of the actual positive-sequence voltage. If
it is higher than 10% of the nominal, the actual voltage is used, if lower – the memory voltage continues to be used.
The memory is established when the positive-sequence voltage stays above 80% of its nominal value for five power system
cycles. For this reason it is important to ensure that the nominal secondary voltage of the VT is entered correctly under the
SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK menu.
Set MEMORY DURATION long enough to ensure stability on close-in reverse three-phase faults. For this purpose, the maxi-
mum fault clearing time (breaker fail time) in the substation should be considered. On the other hand, the MEMORY DURA-
TION cannot be too long as the power system may experience power swing conditions rotating the voltage and current
phasors slowly while the memory voltage is static, as frozen at the beginning of the fault. Keeping the memory in effect for
too long may eventually lead to incorrect operation of the distance functions.
The distance zones can be forced to become self-polarized through the FORCE SELF-POLAR setting. Any user-selected con-
dition (FlexLogic™ operand) can be configured to force self-polarization. When the selected operand is asserted (logic 1),
the distance functions become self-polarized regardless of other memory voltage logic conditions. When the selected oper-
and is de-asserted (logic 0), the distance functions follow other conditions of the memory voltage logic as shown below.
The distance zones can be forced to become memory-polarized through the FORCE MEM-POLAR setting. Any user-selected
condition (any FlexLogic™ operand) can be configured to force memory polarization. When the selected operand is
asserted (logic 1), the distance functions become memory-polarized regardless of the positive-sequence voltage magni-
tude at this time. When the selected operand is de-asserted (logic 0), the distance functions follow other conditions of the
memory voltage logic.
The FORCE SELF-POLAR and FORCE MEM-POLAR settings should never be asserted simultaneously. If this happens, the logic
will give higher priority to forcing self-polarization as indicated in the logic below. This is consistent with the overall philoso-
phy of distance memory polarization.
The memory polarization cannot be applied permanently but for a limited time only; the self-polarization may be
applied permanently and therefore should take higher priority.
NOTE
The distance zones of the L90 are identical to that of the UR-series D60 Line Distance Relay. For additional infor-
mation on the L90 distance functions, please refer to Chapter 8 of the D60 manual, available on the GE EnerVista
NOTE
CD or free of charge on the GE Multilin web page.
SETTING
Force Memory Polarization
Update memory
Off = 0
AND RUN
SETTING
Memory duration
SETTING TIMER 0
Distance Source | V_1 | < 1.15 pu 5 cycles AND
= VA, Vrms_A | Vrms – | V | | < Vrms / 8 AND Treset
S Q
= VB, Vrms_B | Vrms – | V | | < Vrms / 8 0 AND
= VC, Vrms_C | Vrms – | V | | < Vrms / 8
= V_1 | V_1 | > 0.80 pu TIMER Use V_1 memory
6 cycles OR
= IA | IA | < 0.05 pu
| IB | < 0.05 pu
AND
R Use V_1
= IB OR
0
= IC | IC | < 0.05 pu AND
| V_1 | < 0.10 pu
SETTING
Force Self Polarization
Off = 0 827842A7.CDR
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to “Non-directional”, the mho function becomes an offset
mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
The phase quadrilateral distance function is comprised of a reactance characteristic, right and left blinders, and 100%
memory-polarized directional and current supervising characteristics. When set to “Non-directional”, the quadrilateral func-
tion applies a reactance line in the reverse direction instead of the directional comparators. Refer to Chapter 8 for additional
information.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1. The SIGNAL SOURCE setting (common for the distance elements of all zones as entered under SETTINGS ÖØ GROUPED
ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE).
2. The MEMORY DURATION setting (common for the distance elements of all zones as entered under SETTINGS ÖØ
GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE).
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8: Theory of operation.
Although all zones can be used as either instantaneous elements (pickup [PKP] and dropout [DPO] FlexLogic™ operands)
or time-delayed elements (operate [OP] FlexLogic™ operands), only zone 1 is intended for the instantaneous under-reach-
ing tripping mode.
Ensure that the PHASE VT SECONDARY VOLTAGE setting (see the SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ
VOLTAGE BANK menu) is set correctly to prevent improper operation of associated memory action.
WARNING
• PHS DIST Z1 DIR: All phase distance zones are reversible. The forward direction is defined by the PHS DIST Z1 RCA
setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the PHS DIST Z1 REACH and PHS DIST Z1 RCA settings, and the reverse reach imped-
ance defined by PHS DIST Z1 REV REACH and PHS DIST Z1 REV REACH RCA as illustrated below.
• PHS DIST Z1 SHAPE: This setting selects the shape of the phase distance function between the mho and quadrilat-
eral characteristics. The selection is available on a per-zone basis. The two characteristics and their possible varia-
tions are shown in the following figures.
COMP LIMIT
H
REAC
DIR COMP LIMIT
DIR RCA
RCA
837720A1.CDR
5
COMP LIMIT
R E AC H
RCA
REV REACH
RCA
HE AC
REV R
837802A1.CDR
COMP LIMIT
COMP LIMIT
REACH
DIR COMP LIMIT
DIR RCA
LFT BLD RCA RCA RGT BLD RCA
R
-LFT BLD RGT BLD
837721A1.CDR
COMP LIMIT
COMP LIMIT
5
R E AC H
R
-LFT BLD RGT BLD
REV REACH
R E V R E AC H
RCA
COMP LIMIT
COMP LIMIT
837803A1.CDR
H
REAC
REAC
R R
H
REAC
R R
837722A1.CDR
H
REAC
REAC
R R
REAC
R R
837723A1.CDR
• PHS DIST Z1 XFMR VOL CONNECTION: The phase distance elements can be applied to look through a three-phase
delta-wye or wye-delta power transformer. In addition, VTs and CTs could be located independently from one another
at different windings of the transformer. If the potential source is located at the correct side of the transformer, this set-
ting shall be set to “None”.
This setting specifies the location of the voltage source with respect to the involved power transformer in the direction
of the zone. The following figure illustrates the usage of this setting. In section (a), zone 1 is looking through a trans-
former from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), Zone 3 is
looking through a transformer from the wye into the delta winding. Therefore, the Z3 setting shall be set to “Yd1”. The
zone is restricted by the potential point (location of the VTs) as illustrated in Figure (e).
• PHS DIST Z1 XFMR CUR CONNECTION: This setting specifies the location of the current source with respect to the
involved power transformer in the direction of the zone. In section (a) of the following figure, zone 1 is looking through
a transformer from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), the
CTs are located at the same side as the read point. Therefore, the Z3 setting shall be set to “None”.
See the Theory of operation chapter for more details, and the Application of settings chapter for information on calcu-
lating distance reach settings in applications involving power transformers.
(a) (b)
delta wye, 330o lag delta wye, 330o lag
Z3 Z3
Z1 Z1
5
Z1 XFRM VOL CONNECTION = Dy11 Z1 XFRM VOL CONNECTION = None
Z1 XFRM CUR CONNECTION = Dy11 Z1 XFRM CUR CONNECTION = Dy11
(c) (e)
delta wye, 330o lag
L1 L2
Z3 Zone 3
Zone 1
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1 ZL1 ZT ZL2
Z1
• PHS DIST Z1 REV REACH: This setting defines the reverse reach of the zone set to non-directional (PHS DIST Z1 DIR
setting). The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to
“Forward” or “Reverse”.
• PHS DIST Z1 REV REACH RCA: This setting defines the angle of the reverse reach impedance if the zone is set to
non-directional (PHS DIST Z1 DIR setting). This setting does not apply when the zone direction is set to “Forward” or
“Reverse”.
• PHS DIST Z1 COMP LIMIT: This setting shapes the operating characteristic. In particular, it produces the lens-type
characteristic of the mho function and a tent-shaped characteristic of the reactance boundary of the quadrilateral func-
tion. If the mho shape is selected, the same limit angle applies to both the mho and supervising reactance compara-
tors. In conjunction with the mho shape selection, the setting improves loadability of the protected line. In conjunction
with the quadrilateral characteristic, this setting improves security for faults close to the reach point by adjusting the
reactance boundary into a tent-shape.
• PHS DIST Z1 DIR RCA: This setting selects the characteristic angle (or maximum torque angle) of the directional
supervising function. If the mho shape is applied, the directional function is an extra supervising function as the
dynamic mho characteristic is itself directional. In conjunction with the quadrilateral shape, this setting defines the only
directional function built into the phase distance element. The directional function uses the memory voltage for polar-
ization. This setting typically equals the distance characteristic angle PHS DIST Z1 RCA.
• PHS DIST Z1 DIR COMP LIMIT: Selects the comparator limit angle for the directional supervising function.
• PHS DIST Z1 QUAD RGT BLD: This setting defines the right blinder position of the quadrilateral characteristic along
the resistive axis of the impedance plane (see the Quadrilateral distance characteristic figures). The angular position of
the blinder is adjustable with the use of the PHS DIST Z1 QUAD RGT BLD RCA setting. This setting applies only to the
quadrilateral characteristic and should be set giving consideration to the maximum load current and required resistive
coverage.
5 • PHS DIST Z1 QUAD RGT BLD RCA: This setting defines the angular position of the right blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figures).
• PHS DIST Z1 QUAD LFT BLD: This setting defines the left blinder position of the quadrilateral characteristic along the
resistive axis of the impedance plane (see the Quadrilateral distance characteristic figures). The angular position of the
blinder is adjustable with the use of the PHS DIST Z1 QUAD LFT BLD RCA setting. This setting applies only to the quadri-
lateral characteristic and should be set with consideration to the maximum load current.
• PHS DIST Z1 QUAD LFT BLD RCA: This setting defines the angular position of the left blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figures).
• PHS DIST Z1 SUPV: The phase distance elements are supervised by the magnitude of the line-to-line current (fault
loop current used for the distance calculations). For convenience, 3 is accommodated by the pickup (that is, before
being used, the entered value of the threshold setting is multiplied by 3 ).
If the minimum fault current level is sufficient, the current supervision pickup should be set above maximum full load
current preventing maloperation under VT fuse fail conditions. This requirement may be difficult to meet for remote
faults at the end of zones 2 and above. If this is the case, the current supervision pickup would be set below the full
load current, but this may result in maloperation during fuse fail conditions.
• PHS DIST Z1 VOLT LEVEL: This setting is relevant for applications on series-compensated lines, or in general, if
series capacitors are located between the relaying point and a point where the zone shall not overreach. For plain
(non-compensated) lines, set to zero. Otherwise, the setting is entered in per unit of the phase VT bank configured
under the DISTANCE SOURCE. Effectively, this setting facilitates dynamic current-based reach reduction. In non-direc-
tional applications (PHS DIST Z1 DIR set to “Non-directional”), this setting applies only to the forward reach of the non-
directional zone. See chapters 8 and 9 for information on calculating this setting for series compensated lines.
• PHS DIST Z1 DELAY: This setting allows the user to delay operation of the distance elements and implement stepped
distance protection. The distance element timers for zones 2 and higher apply a short dropout delay to cope with faults
located close to the zone boundary when small oscillations in the voltages or currents could inadvertently reset the
timer. Zone 1 does not need any drop out delay since it is sealed-in by the presence of current.
• PHS DIST Z1 BLK: This setting enables the user to select a FlexLogic™ operand to block a given distance element.
VT fuse fail detection is one of the applications for this setting.
AND
OR
SETTING
PH DIST Z1 DELAY AND FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND TPKP OR OR PH DIST Z1 OP
PH DIST Z1 PKP AB
0
FLEXLOGIC OPERAND TPKP
PH DIST Z1 PKP BC
0 AND
FLEXLOGIC OPERAND TPKP OR
PH DIST Z1 PKP CA
0 FLEXLOGIC OPERANDS
PH DIST Z1 OP AB
PH DIST Z1 OP BC
AND
FLEXLOGIC OPERANDS PH DIST Z1 OP CA
PH DIST Z1 SUPN IAB
AND
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
AND
OPEN POLE OP **
** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1. 837017A8.CDR
from the open pole element (D60, L60, and L90 only)
FLEXLOGIC OPERAND
OPEN POLE OP
0
5
FLEXLOGIC OPERAND SETTING FLEXLOGIC OPERAND
TIMER
PH DIST Z2 PKP BC PH DIST Z2 DELAY AND PH DIST Z2 OP BC
0 ms AND
OR TPKP
20 ms OR
0
FLEXLOGIC OPERAND
TIMER FLEXLOGIC OPERAND
PH DIST Z2 PKP CA SETTING
0 ms AND AND PH DIST Z2 OP CA
PH DIST Z2 DELAY
OR
from the trip output element OR
TPKP
20 ms
FLEXLOGIC OPERAND 0
FLEXLOGIC OPERAND
TRIP Z2 PH TMR INIT
OR PH DIST Z2 OP
837036A1.CDR
FLEXLOGIC OPERAND
OPEN POLE OP **
TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP AB TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP AB
0
TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP BC TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP BC
0
TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP CA TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP CA
0
FLEXLOGIC OPERAND
OR PH DIST Z3 OP
SETTINGS
PH DIST Z1 DIR
5 PH DIST Z1 SHAPE
PH DIST Z1 XFMR
VOL CONNECTION
SETTING PH DIST Z1 XFMR
PH DIST Z1 FUNCTION CUR CONNECTION
Enabled = 1 PH DIST Z1 REACH
Disabled = 0 PH DIST Z1 RCA
PH DIST Z1 REV REACH
AND PH DIST Z1 REV REACH RCA
SETTING
PH DIST Z1 COMP LIMIT
PH DIST Z1 BLK
PH DIST Z1 QUAD RGT BLD
Off = 0
PH DIST Z1 QUAD RGT BLD RCA Quadrilateral
PH DIST Z1 QUAD LFT BLD characteristic only
PH DIST Z1 QUAD LFT BLD RCA
SETTING PH DIST Z1 VOLT LEVEL FLEXLOGIC OPERANDS
DISTANCE SOURCE RUN AND PH DIST Z1 PKP AB
IA-IB PH DIST Z1 DPO AB
A-B ELEMENT
IB-IC
IC-IA RUN FLEXLOGIC OPERANDS
VAG-VBG B-C ELEMENT AND PH DIST Z1 PKP BC
Wye
VTs
SETTING
PHS DIST Z1 SUPV
RUN FLEXLOGIC OPERAND
| IA – IB | > 3 × Pickup PH DIST Z1 SUPN IAB
The ground mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, current, and phase selection supervising characteristics. The ground quadrilateral distance function is com-
posed of a reactance characteristic, right and left blinders, and 100% memory-polarized directional, overcurrent, and phase
selection supervising characteristics.
When set to non-directional, the mho function becomes an offset mho with the reverse reach controlled independently from
the forward reach, and all the directional characteristics removed. When set to non-directional, the quadrilateral function
applies a reactance line in the reverse direction instead of the directional comparators.
The reactance supervision for the mho function uses the zero-sequence current for polarization. The reactance line of the
quadrilateral function uses either zero-sequence or negative-sequence current as a polarizing quantity. The selection is
controlled by a user setting and depends on the degree of non-homogeneity of the zero-sequence and negative-sequence
equivalent networks.
5 The directional supervision uses memory voltage as polarizing quantity and both zero- and negative-sequence currents as
operating quantities.
The phase selection supervision restrains the ground elements during double-line-to-ground faults as they – by principles
of distance relaying – may be inaccurate in such conditions. Ground distance zones 1 and higher apply additional zero-
sequence directional supervision. See chapter 8 for additional details.
Each ground distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1. The SIGNAL SOURCE setting (common for both phase and ground elements for all zones as entered under the SETTINGS
ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE menu).
2. The MEMORY DURATION setting (common for both phase and ground elements for all zones as entered under the SET-
TINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE menu).
The common distance settings noted at the start of this section must be properly chosen for correct operation of the ground
distance elements.
Although all ground distance zones can be used as either instantaneous elements (pickup [PKP] and dropout [DPO] Flex-
Logic™ signals) or time-delayed elements (operate [OP] FlexLogic™ signals), only zone 1 is intended for the instantaneous
under-reaching tripping mode.
Ensure that the PHASE VT SECONDARY VOLTAGE (see the SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE
BANK menu) is set correctly to prevent improper operation of associated memory action.
WARNING
• GND DIST Z1 DIR: All ground distance zones are reversible. The forward direction is defined by the GND DIST Z1 RCA
setting and the reverse direction is shifted by 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the GND DIST Z1 REACH and GND DIST Z1 RCA settings, and the reverse reach imped-
ance defined by the GND DIST Z1 REV REACH and GND DIST Z1 REV REACH RCA settings.
• GND DIST Z1 SHAPE: This setting selects the shape of the ground distance characteristic between the mho and
quadrilateral characteristics. The selection is available on a per-zone basis.
The directional and non-directional quadrilateral ground distance characteristics are shown below. The directional and
non-directional mho ground distance characteristics are the same as those shown for the phase distance element in
the previous sub-section.
X
"+" NON-HOMOGEN. ANG
REACH
DIR COMP LIMIT
DIR RCA
LFT BLD RCA RCA RGT BLD RCA
R
-LFT BLD RGT BLD
837769A1.CDR
X
"+" NON-HOMOGEN. ANG
5
REACH
R
-LFT BLD RGT BLD
RE V REACH
REV REACH
RCA
837770A1.CDR
• GND DIST Z1 ZOM/Z1 ANG: This setting specifies the angle difference between the mutual zero-sequence imped-
ance between the lines and the positive-sequence impedance of the protected line.
• GND DIST Z1 REACH: This setting defines the reach of the zone for the forward and reverse applications. In non-
directional applications, this setting defines the forward reach of the zone. The reverse reach impedance in non-direc-
tional applications is set independently. The angle of the reach impedance is entered as the GND DIST Z1 RCA setting.
The reach impedance is entered in secondary ohms.
• GND DIST Z1 RCA: This setting specifies the characteristic angle (similar to the maximum torque angle in previous
technologies) of the ground distance characteristic for the forward and reverse applications. In the non-directional
applications this setting defines the forward reach of the zone. The reverse reach impedance in the non-directional
applications is set independently. This setting is independent from the GND DIST Z1 DIR RCA setting (the characteristic
angle of an extra directional supervising function).
The relay internally performs zero-sequence compensation for the protected circuit based on the values
entered for GND DIST Z1 Z0/Z1 MAG and GND DIST Z1 Z0/Z1 ANG, and if configured to do so, zero-sequence com-
NOTE
pensation for mutual coupling based on the values entered for GND DIST Z1 Z0M/Z1 MAG and GND DIST Z1 Z0M/Z1
ANG. The GND DIST Z1 REACH and GND DIST Z1 RCA should, therefore, be entered in terms of positive sequence
quantities. Refer to chapters 8 for additional information
• GND DIST Z1 REV REACH: This setting defines the reverse reach of the zone set to non-directional (GND DIST Z1 DIR
setting). The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to
“Forward” or “Reverse”.
• GND DIST Z1 REV REACH RCA: This setting defines the angle of the reverse reach impedance if the zone is set to
non-directional (GND DIST Z1 DIR setting). This setting does not apply when the zone direction is set to “Forward” or
“Reverse”.
• GND DIST Z1 POL CURRENT: This setting applies only if the GND DIST Z1 SHAPE is set to “Quad” and controls the
5 polarizing current used by the reactance comparator of the quadrilateral characteristic. Either the zero-sequence or
negative-sequence current could be used. In general, a variety of system conditions must be examined to select an
optimum polarizing current. This setting becomes less relevant when the resistive coverage and zone reach are set
conservatively. Also, this setting is more relevant in lower voltage applications such as on distribution lines or cables,
as compared with high-voltage transmission lines. This setting applies to both the zone 1 and reverse reactance lines
if the zone is set to non-directional. Refer to chapters 8 and 9 for additional information.
• GND DIST Z1 NON-HOMOGEN ANG: This setting applies only if the GND DIST Z1 SHAPE is set to “Quad” and provides
a method to correct the angle of the polarizing current of the reactance comparator for non-homogeneity of the zero-
sequence or negative-sequence networks. In general, a variety of system conditions must be examined to select this
setting. In many applications this angle is used to reduce the reach at high resistances in order to avoid overreaching
under far-out reach settings and/or when the sequence networks are greatly non-homogeneous. This setting applies to
both the forward and reverse reactance lines if the zone is set to non-directional. Refer to chapters 8 and 9 for addi-
tional information.
• GND DIST Z1 COMP LIMIT: This setting shapes the operating characteristic. In particular, it enables a lens-shaped
characteristic of the mho function and a tent-shaped characteristic of the quadrilateral function reactance boundary. If
the mho shape is selected, the same limit angle applies to mho and supervising reactance comparators. In conjunction
with the mho shape selection, this setting improves loadability of the protected line. In conjunction with the quadrilat-
eral characteristic, this setting improves security for faults close to the reach point by adjusting the reactance boundary
into a tent-shape.
• GND DIST Z1 DIR RCA: Selects the characteristic angle (or ‘maximum torque angle’) of the directional supervising
function. If the mho shape is applied, the directional function is an extra supervising function, as the dynamic mho
characteristic itself is a directional one. In conjunction with the quadrilateral shape selection, this setting defines the
only directional function built into the ground distance element. The directional function uses memory voltage for polar-
ization.
• GND DIST Z1 DIR COMP LIMIT: This setting selects the comparator limit angle for the directional supervising function.
• GND DIST Z1 QUAD RGT BLD: This setting defines the right blinder position of the quadrilateral characteristic along
the resistive axis of the impedance plane (see the Quadrilateral distance characteristic figure). The angular position of
the blinder is adjustable with the use of the GND DIST Z1 QUAD RGT BLD RCA setting. This setting applies only to the
quadrilateral characteristic and should be set with consideration to the maximum load current and required resistive
coverage.
• GND DIST Z1 QUAD RGT BLD RCA: This setting defines the angular position of the right blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figure).
• GND DIST Z1 QUAD LFT BLD: This setting defines the left blinder position of the quadrilateral characteristic along the
resistive axis of the impedance plane (see the Quadrilateral distance characteristic figure). The angular position of the
blinder is adjustable with the use of the GND DIST Z1 QUAD LFT BLD RCA setting. This setting applies only to the quadri-
lateral characteristic and should be set with consideration to the maximum load current.
• GND DIST Z1 QUAD LFT BLD RCA: This setting defines the angular position of the left blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figure).
• GND DIST Z1 SUPV: The ground distance elements are supervised by the magnitude of the neutral (3I_0) current.
The current supervision pickup should be set less than the minimum 3I_0 current for the end of the zone fault, taking
into account the desired fault resistance coverage to prevent maloperation due to VT fuse failure. Settings less than
0.2 pu are not recommended and should be applied with caution. To enhance ground distance security against spuri-
ous neutral current during switch-off transients, three-phase faults, and phase-to-phase faults, a positive-sequence
current restraint of 5% is applied to the neutral current supervision magnitude.
• GND DIST Z1 VOLT LEVEL: This setting is relevant for applications on series-compensated lines, or in general, if
series capacitors are located between the relaying point and a point for which the zone shall not overreach. For plain
(non-compensated) lines, this setting shall be set to zero. Otherwise, the setting is entered in per unit of the VT bank
configured under the DISTANCE SOURCE. Effectively, this setting facilitates dynamic current-based reach reduction. In
non-directional applications (GND DIST Z1 DIR set to “Non-directional”), this setting applies only to the forward reach of
the non-directional zone. See chapters 8 and 9 for additional details and information on calculating this setting value
for applications on series compensated lines.
• GND DIST Z1 DELAY: This setting enables the user to delay operation of the distance elements and implement a
stepped distance backup protection. The distance element timer applies a short drop out delay to cope with faults
located close to the boundary of the zone when small oscillations in the voltages or currents could inadvertently reset
the timer. 5
• GND DIST Z1 BLK: This setting enables the user to select a FlexLogic™ operand to block the given distance element.
VT fuse fail detection is one of the applications for this setting.
FLEXLOGIC OPERANDS
GND DIST Z1 OP A
SETTING GND DIST Z1 OP B
GND DIST Z1 DELAY AND GND DIST Z1 OP C
FLEXLOGIC OPERAND TPKP OR
GND DIST Z1 PKP A
0
FLEXLOGIC OPERAND TPKP
GND DIST Z1 PKP B
0 FLEXLOGIC OPERAND
AND
FLEXLOGIC OPERAND TPKP
OR OR GND DIST Z1 OP
GND DIST Z1 PKP C
0
FLEXLOGIC OPERANDS
GND DIST Z1 SUPN IN AND
AND
OPEN POLE OP ** OR
** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1. 837018A7.CDR
from the open pole detector element D60, L60, and L90 only)
FLEXLOGIC OPERAND
OPEN POLE OP **
FLEXLOGIC OPERAND
TIMER FLEXLOGIC OPERAND
GND DIST Z2 PKP C SETTING
0 ms AND AND GND DIST Z2 OP C
GND DIST Z2 DELAY
OR
OR
TPKP
from the trip output element 20 ms
FLEXLOGIC OPERAND 0
FLEXLOGIC OPERAND
TRIP Z2 GR TMR INIT
OR GND DIST Z2 OP
837037A1.CDR
5 FLEXLOGIC OPERAND
OPEN POLE OP **
TIMER SETTING
FLEXLOGIC OPERAND 0 ms GND DIST Z3 DELAY
AND
GND DIST Z3 PKP A TPKP FLEXLOGIC OPERAND
20 ms OR GND DIST Z3 OP A
0
TIMER SETTING
FLEXLOGIC OPERAND 0 ms GND DIST Z3 DELAY
AND
GND DIST Z3 PKP B TPKP FLEXLOGIC OPERAND
20 ms OR GND DIST Z3 OP B
0
TIMER SETTING
FLEXLOGIC OPERAND 0 ms GND DIST Z3 DELAY
AND
GND DIST Z3 PKP C TPKP FLEXLOGIC OPERAND
20 ms OR GND DIST Z3 OP C
0
FLEXLOGIC OPERAND
OR GND DIST Z3 OP
SETTINGS
GND DIST Z1 DIR
GND DIST Z1 SHAPE
GND DIST Z1 Z0/Z1 MAG
GND DIST Z1 Z0/Z1 ANG
GND DIST Z1 ZOM/Z1 MAG
GND DIST Z1 ZOM/Z1 ANG
GND DIST Z1 REACH
GND DIST Z1 RCA
GND DIST Z1 REV REACH
SETTING
GND DIST Z1 FUNCTION GND DIST Z1 REV REACH RCA
Enabled = 1 GND DIST Z1 POL CURRENT
GND DIST Z1 NON-HOMGEN ANG
Disabled = 0
GND DIST Z1 COMP LIMIT
AND GND DIST Z1 DIR RCA
SETTING
GND DIST Z1 DIR COMP LIMIT
GND DIST Z1 BLK
GND DIST Z1 VOLT LEVEL
Off = 0
GND DIST Z1 QUAD RGT BLD
Quadrilateral
GND DIST Z1 QUAD RGT BLD RCA characteristic
GND DIST Z1 QUAD LFT BLD only
SETTING GND DIST Z1 QUAD LFT BLD RCA
DISTANCE SOURCE RUN
IA-IB
IB-IC FLEXLOGIC OPERANDS
A ELEMENT
IC-IA AND GND DIST Z1 PKP AB
VAG-VBG GND DIST Z1 DPO A
RUN
Wye
VTs
VBG-VCG
VCG-VAG FLEXLOGIC OPERANDS
B ELEMENT
VAB AND GND DIST Z1 PKP B
Delta
VCA RUN
I_2
I_0
V_1
C ELEMENT
AND
FLEXLOGIC OPERANDS
GND DIST Z1 PKP C
5
MEMORY
GND DIST Z1 DPO C
I_1
IN
TIMER FLEXLOGIC OPERAND
V_1 > 0.80 pu 1 cycle OR GND DIST Z1 PKP
OR
1 cycle
I_1 > 0.025 pu
SETTING
GND DIST Z1 SUPV
RUN FLEXLOGIC OPERAND
| IN – 0.05 × I_1 | > Pickup GND DIST Z1 SUPN IN
837007AF.CDR
SETTINGS
GND DIST Z2 DIR
GND DIST Z2 SHAPE
GND DIST Z2 Z0/Z2 MAG
GND DIST Z2 Z0/Z2 ANG
GND DIST Z2 ZOM/Z1 MAG
GND DIST Z2 ZOM/Z1 ANG
GND DIST Z2 REACH
GND DIST Z2 RCA
GND DIST Z2 REV REACH
SETTING
GND DIST Z2 FUNCTION GND DIST Z2 REV REACH RCA
Enabled = 1 GND DIST Z2 POL CURRENT
GND DIST Z2 NON-HOMGEN ANG
Disabled = 0
GND DIST Z2 COMP LIMIT
AND GND DIST Z2 DIR RCA
SETTING
GND DIST Z2 DIR COMP LIMIT
GND DIST Z2 BLK
GND DIST Z2 VOLT LEVEL
Off = 0
GND DIST Z2 QUAD RGT BLD
Quadrilateral
GND DIST Z2 QUAD RGT BLD RCA characteristic
GND DIST Z2 QUAD LFT BLD only
SETTING GND DIST Z2 QUAD LFT BLD RCA
DISTANCE SOURCE RUN
IA-IB
IB-IC A ELEMENT FLEXLOGIC OPERANDS
IC-IA AND GND DIST Z2 PKP AB
VAG-VBG GND DIST Z2 DPO A
RUN
Wye
VTs
VBG-VCG
VCG-VAG
B ELEMENT FLEXLOGIC OPERANDS
VAB
AND GND DIST Z2 PKP B
Delta
VBC
VTs
5 I_2
I_0
V_1 MEMORY
C ELEMENT
AND
FLEXLOGIC OPERANDS
GND DIST Z2 PKP C
I_1 GND DIST Z2 DPO C
IN
TIMER
V_1 > 0.80 pu 1 cycle FLEXLOGIC OPERAND
OR GND DIST Z2 PKP
OR
1 cycle
I_1 > 0.025 pu
SETTING
GND DIST Z2 SUPV
RUN FLEXLOGIC OPERAND
| IN – 0.05 × I_1 | > Pickup GND DIST Z2 SUPN IN
GND DIST Z2 DIR SUPN
OR
OPEN POLE OP **
** D60, L60, and L90 only 837011AH.CDR
SETTING
Distance Source RUN
= V_0 OR
Zero-sequence
FLEXLOGIC OPERAND
= I_0 directional characteristic
TIMER AND GND DIST Z2 DIR SUPN
tpickup
FLEXLOGIC OPERAND
OPEN POLE OP treset
Co-ordinating time:
pickup = 1.0 cycle, reset = 1.0 cycle 837009A7.CDR
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ POWER SWING DETECT
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element mea-
sures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-selectable
operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and tripping indications are
given through FlexLogic™ operands. The element incorporates an adaptive disturbance detector. This function does not
trigger on power swings, but is capable of detecting faster disturbances – faults in particular – that may occur during power
swings. Operation of this dedicated disturbance detector is signaled via the POWER SWING 50DD operand.
The power swing detect element asserts two outputs intended for blocking selected protection elements on power swings:
POWER SWING BLOCK is a traditional signal that is safely asserted for the entire duration of the power swing, and POWER
SWING UN/BLOCK is established in the same way, but resets when an extra disturbance is detected during the power swing.
The POWER SWING UN/BLOCK operand may be used for blocking selected protection elements if the intent is to respond to
faults during power swing conditions.
Different protection elements respond differently to power swings. If tripping is required for faults during power swing condi-
tions, some elements may be blocked permanently (using the POWER SWING BLOCK operand), and others may be blocked
and dynamically unblocked upon fault detection (using the POWER SWING UN/BLOCK operand).
The operating characteristic and logic figures should be viewed along with the following discussion to develop an under-
standing of the operation of the element.
The power swing detect element operates in three-step or two-step mode:
• Three-step operation: The power swing blocking sequence essentially times the passage of the locus of the positive-
sequence impedance between the outer and the middle characteristic boundaries. If the locus enters the outer charac-
teristic (indicated by the POWER SWING OUTER FlexLogic™ operand) but stays outside the middle characteristic (indi-
cated by the POWER SWING MIDDLE FlexLogic™ operand) for an interval longer than POWER SWING PICKUP DELAY 1,
the power swing blocking signal (POWER SWING BLOCK FlexLogic™ operand) is established and sealed-in. The block-
ing signal resets when the locus leaves the outer characteristic, but not sooner than the POWER SWING RESET DELAY 1
time.
• Two-step operation: If the two-step mode is selected, the sequence is identical, but it is the outer and inner character-
istics that are used to time the power swing locus.
The out-of-step tripping feature operates as follows for three-step and two-step power swing detection modes:
• Three-step operation: The out-of-step trip sequence identifies unstable power swings by determining if the imped-
ance locus spends a finite time between the outer and middle characteristics and then a finite time between the middle
and inner characteristics. The first step is similar to the power swing blocking sequence. After timer POWER SWING
PICKUP DELAY 1 times out, latch 1 is set as long as the impedance stays within the outer characteristic.
If afterwards, at any time (given the impedance stays within the outer characteristic), the locus enters the middle char-
acteristic but stays outside the inner characteristic for a period of time defined as POWER SWING PICKUP DELAY 2, latch
2 is set as long as the impedance stays inside the outer characteristic. If afterwards, at any time (given the impedance
stays within the outer characteristic), the locus enters the inner characteristic and stays there for a period of time
defined as POWER SWING PICKUP DELAY 3, latch 2 is set as long as the impedance stays inside the outer characteristic;
the element is now ready to trip.
If the "Early" trip mode is selected, the POWER SWING TRIP operand is set immediately and sealed-in for the interval 5
set by the POWER SWING SEAL-IN DELAY. If the "Delayed" trip mode is selected, the element waits until the impedance
locus leaves the inner characteristic, then times out the POWER SWING PICKUP DELAY 2 and sets Latch 4; the element is
now ready to trip. The trip operand is set later, when the impedance locus leaves the outer characteristic.
• Two-step operation: The two-step mode of operation is similar to the three-step mode with two exceptions. First, the
initial stage monitors the time spent by the impedance locus between the outer and inner characteristics. Second, the
stage involving the POWER SWING PICKUP DELAY 2 timer is bypassed. It is up to the user to integrate the blocking
(POWER SWING BLOCK) and tripping (POWER SWING TRIP) FlexLogic™ operands with other protection functions and
output contacts in order to make this element fully operational.
The element can be set to use either lens (mho) or rectangular (quadrilateral) characteristics as illustrated below. When set
to “Mho”, the element applies the right and left blinders as well. If the blinders are not required, their settings should be set
high enough to effectively disable the blinders.
R
TE
OU
ACH
E
DL
FWD RE
ID
M
R
NE
IN
FW
E
DR
GL
AN
CA
LE IT
IM
ANG L EL
RE
IT DD R
MI
V
LIM
RC
R
NE
A
IN
H
REV REAC
OUTER LIMIT ANGLE
827843A2.CDR
842734A1.CDR
INNER LFT BL
D INNER RGT BL
D
MIDDLE LFT BL
ACH OUT
ACH MID
D MIDDLE RGT
BLD
OUTER LFT BL
D OUTER RGT BL
D
QUAD FWD RE
QUAD FWD RE
FWD REACH
FWD RCA
CH MID
REV REACH
ACH OUT
QUAD REV REA
QUAD REV RE
842735A1.CDR 5
Figure 5–77: POWER SWING DETECT QUADRILATERAL OPERATING CHARACTERISTICS
The FlexLogic™ output operands for the power swing detect element are described below:
• The POWER SWING OUTER, POWER SWING MIDDLE, POWER SWING INNER, POWER SWING TMR2 PKP, POWER SWING
TMR3 PKP, and POWER SWING TMR4 PKP FlexLogic™ operands are auxiliary operands that could be used to facilitate
testing and special applications.
• The POWER SWING BLOCK FlexLogic™ operand shall be used to block selected protection elements such as distance
functions.
• The POWER SWING UN/BLOCK FlexLogic™ operand shall be used to block those protection elements that are intended
to be blocked under power swings, but subsequently unblocked should a fault occur after the power swing blocking
condition has been established.
• The POWER SWING 50DD FlexLogic™ operand indicates that an adaptive disturbance detector integrated with the ele-
ment has picked up. This operand will trigger on faults occurring during power swing conditions. This includes both
three-phase and single-pole-open conditions.
• The POWER SWING INCOMING FlexLogic™ operand indicates an unstable power swing with an incoming locus (the
locus enters the inner characteristic).
• The POWER SWING OUTGOING FlexLogic™ operand indicates an unstable power swing with an outgoing locus (the
locus leaving the outer characteristic). This operand can be used to count unstable swings and take certain action only
after pre-defined number of unstable power swings.
• The POWER SWING TRIP FlexLogic™ operand is a trip command.
The settings for the power swing detect element are described below:
• POWER SWING FUNCTION: This setting enables and disables the entire power swing detection element. The setting
applies to both power swing blocking and out-of-step tripping functions.
• POWER SWING SOURCE: The source setting identifies the signal source for both blocking and tripping functions.
• POWER SWING SHAPE: This setting selects the shapes (either “Mho” or “Quad”) of the outer, middle and, inner char-
acteristics of the power swing detect element. The operating principle is not affected. The “Mho” characteristics use the
left and right blinders.
• POWER SWING MODE: This setting selects between the two-step and three-step operating modes and applies to
both power swing blocking and out-of-step tripping functions. The three-step mode applies if there is enough space
between the maximum load impedances and distance characteristics of the relay that all three (outer, middle, and
inner) characteristics can be placed between the load and the distance characteristics. Whether the spans between
the outer and middle as well as the middle and inner characteristics are sufficient should be determined by analysis of
the fastest power swings expected in correlation with settings of the power swing timers.
The two-step mode uses only the outer and inner characteristics for both blocking and tripping functions. This leaves
more space in heavily loaded systems to place two power swing characteristics between the distance characteristics
and the maximum load, but allows for only one determination of the impedance trajectory.
• POWER SWING SUPV: A common overcurrent pickup level supervises all three power swing characteristics. The
supervision responds to the positive sequence current.
• POWER SWING FWD REACH: This setting specifies the forward reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system consisting of a line and two equivalent sources, this reach should be
higher than the sum of the line and remote source positive-sequence impedances. Detailed transient stability studies
may be needed for complex systems in order to determine this setting. The angle of this reach impedance is specified
by the POWER SWING FWD RCA setting.
• POWER SWING QUAD FWD REACH MID: This setting specifies the forward reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING QUAD FWD REACH OUT: This setting specifies the forward reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING FWD RCA: This setting specifies the angle of the forward reach impedance for the mho characteris-
5 tics, angles of all the blinders, and both forward and reverse reach impedances of the quadrilateral characteristics.
• POWER SWING REV REACH: This setting specifies the reverse reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system of a line and two equivalent sources, this reach should be higher than
the positive-sequence impedance of the local source. Detailed transient stability studies may be needed for complex
systems to determine this setting. The angle of this reach impedance is specified by the POWER SWING REV RCA setting
for “Mho”, and the POWER SWING FWD RCA setting for “Quad”.
• POWER SWING QUAD REV REACH MID: This setting specifies the reverse reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING QUAD REV REACH OUT: This setting specifies the reverse reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING REV RCA: This setting specifies the angle of the reverse reach impedance for the mho characteris-
tics. This setting applies to mho shapes only.
• POWER SWING OUTER LIMIT ANGLE: This setting defines the outer power swing characteristic. The convention
depicted in the Power swing detect characteristic diagram should be observed: values greater than 90° result in an
apple-shaped characteristic; values less than 90° result in a lens shaped characteristic. This angle must be selected in
consideration of the maximum expected load. If the maximum load angle is known, the outer limit angle should be
coordinated with a 20° security margin. Detailed studies may be needed for complex systems to determine this setting.
This setting applies to mho shapes only.
• POWER SWING MIDDLE LIMIT ANGLE: This setting defines the middle power swing detect characteristic. It is rele-
vant only for the 3-step mode. A typical value would be close to the average of the outer and inner limit angles. This
setting applies to mho shapes only.
• POWER SWING INNER LIMIT ANGLE: This setting defines the inner power swing detect characteristic. The inner
characteristic is used by the out-of-step tripping function: beyond the inner characteristic out-of-step trip action is defi-
nite (the actual trip may be delayed as per the TRIP MODE setting). Therefore, this angle must be selected in consider-
ation to the power swing angle beyond which the system becomes unstable and cannot recover.
The inner characteristic is also used by the power swing blocking function in the two-step mode. In this case, set this
angle large enough so that the characteristics of the distance elements are safely enclosed by the inner characteristic.
This setting applies to mho shapes only.
• POWER SWING OUTER, MIDDLE, and INNER RGT BLD: These settings specify the resistive reach of the right
blinder. The blinder applies to both “Mho” and “Quad” characteristics. Set these value high if no blinder is required for
the “Mho” characteristic.
• POWER SWING OUTER, MIDDLE, and INNER LFT BLD: These settings specify the resistive reach of the left blinder.
Enter a positive value; the relay automatically uses a negative value. The blinder applies to both “Mho” and “Quad”
characteristics. Set this value high if no blinder is required for the “Mho” characteristic.
• POWER SWING PICKUP DELAY 1: All the coordinating timers are related to each other and should be set to detect
the fastest expected power swing and produce out-of-step tripping in a secure manner. The timers should be set in
consideration to the power swing detect characteristics, mode of power swing detect operation and mode of out-of-
step tripping. This timer defines the interval that the impedance locus must spend between the outer and inner charac-
teristics (two-step operating mode), or between the outer and middle characteristics (three-step operating mode)
before the power swing blocking signal is established. This time delay must be set shorter than the time required for
the impedance locus to travel between the two selected characteristics during the fastest expected power swing. This
setting is relevant for both power swing blocking and out-of-step tripping.
• POWER SWING RESET DELAY 1: This setting defines the dropout delay for the power swing blocking signal. Detec-
tion of a condition requiring a block output sets latch 1 after PICKUP DELAY 1 time. When the impedance locus leaves
the outer characteristic, timer POWER SWING RESET DELAY 1 is started. When the timer times-out the latch is reset. This
setting should be selected to give extra security for the power swing blocking action.
• POWER SWING PICKUP DELAY 2: Controls the out-of-step tripping function in the three-step mode only. This timer
defines the interval the impedance locus must spend between the middle and inner characteristics before the second
step of the out-of-step tripping sequence is completed. This time delay must be set shorter than the time required for
the impedance locus to travel between the two characteristics during the fastest expected power swing. 5
• POWER SWING PICKUP DELAY 3: Controls the out-of-step tripping function only. It defines the interval the imped-
ance locus must spend within the inner characteristic before the last step of the out-of-step tripping sequence is com-
pleted and the element is armed to trip. The actual moment of tripping is controlled by the TRIP MODE setting. This time
delay is provided for extra security before the out-of-step trip action is executed.
• POWER SWING PICKUP DELAY 4: Controls the out-of-step tripping function in “Delayed” trip mode only. This timer
defines the interval the impedance locus must spend outside the inner characteristic but within the outer characteristic
before the element is armed for the delayed trip. The delayed trip occurs when the impedance leaves the outer charac-
teristic. This time delay is provided for extra security and should be set considering the fastest expected power swing.
• POWER SWING SEAL-IN DELAY: The out-of-step trip FlexLogic™ operand (POWER SWING TRIP) is sealed-in for the
specified period of time. The sealing-in is crucial in the delayed trip mode, as the original trip signal is a very short
pulse occurring when the impedance locus leaves the outer characteristic after the out-of-step sequence is completed.
• POWER SWING TRIP MODE: Selection of the “Early” trip mode results in an instantaneous trip after the last step in
the out-of-step tripping sequence is completed. The early trip mode will stress the circuit breakers as the currents at
that moment are high (the electromotive forces of the two equivalent systems are approximately 180° apart). Selection
of the “Delayed” trip mode results in a trip at the moment when the impedance locus leaves the outer characteristic.
delayed trip mode will relax the operating conditions for the breakers as the currents at that moment are low. The
selection should be made considering the capability of the breakers in the system.
• POWER SWING BLK: This setting specifies the FlexLogic™ operand used for blocking the out-of-step function only.
The power swing blocking function is operational all the time as long as the element is enabled. The blocking signal
resets the output POWER SWING TRIP operand but does not stop the out-of-step tripping sequence.
SETTINGS
POWER SWING POWER SWING OUTER
SHAPE: LIMIT ANGLE:
POWER SWING FWD POWER SWING MIDDLE
REACH: LIMIT ANGLE:
POWER SWING QUAD POWER SWING INNER
FWD REACH MID: LIMIT ANGLE:
POWER SWING QUAD POWER SWING OUTER
FWD REACH OUT: RGT BLD:
POWER SWING FWD POWER SWING OUTER
RCA: LFT BLD:
SETTING POWER SWING REV POWER SWING MIDDLE
POWER SWING REACH: RGT BLD:
FUNCTION: POWER SWING QUAD REV POWER SWING MIDDLE
Disabled = 0 REACH MID: LFT BLD:
Enabled = 1 POWER SWING QUAD REV POWER SWING INNER
REACH OUT: RGT BLD:
SETTING POWER SWING REV POWER SWING INNER
RCA: LFT BLD:
POWER SWING SOURCE:
RUN
FLEXLOGIC OPERAND
V_1 OUTER IMPEDANCE
AND POWER SWING OUTER
I_1 REGION
RUN
FLEXLOGIC OPERAND
MIDDLE IMPEDANCE
AND POWER SWING MIDDLE
REGION
RUN
FLEXLOGIC OPERAND
INNER IMPEDANCE
AND POWER SWING INNER
REGION
SETTING
POWER SWING
SUPV:
RUN
SETTING
POWER SWING FUNCTION:
Disabled = 0
TIMER
Enabled = 1
0
SETTING 10 cycles
SETTING SETTINGS
POWER SWING
POWER SWING MODE:
DELAY 1 PICKUP:
POWER SWING
3-step
AND DELAY 1 RESET:
FLEXLOGIC OPERANDS
tPKP
S Q1 POWER SWING BLOCK
tRST
POWER SWING UN/BLOCK
AND L1 S Q5
2-step FLEXLOGIC OPERAND
L5
R POWER SWING 50DD
R
OR
OR
SETTING
POWER SWING FLEXLOGIC OPERAND
DELAY 2 PICKUP:
POWER SWING TMR2 PKP
tPKP
AND S Q2
0
L2
R
3-step
2-step
FLEXLOGIC OPERAND
SETTING POWER SWING TMR3 PKP
POWER SWING
DELAY 3 PICKUP: FLEXLOGIC OPERAND
tPKP POWER SWING INCOMING
AND
0 S Q3
R
L3 SETTING
POWER SWING TRIP
5
MODE:
SETTING SETTING
POWER SWING POWER SWING
DELAY 4 PICKUP: Early
SEAL-IN DELAY:
tPKP 0
AND S Q4 FLEXLOGIC OPERAND
0 tRST
L4 AND POWER SWING TRIP
R AND
Delayed
FLEXLOGIC OPERAND
POWER SWING OUTGOING
827841A4.CDR
5 MESSAGE
TARGET: Self-reset
LOAD ENCROACHMENT Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
The load encroachment element responds to the positive-sequence voltage and current and applies a characteristic shown
in the figure below.
X
ANGLE
–REACH REACH
R
ANGLE
LOAD ENCROACHMENT
LOAD ENCROACHMENT
OPERATE
OPERATE
827846A1.CDR
837731A1.CDR
SETTING
LOAD ENCROACHMENT
FUNCTION:
Disabled=0
Enabled=1 SETTINGS
LOAD ENCROACHMENT
SETTING REACH:
SETTINGS
LOAD ENCROACHMENT
LOAD ENCRMNT BLK:
ANGLE: LOAD ENCROACHMENT
Off=0 RUN PKP DELAY:
AND FLEXLOGIC OPERANDS
LOAD ENCROACHMENT
LOAD ENCHR PKP
RST DELAY:
SETTING SETTING LOAD ENCHR DPO
Load Encroachment t PKP
LOAD ENCROACHMENT LOAD ENCROACHMENT t RST LOAD ENCHR OP
SOURCE: MIN VOLT: Characteristic
Pos Seq Voltage (V_1) V_1 > Pickup
Pos Seq Current (I_1)
827847A2.CDR
a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1(6) Ö PHASE CURRENT
5 If none of these curve shapes is adequate, FlexCurves™ may be used to customize the inverse time curve characteristics.
The definite time curve is also an option that may be appropriate if only simple protection is required.
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable indi-
cates that the energy capacity has reached 100%, a time overcurrent element will operate. If less than 100% energy capac-
ity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value, the
variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed”. The “Instan-
taneous” selection is intended for applications with other relays, such as most static relays, which set the energy capacity
directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the relay must
coordinate with electromechanical relays.
IEEE CURVES:
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications
for extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:
A tr
---------------------------------- + B -----------------------------------
-
T = TDM × ⎛ ---------------
I -⎞ p T TDM × 2
1 – ⎛ ---------------- ⎞
, = I (EQ 5.10)
⎝ I pickup⎠ – 1
RESET
⎝ I pickup ⎠
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting
A, B, p = constants, TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”),
tr = characteristic constant
IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
K tr
--------------------------------------- --------------------------------------
-
T = TDM × ( I ⁄ I pickup ) E – 1 , T RESET = TDM × 1 – ( I ⁄ I 2 (EQ 5.11)
pickup )
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting, K, E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)
IAC CURVES:
The curves for the General Electric type IAC relay family are derived from the formulae:
⎛ B D E ⎞ tr
T = TDM × ⎜ A + ------------------------------ + -------------------------------------2- + -------------------------------------3-⎟ , T RESET = TDM × -------------------------------
- (EQ 5.12)
⎝ ( I ⁄ I ) – C ( ( I ⁄ I ) – C ) ( ( I ⁄ I ) – C ) ⎠ 2
pkp pkp pkp 1 – ( I ⁄ I pkp )
where: T = operate time (in seconds), TDM = Multiplier setting, I = Input current, Ipkp = Pickup Current setting, A to E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)
I2t CURVES:
The curves for the I2t are derived from the formulae:
100 100
-------------------------- ----------------------------
T = TDM × ⎛ ---------------
I ⎞ 2 , T RESET = TDM × ⎛ I ⎞ – 2
- ---------------- (EQ 5.13)
⎝ I pickup ⎠ ⎝ I pickup ⎠
where: T = Operate Time (sec.); TDM = Multiplier Setting; I = Input Current; Ipickup = Pickup Current Setting;
TRESET = Reset Time in sec. (assuming energy capacity is 100% and RESET: Timed)
FLEXCURVES™:
The custom FlexCurves™ are described in detail in the FlexCurves™ section of this chapter. The curve shapes for the
FlexCurves™ are derived from the formulae:
The phase time overcurrent element can provide a desired time-delay operating characteristic versus the applied current or
be used as a simple definite time element. The phase current input quantities may be programmed as fundamental phasor
magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse Time overcurrent
curves characteristic sub-section earlier for details on curve setup, trip times, and reset operation). When the element is
blocked, the time accumulator will reset according to the reset characteristic. For example, if the element reset characteris-
tic is set to “Instantaneous” and the element is blocked, the time accumulator will be cleared immediately.
The PHASE TOC1 PICKUP setting can be dynamically reduced by a voltage restraint feature (when enabled). This is accom-
plished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see
the figure below); the pickup level is calculated as ‘Mvr’ times the PHASE TOC1 PICKUP setting. If the voltage restraint feature
is disabled, the pickup level always remains at the setting value.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
818784A4.CDR
SETTING
PHASE TOC1
FUNCTION:
Disabled=0
Enabled=1
SETTING
PHASE TOC1
BLOCK-A :
Off=0
5 SETTING
PHASE TOC1
BLOCK-B:
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
RESTRAINT: OR PHASE TOC1 OP
Enabled
827072A4.CDR
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing
curves are shown below for form-A contacts in a 60 Hz system.
35
30
25
20
Milliseconds
15
Maximum
10 Minimum
0
1.05 1.1 1.2 1.5 2 5 10 15 20
SETTING
827033A6.VSD
PHASE IOC1
BLOCK-C:
Off = 0
The phase directional elements (one for each of phases A, B, and C) determine the phase current flow direction for steady
state and fault conditions and can be used to control the operation of the phase overcurrent elements via the BLOCK inputs
of these elements. 5
S
UT 0
TP
OU
–90°
VPol
VAG(Faulted) IA
ECA
set at 30°
VBC
VBC
VCG VBG +90°
To increase security for three phase faults very close to the VTs used to measure the polarizing voltage, a voltage memory
feature is incorporated. This feature stores the polarizing voltage the moment before the voltage collapses, and uses it to
determine direction. The voltage memory remains valid for one second after the voltage has collapsed.
The main component of the phase directional element is the phase angle comparator with two inputs: the operating signal
(phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic angle, ECA).
The following table shows the operating and polarizing signals used for phase directional control:
PHASE OPERATING POLARIZING SIGNAL Vpol
SIGNAL
ABC PHASE SEQUENCE ACB PHASE SEQUENCE
A angle of IA angle of VBC × (1∠ECA) angle of VCB × (1∠ECA)
B angle of IB angle of VCA × (1∠ECA) angle of VAC × 1∠ECA)
C angle of IC angle of VAB × (1∠ECA) angle of VBA × (1∠ECA)
MODE OF OPERATION:
• When the function is “Disabled”, or the operating current is below 5% × CT nominal, the element output is “0”.
• When the function is “Enabled”, the operating current is above 5% × CT nominal, and the polarizing voltage is above
the PRODUCT SETUP ÖØ DISPLAY PROPERTIES ÖØ VOLTAGE CUT-OFF LEVEL value, the element output is dependent on
the phase angle between the operating and polarizing signals:
– The element output is logic “0” when the operating current is within polarizing voltage ±90°.
– For all other angles, the element output is logic “1”.
• Once the voltage memory has expired, the phase overcurrent elements under directional control can be set to block or
trip on overcurrent as follows:
5 – When BLOCK WHEN V MEM EXP is set to “Yes”, the directional element will block the operation of any phase
overcurrent element under directional control when voltage memory expires.
– When BLOCK WHEN V MEM EXP is set to “No”, the directional element allows tripping of phase overcurrent elements
under directional control when voltage memory expires.
In all cases, directional blocking will be permitted to resume when the polarizing voltage becomes greater than the ‘polariz-
ing voltage threshold’.
SETTINGS:
• PHASE DIR 1 SIGNAL SOURCE: This setting is used to select the source for the operating and polarizing signals.
The operating current for the phase directional element is the phase current for the selected current source. The polar-
izing voltage is the line voltage from the phase VTs, based on the 90° or ‘quadrature’ connection and shifted in the
leading direction by the element characteristic angle (ECA).
• PHASE DIR 1 ECA: This setting is used to select the element characteristic angle, i.e. the angle by which the polariz-
ing voltage is shifted in the leading direction to achieve dependable operation. In the design of the UR-series elements,
a block is applied to an element by asserting logic 1 at the blocking input. This element should be programmed via the
ECA setting so that the output is logic 1 for current in the non-tripping direction.
• PHASE DIR 1 POL V THRESHOLD: This setting is used to establish the minimum level of voltage for which the phase
angle measurement is reliable. The setting is based on VT accuracy. The default value is “0.700 pu”.
• PHASE DIR 1 BLOCK WHEN V MEM EXP: This setting is used to select the required operation upon expiration of
voltage memory. When set to "Yes", the directional element blocks the operation of any phase overcurrent element
under directional control, when voltage memory expires; when set to "No", the directional element allows tripping of
phase overcurrent elements under directional control.
The phase directional element responds to the forward load current. In the case of a following reverse fault,
the element needs some time – in the order of 8 ms – to establish a blocking signal. Some protection ele-
NOTE
ments such as instantaneous overcurrent may respond to reverse faults before the blocking signal is
established. Therefore, a coordination time of at least 10 ms must be added to all the instantaneous protec-
tion elements under the supervision of the phase directional element. If current reversal is of a concern, a
longer delay – in the order of 20 ms – may be needed.
SETTING
PHASE DIR 1
FUNCTION:
Disabled=0
Enabled=1
SETTING
AND
PHASE DIR 1
BLOCK:
Off=0
SETTING
FLEXLOGIC OPERAND
PHASE B LOGIC SIMILAR TO PHASE A PH DIR1 BLK B
5
FLEXLOGIC OPERAND
PHASE C LOGIC SIMILAR TO PHASE A PH DIR1 BLK C
827078A6.CDR
a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1(6) Ö NEUTRAL CURRENT
The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3Io from the phase
currents and may be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse time overcurrent curve
characteristics section for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instan-
taneous” and the element is blocked, the time accumulator will be cleared immediately.
SETTINGS
NEUTRAL TOC1
SETTING INPUT:
NEUTRAL TOC1 NEUTRAL TOC1
FUNCTION: PICKUP:
Disabled = 0 NEUTRAL TOC1
Enabled = 1 CURVE:
NEUTRAL TOC1
TD MULTIPLIER:
NEUTRAL TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: NEUTRAL TOC1 PKP
NEUTRAL TOC1
AND RUN IN ≥ PICKUP NEUTRAL TOC1 DPO
SOURCE:
NEUTRAL TOC1 OP
IN t
I
SETTING
NEUTRAL TOC1
BLOCK:
Off = 0 827034A3.VSD
The neutral instantaneous overcurrent element may be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency pha-
sor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion 5
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when forming
the operating quantity of the element as follows:
I op = 3 × ( I_0 – K ⋅ I_1 ) where K = 1 ⁄ 16 (EQ 5.18)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection:
I op = 0.9375 ⋅ I injected ; three-phase pure zero-sequence injection: I op = 3 × I injected ).
SETTING
Off=0
SETTING
The neutral directional overcurrent element provides both forward and reverse fault direction indications the NEUTRAL DIR
OC1 FWD and NEUTRAL DIR OC1 REV operands, respectively. The output operand is asserted if the magnitude of the oper-
ating current is above a pickup level (overcurrent unit) and the fault direction is seen as forward or reverse, respectively
(directional unit).
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of the either the neutral current calcu-
lated from the phase currents or the ground current. There are separate pickup settings for the forward-looking and
reverse-looking functions. If set to use the calculated 3I_0, the element applies a positive-sequence restraint for better per-
formance: a small user-programmable portion of the positive-sequence current magnitude is subtracted from the zero-
sequence current magnitude when forming the operating quantity.
I op = 3 × ( I_0 – K × I_1 ) (EQ 5.19)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions.
• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
Iop = (1 – K) × Iinjected ; three-phase pure zero-sequence injection: Iop = 3 × Iinjected).
The positive-sequence restraint is removed for low currents. If the positive-sequence current is below 0.8 pu, the restraint is
removed by changing the constant K to zero. This facilitates better response to high-resistance faults when the unbalance
is very small and there is no danger of excessive CT errors as the current is low.
The directional unit uses the zero-sequence current (I_0) or ground current (IG) for fault direction discrimination and may
be programmed to use either zero-sequence voltage (“Calculated V0” or “Measured VX”), ground current (IG), or both for
polarizing. The following tables define the neutral directional overcurrent element.
1
where: V_0 = --- ( VAG + VBG + VCG ) = zero sequence voltage ,
3
1 1
I_0 = --- IN = --- ( IA + IB + IC ) = zero sequence current ,
3 3
ECA = element characteristic angle and IG = ground current
When NEUTRAL DIR OC1 POL VOLT is set to “Measured VX”, one-third of this voltage is used in place of V_0. The following
figure explains the usage of the voltage polarized directional unit of the element.
The figure below shows the voltage-polarized phase angle comparator characteristics for a phase A to ground fault, with:
• ECA = 90° (element characteristic angle = centerline of operating characteristic)
• FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
• REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
nation bringing more security to the element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore,
should be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and should be used for the blocking direction. This allows for better protection coordination.
The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other
protection elements.
REV LA FWD LA
line –3V_0 line line
VAG
(reference)
LA
LA
3I_0 line
ECA
ECA line
–ECA line
–3I_0 line LA
VCG LA
5 VBG
FWD LA
REV LA line
3V_0 line
line 827805A1.CDR
For a choice of current polarizing, it is recommended that the polarizing signal be analyzed to ensure that a known
direction is maintained irrespective of the fault location. For example, if using an autotransformer neutral current
as a polarizing source, it should be ensured that a reversal of the ground current does not occur for a high-side
fault. The low-side system impedance should be assumed minimal when checking for this condition. A similar sit-
uation arises for a wye/delta/wye transformer, where current in one transformer winding neutral may reverse when
faults on both sides of the transformer are considered.
– If “Dual” polarizing is selected, the element performs both directional comparisons as described above. A given
direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward
and reverse) indication occurs, the forward direction overrides the reverse direction.
• NEUTRAL DIR OC1 POL VOLT: Selects the polarizing voltage used by the directional unit when "Voltage" or "Dual"
polarizing mode is set. The polarizing voltage can be programmed to be either the zero-sequence voltage calculated
from the phase voltages ("Calculated V0") or supplied externally as an auxiliary voltage ("Measured VX").
• NEUTRAL DIR OC1 OP CURR: This setting indicates whether the 3I_0 current calculated from the phase currents, or
the ground current shall be used by this protection. This setting acts as a switch between the neutral and ground
modes of operation (67N and 67G). If set to “Calculated 3I0” the element uses the phase currents and applies the pos-
itive-sequence restraint; if set to “Measured IG” the element uses ground current supplied to the ground CT of the CT
bank configured as NEUTRAL DIR OC1 SOURCE. If this setting is “Measured IG”, then the NEUTRAL DIR OC1 POLARIZING
setting must be “Voltage”, as it is not possible to use the ground current as an operating and polarizing signal simulta-
neously.
• NEUTRAL DIR OC1 POS-SEQ RESTRAINT: This setting controls the amount of the positive-sequence restraint. Set
to 0.063 for backward compatibility with firmware revision 3.40 and older. Set to zero to remove the restraint. Set
higher if large system unbalances or poor CT performance are expected.
• NEUTRAL DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary appli-
cation for the offset impedance is to guarantee correct identification of fault direction on series compensated lines. In
regular applications, the offset impedance ensures proper operation even if the zero-sequence voltage at the relaying
point is very small. If this is the intent, the offset impedance shall not be larger than the zero-sequence impedance of
the protected circuit. Practically, it shall be several times smaller. The offset impedance shall be entered in secondary
ohms.
See chapter 8 for additional details and chapter 9 for information on how to calculate this setting
• NEUTRAL DIR OC1 FWD ECA: This setting defines the characteristic angle (ECA) for the forward direction in the 5
"Voltage" polarizing mode. The "Current" polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is
the angle set for the forward direction shifted by 180°.
• NEUTRAL DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.
• NEUTRAL DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
forward direction. When selecting this setting it must be kept in mind that the design uses a ‘positive-sequence
restraint’ technique for the “Calculated 3I0” mode of operation.
• NEUTRAL DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint
technique for the “Calculated 3I0” mode of operation.
SETTING
NEUTRAL DIR OC1 FWD
PICKUP:
NEUTRAL DIR OC1 OP
CURR:
SETTING
AND SETTINGS
NEUTRAL DIR OC1 BLK: AND
NEUTRAL DIR OC1 FWD
ECA:
Off=0
NEUTRAL DIR OC1 FWD FLEXLOGIC OPERAND
LIMIT ANGLE:
SETTING AND NEUTRAL DIR OC1 FWD
NEUTRAL DIR OC1 NEUTRAL DIR OC1 REV
SOURCE: LIMIT ANGLE:
}
Measured VX OR
Calculated V_0 FWD
1.25 cy
}
-3V_0 AND
Zero Seq Crt (I_0) 1.5 cy
Ground Crt (IG) REV
3I_0 REV
Voltage Polarization
5 Current
Dual OR
REV
OR
NOTE:
1) CURRENT POLARIZING IS POSSIBLE ONLY IN RELAYS WITH
THE GROUND CURRENT INPUTS CONNECTED TO
AN ADEQUATE CURRENT POLARIZING SOURCE SETTING
NEUTRAL DIR OC1 REV
2) GROUND CURRENT CAN NOT BE USED FOR POLARIZATION PICKUP:
AND OPERATION SIMULTANEOUSLY AND FLEXLOGIC OPERAND
NEUTRAL DIR OC1 OP
3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN CURR: NEUTRAL DIR OC1 REV
I_1 IS BELOW 0.8pu NEUTRAL DIR OC1 POS-
SEQ RESTRAINT:
RUN
3( I_0 - K I_1 ) PICKUP 827077AB.CDR
OR
IG PICKUP
MESSAGE
WATTMETRIC GND FLT 1 Range: 0.001 to 1.200 pu in steps of 0.001
5
REF PWR: 0.500 pu
WATTMETRIC GND FLT 1 Range: 0 to 360° Lag in steps of 1
MESSAGE
ECA: 0° Lag
WATTMETRIC GND FLT 1 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PWR PKP DEL: 0.20 s
WATTMETRIC GND FLT 1 Range: Definite Time, Inverse, FlexCurves A through D
MESSAGE
CURVE: Definite Time
WATTMETRIC GND FLT 1 Range: 0.01 to 2.00 s in steps of 0.01
MESSAGE
MULTIPLIER: 1.00 s
WATT GND FLT 1 BLK: Range: FlexLogic™ operand
MESSAGE
Off
WATTMETRIC GND FLT 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
WATTMETRIC GND FLT 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
The wattmetric zero-sequence directional element responds to power derived from zero-sequence voltage and current in a
direction specified by the element characteristic angle. The angle can be set within all four quadrants and the power can be
active or reactive. Therefore, the element may be used to sense either forward or reverse ground faults in either inductive,
capacitive or resistive networks. The inverse time characteristic allows time coordination of elements across the network.
Typical applications include ground fault protection in solidly grounded transmission networks, grounded/ungrounded/resis-
tor-grounded/resonant-grounded distribution networks, or for directionalizing other non-directional ground elements.
• WATTMETRIC GND FLT 1 VOLT: The element uses neutral voltage (that is, three times the zero-sequence voltage).
This setting allows selecting between the internally calculated neutral voltage, or externally supplied voltage (broken
delta VT connected to the auxiliary channel bank of the relay). When the latter selection is made, the auxiliary channel
must be identified by the user as a neutral voltage under the VT bank settings. This element will operate only if the aux-
iliary voltage is configured as neutral.
• WATTMETRIC GND FLT 1 OV PKP: This setting specifies the minimum zero sequence voltage supervising the direc-
tional power measurement. This threshold should be higher than possible unbalance during normal operation of the
system. Typically, this setting would be selected at 0.1 to 0.2 pu for the ungrounded or resonant grounded systems,
and at 0.05 to 0.1 pu for solidly or resistor-grounded systems. When using externally supplied voltage via the auxiliary
voltage channel, 1 pu is the nominal voltage of this channel as per VT bank settings. When using internally calculated
neutral voltage, 1 pu is the nominal phase to ground voltage as per the VT bank settings.
• WATTMETRIC GND FLT 1 CURR: The element responds to the neutral current (that is, three times zero-sequence
current), either calculated internally from the phase currents or supplied externally via the ground CT input from more
accurate sources such as the core balanced CT. This setting allows selecting the source of the operating current.
• WATTMETRIC GND FLT 1 OC PKP: This setting specifies the current supervision level for the measurement of the
zero-sequence power.
• WATTMETRIC GND FLT 1 OC PKP DEL: This setting specifies delay for the overcurrent portion of this element. The
delay applies to the WATTMETRIC 1 PKP operand driven from the overcurrent condition.
• WATTMETRIC GND FLT 1 PWR PKP: This setting specifies the operating point of the element. A value of 1 pu is a
product of the 1 pu voltage as specified for the overvoltage condition of this element, and 1 pu current as specified for
the overcurrent condition of this element.
• WATTMETRIC GND FLT 1 REF PWR: This setting is used to calculate the inverse time characteristic delay (defined
by Sref in the following equations). A value of 1 pu represents the product of a 1 pu voltage (as specified in the overvolt-
age condition for this element) and a 1 pu current (as specified in the overcurrent condition for this element.
• WATTMETRIC GND FLT 1 ECA: This setting adjusts the maximum torque angle of the element. The operating power
is calculated as:
5 where * indicates complex conjugate. By varying the element characteristic angle (ECA), the element can be made to
respond to forward or reverse direction in inductive, resistive, or capacitive networks as shown in the Wattmetric char-
acteristic angle response diagram.
• WATTMETRIC GND FLT 1 PWR PKP DEL: This setting defines a definite time delay before the inverse time charac-
teristic is activated. If the curve selection is set as “Definite Time”, the element would operate after this security time
delay. If the curve selection is “Inverse” or one of the FlexCurves, the element uses both the definite and inverse time
timers simultaneously. The definite time timer, specified by this setting, is used and when expires it releases the
inverse time timer for operation (torque control).
• WATTMETRIC GND FLT 1 CURVE: This setting allows choosing one of three methods to delay operate signal once all
conditions are met to discriminate fault direction.
The “Definite Time” selection allows for a fixed time delay defined by the WATTMETRIC GND FLT 1 PWR PKP DEL setting.
The “Inverse” selection allows for inverse time characteristics delay defined by the following formula:
S ref
t = m × ---------- (EQ 5.21)
S op
where m is a multiplier defined by the multiplier setting, Sref is the multiplier setting, and Sop is the operating power at
the time. This timer starts after the definite time timer expires.
The four FlexCurves allow for custom user-programmable time characteristics. When working with FlexCurves, the
element uses the operate to pickup ratio, and the multiplier setting is not applied:
S op
t = FlexCurve ⎛ ----------⎞ (EQ 5.22)
⎝ S ref⎠
Again, the FlexCurve timer starts after the definite time timer expires.
INDUCTIVE NETWORK
Vn Vn
In In
RESISTIVE NETWORK
Vn Vn
In In
In In
CAPACITIIVE NETWORK
5
Vn Vn
837804A1.CDR
SETTINGS SETTINGS
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
SOURCE: PWR PICKUP:
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
CURRENT: SETTING SETTINGS
OC PICKUP:
Calculated: Measured: WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
WATTMETRIC GND FLT 1
Neutral, In Ground, Ig ECA: OV PICKUP: CURVE:
SETTING
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
VOLTAGE: S = V*conj (I*exp(-j*ECA)) SOP > PWR PICKUP WATTMETRIC GND FLT 1 REF PWR:
Calculated: Measured: 1 PWR PKP DEL:
WATTMETRIC GND FLT 1
Neutral, Vn Auxiliary, Vx MULTIPLIER:
VMAG > OV PICKUP
AND
tPKP RUN
0 FLEXLOGIC OPERAND
IMAG > OC PICKUP SREF
SETTINGS t = m× WATTMETRIC 1 OP
SOP
WATTMETRIC GND FLT
AND
SETTING
1 FUNCTION:
WATTMETRIC GND FLT 1
Enabled = 1
OC PKP DEL:
AND
5 MESSAGE
GROUND TOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the funda-
mental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to
the Inverse time overcurrent curve characteristics section for details). When the element is blocked, the time accumulator
will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and
the element is blocked, the time accumulator will be cleared immediately.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
SETTINGS
GROUND TOC1
SETTING INPUT:
GROUND TOC1 GROUND TOC1
FUNCTION: PICKUP:
Disabled = 0 GROUND TOC1
Enabled = 1 CURVE:
GROUND TOC1
TD MULTIPLIER:
GROUND TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: GROUND TOC1 PKP
GROUND TOC1
AND RUN IG ≥ PICKUP GROUND TOC1 DPO
SOURCE:
GROUND TOC1 OP
IG t
I
SETTING
GROUND TOC1
BLOCK:
827036A3.VSD
Off = 0
The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude. 5
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
FLEXLOGIC OPERANDS
SETTING GROUND IOC1 PKP
GROUND IOC1
GROUND IOIC DPO
FUNCTION:
Disabled = 0 SETTINGS GROUND IOC1 OP
5 MESSAGE
NEG SEQ TOC1
EVENTS: Disabled
Range: Disabled, Enabled
The negative-sequence time overcurrent element may be used to determine and clear unbalance in the system. The input
for calculating negative-sequence current is the fundamental phasor value.
Two methods of resetting operation are available; “Timed” and “Instantaneous” (refer to the Inverse Time Overcurrent Char-
acteristics sub-section for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instan-
taneous” and the element is blocked, the time accumulator will be cleared immediately.
SETTING
Off=0
t
SETTING
The negative-sequence instantaneous overcurrent element may be used as an instantaneous function with no intentional
delay or as a definite time function. The element responds to the negative-sequence current fundamental frequency phasor
magnitude (calculated from the phase currents) and applies a positive-sequence restraint for better performance: a small 5
portion (12.5%) of the positive-sequence current magnitude is subtracted from the negative-sequence current magnitude
when forming the operating quantity:
I op = I_2 – K ⋅ I_1 where K = 1 ⁄ 8 (EQ 5.23)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence cur-
rents resulting from:
• system unbalances under heavy load conditions
• transformation errors of current transformers (CTs) during three-phase faults
• fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
I op = 0.2917 ⋅ I injected ; three-phase injection, opposite rotation: I op = I injected ).
SETTING
Off=0
SETTING
I_2 827058A5.CDR
NEG SEQ DIR OC1 NEG SEQ DIR OC1 Range: Disabled, Enabled
FUNCTION: Disabled
NEG SEQ DIR OC1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEG SEQ DIR OC1 Range: 0.00 to 250.00 ohms in steps of 0.01
MESSAGE
OFFSET: 0.00 Ω
NEG SEQ DIR OC1 Range: Neg Sequence, Zero Sequence
MESSAGE
TYPE: Neg Sequence
NEG SEQ DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001
MESSAGE
SEQ RESTRAINT: 0.063
NEG SEQ DIR OC1 FWD Range: 0 to 90° Lag in steps of 1
MESSAGE
ECA: 75° Lag
NEG SEQ DIR OC1 FWD Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
NEG SEQ DIR OC1 FWD Range: 0.015 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
NEG SEQ DIR OC1 REV Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
5 NEG SEQ DIR OC1 REV Range: 0.015 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
NEG SEQ DIR OC1 BLK: Range: FlexLogic™ operand
MESSAGE
Off
NEG SEQ DIR OC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
NEG SEQ DIR OC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
There are two negative-sequence directional overcurrent protection elements available. The element provides both forward
and reverse fault direction indications through its output operands NEG SEQ DIR OC1 FWD and NEG SEQ DIR OC1 REV,
respectively. The output operand is asserted if the magnitude of the operating current is above a pickup level (overcurrent
unit) and the fault direction is seen as forward or reverse, respectively (directional unit).
The overcurrent unit of the element essentially responds to the magnitude of a fundamental frequency phasor of either
the negative-sequence or zero-sequence current as per user selection. The zero-sequence current should not be mistaken
with the neutral current (factor 3 difference).
A positive-sequence restraint is applied for better performance: a small user-programmable portion of the positive-
sequence current magnitude is subtracted from the negative or zero-sequence current magnitude, respectively, when form-
ing the element operating quantity.
I op = I_2 – K × I_1 or I op = 3 × I_0 – K × I_1 (EQ 5.24)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and
zero-sequence currents resulting from:
• System unbalances under heavy load conditions.
• Transformation errors of current transformers (CTs).
• Fault inception and switch-off transients.
The positive-sequence restraint must be considered when testing for pick-up accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay:
• Single-phase injection: Iop = 1/3 × (1 – K) × Iinjected.
• Three-phase pure zero- or negative-sequence injection, respectively: Iop = Iinjected.
• The directional unit uses the negative-sequence current and voltage for fault direction discrimination.
The following table defines the negative-sequence directional overcurrent element.
OVERCURRENT UNIT DIRECTIONAL UNIT
MODE OPERATING CURRENT DIRECTION COMPARED PHASORS
Negative-sequence Iop = |I_2| – K × I_1| Forward –V_2 + Z_offset × I_2 I_2 × 1∠ECA
Reverse –V_2 + Z_offset × I_2 –(I_2 × 1∠ECA)
Zero-sequence Iop = 3 × |I_0| – K × |I_1| Forward –V_2 + Z_offset × I_2 I_2 × 1∠ECA
Reverse –V_2 + Z_offset × I_2 –(I_2 × 1∠ECA)
The negative-sequence voltage must be greater than 0.02 pu to be validated for use as a polarizing signal. If the polarizing
signal is not validated neither forward nor reverse indication is given. The following figure explains the usage of the voltage
polarized directional unit of the element.
The figure below shows the phase angle comparator characteristics for a phase A to ground fault, with settings of:
ECA = 75° (element characteristic angle = centerline of operating characteristic)
FWD LA = 80° (forward limit angle = ± the angular limit with the ECA for operation)
REV LA = 80° (reverse limit angle = ± the angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
5
nation bringing more security to the element operation.
–V_2 line
REV FWD
LA LA VAG (reference)
REV Operating
Region
LA
ECA line
LA ECA
I_2 line
–I_2 line LA
FWD Operating
Region
–ECA line
LA
VCG VBG
REV FWD
LA LA
V_2 line 827806A2.CDR
bias should be taken into account when using the negative-sequence directional overcurrent element to directionalize other
protection elements. The negative-sequence directional pickup must be greater than the PRODUCT SETUP ÖØ DISPLAY
PROPERTIES ÖØ CURRENT CUT-OFF LEVEL setting value.
• NEG SEQ DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary applica-
tion for the offset impedance is to guarantee correct identification of fault direction on series compensated lines (see
the Application of settings chapter for information on how to calculate this setting). In regular applications, the offset
impedance ensures proper operation even if the negative-sequence voltage at the relaying point is very small. If this is
the intent, the offset impedance shall not be larger than the negative-sequence impedance of the protected circuit.
Practically, it shall be several times smaller. The offset impedance shall be entered in secondary ohms. See the Theory
of operation chapter for additional details.
• NEG SEQ DIR OC1 TYPE: This setting selects the operating mode for the overcurrent unit of the element. The
choices are “Neg Sequence” and “Zero Sequence”. In some applications it is advantageous to use a directional nega-
tive-sequence overcurrent function instead of a directional zero-sequence overcurrent function as inter-circuit mutual
effects are minimized.
• NEG SEQ DIR OC1 POS-SEQ RESTRAINT: This setting controls the positive-sequence restraint. Set to 0.063 (in
“Zero Sequence” mode) or 0.125 (in “Neg Sequence” mode) for backward compatibility with revisions 3.40 and earlier.
Set to zero to remove the restraint. Set higher if large system unbalances or poor CT performance are expected.
• NEG SEQ DIR OC1 FWD ECA: This setting select the element characteristic angle (ECA) for the forward direction.
The element characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°.
• NEG SEQ DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.
• NEG SEQ DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
5 selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
• NEG SEQ DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEG SEQ DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
SETTINGS
Forward Pickup
Positive-Sequence Restraint
AND RUN
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ BREAKER FAILURE Ö BREAKER FAILURE 1(2)
In general, a breaker failure scheme determines that a breaker signaled to trip has not cleared a fault within a definite time,
so further tripping action must be performed. Tripping from the breaker failure scheme should trip all breakers, both local
and remote, that can supply current to the faulted zone. Usually operation of a breaker failure element will cause clearing of
a larger section of the power system than the initial trip. Because breaker failure can result in tripping a large number of
breakers and this affects system safety and stability, a very high level of security is required.
Two schemes are provided: one for three-pole tripping only (identified by the name “3BF”) and one for three pole plus sin-
gle-pole operation (identified by the name “1BF”). The philosophy used in these schemes is identical. The operation of a
breaker failure element includes three stages: initiation, determination of a breaker failure condition, and output.
INITIATION STAGE:
A FlexLogic™ operand representing the protection trip signal initially sent to the breaker must be selected to initiate the
scheme. The initiating signal should be sealed-in if primary fault detection can reset before the breaker failure timers have
finished timing. The seal-in is supervised by current level, so it is reset when the fault is cleared. If desired, an incomplete
sequence seal-in reset can be implemented by using the initiating operand to also initiate a FlexLogic™ timer, set longer
than any breaker failure timer, whose output operand is selected to block the breaker failure scheme.
For the L90 relay, the protection trip signal initially sent to the breaker is already programmed as a trip output. The
protection trip signal does not include other breaker commands that are not indicative of a fault in the protected
NOTE
zone.
Schemes can be initiated either directly or with current level supervision. It is particularly important in any application to
decide if a current-supervised initiate is to be used. The use of a current-supervised initiate results in the breaker failure ele-
ment not being initiated for a breaker that has very little or no current flowing through it, which may be the case for trans-
former faults. For those situations where it is required to maintain breaker fail coverage for fault levels below the BF1 PH
AMP SUPV PICKUP or the BF1 N AMP SUPV PICKUP setting, a current supervised initiate should not be used. This feature
should be utilized for those situations where coordinating margins may be reduced when high speed reclosing is used.
Thus, if this choice is made, fault levels must always be above the supervision pickup levels for dependable operation of
the breaker fail scheme. This can also occur in breaker-and-a-half or ring bus configurations where the first breaker closes
into a fault; the protection trips and attempts to initiate breaker failure for the second breaker, which is in the process of
closing, but does not yet have current flowing through it.
When the scheme is initiated, it immediately sends a trip signal to the breaker initially signaled to trip (this feature is usually
described as re-trip). This reduces the possibility of widespread tripping that results from a declaration of a failed breaker.
DETERMINATION OF A BREAKER FAILURE CONDITION:
The schemes determine a breaker failure condition via three paths. Each of these paths is equipped with a time delay, after
which a failed breaker is declared and trip signals are sent to all breakers required to clear the zone. The delayed paths are
associated with breaker failure timers 1, 2, and 3, which are intended to have delays increasing with increasing timer num-
bers. These delayed paths are individually enabled to allow for maximum flexibility.
Timer 1 logic (early path) is supervised by a fast-operating breaker auxiliary contact. If the breaker is still closed (as indi-
cated by the auxiliary contact) and fault current is detected after the delay interval, an output is issued. Operation of the
breaker auxiliary switch indicates that the breaker has mechanically operated. The continued presence of current indicates
that the breaker has failed to interrupt the circuit.
Timer 2 logic (main path) is not supervised by a breaker auxiliary contact. If fault current is detected after the delay interval,
an output is issued. This path is intended to detect a breaker that opens mechanically but fails to interrupt fault current; the
logic therefore does not use a breaker auxiliary contact.
The timer 1 and 2 paths provide two levels of current supervision, high-set and low-set, that allow the supervision level to
change from a current which flows before a breaker inserts an opening resistor into the faulted circuit to a lower level after
resistor insertion. The high-set detector is enabled after timeout of timer 1 or 2, along with a timer that will enable the low-
set detector after its delay interval. The delay interval between high-set and low-set is the expected breaker opening time.
Both current detectors provide a fast operating time for currents at small multiples of the pickup value. The overcurrent
detectors are required to operate after the breaker failure delay interval to eliminate the need for very fast resetting overcur-
rent detectors. 5
Timer 3 logic (slow path) is supervised by a breaker auxiliary contact and a control switch contact used to indicate that the
breaker is in or out-of-service, disabling this path when the breaker is out-of-service for maintenance. There is no current
level check in this logic as it is intended to detect low magnitude faults and it is therefore the slowest to operate.
OUTPUT:
The outputs from the schemes are:
• FlexLogic™ operands that report on the operation of portions of the scheme
• FlexLogic™ operand used to re-trip the protected breaker
• FlexLogic™ operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an
adjustable period.
• Target message indicating a failed breaker has been declared
• Illumination of the faceplate Trip LED (and the Phase A, B or C LED, if applicable)
MAIN PATH SEQUENCE:
FAULT cycles
OCCURS
0 1 2 3 4 5 6 7 8 9 10 11
827083A6.CDR
The current supervision elements reset in less than 0.7 of a power cycle for any multiple of pickup current as shown below.
0.8
Margin
Maximum
0.4
0.2
0
0 20 40 60 80 100 120 140
Mulitple of pickup fault current
threshold setting 836769A4.CDR
5 •
the supervision pickup level.
BF1 USE SEAL-IN: If set to "Yes", the element will only be sealed-in if current flowing through the breaker is above the
supervision pickup level.
• BF1 3-POLE INITIATE: This setting selects the FlexLogic™ operand that will initiate three-pole tripping of the breaker.
• BF1 PH AMP SUPV PICKUP: This setting is used to set the phase current initiation and seal-in supervision level.
Generally this setting should detect the lowest expected fault current on the protected breaker. It can be set as low as
necessary (lower than breaker resistor current or lower than load current) – high-set and low-set current supervision
will guarantee correct operation.
• BF1 N AMP SUPV PICKUP: This setting is used to set the neutral current initiate and seal-in supervision level. Gener-
ally this setting should detect the lowest expected fault current on the protected breaker. Neutral current supervision is
used only in the three phase scheme to provide increased sensitivity. This setting is valid only for three-pole tripping
schemes.
• BF1 USE TIMER 1: If set to "Yes", the early path is operational.
• BF1 TIMER 1 PICKUP DELAY: Timer 1 is set to the shortest time required for breaker auxiliary contact Status-1 to
open, from the time the initial trip signal is applied to the breaker trip circuit, plus a safety margin.
• BF1 USE TIMER 2: If set to "Yes", the main path is operational.
• BF1 TIMER 2 PICKUP DELAY: Timer 2 is set to the expected opening time of the breaker, plus a safety margin. This
safety margin was historically intended to allow for measuring and timing errors in the breaker failure scheme equip-
ment. In microprocessor relays this time is not significant. In L90 relays, which use a Fourier transform, the calculated
current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag
should be included in the overall margin duration, as it occurs after current interruption. The Breaker failure main path
sequence diagram below shows a margin of two cycles; this interval is considered the minimum appropriate for most
applications.
Note that in bulk oil circuit breakers, the interrupting time for currents less than 25% of the interrupting rating can be
significantly longer than the normal interrupting time.
• BF1 USE TIMER 3: If set to "Yes", the Slow Path is operational.
• BF1 TIMER 3 PICKUP DELAY: Timer 3 is set to the same interval as timer 2, plus an increased safety margin.
Because this path is intended to operate only for low level faults, the delay can be in the order of 300 to 500 ms.
• BF1 BKR POS1 φA/3P: This setting selects the FlexLogic™ operand that represents the protected breaker early-type
auxiliary switch contact (52/a). When using the single-pole breaker failure scheme, this operand represents the pro-
tected breaker early-type auxiliary switch contact on pole A. This is normally a non-multiplied form-A contact. The con-
tact may even be adjusted to have the shortest possible operating time.
• BF1 BKR POS2 φA/3P: This setting selects the FlexLogic™ operand that represents the breaker normal-type auxiliary
switch contact (52/a). When using the single-pole breaker failure scheme, this operand represents the protected
breaker auxiliary switch contact on pole A. This may be a multiplied contact.
• BF1 BREAKER TEST ON: This setting is used to select the FlexLogic™ operand that represents the breaker in-ser-
vice/out-of-service switch set to the out-of-service position.
• BF1 PH AMP HISET PICKUP: This setting sets the phase current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, before a breaker opening resistor is inserted.
• BF1 N AMP HISET PICKUP: This setting sets the neutral current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, before a breaker opening resistor is inserted.
Neutral current supervision is used only in the three pole scheme to provide increased sensitivity. This setting is valid
only for three-pole breaker failure schemes.
• BF1 PH AMP LOSET PICKUP: This setting sets the phase current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted
(approximately 90% of the resistor current).
• BF1 N AMP LOSET PICKUP: This setting sets the neutral current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted
(approximately 90% of the resistor current). This setting is valid only for three-pole breaker failure schemes.
• BF1 LOSET TIME DELAY: Sets the pickup delay for current detection after opening resistor insertion.
• BF1 TRIP DROPOUT DELAY: This setting is used to set the period of time for which the trip output is sealed-in. This
timer must be coordinated with the automatic reclosing scheme of the failed breaker, to which the breaker failure ele-
5
ment sends a cancel reclosure signal. Reclosure of a remote breaker can also be prevented by holding a transfer trip
signal on longer than the reclaim time.
• BF1 PH A INITIATE / BF1 PH B INITIATE / BF 1 PH C INITIATE: These settings select the FlexLogic™ operand to ini-
tiate phase A, B, or C single-pole tripping of the breaker and the phase A, B, or C portion of the scheme, accordingly.
This setting is only valid for single-pole breaker failure schemes.
• BF1 BKR POS1 φB / BF1 BKR POS 1 φC: These settings select the FlexLogic™ operand to represents the protected
breaker early-type auxiliary switch contact on poles B or C, accordingly. This contact is normally a non-multiplied Form-
A contact. The contact may even be adjusted to have the shortest possible operating time. This setting is valid only for
single-pole breaker failure schemes.
• BF1 BKR POS2 φB: Selects the FlexLogic™ operand that represents the protected breaker normal-type auxiliary
switch contact on pole B (52/a). This may be a multiplied contact. This setting is valid only for single-pole breaker fail-
ure schemes.
• BF1 BKR POS2 φC: This setting selects the FlexLogic™ operand that represents the protected breaker normal-type
auxiliary switch contact on pole C (52/a). This may be a multiplied contact. For single-pole operation, the scheme has
the same overall general concept except that it provides re-tripping of each single pole of the protected breaker. The
approach shown in the following single pole tripping diagram uses the initiating information to determine which pole is
supposed to trip. The logic is segregated on a per-pole basis. The overcurrent detectors have ganged settings. This
setting is valid only for single-pole breaker failure schemes.
Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be
given via output operand BKR FAIL 1 TRIP OP.
SETTING
BF1 FUNCTION:
Enable=1
Disable=0
SETTING AND
BF1 BLOCK :
Off=0
SETTING
BF1 PH A INITIATE:
OR
Off=0
FLEXLOGIC OPERAND
Off=0 Initiated Ph A
5 SETTING
TO SHEET 2 OF 2
YES=1
NO=0 AND
YES=1
NO=0 OR
OR
TO SHEET 2 OF 2
FLEXLOGIC OPERAND (Initiated)
SETTING
OR
BF1 PH B INITIATE : OR BKR FAIL 1 RETRIPB
AND
Off=0 AND
SEAL-IN PATH
Initiated Ph B
TO SHEET 2 OF 2
OR
SETTING OR
BF1 PH C INITIATE : FLEXLOGIC OPERAND
OR
BKR FAIL 1 RETRIPC
Off=0
AND
SETTING AND
SETTING SEAL-IN PATH
BF1 PH AMP SUPV
BF1 SOURCE : PICKUP : Initiated Ph C
RUN TO SHEET 2 OF 2
IA IA PICKUP
RUN
IB IB PICKUP OR
RUN
IC IC PICKUP
} TO SHEET 2 OF 2
(827070.CDR)
827069A6.CDR
GE Multilin
Breaker Pos 1 Phase A/3P
Off = 0 OR BKR FAIL 1 T2 OP
Use Timer 1 SETTING
5 SETTINGS
SETTING
No = 0 Timer 1 Pickup Delay AND Phase Current HiSet Pickup
Yes = 1 RUN
OR
AND IA Pickup
0
Initiated phase A
from single-pole breaker SETTING
failure logic sheet 1 SETTING
Timer 2 Pickup Delay LoSet Time Delay SETTING
Phase Current LoSet Pickup
SETTING
AND RUN
Use Timer 2
0 0
Yes = 1 IA Pickup
No = 0
SETTING
SETTINGS
Timer 1 Pickup Delay AND SETTING
Breaker Pos 1 Phase B
Phase Current HiSet Pickup
Off = 0
AND OR RUN
0
Initiated phase B IB Pickup
from single-pole breaker SETTING
failure logic sheet 1 SETTING
SETTING Trip Dropout Delay
Timer 2 Pickup Delay
LoSet Time Delay SETTING 0 FLEXLOGIC OPERAND
Phase Current LoSet Pickup OR BKR FAIL 1 TRIP OP
AND
SETTINGS RUN
0
Breaker Pos 1 Phase B 0
IB Pickup
Off = 0
SETTING
SETTING
AND Phase Current HiSet Pickup
Timer 1 Pickup Delay
RUN
AND OR IC Pickup
0
Initiated phase C
from single-pole breaker SETTING
failure logic sheet 1 SETTING LoSet Time Delay SETTING
Timer 2 Pickup Delay
Phase Current LoSet Pickup
IA
IB
IC
SETTINGS
Use Timer 3
Yes = 1
Breaker Pos 2 Phase A/3P
Initiated
from single-pole breaker failure logic sheet 1 827070A5.CDR
5.6 GROUPED ELEMENTS
5-193
5
5.6 GROUPED ELEMENTS 5 SETTINGS
a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS
5 MESSAGE
AUXILIARY OV1
See page 5–201.
AUXILIARY OV2
MESSAGE See page 5–201.
These protection elements can be used for a variety of applications such as:
• Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a specified time
delay.
• Permissive Functions: The undervoltage feature may be used to block the functioning of external devices by operat-
ing an output relay when the voltage falls below the specified voltage setting. The undervoltage feature may also be
used to block the functioning of other elements through the block feature of those elements.
• Source Transfer Schemes: In the event of an undervoltage, a transfer signal may be generated to transfer a load
from its normal source to a standby or emergency power source.
The undervoltage elements can be programmed to have a definite time delay characteristic. The definite time curve oper-
ates when the voltage drops below the pickup level for a specified period of time. The time delay is adjustable from 0 to
600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char-
acteristic.
The undervoltage delay setting defines the family of curves shown below.
D
T = ---------------------------------
- (EQ 5.25)
⎛ 1 – ------------------
V ⎞
⎝ V pickup⎠
Time (seconds)
% of voltage pickup
842788A1.CDR
NOTE
b) PHASE UNDERVOLTAGE (ANSI 27P)
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS Ö PHASE UNDERVOLTAGE1(3)
This element may be used to give a desired time-delay operating characteristic versus the applied fundamental voltage
(phase-to-ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting
selects the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage
below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition).
SETTING SETTING
PHASE UV1 PHASE UV1
FUNCTION: PICKUP:
Disabled = 0 PHASE UV1
Enabled = 1 CURVE:
PHASE UV1
SETTING DELAY: FLEXLOGIC OPERANDS
AND
PHASE UV1 AND RUN VAG or VAB < PICKUP PHASE UV1 A PKP
BLOCK: t PHASE UV1 A DPO
Off = 0 PHASE UV1 A OP
V
SETTING
SETTING AND RUN VBG or VBC< PICKUP PHASE UV1 B PKP
}
PHASE UV1
t PHASE UV1 B DPO
PHASE UV1 SOURCE: MINIMUM VOLTAGE:
PHASE UV1 B OP
VAG or VAB < Minimum
Source VT = Delta V
VBG or VBC < Minimum
VAB AND RUN VCG or VCA < PICKUP PHASE UV1 C PKP
VCG or VCA < Minimum
VBC t PHASE UV1 C DPO
VCA PHASE UV1 C OP
Source VT = Wye V
FLEXLOGIC OPERAND
SETTING OR PHASE UV1 PKP
827039AB.CDR
The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a definite
time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal-
culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below.
SETTINGS
SETTING
PHASE OV1 PICKUP
PHASE OV1 SETTING DELAY:
FUNCTION: FLEXLOGIC OPERANDS
PHASE OV1 PHASE OV1 RESET
Disabled = 0 PICKUP: DELAY: PHASE OV1 A PKP
Enabled = 1 PHASE OV1 A DPO
RUN tPKP
VAB ≥ PICKUP PHASE OV1 A OP
tRST
PHASE OV1 B PKP
SETTING
AND RUN tPKP PHASE OV1 B DPO
PHASE OV1 VBC ≥ PICKUP
BLOCK: PHASE OV1 B OP
tRST
RUN PHASE OV1 C PKP
Off = 0
VCA ≥ PICKUP tPKP PHASE OV1 C DPO
PHASE OV1 C OP
tRST
SETTING
PHASE OV1
SOURCE: FLEXLOGIC OPERAND
Source VT = Delta OR PHASE OV1 OP
VAB
VBC
FLEXLOGIC OPERAND
VCA
AND PHASE OV1 DPO
Source VT = Wye
FLEXLOGIC OPERAND
OR PHASE OV1 PKP
827066A7.CDR
There are three neutral overvoltage elements available. The neutral overvoltage element can be used to detect asymmetri-
cal system voltage condition due to a ground fault or to the loss of one or two phases of the source. The element responds
to the system neutral voltage (3V_0), calculated from the phase voltages. The nominal secondary voltage of the phase volt-
age channels entered under SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK Ö PHASE VT SECONDARY is the
p.u. base used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic versus the applied voltage (initialized
from FlexCurves A, B, or C) or be used as a definite time element. The NEUTRAL OV1 PICKUP DELAY setting applies only if
the NEUTRAL OV1 CURVE setting is “Definite time”. The source assigned to this element must be configured for a phase VT.
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.
The L90 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt-
age conditions of the auxiliary voltage. The AUX UV1 PICKUP selects the voltage level at which the time undervoltage ele-
ment starts timing. The nominal secondary voltage of the auxiliary voltage channel entered under SETTINGS ÖØ SYSTEM
SETUP Ö AC INPUTS ÖØ VOLTAGE BANK X5 ÖØ AUXILIARY VT X5 SECONDARY is the per-unit base used when setting the
pickup level.
The AUX UV1 DELAY setting selects the minimum operating time of the auxiliary undervoltage element. Both AUX UV1 PICKUP
and AUX UV1 DELAY settings establish the operating curve of the undervoltage element. The auxiliary undervoltage element
can be programmed to use either definite time delay or inverse time delay characteristics. The operating characteristics
and equations for both definite and inverse time delay are as for the phase undervoltage element.
The element resets instantaneously. The minimum voltage setting selects the operating voltage below which the element is
blocked.
SETTING
AUX UV1
FUNCTION: SETTING
Disabled=0
AUX UV1 PICKUP:
Enabled=1
827849A2.CDR
The L90 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM
SETUP Ö AC INPUTS ØÖ VOLTAGE BANK X5 ØÖ AUXILIARY VT X5 SECONDARY is the per-unit (pu) base used when setting the
pickup level.
A typical application for this element is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta
VT connection.
SETTING
AUX OV1
FUNCTION:
Disabled=0
SETTING
Enabled=1
AUX OV1 PICKUP: SETTING
SETTING
AND RUN AUX OV1 PICKUP
DELAY :
AUX OV1 BLOCK:
AUX OV1 RESET
Off=0 DELAY :
FLEXLOGIC OPERANDS
Vx < Pickup tPKP
SETTING tRST AUX OV1 OP
AUX OV1 DPO
AUX OV1 SIGNAL
SOURCE: AUX OV1 PKP
AUXILIARY VOLT (Vx)
827836A2.CDR
a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS ÖØ SETTING GROUP 1(6) ÖØ SUPERVISING ELEMENTS
SUPERVISING DISTURBANCE
See page 5-203.
ELEMENTS DETECTOR
87L TRIP
MESSAGE See page 5-205.
b) DISTURBANCE DETECTOR
PATH: SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1(6) ÖØ SUPERVISING ELEMENTS Ö DISTURBANCE DETECTOR
• DD LOGIC SEAL-IN: This setting is used to maintain disturbance detector output for such conditions as balanced
three-phase fault, low level time overcurrent fault, etc. whenever the disturbance detector might reset. Output of the
disturbance detector will be maintained until the chosen FlexLogic™ operand resets.
The user may disable the DD EVENTS setting as the disturbance detector element will respond to any current distur-
bance on the system which may result in filling the events buffer and possible loss of valuable data.
NOTE
SETTING
DD FUNCTION:
Enabled=1
Disabled=0
LOGIC
ACTUAL DELTA LEVEL
COMPUTE SEQ. DETECTOR
CURRENTS RUN
ABS (I_1-I_1')>0.04 pu
I_1
(I_1' is 4 cycles old)
ABS (I_2-I_2')>0.04 pu
I_2 OR
(I_2' is 4 cycles old)
ABS (I_0-I_0')>0.04 pu
I_0
(I_0' is 4 cycles old)
LOGIC
SETTING
ADAPTIVE LEVEL
DD CONTROL DETECTOR
LOGIC:
AND RUN
5 Off=0
I_0 > 0.12 to 0.24 pu
OR
OR
I_2 > 0.12 to 0.24 pu
NOTE:
ADJUSTMENTS ARE
MADE ONCE EVERY
8 CYCLES TO THE
NEXT LEVEL (HIGHER
OR LOWER) IN 0.02 pu
SETTING STEPS USING THE FLEXLOGIC OPERAND
HIGHEST VALUE OF OR 50DD SV
DD LOGIC
I_0 AND I_2.
SEAL-IN:
Off=0
AND
SETTING
DD NON-CURRENT
SUPV:
AND
Off=0
827044A6.CDR
c) 87L TRIP
PATH: SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1(6) ÖØ SUPERVISING ELEMENTS ÖØ 87L TRIP
• 87L TRIP FUNCTION: This setting is used to enable or disable the element.
• 87L TRIP SOURCE: This setting is used to assign a source for seal-in function.
• 87L TRIP MODE: This setting is used to select either three-pole or single-pole mode of operation.
• 87L TRIP SUPV: This setting is used to assign a trip supervising element. The 50DD SV FlexLogic™ operand is recom-
mended (the element has to be enabled); otherwise, elements like instantaneous overcurrent, distance, etc. can be
used.
• 87L TRIP FORCE 3-Φ: This setting is used to select an element forcing three-pole tripping if any type fault occurs
when this element is active. Autoreclosure disabled can be utilized, or the autoreclosure counter if, for example, the
second trip is required to be a three-pole signal. Likewise, any operand representing a change in the power system
configuration, can be applied.
• 87L TRIP SEAL-IN: This setting is used to enable/disable seal-in of the trip signal by measurement of the current flow-
ing.
• 87L TRIP SEAL-IN PICKUP: This setting is used to select a pickup setting of the current seal-in function.
SETTING
87L TRIP FUNCTION
= Disabled
= Enabled
SETTING SETTING
87L TRIP SOURCE 87L TRIP SEAL-IN PICKUP
= Ia Ia > PICKUP
= Ib Ib > PICKUP
= Ic Ic > PICKUP
SETTING
87L TRIP SEAL-IN
= Enabled
AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP A
87L DIFF OP A
AND
OR
FLEXLOGIC OPERAND
87L RECVD DTT A
AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP B
87L DIFF OP B
AND
OR
FLEXLOGIC OPERAND
87L RECVD DTT B
5 FLEXLOGIC OPERAND
87L DIFF OP C
AND
AND
OR
FLEXLOGIC OPERAND
87L TRIP OP C
OR FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR 87L TRIP OP
87L RECVD DTT C
OR
SETTING AND
AND
FLEXLOGIC OPERANDS OR
AND
OPEN POLE OP ΦA
OPEN POLE OP ΦB
OPEN POLE OP ΦC AND OR
OPEN POLE OP
AND
AND
SETTING OR
87L TRIP FORCE 3-Φ
= Off 831020A5.CDR
Control elements are generally used for control rather than protection. See the Introduction to Elements section at the
beginning of this chapter for further information.
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic™ and assign-
ing them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip condition-
ing such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista UR Setup software A protection summary
is displayed by navigating to a specific protection or control protection element and checking the desired bus box. Once the
desired element is selected for a specific bus, a list of element operate-type operands are displayed and can be assigned
to a trip bus. If more than one operate-type operand is required, it may be assigned directly from the trip bus menu.
SETTINGS
TRIP BUS 1 INPUT 1
SETTINGS
= Off
TRIP BUS 1 PICKUP
TRIP BUS 1 INPUT 2
DELAY
= Off Non-volatile,
TRIP BUS 1 RESET
OR set-dominant
***
DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
↓
Range: up to 16 alphanumeric characters
MESSAGE
GROUP 6 NAME:
5
SETTING GROUP Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED
ELEMENTS settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
LED) is in service.
The SETTING GROUPS BLK setting prevents the active setting group from changing when the FlexLogic™ parameter is set to
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON settings select a FlexLogic™ operand which, when set, will make the
particular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a
given time – the highest-numbered group which is activated by its ACTIVATE ON parameter takes priority over the lower-
numbered groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically
becomes active if no other group is active.
The SETTING GROUP 1 NAME to SETTING GROUP 6 NAME settings allows to user to assign a name to each of the six settings
groups. Once programmed, this name will appear on the second line of the GROUPED ELEMENTS Ö SETTING GROUP 1(6)
menu display.
The relay can be set up via a FlexLogic™ equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic™ equation (see the figure below) illustrates requests via remote communications
(for example, VIRTUAL INPUT 1 ON) or from a local contact input (for example, CONTACT IP 1 ON) to initiate the use of a par-
ticular settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular
settings group. The assigned VIRTUAL OUTPUT 1 operand is used to control the “On” state of a particular settings group.
1 VIRT IP 1 ON (VI1)
OR (2)
2 CONT IP 1 ON (H5A)
3 OR (2)
AND (3) = VIRT OP 1 (VO1)
4 PHASE TOC1 PKP
5 NOT
7 NOT
8 AND (3)
9 = VIRT OP 1 (VO1)
10 END
842789A1.CDR
5 MESSAGE
RANGE: 7
SELECTOR 1 TIME-OUT: Range: 3.0 to 60.0 s in steps of 0.1
MESSAGE
5.0 s
SELECTOR 1 STEP-UP: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 STEP-UP Range: Time-out, Acknowledge
MESSAGE
MODE: Time-out
SELECTOR 1 ACK: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT A0: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT A1: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT A2: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT Range: Time-out, Acknowledge
MESSAGE
MODE: Time-out
SELECTOR 1 3BIT ACK: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 POWER-UP Range: Restore, Synchronize, Sync/Restore
MESSAGE
MODE: Restore
SELECTOR 1 TARGETS: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
SELECTOR 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows set-
ting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after time-
out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory.
Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user set-
ting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out
of range.
• SELECTOR 1 FULL RANGE: This setting defines the upper position of the selector. When stepping up through avail-
able positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-
bit control word for programming the selector to a desired position, the change would take place only if the control word
is within the range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established
by setting the SELECTOR ALARM FlexLogic™ operand for 3 seconds.
• SELECTOR 1 TIME-OUT: This setting defines the time-out period for the selector. This value is used by the relay in
the following two ways. When the SELECTOR STEP-UP MODE is “Time-out”, the setting specifies the required period of
inactivity of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEP-
UP MODE is “Acknowledge”, the setting specifies the period of time for the acknowledging input to appear. The timer is
re-started by any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT
timer expires; otherwise, the change will not take place and an alarm will be set.
• SELECTOR 1 STEP-UP: This setting specifies a control input for the selector switch. The switch is shifted to a new
position at each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1
FULL RANGE) to the first (position 1). Consecutive pulses of this control operand must not occur faster than every
50 ms. After each rising edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1: 5
POS Z CHNG INITIATED target message is displayed, where Z the pre-selected position. The message is displayed for
the time specified by the FLASH MESSAGE TIME setting. The pre-selected position is applied after the selector times out
(“Time-out” mode), or when the acknowledging signal appears before the element times out (“Acknowledge” mode).
When the new position is applied, the relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically,
a user-programmable pushbutton is configured as the stepping up control input.
• SELECTOR 1 STEP-UP MODE: This setting defines the selector mode of operation. When set to “Time-out”, the
selector will change its position after a pre-defined period of inactivity at the control input. The change is automatic and
does not require any explicit confirmation of the intent to change the selector's position. When set to “Acknowledge”,
the selector will change its position only after the intent is confirmed through a separate acknowledging signal. If the
acknowledging signal does not appear within a pre-defined period of time, the selector does not accept the change
and an alarm is established by setting the SELECTOR STP ALARM output FlexLogic™ operand for 3 seconds.
• SELECTOR 1 ACK: This setting specifies an acknowledging input for the stepping up control input. The pre-selected
position is applied on the rising edge of the assigned operand. This setting is active only under “Acknowledge” mode of
operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the
last activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input.
• SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con-
trol word pre-selects the position using the following encoding convention:
A2 A1 A0 POSITION
0 0 0 rest
0 0 1 1
0 1 0 2
0 1 1 3
1 0 0 4
1 0 1 5
1 1 0 6
1 1 1 7
The “rest” position (0, 0, 0) does not generate an action and is intended for situations when the device generating the
three-bit control word is having a problem. When SELECTOR 1 3BIT MODE is “Time-out”, the pre-selected position is
applied in SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is
“Acknowledge”, the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging
input.
The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2)
lock-out mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit
control sequence is initiated, the stepping up input is inactive.
• SELECTOR 1 3BIT MODE: This setting defines the selector mode of operation. When set to “Time-out”, the selector
changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not
require explicit confirmation to change the selector position. When set to “Acknowledge”, the selector changes its posi-
tion only after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a
pre-defined period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT
ALARM FlexLogic™ operand for 3 seconds.
• SELECTOR 1 3BIT ACK: This setting specifies an acknowledging input for the three-bit control input. The pre-
selected position is applied on the rising edge of the assigned FlexLogic™ operand. This setting is active only under
the “Acknowledge” mode of operation. The acknowledging signal must appear within the time defined by the SELEC-
TOR TIME-OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and
three-bit control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK, accord-
ingly).
• SELECTOR 1 POWER-UP MODE: This setting specifies the element behavior on power up of the relay.
When set to “Restore”, the last position of the selector (stored in the non-volatile memory) is restored after powering up
the relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and
The operation of “Synch/Restore” mode is similar to the “Synchronize” mode. The only difference is that after an
unsuccessful synchronization attempt, the switch will attempt to restore the position stored in the relay memory. The
“Synch/Restore” mode is useful for applications where the selector switch is employed to change the setting group in
redundant (two relay) protection schemes.
• SELECTOR 1 EVENTS: If enabled, the following events are logged:
The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting.
STEP-UP
T T
3BIT A0
3BIT A1
3BIT A2
T T
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6 5
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842737A1.CDR
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
5 POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842736A1.CDR
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS menu:
OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS Ö PRODUCT
SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:
SETTINGS
SELECTOR 1 FULL RANGE:
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
842012A2.CDR
TRIP OUTPUT TRIP MODE: Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
Disabled
TRIP 3-POLE INPUT-1: Range: FlexLogic™ operand
MESSAGE
Off
TRIP 3-POLE INPUT-2: Range: FlexLogic™ operand
MESSAGE
Off
↓
TRIP 3-POLE INPUT-6: Range: FlexLogic™ operand
MESSAGE
Off
TRIP 1-POLE INPUT-1: Range: FlexLogic™ operand
MESSAGE
Off
TRIP 1-POLE INPUT-2: Range: FlexLogic™ operand
MESSAGE
Off
↓
TRIP 1-POLE INPUT-6: Range: FlexLogic™ operand
MESSAGE
Off
5 MESSAGE
TRIP RECLOSE INPUT-1:
Off
Range: FlexLogic™ operand
The trip output element is primarily used to collect trip requests from protection elements and other inputs to generate out-
put operands to initiate trip operations. Three pole trips will only initiate reclosure if programmed to do so, whereas single
pole trips will always automatically initiate reclosure. The TRIP 3-POLE and TRIP 1-POLE output operands can also be used
as inputs to a FlexLogic™ OR gate to operate the faceplate Trip indicator LED.
THREE POLE OPERATION:
In applications where single-pole tripping is not required this element provides a convenient method of collecting inputs to
initiate tripping of circuit breakers, the reclose element and breaker failure elements.
SINGLE POLE OPERATION:
This element must be used in single pole operation applications.
NOTE
5
In these applications this element is used to:
• Determine if a single pole operation should be performed.
• Collect inputs to initiate three pole tripping, the recloser and breaker failure elements.
• Collect inputs to initiate single pole tripping, the recloser and breaker failure elements.
• Assign a higher priority to pilot aided scheme outputs than to exclusively local inputs.
The trip output element works in association with other L90 elements (refer to the Theory of operation chapter for a com-
plete description of single-pole operations) that must be programmed and in-service for successful operation. The neces-
sary elements are: recloser, breaker control, open pole detector, and phase selector. The recloser must also be in the
“Reset” state before a single pole trip can be issued. Outputs from this element are also directly connected as initiate sig-
nals to the breaker failure elements.
The trip output element is used to aggregate inputs from appropriate protection elements (including 87L line differential, dis-
tance, and instantaneous overcurrent functions) to provide single-pole tripping. The line current differential function is hard-
wired through the 87L TRIP function, which has to be enabled and configured properly.
The 87L TRIP function collects inputs from both the 87L line differential and 87L DTT functions. It can be supervised by the
disturbance detector and determines if the fault type is single-line-to-ground or multi-phase. The 87L TRIP function sends a
direct command to the trip output element to execute appropriate tripping action without any consultation with phase selec-
tor.
Other protective functions, such as distance and overcurrent, need to be assigned to appropriate trip output single-pole or
three-pole inputs and will require phase selector fault identification for tripping action. A timer defined by the TRIP PILOT PRI-
ORITY setting can be used to delay the output decision from other local protection elements to give 87L operational priority.
This prevents three-pole operation where a single pole operation is permitted.
To ensure correct operation of the single-pole tripping feature, any non-distance protection used for single pole trip-
ping (such as high-set overcurrent using the instantaneous or directional overcurrent elements) must be blocked by
NOTE the OPEN POLE OP ΦA, OPEN POLE OP ΦB, or OPEN POLE OP ΦC operands. For example, instantaneous overcur-
rent phase A will be blocked by OPEN POLE OP ΦA operand. This blocking condition is pre-wired for distance pro-
tection.
The following settings are available for the trip output element.
• TRIP MODE: This setting is used to select the required mode of operation. If selected to “3 Pole Only” outputs for all
three phases are always set simultaneously. If selected to “3 Pole & 1 Pole” outputs for all three phases are set simul-
taneously unless the phase selector or a pilot aided scheme determines the fault is single-phase-to-ground. If the fault
is identified as being AG, BG or CG only the operands for the faulted phase will be asserted.
• TRIP 3-POLE INPUT-1 to TRIP 3-POLE INPUT-6: These settings are used to select an operand representing a fault
condition that is not desired to initiate a single pole operation (for example, phase undervoltage). Use a FlexLogic OR-
gate if more than six inputs are required.
• TRIP 1-POLE INPUT-1 to TRIP 1-POLE INPUT-6: These settings are used to select an operand representing a fault
condition that is desired to initiate a single pole trip-and-reclose if the fault is single phase to ground (for example, dis-
tance zone 1). Use a FlexLogic™ OR-gate if more than six inputs are required. The inputs do not have to be phase-
specific as the phase selector determines the fault type.
The AR FORCE 3-P TRIP operand is asserted by the autorecloser 1.5 cycles after single-pole reclosing is initiated. This
operand calls for a three-pole trip if any protection element configured under TRIP 1-POLE INPUT remains picked-up. The
open pole detector provides blocking inputs to distance elements, and therefore the latter will reset immediately after
the TRIP 1-POLE operand is asserted. For other protection elements used in single-pole tripping, the user must ensure
they will reset immediately after tripping, otherwise the fact that they are still picked up will be detected as an evolving
fault and the relay will trip three-poles. For example, if high-set phase instantaneous overcurrent is used (TRIP 1-POLE
INPUT X: “PHASE IOC1 OP”), then OPEN POLE OP ΦA shall be used for blocking phase A of the instantaneous overcur-
rent element. In this way, after tripping phase A, the phase a instantaneous overcurrent element is forced to reset.
Phases B and C are still operational and can detect an evolving fault as soon as 8 ms after tripping phase A. Neutral
and negative-sequence instantaneous overcurrent elements shall be blocked from the OPEN POLE BLK N operand
unless the pickup setting is high enough to prevent pickup during single-pole reclosing.
• TRIP RECLOSE INPUT-1 to TRIP RECLOSE INPUT-6: These settings select an operand representing a fault condi-
tion that is desired to initiate three pole reclosing (for example, phase distance zone 1). Use a FlexLogic™ OR-gate if
5 more than six inputs are required. These inputs will also include the TRIP 1-POLE INPUT-1 to TRIP 1-POLE INPUT-6 values,
which are intended to initiate three-pole reclosing in situations where single-pole tripping commands are changed to
three-pole tripping commands. This may happen in cases where the phase selector identifies a multi-phase fault or the
AR FORCE 3P TRIP command is present.
• TRIP SEAL-IN DELAY: This setting specifies the minimum time that trip command signals are maintained to provide
sufficient time to open the breaker poles. If a value of “0” is specified, then the output signal is reset once the protection
elements initiating the trip are reset. If a value other than “0” is specified, then the protection elements must reset and
the timer initiated at the first trip command must expire.
• TRIP RESET: This setting selects the option to reset the trip latches. If “Pole Curr OR Custom” is chosen, then the
OPEN POLE CURRENT PKP setting should be programmed accordingly. If “CBaux OR Custom” is chosen, then the break-
ers should be set appropriately. Both the “Current” and “CBaux” options can be complimented by custom conditions
using the BKR ΦA OPEN, BKR ΦB OPEN, and BKR ΦC OPEN settings indicated below. Alternately, a purely custom condi-
tion can be applied to reset trip output latches.
• START TMR Z2PH Inp1 and START TMR Z2PH Inp2: These settings select an operand that will start the phase dis-
tance zone 2 timer to avoid a trip delay if the fault evolves from one type to another type (for example, from a single-
line–to-ground fault to a multi-phase fault) or from one zone of protection to another zone of protection (for example,
from zone 3 to zone 2). For instance, the GND DIST Z2 PKP FlexLogic™ operand or the PH DIST Z3 PKP FlexLogic™
operand could be assigned to either of these settings. Use a FlexLogic OR-gate if more than two inputs are required.
Refer to phase distance logic diagrams for additional information.
• START TMR Z2GR Inp1 and START TMR Z2GR Inp2: These settings select an operand that will start the ground dis-
tance zone 2 timer to avoid a trip delay if the fault evolves from one zone of protection to another zone of protection (for
example, from zone 3 to zone 2). For instance, the GND DIST Z3 PKP FlexLogic™ operand could be assigned to these
settings. Use a FlexLogic OR-gate if more than two inputs are required. Refer to ground distance logic diagrams for
additional information.
• BKR ΦA OPEN, BKR ΦB OPEN, and BKR ΦC OPEN: This settings are used to select an operand to indicates that
phase A, B, or C of the breaker is open, respectively.
• TRIP FORCE 3-POLE: Selects an operand that will force an input selected for single pole operation to produce a three
pole operation. The AR DISABLED FlexLogic™ operand is the recommended value for this setting. Power system con-
figurations or conditions which require such operations may be considered as well.
• TRIP PILOT PRIORITY: This setting is used to set an interval equal to the inter-relay channel communications time,
plus an appropriate margin, during which outputs are not asserted. This delay permits fault identification information
from a remote terminal to be used instead of local data only.
• REVERSE FAULT: This setting should be used to guarantee accuracy of single-pole tripping under evolving external to
internal faults. When a close-in external fault occurs, the relay is biased toward very fast operation on a following inter-
nal fault. This is primarily due to depressed voltages and elevated currents in response to the first, external fault. The
phase selector may exhibit some time lag compared to the main protection elements. This may potentially result in a
spurious three-pole operation on a single-line-to-ground internal fault. Delaying tripping on internal faults that follow
detection of reverse faults solves the problem.
As long as the operand indicated under this setting is asserted the trip action will be delayed by TRIP DELAY ON EVOLV
FAULTS time. Typically this operand should combine reverse zone indications (such as zone 4 pickup) with a half-cycle
pickup delay, and two-cycle dropout delay. This setting should be used only in single-pole tripping applications, when
evolving faults are of importance, and slightly delayed operation on evolving faults could be traded for enhanced accu-
racy of single-pole tripping.
• TRIP DELAY ON EVOLV FAULTS: This setting should be used in conjunction with the REVERSE FAULT setting (see
above). Typically this value should be set around half a power system cycle. This setting should be used only in single-
pole tripping applications, when evolving faults are of importance, and slightly delayed operation on evolving faults
could be traded for enhanced accuracy of single-pole tripping.
SETTINGS
Trip Mode
= 3 Pole Only
OR
= 3 Pole and 1 Pole
Trip Force 3-Pole 3P FLEXLOGIC OPERAND
= Off OR TRIP FORCE 3-POLE
FLEXLOGIC OPERAND
2 cyc
OPEN POLE OP
0 AND
OR
FLEXLOGIC OPERAND
AR FORCE 3P TRIP
To trip output
ENABLED logic sheet 2,
SETTING AND 837034A2
Open Pole Mode
= Accelerated
FLEXLOGIC OPERAND
AND
LINE PICKUP OP
FLEXLOGIC OPERANDS
POTT TRIP 3P
DUTT TRIP 3P
PUTT TRIP 3P
D60 only AND
HYBRID POTT TRIP 3P OR
DIR BLOCK TRIP 3P
DCUB TRIP 3P
L90 only 87L TRIP 3P OP
SETTING
Trip 3-Pole Input 1
= Off OR
…
AND
SETTING OR
SETTING
Trip 1-Pole Input 1 AND
= Off
…
SETTING
AND
SETTING OR TRIP PILOT
Trip 1-Pole Input 6 PRIORITY
AND
= Off
FLEXLOGIC OPERANDS 0
PHASE SELECT MULTI-P
OR
PHASE SELECT VOID AND OR PHASE A
PHASE SELECT AG 0
PHASE SELECT BG
PHASE SELECT CG AND OR PHASE B
0 To trip output
FLEXLOGIC OPERANDS logic sheet 2,
POTT TRIP A 837034A2
AND OR PHASE C
DUTT TRIP A 0
PUTT TRIP A
D60 only HYBRID POTT TRIP A OR
{
OR Only 1 of 3 can
DIR BLOCK TRIP A 3P
be asserted
DCUB TRIP A
L90 only 87L TRIP OP A
FLEXLOGIC OPERANDS
POTT TRIP B
DUTT TRIP B
PUTT TRIP B
D60 only HYBRID POTT TRIP B OR
DIR BLOCK TRIP B
DCUB TRIP B
L90 only 87L TRIP OP B
FLEXLOGIC OPERANDS
POTT TRIP C
DUTT TRIP C
PUTT TRIP C
D60 only HYBRID POTT TRIP C OR
DIR BLOCK TRIP C
DCUB TRIP C
L90 only 87L TRIP OP C 837025AG.CDR
SETTING
Trip Delay on Evolving Faults
From trip output logic sheet 1, 837025AG
PHASE A S
OR FLEXLOGIC OPERAND
PHASE B 0
Latch TRIP PHASE A
PHASE C
AND R
SETTING
Trip Delay on Evolving Faults
0
SETTING OR S FLEXLOGIC OPERAND
Reverse Fault
AND Latch TRIP PHASE B
= Off
R
SETTING
Trip Delay on Evolving Faults
0
OR S FLEXLOGIC OPERAND
Latch TRIP PHASE C
From trip output logic AND
R
sheet 1, 837025AG
3P S FLEXLOGIC OPERAND
Latch TRIP 3-POLE
OR R OR TRIP OUTPUT OP
AND
SETTING
FLEXLOGIC OPERAND
Trip Seal-In Delay AND
AND TRIP 1-POLE
XOR
OR
0 AND
TIMER
FLEXLOGIC OPERAND
0
FLEXLOGIC OPERANDS
SETTING
Trip Reset
AND
20 ms
TRIP AR INIT 3-POLE
5
OPEN POLE I< ΦA
OR
OPEN POLE BKR ΦA OP
Pole Curr OR Custom
SETTING
CBaux OR Custom AND
Bkr Phase A Open OR
= Off
Custom
FLEXLOGIC OPERANDS
OPEN POLE I< ΦB
OR
OPEN POLE BKR ΦB OP
Pole Curr OR Custom
SETTING
AND
Bkr Phase B Open CBaux OR Custom
OR
= Off
Custom
FLEXLOGIC OPERANDS
OPEN POLE I< ΦB
OR
OPEN POLE BKR ΦB OP
Pole Curr OR Custom
SETTING
AND
Bkr Phase B Open CBaux OR Custom
OR
= Off
Custom
SETTING
Trip Reclose Input 1
= Off
SETTING OR
Trip Reclose Input 6
= Off
SETTINGS
Start Timer Z2Ph In1
= Off to phase distance zone 2 logic
Start Timer Z2Ph In2 OR FLEXLOGIC OPERAND
= Off AND TRIP Z2PH TMR INIT
Start Timer Z2Gr In1
to ground distance zone 2 logic
= Off
FLEXLOGIC OPERAND
Start Timer Z2Gr In2 OR
AND TRIP Z2GR TMR INIT
= Off
5.7.6 SYNCHROCHECK
5 MESSAGE
SELECT: LV1 and DV2 DV1 Xor DV2, DV1 and DV2
If one or both sources are de-energized, the synchrocheck programming can allow for closing of the circuit breaker using
undervoltage control to by-pass the synchrocheck measurements (dead source function).
• SYNCHK1 V1 SOURCE: This setting selects the source for voltage V1 (see NOTES below).
• SYNCHK1 V2 SOURCE: This setting selects the source for voltage V2, which must not be the same as used for the
V1 (see NOTES below).
• SYNCHK1 MAX VOLT DIFF: This setting selects the maximum primary voltage difference in volts between the two
sources. A primary voltage magnitude difference between the two input voltages below this value is within the permis-
sible limit for synchronism.
• SYNCHK1 MAX ANGLE DIFF: This setting selects the maximum angular difference in degrees between the two
sources. An angular difference between the two input voltage phasors below this value is within the permissible limit
for synchronism.
• SYNCHK1 MAX FREQ DIFF: This setting selects the maximum frequency difference in ‘Hz’ between the two sources.
A frequency difference between the two input voltage systems below this value is within the permissible limit for syn-
chronism.
• SYNCHK1 MAX FREQ HYSTERESIS: This setting specifies the required hysteresis for the maximum frequency differ-
ence condition. The condition becomes satisfied when the frequency difference becomes lower than SYNCHK1 MAX
FREQ DIFF. Once the Synchrocheck element has operated, the frequency difference must increase above the SYNCHK1
MAX FREQ DIFF + SYNCHK1 MAX FREQ HYSTERESIS sum to drop out (assuming the other two conditions, voltage and
angle, remain satisfied).
• SYNCHK1 DEAD SOURCE SELECT: This setting selects the combination of dead and live sources that will by-pass
synchronism check function and permit the breaker to be closed when one or both of the two voltages (V1 or/and V2)
are below the maximum voltage threshold. A dead or live source is declared by monitoring the voltage level. Six
options are available:
None: Dead Source function is disabled
5
LV1 and DV2: Live V1 and Dead V2
DV1 and LV2: Dead V1 and Live V2
DV1 or DV2: Dead V1 or Dead V2
DV1 Xor DV2: Dead V1 exclusive-or Dead V2 (one source is Dead and the other is Live)
DV1 and DV2: Dead V1 and Dead V2
• SYNCHK1 DEAD V1 MAX VOLT: This setting establishes a maximum voltage magnitude for V1 in 1 ‘pu’. Below this
magnitude, the V1 voltage input used for synchrocheck will be considered “Dead” or de-energized.
• SYNCHK1 DEAD V2 MAX VOLT: This setting establishes a maximum voltage magnitude for V2 in ‘pu’. Below this
magnitude, the V2 voltage input used for synchrocheck will be considered “Dead” or de-energized.
• SYNCHK1 LIVE V1 MIN VOLT: This setting establishes a minimum voltage magnitude for V1 in ‘pu’. Above this mag-
nitude, the V1 voltage input used for synchrocheck will be considered “Live” or energized.
• SYNCHK1 LIVE V2 MIN VOLT: This setting establishes a minimum voltage magnitude for V2 in ‘pu’. Above this mag-
nitude, the V2 voltage input used for synchrocheck will be considered “Live” or energized.
NOTES ON THE SYNCHROCHECK FUNCTION:
1. The selected sources for synchrocheck inputs V1 and V2 (which must not be the same source) may include both a
three-phase and an auxiliary voltage. The relay will automatically select the specific voltages to be used by the synch-
rocheck element in accordance with the following table.
The voltages V1 and V2 will be matched automatically so that the corresponding voltages from the two sources will be
used to measure conditions. A phase to phase voltage will be used if available in both sources; if one or both of the
Sources have only an auxiliary voltage, this voltage will be used. For example, if an auxiliary voltage is programmed to
VAG, the synchrocheck element will automatically select VAG from the other source. If the comparison is required on a
specific voltage, the user can externally connect that specific voltage to auxiliary voltage terminals and then use this
"Auxiliary Voltage" to check the synchronism conditions.
If using a single CT/VT module with both phase voltages and an auxiliary voltage, ensure that only the auxiliary voltage
is programmed in one of the sources to be used for synchrocheck.
Exception: Synchronism cannot be checked between Delta connected phase VTs and a Wye con-
nected auxiliary voltage.
NOTE
2. The relay measures frequency and Volts/Hz from an input on a given source with priorities as established by the con-
figuration of input channels to the source. The relay will use the phase channel of a three-phase set of voltages if pro-
grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as
part of the Source and a three-phase set is not.
FLEXLOGIC OPERAND
AND SYNC1 V2 ABOVE MIN
FLEXLOGIC OPERAND
AND SYNC1 V1 ABOVE MIN
FLEXLOGIC OPERAND
AND SYNC1 V1 BELOW MAX
SETTINGS
FLEXLOGIC OPERAND
Function
AND SYNC1 V2 BELOW MAX
Enabled = 1
Disabled = 0
AND
Block
Off = 0
AND
FLEXLOGIC OPERANDS
AND SYNC1 DEAD S OP
AND SYNC1 DEAD S DPO
SETTING
Dead Source Select FLEXLOGIC OPERANDS
AND OR OR SYNC1 CLS OP
None
LV1 and DV2 SYNC1 CLS DPO
DV1 and LV2
AND
DV1 or DV2
DV1 xor DV2
DV1 and DV2
AND
SETTING
Dead V1 Max Volt
V1 ≤ Maximum
XOR
SETTING
Dead V2 Max Volt
OR
V2 ≤ Maximum
SETTING
5
Live V1 Min Volt
AND
V1 ≥ Minimum
SETTING
Live V2 Min Volt
AND
V2 ≥ Minimum
SETTING
CALCULATE Max Volt Diff
SETTING Magnitude V1 Calculate
ΔV ≤ Maximum
V1 Source Angle Φ1 I V1 – V2 I = ΔV
= SRC 1 Frequency F1 FLEXLOGIC OPERANDS
AND SYNC1 SYNC OP
SETTING
SYNC1 SYNC DPO
Max Angle Diff
Calculate
ΔΦ ≤ Maximum
I Φ1 – Φ2 I = ΔΦ
SETTINGS SYNCHROCHECK 1
CALCULATE Max Freq Diff
SETTING Magnitude V2 Freq Hysteresis
V2 Source Angle Φ2 Calculate
ΔF ≤ Maximum
= SRC 2 Frequency F2 I F1 – F2 I = ΔF
ACTUAL VALUE
Synchrocheck 1 ΔV
Synchrocheck 1 ΔΦ
Synchrocheck 1 ΔF
827076AB.CDR
5 MESSAGE
EVENTS: Disabled
There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic™ operand
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name which will be referenced in any target message, a blocking input from any selected FlexLogic™
operand, and a timer for pickup and reset delays for the output operand.
• DIGITAL ELEMENT 1 INPUT: Selects a FlexLogic™ operand to be monitored by the digital element.
• DIGITAL ELEMENT 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set to "0".
• DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”.
• DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to
“Disabled”, the operation of the pickup LED is blocked.
SETTING
DIGITAL ELEMENT 01
FUNCTION:
Disabled = 0 SETTINGS
Enabled = 1 DIGITAL ELEMENT 01
SETTING PICKUP DELAY:
DIGITAL ELEMENT 01 DIGITAL ELEMENT 01 FLEXLOGIC OPERANDS
SETTING
NAME: RESET DELAY:
DIGITAL ELEMENT 01 DIG ELEM 01 DPO
AND RUN tPKP
INPUT: DIG ELEM 01 PKP
Off = 0 DIG ELEM 01 OP
INPUT = 1 tRST
SETTING
DIGITAL ELEMENT 01
BLOCK:
827042A1.VSD
Off = 0
As long as the current through the voltage monitor is above a threshold (see technical specifications for form-A), the “Cont
Op 1 VOn” FlexLogic™ operand will be set (for contact input 1 – corresponding operands exist for each contact output). If
the output circuit has a high resistance or the DC current is interrupted, the trickle current will drop below the threshold and
the “Cont Op 1 VOff” FlexLogic™ operand will be set. Consequently, the state of these operands can be used as indicators
of the integrity of the circuits in which form-A contacts are inserted.
EXAMPLE 1: BREAKER TRIP CIRCUIT INTEGRITY MONITORING
In many applications it is desired to monitor the breaker trip circuit integrity so problems can be detected before a trip oper-
ation is required. The circuit is considered to be healthy when the voltage monitor connected across the trip output contact
detects a low level of current, well below the operating current of the breaker trip coil. If the circuit presents a high resis-
tance, the trickle current will fall below the monitor threshold and an alarm would be declared.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the
breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must
include the breaker position.
UR-series device
with form-A contacts
H1a
I
H1b DC–
V DC+
H1c 52a Trip coil
5
I = current monitor
V = voltage monitor 827073A2.CDR
The PICKUP DELAY setting should be greater than the operating time of the breaker to avoid nuisance
alarms.
NOTE
UR-series device
with form-A contacts
5 H1a
Values for resistor “R”
Power supply Resistance Power
I
24 V DC 1000 Ω 2W
H1b DC– 30 V DC 5000 Ω 2W
48 V DC 10000 Ω 2W
V DC+
110 V DC 25000 Ω 5W
H1c 52a Trip coil
125 V DC 25000 Ω 5W
R
250 V DC 50000 Ω 5W
Bypass
I = current monitor resistor
V = voltage monitor 827074A3.CDR
There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
• COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
• COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
• COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic™ output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set
value.
• COUNTER 1 UP: Selects the FlexLogic™ operand for incrementing the counter. If an enabled UP input is received
when the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
• COUNTER 1 DOWN: Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
• COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are
blocked.
• CNT1 SET TO PRESET: Selects the FlexLogic™ operand used to set the count to the preset value. The counter will
be set to the preset value in the following situations:
1. When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled
and CNT1 SET TO PRESET operand is 0, the counter will be set to 0).
2. When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO
PRESET changing from 1 to 0 while the counter is running has no effect on the count).
3. When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value
1 (when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the
value 0, the counter will be set to 0).
• COUNTER 1 RESET: Selects the FlexLogic™ operand for setting the count to either “0” or the preset value depending
on the state of the CNT1 SET TO PRESET operand.
• COUNTER 1 FREEZE/RESET: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and resetting the count to “0”.
• COUNTER 1 FREEZE/COUNT: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and continuing counting. The present accumulated
value and captured frozen value with the associated date/time stamp are available as actual values. If control power is
interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation.
SETTING
COUNTER 1 FUNCTION:
Disabled = 0
SETTINGS
Enabled = 1
COUNTER 1 NAME:
5 SETTING
COUNTER 1 UP:
AND COUNTER 1 UNITS:
COUNTER 1 PRESET:
RUN
Off = 0 SETTING
FLEXLOGIC
COUNTER 1 COMPARE: OPERANDS
SETTING
CALCULATE Count more than Comp. COUNTER 1 HI
COUNTER 1 DOWN: VALUE Count equal to Comp. COUNTER 1 EQL
Off = 0 Count less than Comp. COUNTER 1 LO
SETTING
COUNTER 1 BLOCK:
Off = 0 SET TO PRESET VALUE
a) MAIN MENU
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS
MONITORING BREAKER 1
See page 5–232.
ELEMENTS ARCING CURRENT
BREAKER 2
MESSAGE See page 5–232.
ARCING CURRENT
BREAKER 3
MESSAGE See page 5–232.
ARCING CURRENT
BREAKER 4
MESSAGE See page 5–232.
ARCING CURRENT
BREAKER
MESSAGE See page 5–234.
FLASHOVER 1
BREAKER
MESSAGE See page 5–234.
FLASHOVER 2
BREAKER
MESSAGE See page 5–234.
FLASHOVER 3
BREAKER
MESSAGE See page 5–234.
FLASHOVER 4
MESSAGE
CONTINUOUS MONITOR
See page 5–237. 5
CT FAILURE
MESSAGE See page 5–239.
DETECTOR
VT FUSE FAILURE 1
MESSAGE See page 5–241.
VT FUSE FAILURE 2
MESSAGE See page 5–241.
VT FUSE FAILURE 3
MESSAGE See page 5–241.
VT FUSE FAILURE 4
MESSAGE See page 5–241.
OPEN POLE
MESSAGE See page 5–242.
There is one breaker arcing current element available per CT bank, with a minimum of two elements. This element calcu-
lates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared passing
through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase and com-
pared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an output operand
to “1”. The accumulated value for each phase can be displayed as an actual value.
The operation of the scheme is shown in the following logic diagram. The same output operand that is selected to operate
the output relay used to trip the breaker, indicating a tripping sequence has begun, is used to initiate this feature. A time
delay is introduced between initiation and the starting of integration to prevent integration of current flow through the
breaker before the contacts have parted. This interval includes the operating time of the output relay, any other auxiliary
relays and the breaker mechanism. For maximum measurement accuracy, the interval between change-of-state of the
operand (from 0 to 1) and contact separation should be measured for the specific installation. Integration of the measured
current continues for 100 ms, which is expected to include the total arcing period.
The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of
the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function. Cor-
rection is implemented to account for a non-zero reset time of the overcurrent function.
Breaker arcing currents and fault duration values are available under the ACTUAL VALUES ÖØ RECORDS ÖØ MAINTENANCE
Ö BREAKER 1(4) menus.
• BKR 1 ARC AMP INT-A(C): Select the same output operands that are configured to operate the output relays used to
trip the breaker. In three-pole tripping applications, the same operand should be configured to initiate arcing current
calculations for poles A, B and C of the breaker. In single-pole tripping applications, per-pole tripping operands should
be configured to initiate the calculations for the poles that are actually tripped.
• BKR 1 ARC AMP DELAY: This setting is used to program the delay interval between the time the tripping sequence is
initiated and the time the breaker contacts are expected to part, starting the integration of the measured current.
• BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set.
Breaker
Contacts Arc
Initiate Part Extinguished
Total Area =
Breaker
Arcing
Current
(kA·cycle)
Programmable
Start Delay 100 ms
Start Stop
Integration Integration
SETTING
BREAKER 1 ARCING
AND
AMP FUNCTION:
SETTING
Disabled=0
Enabled=1 BREAKER 1 ARCING
AMP DELAY: 100 ms
SETTING OR 0 0
BREAKER 1 ARCING
AMP BLOCK:
Off=0
SETTINGS
BREAKER 1 ARCING
AMP INIT-A:
AND
5
Off=0
BREAKER 1 ARCING
AMP INIT-B:
Off=0 OR
BREAKER 1 ARCING
AMP INIT-C:
Off=0
AND RUN
SETTING Integrate
BREAKER 1 ARCING Add to SETTING
AMP SOURCE: AND RUN Accumulator BREAKER 1 ARCING
IA IA 2 -Cycle AMP LIMIT: FLEXLOGIC OPERANDS
Select
2
IB Integrate IB 2 -Cycle Highest KA * Cycle Limit BKR1 ARC OP
IC IC 2 -Cycle Value BKR1 ARC DPO
AND RUN
COMMAND
c) BREAKER FLASHOVER
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS Ö BREAKER FLASHOVER 1(4)
Bus
CTs Breaker
Line/Feeder
Bus VTs
842746A1.CDR
5
The source 1 (SRC1) phase currents are feeder CTs and phase voltages are bus VTs, and Contact Input 1 is set as Breaker
52a contact. The conditions prior to flashover detection are:
1. 52a status = 0.
2. VAg, VBg, or VCg is greater than the pickup setting.
3. IA, IB, IC = 0; no current flows through the breaker.
4. ΔVA is greater than pickup (not applicable in this scheme).
The conditions at flashover detection are:
1. 52a status = 0.
2. VAg, VBg, or VCg is lower than the pickup setting.
3. IA, IB, or IC is greater than the pickup current flowing through the breaker.
4. ΔVA is greater than pickup (not applicable in this scheme).
SIX VT BREAKER FLASHOVER APPLICATION
The per-phase voltage difference approaches zero when the breaker is closed. The is well below any typical minimum
pickup voltage. Select the level of the BRK 1 FLSHOVR DIFF V PKP setting to be less than the voltage difference measured
across the breaker when the close or open breaker resistors are left in service. Prior to flashover, the voltage difference is
larger than BRK 1 FLSHOVR DIFF V PKP. This applies to either the difference between two live voltages per phase or when the
voltage from one side of the breaker has dropped to zero (line de-energized), at least one per-phase voltage is larger than
the BRK 1 FLSHOVR V PKP setting, and no current flows through the breaker poles. During breaker flashover, the per-phase
voltages from both sides of the breaker drops below the pickup value defined by the BRK 1 FLSHOVR V PKP setting, the volt-
age difference drops below the pickup setting, and flashover current is detected. These flashover conditions initiate Flex-
Logic™ pickup operands and start the BRK 1 FLSHOVR PKP DELAY timer.
This application do not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than the
BRK 1 FLSHOVR DIFF V PKP setting. However, monitoring the breaker contact will ensure scheme stability.
Bus
CTs Breaker
Line/Feeder
VTs
VTs
842745A1.CDR
The source 1 (SRC1) phase currents are CTs and phase voltages are bus VTs. The source 2 (SRC2) phase voltages are
line VTs. Contact input 1 is set as the breaker 52a contact (optional).
The conditions prior to flashover detection are:
1. ΔVA is greater than pickup
2. VAg, VBg, or VCg is greater than the pickup setting
3. IA, IB, IC = 0; no current flows through the breaker
4. 52a status = 0 (optional)
The conditions at flashover detection are:
1. ΔVA is less than pickup
2. VAg, VBg, or VCg is lower than the pickup setting
5 3.
4.
IA, IB, or IC is greater than the pickup current flowing through the breaker
52a status = 0 (optional)
The element is operational only when phase-to-ground voltages are connected to relay terminals. The
flashover element will not operate if delta voltages are applied.
NOTE
tion elements, breaker failure, and close and trip commands. A six-cycle time delay applies after the selected Flex-
Logic™ operand resets.
• BRK FLSHOVR PKP DELAY: This setting specifies the time delay to operate after a pickup condition is detected.
SETTINGS
Phase B logic
RESET
SETTINGS
5 cycle
BRK 1 STATUS CLSD A:
0 OR
SET SETTING
RUN dominant
BRK 1 FLSHOVR PKP
FlexLogic operand: On=1
DELAY:
FLEXLOGIC OPERANDS
BRK 1 STATUS CLSD B: Phase B tPKP
logic 0 BRK 1 FLSHOVR OP A
RUN
FLEXLOGIC OPERAND
FlexLogic operand: On=1
Phase B logic BRK 1 FLSHOVR OP B OR BRK 1 FLSHOVR OP
BRK 1 STATUS CLSD C: Phase C RESET
logic OR Phase C logic BRK 1 FLSHOVR OP C
SETTINGS RUN
BRK 1 FLSHOVR SIDE 1 FlexLogic operand: On=1
SRC:
SRC 1, SRC 2, … , SRC 6 SETTING
VA
BRK 1 FLSHOVR AMP PKP:
VB
VC RUN
IA IA > PKP
IB
AND
IC
SETTINGS
SETTING
BRK 1 FLSHOVR SIDE 2
SRC:
SRC 1, SRC 2, … , SRC 6, none
Va
BRK 1 FLSHOVR DIFF V
PKP:
RUN
5
VA = | VA - Va | VA > PKP
Vb
Vc 842018A2.CDR
d) CONTINUOUS MONITOR
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS ÖØ CONTINUOUS MONITOR
The continuous monitor logic is intended to detect the operation of any tripping element that has operated under normal
load conditions; that is, when the disturbance detector has not operated. Because all tripping is supervised by the distur-
bance detector function, no trip will be issued under these conditions. This could occur when an element is incorrectly set
so that it may misoperate under load. The continuous monitor can detect this state and issue an alarm and/or block the trip-
ping of the relay.
SETTING
CONT MONITOR
FUNCTION:
Disabled = 0
Enabled = 1
AND
SETTING
CONT MONITOR
I_SUPV:
Off = 0 AND
SETTING
CONT MONITOR
I_OP: CONSTANT
Off = 0 CONT
MONITOR
TIMER
OR t pkp
= 1 sec
SETTING
CONT MONITOR t RST = 0
V_SUPV:
Off = 0 AND
FLEXLOGIC OPERANDS
5 CONT MONITOR OP
CONT MONITOR PKP
SETTING
CONT MONITOR DPO
CONT MONITOR
V_OP:
AND
Off = 0 827049A3.vsd
e) CT FAILURE DETECTOR
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS ÖØ CT FAILURE DETECTOR
The CT failure function is designed to detect problems with system current transformers used to supply current to the relay.
This logic detects the presence of a zero-sequence current at the supervised source of current without a simultaneous
zero-sequence current at another source, zero-sequence voltage, or some protection element condition.
The CT failure logic (see below) is based on the presence of the zero-sequence current in the supervised CT source and
the absence of one of three or all of the three following conditions.
1. Zero-sequence current at different source current (may be different set of CTs or different CT core of the same CT).
2. Zero-sequence voltage at the assigned source.
3. Appropriate protection element or remote signal.
The CT failure settings are described below.
• CT FAIL FUNCTION: This setting enables or disables operation of the CT failure element.
• CT FAIL BLOCK: This setting selects a FlexLogic™ operand to block operation of the element during some condition
(for example, an open pole in process of the single pole tripping-reclosing) when CT fail should be blocked. Local sig-
nals or remote signals representing operation of some remote current protection elements via communication chan-
nels can also be chosen.
• CT FAIL 3I0 INPUT 1: This setting selects the current source for input 1. The most critical protection element should
also be assigned to the same source.
• CT FAIL 3I0 INPUT 1 PICKUP: This setting selects the 3I_0 pickup value for input 1 (the main supervised CT source).
• CT FAIL 3I0 INPUT 2: This setting selects the current source for input 2. Input 2 should use a different set of CTs or a
different CT core of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared.
• CT FAIL 3I0 INPUT 2 PICKUP: This setting selects the 3I_0 pickup value for input 2 (different CT input) of the relay.
• CT FAIL 3V0 INPUT: This setting selects the voltage source.
• CT FAIL 3V0 INPUT PICKUP: This setting specifies the pickup value for the 3V_0 source.
• CT FAIL PICKUP DELAY: This setting specifies the pickup delay of the CT failure element.
SETTING
CT FAIL FUNCTION:
Disabled=0
Enabled=1
SETTING
CT FAIL BLOCK:
Off=0 SETTING
SETTING SETTING
OR
CT FAIL 3VO INPUT: CT FAIL 3VO INPUT:
f) VT FUSE FAILURE
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS ÖØ VT FUSE FAILURE 1(4)
AND
5
Reset-dominant
OR SET
FAULT
Latch
AND
RESET
SETTING
Function
Disabled = 0
Enabled = 1
AND
COMPARATORS
SOURCE 1 Run
V_2 V_2 > 0.1 pu
Run AND
TIMER
V_1 < 0.80 pu
2 cycles
FLEXLOGIC OPERANDS
Run AND
I_1 < 0.05 pu Latch SRC1 VT FUSE FAIL OP
20 cycles
SRC1 VT FUSE FAIL DPO
FLEXLOGIC OPERANDS
SRC1 50DD OP
OPEN POLE OP
The OPEN POLE OP operand is applicable
AND
to the D60, L60, and L90 only.
RESET
OR
Reset-dominant
AND
FLEXLOGIC OPERAND
AND SRC1 VT FUSE FAIL VOL LOSS
827093AM.CDR
The open pole detector is intended to identify an open pole of the line circuit breaker. The scheme monitors the breakers
auxiliary contacts, current in the circuit and optionally voltage on the line. The scheme generates output operands used to
block the phase selector and some specific protection elements, thus preventing maloperation during the dead time of a
single-pole autoreclose cycle or any other open pole conditions.
The scheme declares an open pole at the moment a single-pole trip is issued.
In two-breaker and breaker-and-a-half applications, an open pole condition is declared when one or more of the following
hold:
• Both breakers have an open pole on the same phase.
• The current on the line drops below a threshold.
• The current and voltage on the line drop below a threshold.
The open pole feature uses signals defined by the GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE Ö DISTANCE
SOURCE setting. Voltage supervision can be used only with wye VTs on the line side of the breaker.
The OPEN POLE CURRENT PICKUP setting establishes the current threshold below which an open pole is declared.
The OPEN POLE LINE XC1 setting specifies positive-sequence reactance of the entire line. If shunt reactors are applied, this
value should be a net capacitive reactance of the line and the reactors installed between the line breakers. The value is
entered in secondary ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed and
utilized by the relay.
The OPEN POLE LINE XC0 setting specifies zero-sequence reactance of the entire line. If shunt reactors are applied, this
value should be a net capacitive reactance of the line and the reactors installed between the line breakers. The value shall
be entered in secondary ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed
and utilized by the relay (OPEN POLE REM OP FlexLogic™ operand).
The OPEN POLE REM CURR PKP setting specifies pickup level for the remote-end current estimated by the relay as the local
current compensated by the calculated charging current. The latter is calculated based on the local voltages and the capac-
itive reactances of the line. This setting is relevant if open pole condition at the remote end of the line is to be sensed and
utilized by the relay (OPEN POLE REM OP FlexLogic™ operand).
The OPEN POLE MODE setting selects the mode of operation of the open pole function. When the “Accelerated” mode is cho-
sen, an open pole will be declared ½ cycle after trip output operation and before the breaker pole opens. This blocks dis-
tance loops involved in the faulted phase and phase selector, and arms the trip output to produce three-pole trip for the next
fault. If the fault evolves into multi-phase fault before breaker pole opens for the first fault, the remaining in-service distance
loops would initiate a three-pole trip. When the “Traditional” mode is selected, then an open pole is declared only after the
breaker opens and current disappears. If the fault evolves into a multi-phase fault before the circuit breaker pole opens for
the first fault, the phase selector will change the fault type from a single-line-to-ground fault to a multi-phase fault, thereby
initiating a three-pole trip.
The OPEN POLE DETECTION setting selects the signals used to detect an open pole condition. When “I AND V AND CBaux”
value is selected, the breaker 52 contacts and the current with optional voltage signals are used to determine open pole
conditions. For the “I AND V only” selection, only the current with optional voltage signals are used.
For convenience, the position of the breaker poles defined in the breaker control feature and available as FlexLogic™ oper-
and BREAKER 1 ΦA CLSD through BREAKER 1 ΦC CLSD and BREAKER 1 OOS are used by the open pole feature if the “I AND
V AND CBaux” detection value is selected.
For correct operation of the open pole detector, the breaker control, trip output, and single-pole autoreclose features must
be enabled and configured properly. When used in configuration with only one breaker, the BREAKER 2 FUNCTION should be
“Enabled” and the BREAKER 2 OUT OF SV setting should be “On” (refer to the Breaker Control section earlier in this chapter
for additional details).
SETTING
Function
= Enabled
to open pole logic sheet 2
= Disabled
AND ENABLED
Block
= Off
to the trip output scheme
FLEXLOGIC OPERANDS
SETTING OPEN POLE I< ΦA
Current Pickup OPEN POLE I< ΦB
RUN OPEN POLE I< ΦC
IA < Pickup
IB < Pickup AND
to open pole logic sheet 2
SETTING IC < Pickup
OR PHASE A
Voltage Supervision AND
= Enabled AND
= Disabled
AND CALCULATE
SETTING RUN AND
to open pole logic sheet 2
Distance Source Voltage
OR PHASE B
= IA supervision AND
= IB calculations
AND
= IC
= VAG VAG > 0.7 pu
= VBG VBG > 0.7 pu AND
to open pole logic sheet 2
= VCG VCG > 0.7 pu
OR PHASE C
AND
SETTINGS FLEXLOGIC OPERANDS AND
to the trip output scheme
Open Pole Line XC1 BREAKER 1 ФA CLSD
Open Pole Line XC0 OR FLEXLOGIC OPERANDS
BREAKER 1 ФB CLSD
OPEN POLE BKR OP ΦA
BREAKER 1 ФC CLSD
Charging current OR OPEN POLE BKR OP ΦB
calculations
OPEN POLE BKR OP ΦC
FLEXLOGIC OPERANDS
BREAKER 1 OOS OR
BREAKER 1 CLOSED OR
Charging OR
5 current
calculatoins
BREAKER 1 OPEN POLE
FLEXLOGIC OPERANDS
BREAKER 2 ФA CLSD
OR
BREAKER 2 ФB CLSD
BREAKER 2 ФC CLSD
OR
FLEXLOGIC OPERANDS
BREAKER 2 OOS OR
BREAKER 2 CLOSED OR
OR
SETTING BREAKER 2 OPEN POLE
Open Pole Detection
= Iand V and CBaux
= I and V only
TIMERS
SETTING 2 cycles
Open Pole Rem Current Pkp 2 cycles
RUN 2 cycles FLEXLOGIC OPERANDS
IA remote < Pickup OPEN POLE REM OP ΦA
2 cycles
IB remote < Pickup OPEN POLE REM OP ΦB
2 cycles
IC remote < Pickup OPEN POLE REM OP ΦC
2 cycles
837024AC.CDR
SETTING
Open Pole Mode FLEXLOGIC OPERAND
= Accelerated OR OPEN POLE OP
= Traditional
837038A1.CDR
5 MESSAGE
POTT SEAL-IN
DELAY: 0.400 s
Range: 0.000 to 65.535 s in steps of 0.001
This scheme is intended for two-terminal line applications only. It uses an over-reaching zone 2 distance element to essen-
tially compare the direction to a fault at both the ends of the line. Ground directional overcurrent functions available in the
relay can be used in conjunction with the zone 2 distance element to key the scheme and initiate its operation. This pro-
vides increased coverage for high resistance faults.
For proper scheme operation, the zone 2 phase and ground distance elements must be enabled, configured, and set per
the rules of distance relaying. The line pickup element should be enabled, configured and set properly to detect line-end-
open/weak-infeed conditions. If used by this scheme, the selected ground directional overcurrent functions must be
enabled, configured, and set accordingly.
• POTT PERMISSIVE ECHO: If set to "Enabled" this setting will result in sending a permissive echo signal to the remote
end. The permissive signal is echoed back upon receiving a reliable POTT RX signal from the remote end while the
line-end-open condition is identified by the line pickup logic. The permissive echo is programmed as a one-shot logic.
The echo is sent only once and then the echo logic locks out for a settable period of time (ECHO LOCKOUT setting). The
duration of the echo pulse does not depend on the duration or shape of the received POTT RX signal but is settable as
ECHO DURATION.
• POTT RX PICKUP DELAY: This setting enables the relay to cope with spurious receive signals. The delay should be
set longer than the longest spurious TX signal that can occur simultaneously with the zone 2 pickup. The selected
delay will increase the response time of the scheme.
• TRANS BLOCK PICKUP DELAY: This setting defines a transient blocking mechanism embedded in the POTT
scheme for coping with the exposure of a ground directional overcurrent function (if used) to current reversal condi-
tions. The transient blocking mechanism applies to the ground overcurrent path only as the reach settings for the zone
2 distance functions is not expected to be long for two-terminal applications, and the security of the distance functions
is not endangered by the current reversal conditions. Upon receiving the POTT RX signal, the transient blocking mech-
anism allows the RX signal to be passed and aligned with the GND DIR O/C FWD indication only for a period of time
defined as TRANS BLOCK PICKUP DELAY. After that the ground directional overcurrent path will be virtually disabled for a
period of time specified as TRANS BLOCK RESET DELAY.
The TRANS BLOCK PICKUP DELAY should be long enough to give the selected ground directional overcurrent function
time to operate, but not longer than the fastest possible operation time of the protection system that can create current
reversal conditions within the reach of the selected ground directional overcurrent function. This setting should take
into account the POTT RX PICKUP DELAY. The POTT RX signal is shaped for aligning with the ground directional indica-
tion as follows: the original RX signal is delayed by the POTT RX PICKUP DELAY, then terminated at TRANS BLOCK PICKUP
DELAY after the pickup of the original POTT TX signal, and eventually, locked-out for TRANS BLOCK RESET DELAY.
• TRANS BLOCK RESET DELAY: This setting defines a transient blocking mechanism embedded in the POTT scheme
for coping with the exposure of a ground directional overcurrent function (if used) to current reversal conditions (see
also the TRANS BLOCK PICKUP DELAY). This delay should be selected long enough to cope with transient conditions
including not only current reversals but also spurious negative and zero-sequence currents occurring during breaker
operations. The breaker failure time of the surrounding protection systems within the reach of the ground directional
function used by the POTT scheme may be considered to make sure that the ground directional function is not jeopar-
dized during delayed breaker operations.
• ECHO DURATION: This setting defines the guaranteed and exact duration of the echo pulse. The duration does not
depend on the duration and shape of the received POTT RX signal. This setting enables the relay to avoid a permanent
lock-up of the transmit/receive loop.
• ECHO LOCKOUT: This setting defines the lockout period for the echo logic after sending the echo pulse. 5
• LINE END OPEN PICKUP DELAY: This setting defines the pickup setting for validation of the line end open conditions
as detected by the Line Pickup logic through the LINE PICKUP LEO PKP FlexLogic™ operand. The validated line end
open condition is a requirement for the POTT scheme to return a received echo signal (if the echo feature is enabled).
The value of this setting should take into account the principle of operation and settings of the line pickup element.
• POTT SEAL-IN DELAY: The output FlexLogic™ operand (POTT OP) is produced according to the POTT scheme logic.
A seal-in time delay is applied to this operand for coping with noisy communication channels. This setting specifies a
minimum guaranteed duration of the POTT OP pulse.
• GND DIR O/C FWD: This setting selectes the FlexLogic™ operand (if any) of a protection element used in addition to
zone 2 for identifying faults on the protected line, and thus, for keying the communication channel and initiating opera-
tion of the scheme. Good directional integrity is the key requirement for an over-reaching forward-looking protection
element used as GND DIR O/C FWD. Even though any FlexLogic™ operand could be used as GND DIR O/C FWD allowing
the user to combine responses of various protection elements, or to apply extra conditions through FlexLogic™ equa-
tions, this extra signal is primarily meant to be the output operand from either the negative-sequence directional over-
current or neutral directional overcurrent elements. Both of these elements have separate forward and reverse output
operands. The forward indication should be used (NEG SEQ DIR OC1 FWD or NEUTRAL DIR OC1 FWD). For greater security
and to overcome spurious directional element operation during transients, adding at least 0.5 cycles of pickup delay to
the forward directional element is recommended.
• POTT RX: This setting enables the user to select the FlexLogic™ operand that represents the receive signal (RX) for
the scheme. Typically an input contact interfacing with a signaling system is used. Other choices include remote inputs
and FlexLogic™ equations. The POTT transmit signal (TX) should be appropriately interfaced with the signaling sys-
tem by assigning the output FlexLogic™ operand (POTT TX) to an output contact. The remote output mechanism is
another choice.
The output operand from the scheme (POTT OP) must be configured to interface with other relay functions, output con-
tacts in particular, in order to make the scheme fully operational. Typically, the output operand should be programmed
to initiate a trip, breaker fail, and autoreclose, and drive a user-programmable LED as per user application.
SETTING
POTT SCHEME
FUNCTION:
Disabled = 0
Enabled = 1
SETTINGS
POTT SEAL-IN
DELAY: FLEXLOGIC OPERAND
SETTING 0 POTT OP
OR t RST
GND DIR O/C FWD: AND
Off = 0
SETTINGS
POTT RX PICKUP
DELAY: AND
FLEXLOGIC OPERAND
t PKP
POTT RX: AND
0
Off = 0
SETTINGS
TRANS BLOCK PICKUP AND
DELAY:
TRANS BLOCK RESET
DELAY:
t PKP
t RST
5
SETTINGS FLEXLOGIC OPERAND
LINE END OPEN PICKUP SETTINGS
DELAY: OR POTT TX
FLEXLOGIC OPERAND
t PKP ECHO DURATION:
LINE PICKUP LEO PKP
0
ECHO LOCKOUT:
SETTING AND Echo duration and lockout logic
Disabled = 0
Enabled = 1 837014A9.CDR
5.7.11 AUTORECLOSE
The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole and
three pole modes, in one or two breaker arrangements. The autoreclose scheme provides four programs with different
operating cycles, depending on the fault type. Each of the four programs can be set to trigger up to four reclosing attempts.
The second, third, and fourth attempts always perform three-pole reclosing and have independent dead time delays.
When used in two breaker applications, the reclosing sequence is selectable. The reclose signal can be sent to one
selected breaker only, to both breakers simultaneously or to both breakers in sequence (one breaker first and then, after a
delay to check that the reclose was successful, to the second breaker). When reclosing in sequence, the first breaker
should reclose with either the single-pole or three-pole dead time according to the fault type and reclose mode; the second
breaker should follow the successful reclosure of the first breaker. When reclosing simultaneously, for the first shot both
breakers should reclose with either the single-pole or three-pole dead time, according to the fault type and the reclose
mode.
The signal used to initiate the autoreclose scheme is the trip output from protection. This signal can be single pole tripping
for single phase faults and three phase tripping for multi-phase faults. The autoreclose scheme has five operating states.
STATE CHARACTERISTICS
Enabled Scheme is permitted to operate
Disabled Scheme is not permitted to operate
Reset Scheme is permitted to operate and shot count is reset to 0
Reclose in progress Scheme has been initiated but the reclose cycle is not finished (successful or not)
Lockout Scheme is not permitted to operate until reset received
AR PROGRAMS:
The autorecloser provides four programs that can cause from one to four reclose attempts (shots). After the first shot, all
subsequent recloses will always be three-pole. If the maximum number of shots selected is “1” (only one reclose attempt)
and the fault is persistent, after the first reclose the scheme will go to lockout upon another Initiate signal.
For the 3-pole reclose programs (modes 3 and 4), an AR FORCE 3-P FlexLogic™ operand is set. This operand can be used
in connection with the tripping logic to cause a three-pole trip for single-phase faults.
There are three initiate programs: single pole initiate, three pole initiate and three pole, time delay initiate. Any of these
reclose initiate signals will start the reclose cycle and set the reclose-in-progress (AR RIP) operand. The reclose-in-progress
operand is sealed-in until the Lockout or Reset signal appears.
The three-pole initiate and three-pole time delay initiate signals are latched until the CLOSE BKR1 OR BKR2 or Lockout or
Reset signal appears.
AR PAUSE:
The pause input offers the possibility of freezing the autoreclose cycle until the pause signal disappears. This may be done
when a trip occurs and simultaneously or previously, some conditions are detected such as out-of step or loss of guard fre-
quency, or a remote transfer trip signal is received. The pause signal blocks all three dead timers. When the ‘pause’ signal
disappears the autoreclose cycle is resumed by initiating AR 3-P DEAD TIME 2.
This feature can be also used when a transformer is tapped from the protected line and a reclose is not desirable until the
transformer is removed from the line. In this case, the reclose scheme is ‘paused’ until the transformer is disconnected. The
AR PAUSE input will force a three-pole trip through the 3-P DEADTIME 2 path.
EVOLVING FAULTS:
1.25 cycles after the single pole dead time has been initiated, the AR FORCE 3P TRIP operand is set and it will be reset only
when the scheme is reset or goes to Lockout. This will ensure that when a fault on one phase evolves to include another
phase during the single pole dead time of the auto-recloser the scheme will force a 3 pole trip and reclose.
RECLOSING SCHEME OPERATION FOR ONE BREAKER:
• Permanent Fault: Consider Mode 1, which calls for 1-Pole or 3-Pole Time Delay 1 for the first reclosure and 3-Pole
Time Delay 2 for the second reclosure, and assume a permanent fault on the line. Also assume the scheme is in the
Reset state. For the first single-phase fault the AR 1-P DEAD TIME timer will be started, while for the first multi-phase fault
the AR 3-P DEAD TIME 1 timer will be started. If the AR 3P TD INIT signal is high, the AR 3-P DEAD TIME 2 will be started for
5 the first shot.
If AR MAX NO OF SHOTS is set to “1”, upon the first reclose the shot counter is set to 1. Upon reclosing, the fault is again
detected by protection and reclose is initiated. The breaker is tripped three-pole through the AR SHOT COUNT >0 oper-
and that will set the AR FORCE 3P operand. Because the shot counter has reached the maximum number of shots per-
mitted the scheme is sent to the Lockout state.
If AR MAX NO OF SHOTS is set to “2”, upon the first reclose the shot counter is set to 1. Upon reclosing, the fault is again
detected by protection and reclose is initiated. The breaker is tripped three-pole through the AR SHOT COUNT >0 oper-
and that will set the AR FORCE 3P operand. After the second reclose the shot counter is set to 2. Upon reclosing, the
fault is again detected by protection, the breaker is tripped three-pole, and reclose is initiated again. Because the shot
counter has reached the maximum number of shots permitted the scheme is sent to the lockout state.
• Transient Fault: When a reclose output signal is sent to close the breaker the reset timer is started. If the reclosure
sequence is successful (there is no initiating signal and the breaker is closed) the reset timer will time out returning the
scheme to the reset state with the shot counter set to "0" making it ready for a new reclose cycle.
RECLOSING SCHEME OPERATION FOR TWO BREAKERS:
• Permanent Fault: The general method of operation is the same as that outlined for the one breaker applications
except for the following description, which assumes AR BKR SEQUENCE is “1-2” (reclose Breaker 1 before Breaker 2)
The signal output from the dead time timers passes through the breaker selection logic to initiate reclosing of Breaker
1. The Close Breaker 1 signal will initiate the Transfer Timer. After the reclose of the first breaker the fault is again
detected by the protection, the breaker is tripped three pole and the autoreclose scheme is initiated. The Initiate signal
will stop the transfer timer. After the 3-P dead time times out the Close Breaker 1 signal will close first breaker again
and will start the transfer timer. Since the fault is permanent the protection will trip again initiating the autoreclose
scheme that will be sent to Lockout by the SHOT COUNT = MAX signal.
• Transient Fault: When the first reclose output signal is sent to close Breaker 1, the reset timer is started. The close
Breaker 1 signal initiates the transfer timer that times out and sends the close signal to the second breaker. If the reclo-
sure sequence is successful (both breakers closed and there is no initiating signal) the reset timer will time out, return-
ing the scheme to the reset state with the shot counter set to 0. The scheme will be ready for a new reclose cycle.
Once the Lockout state is set it will be latched until one or more of the following occurs:
• The scheme is intentionally reset from Lockout, employing the Reset setting of the Autorecloser;
• The Breaker(s) is(are) manually closed from panel switch, SCADA or other remote control through the AR BRK MAN
CLOSE setting;
• 10 seconds after breaker control detects that breaker(s) were closed.
BREAKER OPEN BEFORE FAULT:
A logic circuit is provided that inhibits the close breaker 1 and close breaker 2 outputs if a reclose initiate (RIP) indicator is
not present within 30 ms of the Breaker Any Phase Open input. This feature is intended to prevent reclosing if one of the
breakers was open in advance of a reclose initiate input to the recloser. This logic circuit resets when the breaker is closed.
TRANSFER RECLOSE WHEN BREAKER IS BLOCKED:
1. When the reclosing sequence 1-2 is selected and Breaker 1 is blocked (AR BKR1 BLK operand is set) the reclose signal
can be transferred direct to the Breaker 2 if AR TRANSFER 1 TO 2 is set to “Yes”. If set to “No”, the scheme will be sent to
Lockout by the incomplete sequence timer.
2. When the reclosing sequence 2-1 is selected and Breaker 2 is blocked (AR BKR2 BLK operand is set) the reclose signal
can be transferred direct to the Breaker 1 if AR TRANSFER 2 TO 1 is set to “Yes”. If set to “No” the scheme will be sent to
Lockout by the incomplete sequence timer.
FORCE 3-POLE TRIPPING:
The reclosing scheme contains logic that is used to signal trip logic that three-pole tripping is required for certain conditions.
This signal is activated by any of the following:
• Autoreclose scheme is paused after it was initiated.
• Autoreclose scheme is in the lockout state.
USE OF SETTINGS:
The single-phase autoreclose settings are described below.
• AR MODE: This setting selects the Autoreclose operating mode, which functions in conjunction with signals received
at the initiation inputs as described previously.
• AR MAX NUMBER OF SHOTS: This setting specifies the number of reclosures that can be attempted before reclo-
5 sure goes to lockout when the fault is permanent.
• AR INITIATE MODE: This setting selects the autoreclose initiation mode. When selected as “Protection AND CB”, the
autoreclose element will be initiated by protection operation and will begin incrementing the autoreclose dead time
timer when a circuit breaker is open. Breaker status is determined from breaker auxiliary contacts which should be cor-
rectly configured in breaker settings. In “Protection only” initiation mode, the autoreclose element will be initiated by
protection operation and will begin incrementing the dead time when protection resets, without the need of breaker
auxiliary contacts.
• AR BLOCK BKR1: This input selects an operand that will block the reclose command for breaker 1. This condition can
be for example: breaker low air pressure, reclose in progress on another line (for the central breaker in a breaker and
a half arrangement), or a sum of conditions combined in FlexLogic™.
• AR CLOSE TIME BKR1:This setting represents the closing time for the breaker 1 from the moment the “Close” com-
mand is sent to the moment the contacts are closed.
• AR BKR MAN CLOSE: This setting selects a FlexLogic™ operand that represents manual close command to a
breaker associated with the autoreclose scheme.
• AR BLK TIME UPON MAN CLS: The autoreclose scheme can be disabled for a programmable time delay after an
associated circuit breaker is manually commanded to close, preventing reclosing onto an existing fault such as
grounds on the line. This delay must be longer than the slowest expected trip from any protection not blocked after
manual closing. If the autoreclose scheme is not initiated after a manual close and this time expires the autoreclose
scheme is set to the reset state.
• AR 1P INIT: This setting selects a FlexLogic™ operand that is intended to initiate single-pole autoreclosure.
• AR 3P INIT: This setting selects a FlexLogic™ operand that is intended to initiate three-pole autoreclosure, first timer
(AR 3P DEAD TIME 1) that can be used for a high-speed autoreclosure.
• AR 3P TD INIT: This setting selects a FlexLogic™ operand intended to initiate three-pole autoreclosure. second timer
(AR 3P DEAD TIME 2) can be used for a time-delay autoreclosure.
• AR MULTI-P FAULT: This setting selects a FlexLogic™ operand that indicates a multi-phase fault. The operand value
should be zero for single-phase to ground faults.
• BKR ONE POLE OPEN: This setting selects a FlexLogic™ operand which indicates that the breaker has opened cor-
rectly following a single phase to ground fault and the autoreclose scheme can start timing the single pole dead time
(for 1-2 reclose sequence for example, breaker 1 should trip single pole and breaker 2 should trip 3 pole).
the transfer time. When set to “No”, the closing command will be blocked by the AR BKR2 BLK signal and the scheme
will be sent to lockout by the incomplete sequence timer.
• AR BKR1 FAIL OPTION: This setting establishes how the scheme performs when the breaker closing sequence is 1-
2 and Breaker 1 has failed to close. When set to “Continue” the closing command will be transferred to breaker 2 which
will continue the reclosing cycle until successful (the scheme will reset) or unsuccessful (the scheme will go to Lock-
out). When set to “Lockout” the scheme will go to lockout without attempting to reclose breaker 2.
• AR BKR2 FAIL OPTION: This setting establishes how the scheme performs when the breaker closing sequence is 2-
1 and Breaker 2 has failed to close. When set to “Continue” the closing command will be transferred to breaker 1 which
will continue the reclosing cycle until successful (the scheme will reset) or unsuccessful (the scheme will go to Lock-
out). When set to “Lockout” the scheme will go to lockout without attempting to reclose breaker 1.
• AR 1-P DEAD TIME: Set this intentional delay longer than the estimated de-ionizing time after the first single-pole trip.
• AR BREAKER SEQUENCE: This setting selects the breakers reclose sequence: Select “1” for reclose breaker 1 only,
“2” for reclose breaker 2 only, “1&2” for reclose both breakers simultaneously, “1-2” for reclose breakers sequentially;
Breaker 1 first, and “2-1” for reclose breakers sequentially; Breaker 2 first.
• AR TRANSFER TIME: The transfer time is used only for breaker closing sequence 1-2 or 2-1, when the two breakers
are reclosed sequentially. The transfer timer is initiated by a close signal to the first breaker. The transfer timer trans-
fers the reclose signal from the breaker selected to close first to the second breaker. The time delay setting is based on
the maximum time interval between the autoreclose signal and the protection trip contact closure assuming a perma-
nent fault (unsuccessful reclose). Therefore, the minimum setting is equal to the maximum breaker closing time plus
the maximum line protection operating time plus a suitable margin. This setting will prevent the autoreclose scheme
from transferring the close signal to the second breaker unless a successful reclose of the first breaker occurs.
• AR BUS FLT INIT: This setting is used in breaker-and-a-half applications to allow the autoreclose control function to
perform reclosing with only one breaker previously opened by bus protection. For line faults, both breakers must open
5 for the autoreclose reclosing cycles to take effect.
SETTING
S TIMER
Function
Enabled = 1 Latch EVOLVING FAULT
Block 0
R
Off = 0 1.25 cycles FLEXLOGIC OPERANDS
AR ENABLED
FLEXLOGIC OPERAND OR AR DISABLED
LINE PICKUP OP
AND AND
AR INITIATE
SETTING
SETTING
Breaker Manual Close S
Blk Time Upon Man Cls FLEXLOGIC OPERAND
Off = 0
0 Latch AR RIP
from autoreclose logic sheet 3 OR AND R
BKR MANUAL CLOSE
Lockout FLEXLOGIC OPERANDS
SETTING OR
AR 1-P RIP
1-P Init AR 3-P/1 RIP
Off = 0
AND
OR
FLEXLOGIC OPERAND
SETTING
TRIP 1 POLE OR
1-P Dead Time 1 SETTINGS
Extend Dead T1 AND
SETTING
AND Off = 0
3-P Init 0 Dead T1 Extension OR
Off = 0
AND S
OR Latch SETTING OR
FLEXLOGIC OPERAND 0
OR 3-P Dead Time 1
TRIP AR INIT 3 POLE R
OR AND
SETTING 0
3-P TD Init AND
Off = 0
SETTING
Bkr 1 Pole Open AND SETTING
from autoreclose logic sheet 2 OR
Off = 0 3-P Dead Time 2 OR CLOSE
SHOT COUNT = 1
from autoreclose logic sheet 3 OR
AND
AND 0
BKR ONE POLE OPEN
OR
S OR
SETTING
Bkr 3 Pole Open
Off = 0
AND
AND OR
OR
OR R
Latch SETTING
3-P Dead Time 3 5
from autoreclose logic sheet 3 OR from sheet 2 AND
0
BKR 3 POLE OPEN SHOT COUNT = 2
SETTING
SETTING
OR 3-P Dead Time 4
AR Initiate Mode
= Protection and CB OR S
AND
Latch AND 0
from autoreclose logic sheet 2
OR R
RESET FLEXLOGIC OPERANDS
CLOSE BKR1 OR BKR2 OR AR 3P/2 RIP
AND
AR 3P/3 RIP
FLEXLOGIC OPERAND AR 3P/4 RIP
from sheet 2
AR SHOT COUNT > 0
SHOT COUNT = 3
SETTING
Pause from autoreclose logic sheet 2
Off = 0 BKR FAIL TO RECLS
AND
SETTING
Mode
AND SETTING
1 Pole AND
Inc Seq Time FLEXLOGIC OPERAND
3 Pole-A OR
OR
3 Pole-B OR AR LO
AND
0
OR
AND
TIMER
FLEXLOGIC OPERAND
0
PHASE SELECT MULTI-P AND
5 ms
SETTING OR
Multi P Fault AND
Off = 0 FLEXLOGIC OPERANDS
AR INCOMPLETE SEQ
OR AR FORCE 3P TRIP
RESET
SETTING
Reset
Off = 0
PROTECTION & CB
EVOLVING FAULT
AR DISABLED 827089AR.CDR
5-258
30 ms to autoreclose
BKR1 MNL OPEN
TIMER logic sheet 3
FLEXLOGIC OPERAND
BREAKER 1 OPEN AND
AND OR 0
SETTING FLEXLOGIC OPERAND
Block Bkr1 AR BKR 1 BLK
Off = 0 OR
FLEXLOGIC OPERAND
BREAKER 1 OOS
SETTING AND
From sheet 1 Close Time Bkr1 AND SETTING
Close Time Bkr1
PROTECTION & CB 150 ms
AND
FLEXLOGIC OPERAND
2 ms
SETTING OPEN POLE OP OR 2 ms
AND
Transfer 1 to 2
5.7 CONTROL ELEMENTS
No = 0
SETTING AND S
CLOSE BKR 1 OR 2
AND
from sheet 1 SETTING
CLOSE Close Time Bkr2 AND
150 ms
AND
Lockout FLEXLOGIC OPERAND
2 ms
SETTING AND OPEN POLE OP OR
Transfer 2 to 1
AND
No = 0
AND
S
AND
FLEXLOGIC OPERAND
SETTING
from sheet 1
RESET
to autoreclose
BKR2 MNL OPEN
logic sheet 3
827090AC.CDR
5 SETTINGS
GE Multilin
5 SETTINGS 5.7 CONTROL ELEMENTS
}
FLEXLOGIC OPERAND OR
}
BKR 2 MNL OPEN
1
2
From sheet 2 1&2
1-2
2-1
OR
}
AND
FLEXLOGIC OPERAND
BREAKER 1 MNL CLS
OR
AND
FLEXLOGIC OPERAND
BREAKER 2 MNL CLS
FLEXLOGIC OPERAND
AND
BREAKER 1 CLOSED
FLEXLOGIC OPERAND
AND
BREAKER 2 CLOSED
AND
BKR CLOSED
5
OR (To sheet 1 and 2)
OR
From
Breaker Control
scheme
AND
AND
FLEXLOGIC OPERAND
AND
BREAKER 1 OPEN
OR
FLEXLOGIC OPERAND
AND
BREAKER 2 OPEN
OR BKR 3 POLE OPEN
(To sheet 1)
OR
FLEXLOGIC OPERAND AND
BUS-FLT INIT
OR AND
OFF = 0
AND
AND
FLEXLOGIC OPERAND
AND
BREAKER 1 ONE P OPEN
OR
FLEXLOGIC OPERAND
AND
BREAKER 2 ONE P OPEN
OR
OR
AND
OR
AND
827833AA.CDR
5-260
1ST SHOT 2ND SHOT
F R
A T PROT E
T
U R T TRIP BKR S
L I T PROT RESET E
T P T
5.7 CONTROL ELEMENTS
PREFAULT
AR 1P INIT
AR RIP
1-P DEAD TIME
AR 1-P RIP
1.25 cycle
AR FORCE 3P TRIP
CLOSE
AR CLOSE BKR1
T CLOSE BKR1 T CLOSE BKR1
AR RESET TIME
RESET TIME
BREAKER 1 CLOSED
T TRIP BKR T PROT RESET
T PROT
AR 3P INIT
3-P/2 DEAD TIME
BREAKER 2 CLOSED
AR TRANSFER TIME
GE Multilin
5 SETTINGS 5.8 INPUTS/OUTPUTS
CONTACT INPUTS
CONTACT INPUT
THRESHOLDS
The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each group
of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules) which
contact inputs are available and then display settings for only those inputs.
An alphanumeric ID may be assigned to a contact input for diagnostic, setting, and event recording purposes. The CON-
TACT IP X On” (Logic 1) FlexLogic™ operand corresponds to contact input “X” being closed, while CONTACT IP X Off corre-
sponds to contact input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to
overcome ‘contact bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a maxi-
mum contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT
INPUT EVENTS is set to “Enabled”, every change in the contact input state will trigger an event.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the figure below.
The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-
settable debounce time in order for the L90 to validate the new contact state. In the figure below, the debounce time is set
at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated (de-
bounced), the contact input asserts a corresponding FlexLogic™ operand and logs an event as per user setting.
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the con-
tact input into the Event Recorder (mark no. 2 in the diagram).
Protection and control elements, as well as FlexLogic™ equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic™ operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the fig-
ure below). The update is performed at the beginning of the protection pass so all protection and control functions, as well
as FlexLogic™ equations, are fed with the updated states of the contact inputs.
The FlexLogic™ operand response time to the contact input change is equal to the debounce time setting plus up to one
protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs
just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration of
the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically a
delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is
below 1msec.
For example, 8 protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a con-
tact debounce time setting of 3.0 ms, the FlexLogic™ operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 μs accuracy using the
time of the first scan corresponding to the new state (mark no. 2 below). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the debounce
timer. Keep in mind that the associated FlexLogic™ operand is asserted/de-asserted later, after validating the change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure below) and HIGH-LOW (marks no. 5, 6, 7, and 8 below) transitions.
VOLTAGE
INPUT
USER-PROGRAMMABLE THRESHOLD
6
2 1 3 5
Time stamp of the first
TM
Time stamp of the first At this time, the The FlexLogic
5
scan corresponding to the
At this time, the new
scan corresponding to new (HIGH) operand is going to new validated state is
(LOW) contact state is
the new validated state is contact state is be asserted at this logged in the SOE record
validated
logged in the SOE record validated protection pass
7
RAW CONTACT
The FlexLogicTM
operand is going to be
STATE
de-asserted at this
protection pass
DEBOUNCE TIME
(user setting)
4
The FlexLogicTM operand
DEBOUNCE TIME
The FlexLogicTM operand changes reflecting the
SCAN TIME (user setting)
changes reflecting the validated contact state
FLEXLOGICTM
PROTECTION PASS
(8 times a cycle controlled by the
frequency tracking mechanism)
842709A1.cdr
Figure 5–142: INPUT CONTACT DEBOUNCING MECHANISM AND TIME-STAMPING SAMPLE TIMING
Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value should be selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V
sources and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it in
the Event Records menu, make the following settings changes:
CONTACT INPUT H5A ID: "Breaker Closed (52b)"
CONTACT INPUT H5A EVENTS: "Enabled"
Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the COM-
MANDS menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the appropri-
ate input signal is received.
If the VIRTUAL INPUT x FUNCTION is to “Disabled”, the input will be forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled”, the input operates as shown on the logic diagram and generates output FlexLogic™ operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x TYPE is “Self-Reset”, when the input signal tran-
sits from off to on, the output operand will be set to on for only one evaluation of the FlexLogic™ equations and then return
to off. If set to “Latched”, the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic™ 5
equations. If the operand is to be used anywhere other than internally in a FlexLogic™ equation, it will
NOTE
likely have to be lengthened in time. A FlexLogic™ timer with a delayed reset can perform this function.
SETTING
VIRTUAL INPUT 1
FUNCTION:
Disabled=0
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND
Self - Reset 827080A2.CDR
a) DIGITAL OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö CONTACT OUTPUT H1
Upon startup of the relay, the main processor will determine from an assessment of the modules installed in the chassis
which contact outputs are available and present the settings for only these outputs.
An ID may be assigned to each contact output. The signal that can OPERATE a contact output may be any FlexLogic™
operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic™ operand may be used to
SEAL-IN the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A con-
tacts (see the trip circuit example in the Digital elements section). The monitor will set a flag (see the specifications for
Form-A). The name of the FlexLogic™ operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, CONT OP 1 ION.
5 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect oper-
ation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in the
trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the tripping
circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized in the L90 using the CONT OP 1 ION FlexLogic™ operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic™ operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”
b) LATCHING OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö CONTACT OUTPUT H1a
The L90 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop-
ulates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic™).
The latching output modules, either as a part of the relay or as individual modules, are shipped from the factory with all
latching contacts opened. It is highly recommended to double-check the programming and positions of the latching con-
tacts when replacing a module.
Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring capabili-
ties for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test error is
declared. The error is signaled by the LATCHING OUT ERROR FlexLogic™ operand, event, and target message.
• OUTPUT H1a OPERATE: This setting specifies a FlexLogic™ operand to operate the ‘close coil’ of the contact. The
relay will seal-in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off),
any activity of the OPERATE input, such as subsequent chattering, will not have any effect. With both the OPERATE and
RESET inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.
• OUTPUT H1a RESET: This setting specifies a FlexLogic™ operand to operate the ‘trip coil’ of the contact. The relay
will seal-in this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any
activity of the RESET input, such as subsequent chattering, will not have any effect. With both the OPERATE and RESET
inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.
• OUTPUT H1a TYPE: This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact will close if set to
“Operate-dominant” and will open if set to “Reset-dominant”.
Application Example 1:
A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The 5
following settings should be applied.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a menu (assuming an H4L module):
Program the pushbuttons by making the following changes in the PRODUCT SETUP ÖØ USER-PROGRAMMABLE PUSHBUT-
TONS ÖØ USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:
Application Example 2:
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
Since the two physical contacts in this example are mechanically separated and have individual control inputs, they will not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time may occur. There-
fore, a pair of contacts programmed to be a multi-contact relay will not guarantee any specific sequence of operation (such
as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the con-
trol inputs as shown in the next application example.
Application Example 3:
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
this functionality as described below:
Both timers (Timer 1 and Timer 2) should be set to 20 ms pickup and 0 ms dropout.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1” OUTPUT H1c OPERATE: “VO2”
OUTPUT H1a RESET: “VO4” OUTPUT H1c RESET: “VO3”
Application Example 4:
A latching contact H1a is to be controlled from a single virtual output VO1. The contact should stay closed as long as VO1
is high, and should stay opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic™ equation (EnerVista UR Setup example shown):
5
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
There are 96 virtual outputs that may be assigned via FlexLogic™. If not assigned, the output will be forced to ‘OFF’ (Logic
0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings
would be programmed as follows:
The sharing of digital point state information between GSSE/GOOSE equipped relays is essentially an extension to Flex-
Logic™, allowing distributed FlexLogic™ by making operands available to/from devices on a common communications net-
work. In addition to digital point states, GSSE/GOOSE messages identify the originator of the message and provide other
information required by the communication specification. All devices listen to network messages and capture data only from
messages that have originated in selected devices.
IEC 61850 GSSE messages are compatible with UCA GOOSE messages and contain a fixed set of digital points. IEC
61850 GOOSE messages can, in general, contain any configurable data items. When used by the remote input/output fea-
ture, IEC 61850 GOOSE messages contain the same data as GSSE messages.
Both GSSE and GOOSE messages are designed to be short, reliable, and high priority. GOOSE messages have additional
advantages over GSSE messages due to their support of VLAN (virtual LAN) and Ethernet priority tagging functionality.
The GSSE message structure contains space for 128 bit pairs representing digital point state information. The IEC 61850
specification provides 32 “DNA” bit pairs that represent the state of two pre-defined events and 30 user-defined events. All
remaining bit pairs are “UserSt” bit pairs, which are status bits representing user-definable events. The L90 implementation 5
provides 32 of the 96 available UserSt bit pairs.
The IEC 61850 specification includes features that are used to cope with the loss of communication between transmitting
and receiving devices. Each transmitting device will send a GSSE/GOOSE message upon a successful power-up, when
the state of any included point changes, or after a specified interval (the default update time) if a change-of-state has not
occurred. The transmitting device also sends a ‘hold time’ which is set greater than three times the programmed default
time required by the receiving device.
Receiving devices are constantly monitoring the communications network for messages they require, as recognized by the
identification of the originating device carried in the message. Messages received from remote devices include the mes-
sage time allowed to live. The receiving relay sets a timer assigned to the originating device to this time interval, and if it
has not received another message from this device at time-out, the remote device is declared to be non-communicating, so
it will use the programmed default state for all points from that specific remote device. If a message is received from a
remote device before the time allowed to live expires, all points for that device are updated to the states contained in the
message and the hold timer is restarted. The status of a remote device, where “Offline” indicates non-communicating, can
be displayed.
The remote input/output facility provides for 32 remote inputs and 64 remote outputs.
The L90 provides an additional method of sharing digital point state information among different relays: direct messages.
Direct messages are only used between UR-series relays inter-connected via dedicated type 7X communications modules,
usually between substations. The digital state data conveyed by direct messages are direct inputs and direct outputs.
b) DIRECT MESSAGES
Direct messages are only used between UR-series relays containing the type 7X UR communications module. These mes-
sages are transmitted every one-half of the power frequency cycle (10 ms for 50 Hz and 8.33 ms for 60 Hz) This facility is
of particular value for pilot schemes and transfer tripping. Direct messaging is available on both single channel and dual
channel communications modules. The inputs and outputs on communications channel 1 are numbered 1-1 through 1-8,
and the inputs and outputs on communications channel 2 are numbered 2-1 through 2-8.
Settings associated with direct messages are automatically presented in accordance with the number of
channels provided in the communications module in a specific relay.
NOTE
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE
CONFIGURATION Ö TRANSMISSION ÖØ GSSE ÖØ GSSE ID setting.
In L90 releases previous to 5.0x, these name strings were represented by the RELAY NAME setting.
Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
The REMOTE DEVICE 1 ETYPE APPID setting is only used with GOOSE messages; they are not applicable to GSSE mes-
5 sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The REMOTE DEVICE 1 DATASET setting provides for the choice of the L90 fixed (DNA/UserSt) dataset (that is, containing
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic™
operands. However, GGIO3 data can be read by IEC 61850 clients.
Remote Inputs that create FlexLogic™ operands at the receiving relay are extracted from GSSE/GOOSE messages origi-
nating in remote devices. Each remote input can be selected from a list consisting of 64 selections: DNA-1 through DNA-32
and UserSt-1 through UserSt-32. The function of DNA inputs is defined in the IEC 61850 specification and is presented in
the IEC 61850 DNA Assignments table in the Remote outputs section. The function of UserSt inputs is defined by the user
selection of the FlexLogic™ operand whose state is represented in the GSSE/GOOSE message. A user must program a
DNA point from the appropriate FlexLogic™ operand.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The REMOTE INPUT 1 ID setting allows the user to assign descriptive text to the remote input. The REMOTE IN 1 DEVICE setting
selects the number (1 to 16) of the remote device which originates the required signal, as previously assigned to the remote
device via the setting REMOTE DEVICE 1(16) ID (see the Remote devices section). The REMOTE IN 1 ITEM setting selects the
specific bits of the GSSE/GOOSE message required.
The REMOTE IN 1 DEFAULT STATE setting selects the logic state for this point if the local relay has just completed startup or
the remote device sending the point is declared to be non-communicating. The following choices are available:
• Setting REMOTE IN 1 DEFAULT STATE to “On” value defaults the input to logic 1.
• Setting REMOTE IN 1 DEFAULT STATE to “Off” value defaults the input to logic 0.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/On” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 1.
When communication resumes, the input becomes fully operational.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/Off” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 0.
When communication resumes, the input becomes fully operational.
For additional information on GSSE/GOOOSE messaging, refer to the Remote devices section in this chap-
ter.
NOTE
Remote double-point status inputs are extracted from GOOSE messages originating in the remote device. Each remote
double point status input must be programmed to replicate the logic state of a specific signal from a specific remote device
for local use. This functionality is accomplished with the five remote double-point status input settings.
• REM DPS IN 1 ID: This setting assigns descriptive text to the remote double-point status input.
• REM DPS IN 1 DEV: This setting selects a remote device ID to indicate the origin of a GOOSE message. The range is
selected from the remote device IDs specified in the Remote devices section.
• REM DPS IN 1 ITEM: This setting specifies the required bits of the GOOSE message.
The configurable GOOSE dataset items must be changed to accept a double-point status item from a GOOSE dataset
(changes are made in the SETTINGS ÖØ COMMUNICATION ÖØ IEC 61850 PROTOCOL ÖØ GSSE/GOOSE CONFIGURATION ÖØ
RECEPTION ÖØ CONFIGURABLE GOOSE Ö CONFIGIGURABLE GOOSE 1(8) Ö CONFIG GSE 1 DATASET ITEMS menus). Dataset
items configured to receive any of “GGIO3.ST.IndPos1.stV” to “GGIO3.ST.IndPos5.stV” will accept double-point status
information that will be decoded by the remote double-point status inputs configured to this dataset item.
The remote double point status is recovered from the received IEC 61850 dataset and is available as through the RemDPS
Ip 1 BAD, RemDPS Ip 1 INTERM, RemDPS Ip 1 OFF, and RemDPS Ip 1 ON FlexLogic™ operands. These operands can then be
used in breaker or disconnect control schemes.
Remote outputs (1 to 32) are FlexLogic™ operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic™ oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of
state of any selected digital point. This setting is located in the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTO-
COL ÖØ GSSE/GOOSE CONFIGURATION settings menu.
For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the
Remote Devices section.
NOTE
5.8.9 DIRECT INPUTS/OUTPUTS
a) DESCRIPTION
The relay provides eight direct inputs conveyed on communications channel 1 (numbered 1-1 through 1-8) and eight direct
inputs conveyed on communications channel 2 (on three-terminal systems only, numbered 2-1 through 2-8). The user must
program the remote relay connected to channels 1 and 2 of the local relay by assigning the desired FlexLogic™ operand to
be sent via the selected communications channel.
This relay allows the user to create distributed protection and control schemes via dedicated communications channels.
Some examples are directional comparison pilot schemes and transfer tripping. It should be noted that failures of communi-
cations channels will affect direct input/output functionality. The 87L function must be enabled to utilize the direct inputs.
Direct input and output FlexLogic™ operands to be used at the local relay are assigned as follows:
• Direct input/output 1-1 through direct input/output 1-8 for communications channel 1.
• Direct input/output 2-1 through direct input/output 2-8 for communications channel 2 (three-terminal systems only).
On the two-terminal, two channel system (redundant channel), direct outputs 1-1 to 1-8 are send over both chan-
nels simultaneously and are received separately as direct inputs 1-1 to 1-8 at channel 1 and direct inputs 2-1 to 2-8
NOTE at channel 2. Therefore, to take advantage of redundancy, the respective operands from channel 1 and 2 can be
ORed with FlexLogic™ or mapped separately.
b) DIRECT INPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ DIRECT Ö DIRECT INPUTS
c) DIRECT OUTPUTS
PATH: SETTINGS Ø INPUTS/OUTPUTS ÖØ DIRECT ÖØ DIRECT OUTPUTS
The relay provides eight direct outputs that are conveyed on communications channel 1 (numbered 1-1 through 1-8) and
eight direct outputs that are conveyed on communications channel 2 (numbered 2-1 through 2-8). Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific function (as selected by the user) to be transmitted.
NOTE
L90-1 L90-2
ACTUAL VALUES SETTING
CHANNEL 1 STATUS: DIRECT INPUT 1-1
DEFAULT:
(same for 1-2...1-8)
SETTING
DIRECT OUTPUT 1-1:
On FLEXLOGIC OPERAND
(same for 1-2...1-8) Fail
Off DIRECT I/P 1-1
Off (Flexlogic Operand) OK OR
(same for 1-2...1-8)
831024A1.CDR
5.8.10 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic™ latches) to the reset
state. The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel,
or any programmed operand.
When the RESET command is received by the relay, two FlexLogic™ operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the RESET OP FlexLogic™ operand. Each individual source of a RESET command also creates its individual operand
RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The setting
shown above selects the operand that will create the RESET OP (OPERAND) operand.
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE ANALOGS ÖØ GOOSE ANALOG INPUT 1(16)
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
• ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the ANALOG 1 DEFAULT MODE is set to “Default Value”.This setting is stored as an IEEE 754 / IEC 60559 floating
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
• ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE analog input is defined by the ANALOG 1 DEFAULT setting.
• GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
• GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log™ values in other L90 features, such as FlexElements™. The base factor is applied to the GOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
5 SYNCHROCHECK
(Max Delta Volts)
VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs
The GOOSE analog input FlexAnalog™ values are available for use in other L90 functions that use FlexAnalog™ values.
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE UINTEGERS ÖØ GOOSE UINTEGER INPUT 1(16)
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR-
series devices. The following settings are available for each GOOSE uinteger input.
• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integer
number.
• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.
The GOOSE integer input FlexInteger™ values are available for use in other L90 functions that use FlexInteger™ values.
Hardware and software is provided to receive signals from external transducers and convert these signals into a digital for-
mat for use as required. The relay will accept inputs in the range of –1 to +20 mA DC, suitable for use with most common
transducer output ranges; all inputs are assumed to be linear over the complete range. Specific hardware details are con-
tained in chapter 3.
Before the dcmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
5
dcmA input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels
with the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5F transducer module installed in slot H.
The function of the channel may be either “Enabled” or “Disabled”. If “Disabled”, no actual values are created for the chan-
nel. An alphanumeric “ID” is assigned to each channel; this ID will be included in the channel actual value, along with the
programmed units associated with the parameter measured by the transducer, such as volts, °C, megawatts, etc. This ID is
also used to reference the channel as the input parameter to features designed to measure this type of parameter. The
DCMA INPUT H1 RANGE setting specifies the mA DC range of the transducer connected to the input channel.
The DCMA INPUT H1 MIN VALUE and DCMA INPUT H1 MAX VALUE settings are used to program the span of the transducer in
primary units. For example, a temperature transducer might have a span from 0 to 250°C; in this case the DCMA INPUT H1
MIN VALUE value is “0” and the DCMA INPUT H1 MAX VALUE value is “250”. Another example would be a watts transducer with
a span from –20 to +180 MW; in this case the DCMA INPUT H1 MIN VALUE value would be “–20” and the DCMA INPUT H1 MAX
VALUE value “180”. Intermediate values between the min and max values are scaled linearly.
Hardware and software is provided to receive signals from external resistance temperature detectors and convert these
signals into a digital format for use as required. These channels are intended to be connected to any of the RTD types in
common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5C transducer module installed in the first available slot.
The function of the channel may be either “Enabled” or “Disabled”. If “Disabled”, there will not be an actual value created for
5 the channel. An alphanumeric ID is assigned to the channel; this ID will be included in the channel actual values. It is also
used to reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the
type of RTD connected to the channel configures the channel.
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements™ feature.
In FlexElements™, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting
the operate level at 1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an
output contact directly.
Refer to the following table for reference temperature values for each RTD type.
DCMA OUTPUT H1 DCMA OUTPUT H1 Range: Off, any analog actual value parameter
SOURCE: Off
DCMA OUTPUT H1 Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
MESSAGE
RANGE: –1 to 1 mA
DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
MIN VAL: 0.000 pu
DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
MAX VAL: 1.000 pu
Hardware and software is provided to generate dcmA signals that allow interfacing with external equipment. Specific hard-
ware details are contained in chapter 3. The dcmA output channels are arranged in a manner similar to transducer input or
CT and VT channels. The user configures individual channels with the settings shown below.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an exam-
ple for channel M5 is shown).
The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
5 scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The follow-
ing equation is applied:
The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, e.g. when MAX VAL – MIN
VAL< 0.1 pu. The resulting characteristic is illustrated in the following figure.
Imax
OUTPUT CURRENT
Imin
DRIVING SIGNAL
MIN VAL MAX VAL 842739A1.CDR
The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
P BASE = 115 V × 120 × 1.2 kA = 16.56 MW (EQ 5.31)
The minimum and maximum power values to be monitored (in pu) are:
20.65 MW = – 1.247 pu, maximum power = 20.65 MW- = 1.247 pu
minimum power = –------------------------------ -------------------------- (EQ 5.32)
16.56 MW 16.56 MW
The following settings should be entered:
DCMA OUTPUT H1 SOURCE: “SRC 1 P”
DCMA OUTPUT H1 RANGE: “–1 to 1 mA”
DCMA OUTPUT H1 MIN VAL: “–1.247 pu”
DCMA OUTPUT H1 MAX VAL: “1.247 pu”
With the above settings, the output will represent the power with the scale of 1 mA per 20.65 MW. The worst-case error for
this application can be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 1 – ( – 1 ) ) × 20.65 MW = ± 0.207 MW
• ±1% of reading error for the active power at power factor of 0.9
For example at the reading of 20 MW, the worst-case error is 0.01 × 20 MW + 0.207 MW = 0.407 MW.
EXAMPLE: CURRENT MONITORING
The phase A current (true RMS value) is to be monitored via the H2 current output working with the range from 4 to 20 mA.
The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow-
ing for 50% overload.
The phase current with the 50% overload margin is:
The base unit for current (refer to the FlexElements section in this chapter for additional details) is:
I BASE = 5 kA (EQ 5.34)
The minimum and maximum power values to be monitored (in pu) are:
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 20 – 4 ) × 6.3 kA = ± 0.504 kA
• ±0.25% of reading or ±0.1% of rated (whichever is greater) for currents between 0.1 and 2.0 of nominal
For example, at the reading of 4.2 kA, the worst-case error is max(0.0025 × 4.2 kA, 0.001 × 5 kA) + 0.504 kA = 0.515 kA.
EXAMPLE: VOLTAGE MONITORING
A positive-sequence voltage on a 400 kV system measured via source 2 is to be monitored by the dcmA H3 output with a
range of 0 to 1 mA. The VT secondary setting is 66.4 V, the VT ratio setting is 6024, and the VT connection setting is
“Delta”. The voltage should be monitored in the range from 70% to 110% of nominal.
5 The minimum and maximum positive-sequence voltages to be monitored are:
400 kV 400 kV
V min = 0.7 × ------------------- = 161.66 kV, V max = 1.1 × ------------------- = 254.03 kV (EQ 5.36)
3 3
The base unit for voltage (refer to the FlexElements section in this chapter for additional details) is:
V BASE = 0.0664 kV × 6024 = 400 kV (EQ 5.37)
The minimum and maximum voltage values to be monitored (in pu) are:
minimum voltage = 161.66 kV- = 0.404 pu, maximum voltage = 254.03 kV- = 0.635 pu
-------------------------- -------------------------- (EQ 5.38)
400 kV 400 kV
The following settings should be entered:
DCMA OUTPUT H3 SOURCE: “SRC 2 V_1 mag”
DCMA OUTPUT H3 RANGE: “0 to 1 mA”
DCMA OUTPUT H3 MIN VAL: “0.404 pu”
DCMA OUTPUT H3 MAX VAL: “0.635 pu”
The limit settings differ from the expected 0.7 pu and 1.1 pu because the relay calculates the positive-sequence quantities
scaled to the phase-to-ground voltages, even if the VTs are connected in “Delta” (refer to the Metering conventions section
in chapter 6), while at the same time the VT nominal voltage is 1 pu for the settings. Consequently the settings required in
this example differ from naturally expected by the factor of 3 .
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 1 – 0 ) × 254.03 kV = ± 1.27 kV
• ±0.5% of reading
For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is
0.005 x 230.94 kV + 1.27 kV = 2.42 kV.
The L90 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and
the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face-
plate by a Test Mode LED indicator.
The test mode may be in any of three states: disabled, isolated, or forcible.
In the “Disabled” mode, L90 operation is normal and all test features are disabled.
In the “Isolated” mode, the L90 is prevented from performing certain control actions, including tripping via contact outputs.
All relay contact outputs, including latching outputs, are disabled. Channel tests and phasor measurement unit tests remain
usable on applicable UR-series models.
In the “Forcible” mode, the operand selected by the TEST MODE FORCING setting controls the relay inputs and outputs. If the
test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “Off”, the L90 inputs and outputs oper-
ate normally. If the test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “On”, the L90 con-
tact inputs and outputs are forced to the values specified in the following sections. Forcing may be controlled by manually
changing the operand selected by the TEST MODE FORCING setting between on and off, or by selecting a user-programma-
ble pushbutton, contact input, or communication-based input operand. Channel tests and phasor measurement unit tests
remain usable on applicable UR-series models.
5
Communications based inputs and outputs remain fully operational in test mode. If a control action is programmed
using direct inputs and outputs or remote inputs and outputs, then the test procedure must take this into account.
NOTE
When in “Forcible” mode, the operand selected by the TEST MODE FORCING setting dictates further response of the L90 to
testing conditions. To force contact inputs and outputs through relay settings, set TEST MODE FORCING to “On”. To force con-
tact inputs and outputs through a user-programmable condition, such as FlexLogic™ operand (pushbutton, digital input,
communication-based input, or a combination of these), set TEST MODE FORCING to the desired operand. The contact input
or output is forced when the selected operand assumes a logic 1 state.
The L90 remains fully operational in test mode, allowing for various testing procedures. In particular, the protection and
control elements, FlexLogic™, and communication-based inputs and outputs function normally.
The only difference between the normal operation and the test mode is the behavior of the input and output contacts. The
contact inputs can be forced to report as open or closed or remain fully operational, whereas the contact outputs can be
forced to open, close, freeze, or remain fully operational. The response of the digital input and output contacts to the test
mode is programmed individually for each input and output using the force contact inputs and force contact outputs test
functions described in the following sections.
The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED
indicator, and by the critical fail relay, as shown in the following table.
The TEST MODE FUNCTION setting can only be changed by a direct user command. Following a restart, power up, settings
upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a L90 that has been
placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING
setting and the force contact input and force contact output settings all revert to their default states.
5 FORCE CONTACT
INPUTS
FORCE Cont Ip 1
:Disabled
Range: Disabled, Open, Closed
The relay digital inputs (contact inputs) could be pre-programmed to respond to the test mode in the following ways:
• If set to “Disabled”, the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. This value should be selected if a given input must be operational during the
test. This includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open”, the input is forced to report as opened (Logic 0) for the entire duration of the test mode regardless of
the voltage across the input terminals.
• If set to “Closed”, the input is forced to report as closed (Logic 1) for the entire duration of the test mode regardless of
the voltage across the input terminals.
The force contact inputs feature provides a method of performing checks on the function of all contact inputs. Once
enabled, the relay is placed into test mode, allowing this feature to override the normal function of contact inputs. The Test
Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis-
abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled.
The relay contact outputs can be pre-programmed to respond to the test mode.
If set to “Disabled”, the contact output remains fully operational. If operates when its control operand is logic 1 and will
resets when its control operand is logic 0. If set to “Energized”, the output will close and remain closed for the entire dura-
tion of the test mode, regardless of the status of the operand configured to control the output contact. If set to “De-ener-
gized”, the output will open and remain opened for the entire duration of the test mode regardless of the status of the
operand configured to control the output contact. If set to “Freeze”, the output retains its position from before entering the
test mode, regardless of the status of the operand configured to control the output contact.
These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Sec-
ond, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided.
Example 1: Initiating test mode through user-programmable pushbutton 1
For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as
“Latched” (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, digital input 1
5
should remain operational, digital inputs 2 and 3 should open, and digital input 4 should close. Also, contact output 1 should
freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully operational.
The required settings are shown below.
To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the SETTINGS ÖØ
TESTING Ö TEST MODE menu: TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “PUSHBUTTON 1 ON”
Make the following changes to configure the contact inputs and outputs. In the SETTINGS ÖØ TESTING ÖØ FORCE CONTACT
INPUTS and FORCE CONTACT OUTPUTS menus, set:
FORCE Cont Ip 1: “Disabled”, FORCE Cont Ip 2: “Open”, FORCE Cont Ip 3: “Open”, and FORCE Cont Ip 4: “Closed”
FORCE Cont Op 1: “Freeze”, FORCE Cont Op 2: “De-energized”, FORCE Cont Op 3: “Energized”,
and FORCE Cont Op 4: “Disabled”
Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1
In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1.
Both the pushbutton and the remote input will be programmed as “Latched”. Write the following FlexLogic™ equation:
Set the user-programmable pushbutton as latching by changing SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE
PUSHBUTTONS Ö USER PUSHBUTTON 1 Ö PUSHBUTTON 1 FUNCTION to “Latched”. To enable either pushbutton 1 or remote
input 1 to initiate the Test mode, make the following changes in the SETTINGS ÖØ TESTING Ö TEST MODE menu:
TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “VO1”
Refer to the Commissioning chapter for a detailed description of using the channel tests.
The relay must be in test mode to use the PMU test mode. That is, the TESTING Ö TEST MODE FUNCTION setting must be
“Enabled” and the TESTING ÖØ TEST MODE INITIATE initiating signal must be “On”.
During the PMU test mode, the physical channels (VA, VB, VC, VX, IA, IB, IC, and IG), frequency, and rate of change of fre-
quency are substituted with user values, while the symmetrical components are calculated from the physical channels. The
test values are not explicitly marked in the outgoing data frames. When required, it is recommended to use the user-pro- 5
grammable digital channels to signal the C37.118 client that test values are being sent in place of the real measurements.
SOURCE SRC 4
SYNCHROCHECK
See page 6-19.
TRACKING FREQUENCY
See page 6-19.
FLEXELEMENTS
See page 6-19.
IEC 61850
See page 6-20.
GOOSE ANALOGS
WATTMETRIC
See page 6-20.
GROUND FAULT 1
WATTMETRIC
See page 6-20.
GROUND FAULT 2
PHASOR MEASUREMENT
See page 6-20.
UNIT
TRANSDUCER I/O
See page 6-21.
DCMA INPUTS
TRANSDUCER I/O
See page 6-21.
RTD INPUTS
6.2STATUS
For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.
NOTE
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.
REMOTE DPS INPUTS REMOTE DPS INPUT 1 Range: On, Off, Intermediate, Bad
STATUS: Bad
REMOTE DPS INPUT 2 Range: On, Off, Intermediate, Bad
MESSAGE
STATUS: Bad
↓
The present state of the remote double-point status inputs is shown here. The actual values indicate if the remote double-
point status inputs are in the on (close), off (open), intermediate, or bad state.
The present state of the direct inputs from communications channels 1 and 2 are shown here. The state displayed will be
that of the remote point unless channel 1 or 2 has been declared to have “failed”, in which case the value shown is the pro-
grammed default state defined in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ DIRECT Ö DIRECT INPUTS menu.
CONTACT OUTPUTS Cont Op 1 Range: On, Off, VOff, VOn, IOn, IOff
Off
Cont Op 2 Range: On, Off, VOff, VOn, IOn, IOff
MESSAGE
Off
↓
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff,
On, IOn, and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output.
6.2.8 AUTORECLOSE
a) STATUS
PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATUS
The present state of up to 16 programmed remote devices is shown here. The ALL REMOTE DEVICES ONLINE message indi-
cates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one
required remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATISTICS Ö REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
The status information for two channels is shown here. A brief description of each actual value is below:
• CHANNEL 1(2) STATUS: This represents the receiver status of each channel. If the value is “OK”, the 87L current dif-
ferential element is enabled and data is being received from the remote terminal; If the value is “FAIL”, the 87L element
is enabled and data is not being received from the remote terminal. If “n/a”, the 87L element is disabled.
• CHANNEL 1(2) LOST PACKETS: Current, timing, and control data is transmitted to the remote terminals in data pack-
ets at a rate of two packets per cycle. The number of lost packets represents data packets lost in transmission; this
count can be reset through the COMMANDS ÖØ CLEAR RECORDS menu.
• CHANNEL 1(2) LOCAL LOOPBACK STATUS: The result of the local loopback test is displayed here.
• CHANNEL 1(2) REMOTE LOOPBACK STATUS: The result of the remote loopback test is displayed here.
• CHANNEL 1(2) LOOP DELAY: Displays the round trip channel delay (including loopback processing time of the
remote relay) computed during a remote loopback test under normal relay operation, in milliseconds (ms).
• CHANNEL 1(2) ASYMMETRY: The result of channel asymmetry calculations derived from GPS signal is being dis-
played here for both channels if CHANNEL ASYMMETRY is “Enabled”. A positive “+” sign indicates the transit delay in the
transmitting direction is less than the delay in the receiving direction; a negative “–” sign indicates the transit delay in
the transmitting direction is more than the delay in the receiving direction. A displayed value of “0.0” indicates that
either asymmetry is not present or can not be estimated due to failure with local/remote GPS clock source.
• VALIDITY OF CHANNEL CONFIGURATION: The current state of the communications channel identification check,
and hence validity, is displayed here. If a remote relay ID number does not match the programmed number at the local
relay, the “FAIL” value is displayed. The “n/a” value appears if the local relay ID is set to a default value of “0” or if the
87L element is disabled. Refer to SETTINGS ÖØ SYSTEM SETUP ÖØ L90 POWER SYSTEM section for more information
• PFLL STATUS: This value represents the status of the phase and frequency locked loop (PFLL) filter which uses tim-
ing information from local and remote terminals to synchronize the clocks of all terminals. If PFLL STATUS is “OK”, the
clocks of all terminals are synchronized and 87L protection is enabled. If it is “FAIL”, the clocks of all terminals are not
synchronized and 87L protection is disabled. If “n/a”, then PFLL is disabled.
At startup, the clocks of all terminals are not synchronized and the PFLL status displayed is “FAIL”. It takes
up to 8 seconds after startup for the value displayed to change from “FAIL” to “OK”.
NOTE
PATH: ACTUAL VALUES Ö STATUS ÖØ DIGITAL COUNTERS Ö DIGITAL COUNTERS Counter 1(8) 6
DIGITAL COUNTERS Counter 1 ACCUM:
Counter 1 0
Counter 1 FROZEN:
MESSAGE
0
Counter 1 FROZEN:
MESSAGE
YYYY/MM/DD HH:MM:SS
Counter 1 MICROS:
MESSAGE
0
The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit.
6.2.14 ETHERNET
These values indicate the status of the primary and secondary Ethernet links.
UINT INPUT 16
MESSAGE
0
The L90 Line Current Differential System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
These actual values appear only if the L90 is ordered with an Ethernet switch module (type 2S or 2T). The status informa-
tion for the Ethernet switch is shown in this menu.
• SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on
the Ethernet switch. If the value is “OK”, then data is being received from the remote terminal; If the value is “FAIL”,
then data is not being received from the remote terminal or the port is not connected.
• SWITCH MAC ADDRESS: This value displays the MAC address assigned to the Ethernet switch module.
Voltage +Q
VCG
WATTS = Positive IC
PF = Lead PF = Lag
VARS = Positive
PF = Lag IA
VAG -P +P
Current
IB IA
PF = Lag PF = Lead
UR RELAY
VBG -Q
M LOAD
- 1
Inductive Resistive S=VI
Generator
VCG
+Q
Voltage
PF = Lead PF = Lag
WATTS = Positive
IA
VARS = Negative IC
PF = Lead VAG -P +P
IA
Current
PF = Lag PF = Lead
IB
UR RELAY
VBG -Q
LOAD S=VI
6 Inductive
Resistive
Resistive
- 2
M LOAD
VCG +Q
Voltage
PF = Lead PF = Lag
IB
IA
WATTS = Negative
VAG
VARS = Negative -P +P
PF = Lag
IA
IC PF = Lag PF = Lead
Current
VBG
-Q
UR RELAY
G S=VI
- 3
Generator
Resistive
LOAD
VCG
+Q
Voltage IB
PF = Lead PF = Lag
WATTS = Negative IA
VARS = Positive VAG -P +P
PF = Lead
IC
IA
Current
PF = Lag PF = Lead
VBG -Q
UR RELAY
G 827239AC.CDR
- 4
S=VI
Generator
Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS
-270o
-225o -315o
positive
angle
direction
-180o 0o
UR phase angle
reference
-135o -45o
-90o 827845A1.CDR
6
Figure 6–2: UR PHASE ANGLE MEASUREMENT CONVENTION
The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
Table 6–1: SYMMETRICAL COMPONENTS CALCULATION EXAMPLE
SYSTEM VOLTAGES, SEC. V * VT RELAY INPUTS, SEC. V SYMM. COMP, SEC. V
CONN.
VAG VBG VCG VAB VBC VCA F5AC F6AC F7AC V0 V1 V2
13.9 76.2 79.7 84.9 138.3 85.4 WYE 13.9 76.2 79.7 19.5 56.5 23.3
∠0° ∠–125° ∠–250° ∠–313° ∠–97° ∠–241° ∠0° ∠–125° ∠–250° ∠–192° ∠–7° ∠–187°
UNKNOWN (only V1 and V2 84.9 138.3 85.4 DELTA 84.9 138.3 85.4 N/A 56.5 23.3
can be determined) ∠0° ∠–144° ∠–288° ∠0° ∠–144° ∠–288° ∠–54° ∠–234°
* The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a
relative matter. It is important to remember that the L90 displays are always referenced as specified under SETTINGS
ÖØ SYSTEM SETUP ÖØ POWER SYSTEM ÖØ FREQUENCY AND PHASE REFERENCE.
The example above is illustrated in the following figure.
6
reference
1
UR phase angle
A
reference
WYE VTs
C
B
0
2
U
re R ph
fe a
re se
nc a
e ng
le
A U
1
re R ph
fe a
re se
nc a
e ng
DELTA VTs le
C
B
2
827844A1.CDR
The metered current values are displayed for all line terminals in fundamental phasor form. All angles are shown with
respect to the reference common for all L90 devices; that is, frequency, source currents, and voltages. The metered pri-
mary differential and restraint currents are displayed for the local relay.
Terminal 1 refers to the communication channel 1 interface to a remote L90 at terminal 1. Terminal 2 refers
to the communication channel 2 interface to a remote L90 at terminal 2.
NOTE
6.3.3 SOURCES
a) MAIN MENU
PATH: ACTUAL VALUES ÖØ METERING ÖØ SOURCE SRC1
This menu displays the metered values available for each source.
Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments
for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power val-
ues will be unavailable.
The metered phase current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
The metered ground current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
The metered phase voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
f) POWER METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ POWER
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text will be replaced by whatever name was programmed by the user for the associated source (see SETTINGS ÖØ SYS-
TEM SETUP ÖØ SIGNAL SOURCES).
g) ENERGY METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ ENERGY
The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES). 6
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics.
h) DEMAND METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ DEMAND
The metered values for current and power demand are displayed in this menu. The "SRC 1" text will be replaced by what-
ever name was programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL
SOURCES).
6 The relay measures (absolute values only) the source demand on each phase and average three phase demand for real,
reactive, and apparent power. These parameters can be monitored to reduce supplier demand penalties or for statistical
metering purposes. Demand calculations are based on the measurement type selected in the SETTINGS Ö PRODUCT SETUP
ÖØ DEMAND menu. For each quantity, the relay displays the demand over the most recent demand time interval, the maxi-
mum demand since the last maximum demand reset, and the time and date stamp of this maximum demand value. Maxi-
mum demand quantities can be reset to zero with the CLEAR RECORDS ÖØ CLEAR DEMAND RECORDS command.
i) FREQUENCY METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
SOURCE FREQUENCY is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the SYSTEM SETUP ÖØ POWER SYSTEM settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
If the 87L function is enabled, then dedicated 87L frequency tracking is engaged. In this case, the relay uses the METERING
ÖØ TRACKING FREQUENCY Ö TRACKING FREQUENCY value for all computations, overriding the SOURCE FREQUENCY value.
6.3.4 SYNCHROCHECK
The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-
abled", the corresponding actual values menu item will not be displayed.
The tracking frequency is displayed here. The frequency is tracked based on configuration of the reference source. The
TRACKING FREQUENCY is based upon positive sequence current phasors from all line terminals and is synchronously
adjusted at all terminals. If currents are below 0.125 pu, then the NOMINAL FREQUENCY is used.
6.3.6 FLEXELEMENTS™
FLEXELEMENT 1 FLEXELEMENT 1
OpSig: 0.000 pu
6
The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.
ANALOG INPUT 16
MESSAGE
0.000
The L90 Line Current Differential System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
WATTMETRIC
6 GROUND FAULT 1
WATT GND FLT 1:
0.000 W
This menu displays the wattmetric zero-sequence directional element operating power values.
PMU 1 IA:
MESSAGE
0.0000 kA, 0.00°
PMU 1 IB:
MESSAGE
0.0000 kA, 0.00°
PMU 1 IC:
MESSAGE
0.0000 kA, 0.00°
PMU 1 IG:
MESSAGE
0.0000 kA, 0.00°
PMU 1 I1:
MESSAGE
0.0000 kA, 0.00°
PMU 1 I2:
MESSAGE
0.0000 kA, 0.00°
PMU 1 I0:
MESSAGE
0.0000 kA, 0.00°
PMU 1 FREQUENCY:
MESSAGE
0.0000 Hz
PMU 1 df/dt:
MESSAGE
0.0000 Hz/s
PMU 1 CONFIG CHANGE Range: 0 to 65535
MESSAGE
COUNTER: 0
The above actual values are displayed without the corresponding time stamp as they become available per the recording
rate setting. Also, the recording post-filtering setting is applied to these values.
PATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O DCMA INPUTS Ö DCMA INPUT xx 6
DCMA INPUT xx DCMA INPUT xx
0.000 mA
Actual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
PATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O RTD INPUTS Ö RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and
the bottom line as the value.
NO FAULTS TO REPORT
or
FAULT REPORT 1 FAULT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4
LINE ID: SRC 1
FAULT 1 DATE: Range: YYYY/MM/DD
MESSAGE
2000/08/11
FAULT 1 TIME: Range: HH:MM:SS.ssssss
MESSAGE
00:00:00.000000
FAULT 1 TYPE: Range: not available if the source VTs are in the “Delta”
MESSAGE configuration
ABG
FAULT 1 LOCATION Range: not available if the source VTs are in the “Delta”
MESSAGE configuration
00.0 km
FAULT 1 FAULTED Range: N/A, Local (two-terminal configuration and local
MESSAGE section for three-terminal), Remote 1, Remote 2
SEGMENT: Local
(three-terminal configuration only)
FAULT 1 RECLOSE Range: where applicable
MESSAGE
SHOT: 0
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the SETTINGS Ö PRODUCT
SETUP ÖØ FAULT REPORTS menu for assigning the source and trigger for fault calculations. Refer to the COMMANDS ÖØ
CLEAR RECORDS menu for manual clearing of the fault reports and to the SETTINGS Ö PRODUCT SETUP ÖØ CLEAR RELAY
RECORDS menu for automated clearing of the fault reports.
6 The faulted segment of the line is indicated when the synchronized voltage and currents method is used. When the faulted
segment can be determined, the FAULT 1 FAULTED SEGMENT value displays “N/A”. For three-terminal lines, the fault location
(distance to the fault) is reported as seen from the terminal adjacent to the fault.
EVENT: 3 EVENT 3
MESSAGE
POWER ON DATE: 2000/07/14
EVENT: 2 EVENT 3
MESSAGE
POWER OFF TIME: 14:53:00.03405
EVENT: 1
MESSAGE Date and Time Stamps
EVENTS CLEARED
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. Refer to the COMMANDS Ø CLEAR RECORDS menu for clearing event records.
6.4.3 OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
CYCLES PER RECORD value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. Refer to the COMMANDS ÖØ
CLEAR RECORDS menu for information on clearing the oscillography records.
The number of triggers applicable to the phasor measurement unit recorder is indicated by the NUMBER OF TRIGGERS value.
The status of the phasor measurement unit recorder is indicated as follows:
There is an identical menu for each of the breakers. The BKR 1 ARCING AMP values are in units of kA2-cycles. Refer to the
COMMANDS ÖØ CLEAR RECORDS menu for clearing breaker arcing current records. The BREAKER OPERATING TIME is
defined as the slowest operating time of breaker poles that were initiated to open.
MODEL INFORMATION ORDER CODE LINE 1: Range: standard GE multilin order code format;
L90-E00-HCH-F8F-H6A example order code shown
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed.
COMMANDS
Ø
COMMANDS
MESSAGE
VIRTUAL INPUTS
COMMANDS
MESSAGE
CLEAR RECORDS
COMMANDS
MESSAGE
SET DATE AND TIME
COMMANDS
MESSAGE
RELAY MAINTENANCE
COMMANDS
MESSAGE
PMU ONE-SHOT
The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash mes-
sage appears after successfully command entry:
COMMAND
EXECUTED
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1).
7 This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.
The date and time can be entered here via the faceplate keypad only if the IRIG-B or SNTP signal is not in use. The time
setting is based on the 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com-
mand. The new time will take effect at the moment the ENTER key is clicked.
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
The PERFORM LAMPTEST command turns on all faceplate LEDs and display pixels for a short duration. The UPDATE
ORDER CODE command causes the relay to scan the backplane for the hardware modules and update the order code to
match. If an update occurs, the following message is shown.
UPDATING...
PLEASE WAIT
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message will be shown.
The SERVICE COMMAND is used to perform specific L90 service actions. Presently, there is only one service action available.
Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than “101” is
entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in the
background while the L90 is running, and diagnostic information is stored on the non-volatile memory from time to time
based on the self-checking result. Although the diagnostic information is cleared before the L90 is shipped from the factory,
the user may want to clear the diagnostic information for themselves under certain circumstances. For example, it may be
desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self-
checking variables are reset to their initial state and diagnostics will restart from scratch.
This feature allows pre-scheduling a PMU measurement at a specific point in time. This functionality can be used to test for
accuracy of the PMU, and for manual collection of synchronized measurements through the system, as explained below.
When enabled, the function continuously compares the present time with the pre-set PMU ONE-SHOT TIME. When the two
times match, the function compares the present sequence number of the measured synchrophasors with the pre-set PMU
ONE-SHOT SEQUENCE NUMBER. When the two numbers match, the function freezes the synchrophasor actual values and
the corresponding protocol data items for 30 seconds. This allows manual read-out of the synchrophasor values for the pre-
set time and pre-set sequence number (via the faceplate display, supported communication protocols such as Modbus or
DNP, and the EnerVista UR Setup software).
When freezing the actual values the function also asserts a PMU ONE-SHOT OP FlexLogic™ operand. This operand may be
configured to drive an output contact and trigger an external measuring device such as a digital scope with the intent to ver-
ify the accuracy of the PMU under test.
With reference to the figure below, the PMU one-shot function (when enabled) controls three FlexLogic™ operands:
• The PMU ONE-SHOT EXPIRED operand indicates that the one-shot operation has been executed, and the present time
is at least 30 seconds past the scheduled one-shot time.
• The PMU ONE-SHOT PENDING operand indicates that the one-shot operation is pending; that is, the present time is
before the scheduled one-shot time.
• The PMU ONE-SHOT OP operand indicates the one-shot operation and remains asserted for 30 seconds afterwards.
When the function is disabled, all three operands are de-asserted. The one-shot function applies to all logical PMUs of a
given L90 relay.
7 respect to the timing reference provided to the PMU and not to the absolute UTC time. Therefore a simple IRIG-B genera-
tor could be used instead. Also, the test set does not have to support GPS synchronization. Any stable signal source can
be used. If both the PMU under test and the test set use the timing reference, they should be driven from the same IRIG-B
signal: either the same GPS receiver or IRIG-B generator. Otherwise, the setpoints of the test set and the PMU measure-
ments should not be compared as they are referenced to different time scales.
Figure 7–2: USING THE PMU ONE-SHOT FEATURE TO TEST SYNCHROPHASOR MEASUREMENT ACCURACY
COLLECTING SYNCHRONIZED MEASUREMENTS AD HOC:
The one-shot feature can be used for ad hoc collection of synchronized measurements in the network. Two or more PMU
can be pre-scheduled to freeze their measurements at the same time. When frozen the measurements could be collected
using EnerVista UR Setup or a protocol client.
TARGETS
Ø
DIGITAL ELEMENT 1: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED
DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED
MESSAGE
↓
↓
The status of any active targets will be displayed in the targets menu. If no targets are active, the display will read NO
ACTIVE TARGETS:
When there are no active targets, the first target to become active will cause the display to immediately default to that mes-
sage. If there are active targets and the user is navigating through other messages, and when the default message timer
times out (i.e. the keypad has not been used for a determined period of time), the display will again default back to the tar-
get message.
The range of variables for the target messages is described below. Phase information will be included if applicable. If a tar-
get message status changes, the status with the highest priority will be displayed.
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7
7.2.3 RELAY SELF-TESTS
a) DESCRIPTION
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major and
minor) are listed in the tables below. When either type of self-test error occurs, the Trouble LED Indicator will turn on and a
target message displayed. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
• The critical fail relay on the power supply module is de-energized.
• All other output relays are de-energized and are prevented from further operation.
• The faceplate In Service LED indicator is turned off.
• A RELAY OUT OF SERVICE event is recorded.
MODULE FAILURE___:
Contact Factory (xxx)
INCOMPATIBLE H/W:
Contact Factory (xxx)
• Latched target message: Yes.
• Description of problem: One or more installed hardware modules is not compatible with the L90 order code.
• How often the test is performed: Module dependent.
• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
• Latched target message: No.
• Description of problem: The configuration of modules does not match the order code stored in the L90.
• How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five sec-
onds.
• What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail 7
• Latched target message: No.
• Description of problem: A FlexLogic™ equation is incorrect.
• How often the test is performed: The test is event driven, performed whenever FlexLogic™ equations are modified.
• What to do: Finish all equation editing and use self tests to debug any errors.
MAINTENANCE ALERT:
Replace Battery
MAINTENANCE ALERT:
Direct I/O Ring Break
MAINTENANCE ALERT:
ENET MODULE OFFLINE
MAINTENANCE ALERT:
ENET PORT # OFFLINE
7 • Latched target message: No.
• Description of problem: The Ethernet connection has failed for the specified port.
• How often the test is performed: Every five seconds.
• What to do: Check the Ethernet port connection on the switch.
MAINTENANCE ALERT:
**Bad IRIG-B Signal**
• Latched target message: No.
• Description of problem: A bad IRIG-B input signal has been detected.
• How often the test is performed: Monitored whenever an IRIG-B signal is received.
• What to do: Ensure the following:
– The IRIG-B cable is properly connected.
– Proper cable functionality (that is, check for physical damage or perform a continuity test).
– The IRIG-B receiver is functioning.
– Check the input signal level (it may be less than specification).
MAINTENANCE ALERT:
Port ## Failure
MAINTENANCE ALERT:
SNTP Failure
MAINTENANCE ALERT:
4L Discrepancy
MAINTENANCE ALERT:
GGIO Ind xxx oscill
• How often the test is performed: Event driven. The test is performed when a device programmed to receive GOOSE
messages stops receiving. This can be from 1 to 60 seconds, depending on GOOSE packets.
• What to do: Check GOOSE setup.
TEMP MONITOR:
OVER TEMPERATURE
UNEXPECTED RESTART:
Press “RESET” key
Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level
is not available and intended for factory use only.
The following operations are under command password supervision:
• Operating the breakers via faceplate keypad.
• Changing the state of virtual inputs.
• Clearing the event records.
• Clearing the oscillography records.
• Clearing fault reports.
• Changing the date and time.
• Clearing the breaker arcing current.
• Clearing energy records.
• Clearing the data logger.
• Clearing the user-programmable pushbutton states.
The following operations are under setting password supervision:
• Changing any setting.
• Test mode operation.
The command and setting passwords are defaulted to “0” when the relay is shipped from the factory. When a password is
set to “0”, the password security feature is disabled.
The L90 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the L90, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic™ operands.
• ACCESS LOC SETG OFF: Asserted when local setting access is disabled.
• ACCESS LOC SETG ON: Asserted when local setting access is enabled.
8
• ACCESS LOC CMND OFF: Asserted when local command access is disabled.
• ACCESS LOC CMND ON: Asserted when local command access is enabled.
• ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
• ACCESS REM SETG ON: Asserted when remote setting access is enabled.
• ACCESS REM CMND OFF: Asserted when remote command access is disabled.
• ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
NOTE
CHANGE LOCAL
MESSAGE See page 8–2.
PASSWORDS
ACCESS
MESSAGE See page 8–3.
SUPERVISION
DUAL PERMISSION
MESSAGE See page 8–4.
SECURITY ACCESS
PASSWORD ACCESS Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to “Yes” via the front panel
interface, the following message sequence is invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
8 then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD.
If the setting and command passwords are identical, then this one password allows access to both com-
mands and settings.
NOTE
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.
5. The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.
If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password 8
value.
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
• COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
• SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
DUAL PERMISSION LOCAL SETTING AUTH: Range: selected FlexLogic™ operands (see below)
SECURITY ACCESS On
REMOTE SETTING AUTH: Range: FlexLogic™ operand
MESSAGE
On
8 MESSAGE
ACCESS AUTH Range: 5 to 480 minutes in steps of 1
TIMEOUT: 30 min.
The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic™ operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing
the local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel.
• REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to pro-
viding the remote setting password to gain setting access.
• ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On”. The state of the FlexLogic™ oper-
and is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time-
out is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable
when the Remote Settings Authorization setting is programmed to any operand except “On” or “Off”. The state of the
FlexLogic™ operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is per-
mitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer
expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™
operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.
Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam-
ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows
engineers to configure and test these common settings, then lock them so they are not available to users. For example,
these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate
on the specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers install-
ing the devices. These will be settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings tem-
plates can be applied to both settings files (settings file templates) and online devices (online settings templates). The func-
tionality is identical for both purposes.
The settings template feature requires that both the EnerVista UR Setup software and the L90 firmware are at ver-
sions 5.40 or higher.
NOTE
The software will prompt for a template password. This password is required to use the template feature and must be
at least four characters in length.
8 3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.
By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the
phase time overcurrent settings window in edit mode.
The software will prompt for a template password. This password must be at least four characters in length.
8
Phase time overcurrent window with template applied via
the Template Mode > View In Template Mode command.
The template specifies that only the Pickup and Curve
Phase time overcurrent settings window without template applied.
settings be available.
842858A1.CDR
Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND
Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings tree view is shown below.
Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR
Figure 8–5: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND
Use the following procedure to display settings available for editing and settings locked by the template.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View All Settings option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings
will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
8
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR
Figure 8–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND
4. Verify one more time that you wish to remove the template by clicking Yes.
The EnerVista software will remove all template information and all settings will be available.
The UR allows users to secure parts or all of a FlexLogic™ equation, preventing unauthorized viewing or modification of
critical FlexLogic™ applications. This is accomplished using the settings template feature to lock individual entries within
FlexLogic™ equations.
Secured FlexLogic™ equations will remain secure when files are sent to and retrieved from any UR-series device.
Once the template has been applied, users will only be able to view and edit the FlexLogic™ entries not locked by the tem-
plate. The effect of applying the template to the FlexLogic™ entries in the above procedure is shown below.
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
8
Figure 8–9: SECURED FLEXLOGIC™ IN GRAPHICAL VIEW
A traceability feature for settings files allows the user to quickly determine if the settings in a L90 device have been
changed since the time of installation from a settings file. When a settings file is transfered to a L90 device, the date, time,
and serial number of the L90 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the L90 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the L90
device or obtained from the L90 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
The serial number of the UR-series device and the file transfer
date are added to the settings file when settings files
are transferred to the device.
1. The transfer date of a setting file written to a L90 is logged in the relay and can be viewed via EnerVista UR Setup or
the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
2. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes
have been made to the relay configuration since the settings file was saved.
842863A1.CDR
Traceability data
in settings report
842862A1.CDR
8
Figure 8–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA
842865A1.CDR
The EnerVista security management system is a role-based access control (RBAC) system that allows a security adminis-
trator to easily manage the security privileges of multiple users. This allows for access control of URPlus-series devices by
multiple personnel within a substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The
EnerVista security management system is disabled by default to allow the administrator direct access to the EnerVista soft-
ware after installation. It is recommended that security be enabled before placing the device in service.
The EnerVista security management system is disabled by default. This allows access to the device immediately after
installation. When security is disabled, all users are granted administrator access.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Check the Enable Security box in the lower-left corner to enable the security management system.
Security is now enabled for the EnerVista UR Setup software. It will now be necessary to enter a username and password
upon starting the software.
The following pre-requisites are required to add new users to the EnerVista security management system.
• The user adding the new user must have administrator rights.
• The EnerVista security management system must be enabled.
8
The following procedure describes how to add new users.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Enter a username in the User field. The username must be between 4 and 20 characters in length.
3. Select the user access rights by checking one or more of the fields shown.
The following pre-requisites are required to modify user privileges in the EnerVista security management system.
8 • The user modifying the privileges must have administrator rights.
• The EnerVista security management system must be enabled.
The following procedure describes how to modify user privileges.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Locate the username in the User field.
3. Modify the user access rights by checking or clearing one or more of the fields shown.
All differential techniques rely on the fact that under normal conditions, the sum of the currents entering each phase of a
transmission line from all connected terminals is equal to the charging current for that phase. Beyond the fundamental dif-
ferential principle, the three most important technical considerations are; data consolidation, restraint characteristic, and
sampling synchronization. The L90 uses new and unique concepts in these areas.
Data consolidation refers to the extraction of appropriate parameters to be transmitted from raw samples of transmission
line phase currents. By employing data consolidation, a balance is achieved between transient response and bandwidth
requirements. Consolidation is possible along two dimensions: time and phases. Time consolidation consists of combining
a time sequence of samples to reduce the required bandwidth. Phase consolidation consists of combining information from
three phases and neutral. Although phase consolidation is possible, it is generally not employed in digital schemes,
because it is desired to detect which phase is faulted. The L90 relay transmits data for all three phases.
Time consolidation reduces communications bandwidth requirements. Time consolidation also improves security by elimi-
nating the possibility of falsely interpreting a single corrupted data sample as a fault.
The L90 relay system uses a new consolidation technique called “phaselets”. Phaselets are partial sums of the terms
involved in a complete phasor computation. The use of phaselets in the L90 design improves the transient response perfor-
mance without increasing the bandwidth requirements.
Phaselets themselves are not the same as phasors, but they can be combined into phasors over any time window that is
aligned with an integral number of phaselets (see the Phaselet Computation section in this chapter for details). The number
of phaselets that must be transmitted per cycle per phase is the number of samples per cycle divided by the number of
samples per phaselet. The L90 design uses 64 samples per cycle and 32 samples per phaselet, leading to a phaselet com-
munication bandwidth requirement of 2 phaselets per cycle. Two phaselets per cycle fits comfortably within a communica-
tions bandwidth of 64 Kbaud, and can be used to detect faults within a half cycle plus channel delay.
The second major technical consideration is the restraint characteristic, which is the decision boundary between situations
that are declared to be a fault and those that are not. The L90 uses an innovative adaptive decision process based on an
on-line computation of the sources of measurement error. In this adaptive approach, the restraint region is an ellipse with
variable major axis, minor axis, and orientation. Parameters of the ellipse vary with time to make best use of the accuracy
of current measurements.
The third major element of L90 design is sampling synchronization. In order for a differential scheme to work, the data
being compared must be taken at the same time. This creates a challenge when data is taken at remote locations.
The GE approach to clock synchronization relies upon distributed synchronization. Distributed synchronization is accom-
plished by synchronizing the clocks to each other rather than to a master clock. Clocks are phase synchronized to each
other and frequency synchronized to the power system frequency. Each relay compares the phase of its clock to the phase
of the other clocks and compares the frequency of its clock to the power system frequency and makes appropriate adjust-
ments. As long as there are enough channels operating to provide protection, the clocks will be synchronized.
The L90 system uses a peer to peer architecture in which the relays at every terminal are identical. Each relay computes
differential current and clocks are synchronized to each other in a distributed fashion. The peer to peer architecture is
based on two main concepts that reduce the dependence of the system on the communication channels: replication of pro-
tection and distributed synchronization.
Replication of protection means that each relay is designed to be able to provide protection for the entire system, and does
so whenever it has enough information. Thus a relay provides protection whenever it is able to communicate directly with
all other relays. For a multi-terminal system, the degree of replication is determined by the extent of communication inter-
connection. If there is a channel between every pair of relays, every relay provides protection. If channels are not provided
between every pair of relays, only those relays that are connected to all other relays provide protection. 9
Each L90 relay measures three phase currents 64 times per cycle. Synchronization in sampling is maintained throughout
the system via the distributed synchronization technique.
The next step is the removal of any decaying offset from each phase current measurement. This is done using a digital sim-
ulation of the so-called “mimic circuit” (based on the differential equation of the inductive circuit that generates the offset).
Next, phaselets are computed by each L90 for each phase from the outputs of the mimic calculation, and transmitted to the
other relay terminals. Also, the sum of the squares of the raw data samples is computed for each phase, and transmitted
with the phaselets.
At the receiving relay, the received phaselets are combined into phasors. Also, ground current is reconstructed from phase
information. An elliptical restraint region is computed by combining sources of measurement error. In addition to the
restraint region, a separate disturbance detector is used to enhance security.
The possibility of a fault is indicated by the detection of a disturbance as well as the sum of the current phasors falling out-
side of the elliptical restraint region. The statistical distance from the phasor to the restraint region is an indication of the
severity of the fault. To provide speed of response that is commensurate with fault severity, the distance is filtered. For mild
faults, filtering improves measurement precision at the expense of a slight delay, on the order of one cycle. Severe faults
are detected within a single phaselet. Whenever the sum of phasors falls within the elliptical restraint region, the system
assumes there is no fault, and uses whatever information is available for fine adjustment of the clocks.
The inductive behavior of power system transmission lines gives rise to decaying exponential offsets during transient con-
ditions, which could lead to errors and interfere with the determination of how well measured current fits a sinewave.
The current signals are pre-filtered using an improved digital MIMIC filter. The filter removes effectively the DC compo-
nent(s) guaranteeing transient overshoot below 2% regardless of the initial magnitude and time constant of the dc compo-
nent(s). The filter has significantly better filtering properties for higher frequencies as compared with a classical MIMIC filter.
This was possible without introducing any significant phase delay thanks to the high sampling rate used by the relay. The
output of the MIMIC calculation is the input for the phaselet computation. The MIMIC computation is applied to the data
samples for each phase at each terminal. The equation shown is for one phase at one terminal.
Phaselets are partial sums in the computation for fitting a sine function to measured samples. Each slave computes phase-
lets for each phase current and transmits phaselet information to the master for conversion into phasors. Phaselets enable
the efficient computation of phasors over sample windows that are not restricted to an integer multiple of a half cycle at the
power system frequency. Determining the fundamental power system frequency component of current data samples by
minimizing the sum of the squares of the errors gives rise to the first frequency component of the Discrete Fourier Trans-
form (DFT). In the case of a data window that is a multiple of a half cycle, the computation is simply sine and cosine
weighted sums of the data samples. In the case of a window that is not a multiple of a half-cycle, there is an additional cor-
rection that results from the sine and cosine functions not being orthogonal over such a window. However, the computation
can be expressed as a two by two matrix multiplication of the sine and cosine weighted sums.
Phaselets and sum of squares are computed for each phase at each terminal as follows. For the real part, we have:
N⁄ 2– 1
2π ( p + 1 ⁄ 2 -)⎞
4
I 1_Re_A ( k ) = ----
N
∑ i 1_f_A ( k – p ) ⋅ cos ⎛ -------------------------------
⎝ N ⎠ (EQ 9.1)
p=0
N⁄ 2– 1
2π ( p + 1 ⁄ 2 )-⎞
I 1_Im_A ( k ) 4-
= – ---
N
∑ i 1_f_A ( k – p ) ⋅ sin ⎛ -------------------------------
⎝ N ⎠
(EQ 9.2)
p=0
A disturbance detection algorithm is used to enhance security and to improve transient response. Conditions to detect a
disturbance include the magnitude of zero-sequence current, the magnitude of negative-sequence current, and changes in
positive, negative, or zero-sequence current. Normally, differential protection is performed using a full-cycle Fourier trans-
form. Continuous use of a full-cycle Fourier means that some pre-fault data is also used for computation – this may lead to
a slowdown in the operation of the differential function. To improve operating time, the window is resized to the half-cycle
Fourier once a disturbance is detected, thus removing pre-fault data.
Normally, the sum of the current phasors from all terminals is zero for each phase at every terminal. A fault is detected for a
phase when the sum of the current phasors from each terminal for that phase falls outside of a dynamic elliptical restraint
boundary for that phase. The severity of the fault is computed as follows for each phase.
The differential current is calculated as a sum of local and remote currents. The real part is expressed as:
I DIFF_RE_A = I LOC_PHASOR_RE_A + I REM1_PHASOR_RE_A + I REM2_PHASOR_RE_A (EQ 9.3)
The restraint current is composed from two distinctive terms: traditional and adaptive. Each relay calculates local portion of
the traditional and restraint current to be used locally and sent to remote peers for use with differential calculations. If more
than one CT are connected to the relay (breaker-and-the half applications), then a maximum of all (up to 4) currents is cho-
sen to be processed for traditional restraint:
The current chosen is expressed as:
2 2 2 2 2 2
( I LOC_TRAD_A ) = max ( ( I 1_MAG_A ) , ( I 2_MAG_A ) , ( I 3_MAG_A ) , ( I 4_MAG_A ) , ( I q_MAG_A ) ) (EQ 9.6)
This current is then processed with the slope (S1 and S2) and breakpoint (BP) settings to form a traditional part of the
restraint term for the local current as follows. For two-terminal systems, we have:
2 2
If ( I LOC_TRAD_A ) < BP
2 2
then ( I LOC_REST_TRAD_A ) = 2 ( S 1 ⋅ I LOC_TRAD_A ) (EQ 9.7)
2 2 2 2
else ( I LOC_REST_TRAD_A ) = 2 ( ( S 2 ⋅ I LOC_TRAD_A ) – ( S 2 ⋅ BP ) ) + 2 ( S 1 ⋅ BP )
where: MULTA is a multiplier that increases restraint if CT saturation is detected (see CT Saturation Detection for details);
ILOC_ADA_A is an adaptive restraint term (see Online Estimate Of Measurement Error for details)
The squared restraining current is calculated as a sum of squared local and all remote restraints:
2 2 2 2
( I REST_A ) = ( I LOC_PHASOR_RESTRAINT_A ) + ( I REM1_PHASOR_RESTRAINT_A ) + ( I REM2_PHASOR_RESTRAINT_A ) (EQ 9.10)
The line ground differential function allows sensitive ground protection for single-line to-ground faults, allowing the phase
differential element to be set higher (above load) to provide protection for multi-phase faults. The L90 ground differential
function calculates ground differential current from all terminal phase currents. The maximum phase current is used for the
restraint. The L90 is applied in dual-breaker applications to cope with significant through current at remote terminals that
may cause CT errors or saturation.
The line ground differential function uses the same CT matched and time-aligned phasors as the phase-segregated current
differential function. The operate signal is calculated for both real and imaginary parts as follows:
I OP_87G_RE = I LOC_PHASOR_RE_A + I LOC_PHASOR_RE_B + I LOC_PHASOR_RE_C + I REM1_PHASOR_RE_A + I REM1_PHASOR_RE_B
(EQ 9.12)
+ I REM1_PHASOR_RE_C + I REM2_PHASOR_RE_A + I REM2_PHASOR_RE_B + I REM2_PHASOR_RE_C
The terms for the second remote terminal are omitted in two-terminal applications.
The maximum through current is available locally and re-constructed from the received remote restraint based on the max-
imum remote restraint current shown in the previous section and as indicated below.
For two-terminal applications:
2
2 2 2 ( I REM_RESTRAINT_A )
If ( I REM_REST_A ) < BP , then ( I REM_REST_A ) = ----------------------------------------------------
-
2
2S 1
(EQ 9.14)
2 2
( I REM_RESTRAINT_A ) – 2 ( S 1 × BP )
2 2
else ( I REM_REST_A ) = ------------------------------------------------------------------------------------------
- + BP
2
2S 2
2
2 2 2 ( I REM_RESTRAINT_A )
If ( I REM_REST_A ) < BP , then ( I REM_REST_A ) = ----------------------------------------------------
-
4 2
--- × S
3 1
(EQ 9.15)
2 4 2
( I REM_RESTRAINT_A ) – --- ( S 1 × BP )
2 3
else ( I REM_REST_A ) = ------------------------------------------------------------------------------------------- + BP
2
4 2
--- × S 2
3
The 87G restraining signal is calculated as follows:
2 2 2 2 2 2
( I RES_87G ) = max ( ( I LOC_REST_A ) , ( I LOC_REST_B ) , ( I LOC_REST_C ) , ( I REM1_REST_A ) , ( I REM1_REST_B ) ,
(EQ 9.16)
2 2 2 2
( I REM1_REST_C ) , ( I REM2_REST_A ) , ( I REM2_REST_B ) , ( I REM2_REST_C ) )
The terms for the second remote terminal are omitted in two-terminal applications.
2
The operate signal for the ground differential function, ( I OP_87G ) , is then calculated as:
2 2 2
( I OP_87G ) = ( I OP_87G_RE ) + ( I OP_87G_IM ) (EQ 9.17)
2
The restraint signal, ( I 87G ) , is calculated as follows for two-terminal applications:
2 2 2
( I 87G ) = 2S 87G × ( I RES_87G ) (EQ 9.18)
2
The restraint signal, ( I 87G ) , is calculated as follows for three-terminal applications:
2 4 2 2
( I 87G ) = --- × S 87G × ( I RES_87G ) (EQ 9.19)
3
where S 87G is the slope setting for the ground differential function.
The ground differential element picks up if the following condition holds.
2 2 2 2 2
( ( I OP_87G ) – ( 2P 87G + ( I 87G ) ) > 0 ) and ( ( I RES_87G ) < ( 3 pu ) ) (EQ 9.20)
where P 87G is the pickup setting for the ground differential function.
In other words, when the squared magnitude of the operating signal is greater than the total restraining squared signal, the
element operates. For additional security, the function is blocked if the restraining signal is high, indicating the 87LG func-
tion is not required to clear high-current faults, allowing for more sensitive settings to be used for the 87LG function.
Synchronization of data sampling clocks is needed in a digital differential protection scheme, because measurements must
be made at the same time. Synchronization errors show up as phase angle and transient errors in phasor measurements at
the terminals. By phase angle errors, we mean that identical currents produce phasors with different phase angles. By tran-
sient errors, we mean that when currents change at the same time, the effect is seen at different times at different measure-
ment points. For best results, samples should be taken simultaneously at all terminals.
In the case of peer to peer architecture, synchronization is accomplished by synchronizing the clocks to each other rather
than to a master clock. Each relay compares the phase of its clock to the phase of the other clocks and compares the fre-
quency of its clock to the power system frequency and makes appropriate adjustments. The frequency and phase tracking
algorithm keeps the measurements at all relays within a plus or minus 25 microsecond error during normal conditions for a
2 or 3 terminal system. For 4 or more terminals the error may be somewhat higher, depending on the quality of the commu-
nications channels. The algorithm is unconditionally stable. In the case of 2 and 3 terminal systems, asymmetric communi- 9
cations channel delay is automatically compensated for. In all cases, an estimate of phase error is computed and used to
automatically adapt the restraint region to compensate. Frequency tracking is provided that will accommodate any fre-
quency shift normally encountered in power systems.
Each relay has a digital clock that determines when to take data samples and which is phase synchronized to all other
clocks in the system and frequency synchronized to the power system frequency. Phase synchronization drives the relative
timing error between clocks to zero, and is needed to control the uncertainty in the phase angle of phasor measurements,
which will be held to under 26 microseconds (0.6 degrees). Frequency synchronization to the power system eliminates a
source of error in phasor measurements that arises when data samples do not exactly span one cycle.
The block diagram for clock control for a two terminal system is shown in Figure 8–4. Each relay makes a local estimate of
the difference between the power system frequency and the clock frequency based on the rotation of phasors. Each relay
also makes a local estimate of the time difference between its clock and the other clocks either by exchanging timing infor-
mation over communications channels or from information that is in the current phasors, depending on whichever one is
more accurate at any given time. A loop filter then uses the frequency and phase angle deviation information to make fine
adjustments to the clock frequency. Frequency tracking starts if the current at one or more terminals is above 0.125 pu of
nominal; otherwise, the nominal frequency is used.
RELAY 1 RELAY 2
f System f
+ Frequency +
_ _
Compute Compute
Frequency Frequency
f – f1 Deviation f1 f2 Deviation f – f2
+ +
+ Phase Frequency Phase Frequency +
Loop Filter Loop Filter
+ +
ϕ1 ϕ2
θ θ
GPS GPS
Clock Clock
831026A1.CDR
(PFLL) as shown on the diagram above. If GPS time reference is lost, the channel asymmetry compensation is not
enabled, and the relay clock may start to drift and accumulate differential error. In this case, the 87L function has to be
blocked. Refer to Chapter 9: Application of Settings for samples of how to program the relay.
Estimation of frequency deviation is done locally at each relay based on rotation of positive sequence current, or on rotation
of positive sequence voltage, if it is available. The counter clockwise rotation rate is proportional to the difference between
the desired clock frequency and the actual clock frequency. With the peer to peer architecture, there is redundant frequency
tracking, so it is not necessary that all terminals perform frequency detection.
Normally each relay will detect frequency deviation, but if there is no current flowing nor voltage measurement available at
a particular relay, it will not be able to detect frequency deviation. In that case, the frequency deviation input to the loop filter
is set to zero and frequency tracking is still achieved because of phase locking to the other clocks. If frequency detection is
lost at all terminals because there is no current flowing then the clocks continue to operate at the frequency present at the
time of the loss of frequency detection. Tracking will resume as soon as there is current.
The rotational rate of phasors is equal to the difference between the power system frequency and the ratio of the sampling
frequency divided by the number of samples per cycle. The correction is computed once per power system cycle at each
relay. For conciseness, we use a phasor notation:
I ( n ) = Re ( Phasor n ) + j ⋅ Im ( Phasor n )
I a, k ( n ) = I ( n ) for phase a from the kth terminal at time step n
(EQ 9.21)
I b, k ( n ) = I ( n ) for phase b from the kth terminal at time step n
I c, k ( n ) = I ( n ) for phase c from the kth terminal at time step n
The angle of the deviation phasor for each relay is proportional to the frequency deviation at that terminal. Since the clock
synchronization method maintains frequency synchronism, the frequency deviation is approximately the same for each
relay. The clock deviation frequency is computed from the deviation phasor:
–1
FrequencyDeviation = Δ tan ( Im ( Deviation ) ⁄ Re ( Deviation ) )-
-----f = ------------------------------------------------------------------------------------------------ (EQ 9.24)
f 2π
Note that a four quadrant arctangent can be computed by taking the imaginary and the real part of the deviation separately
for the two arguments of the four quadrant arctangent. Also note that the input to the loop filter is in radian frequency which
is two pi times the frequency in cycles per second; that is, Δω = 2π ⋅ Δf .
So the radian frequency deviation can be calculated simply as:
–1
Δω = Δf ⋅ tan ( Im ( Deviation ) ⁄ Re ( Deviation ) ) (EQ 9.25)
the most reliable source of phase information but suffer from a phase offset due to a difference in the channel delays in
each direction between a pair of relays. In some cases, one or both directions may be switched to a different physical path,
leading to gross phase error.
The primary source of phase information are CPU time-tagged messages. If GPS compensation is enabled, GPS time
stamps are used to compensate for asymmetry. In all cases, frequency deviation information is also used when available.
The phase difference between a pair of clocks is computed by an exchange of time stamps. Each relay exchanges time
stamps with all other relays that can be reached.
It is not necessary to exchange stamps with every relay, and the method works even with some of the channels failed. For
each relay that a given relay can exchange time stamps with, the clock deviation is computed each time a complete set of
time stamps arrives. The net deviation is the total deviation divided by the total number of relays involved in the exchange.
For example, in the case of two terminals, each relay computes a single time deviation from time stamps, and divides the
result by two. In the case of three terminals, each relay computes two time deviations and divides the result by three. If a
channel is lost, the single deviation that remains is divided by two.
Four time stamps are needed to compute round trip delay time and phase deviation. Three stamps are included in the mes-
sage in each direction. The fourth time stamp is the time when the message is received. Each time a message is received
the oldest two stamps of the four time stamps are saved to become the first two time stamps of the next outgoing message.
The third time stamp of an outgoing message is the time when the message is transmitted. A fixed time shift is allowed
between the stamp values and the actual events, provided the shift for outgoing message time stamps is the same for all
relays, and the shift incoming message time stamps is also identical.
To reduce bandwidth requirements, time stamps are spread over 3 messages. In the case of systems with 4 messages per
cycle, time stamps are sent out on three of the four messages, so a complete set is sent once per cycle. In the case of sys-
tems with 1 message per cycle, three time stamps are sent out each cycle in a single message. The transmit and receive
time stamps are based on the first message in the sequence.
One of the strengths of this approach is that it is not necessary to explicitly identify or match time stamp messages. Usually,
two of the time stamps in an outgoing message are simply taken from the last incoming message. The third time stamp is
the transmittal time. However, there are two circumstances when these time stamps are not available. One situation is
when the first message is transmitted by a given relay. The second is when the exchange is broken long enough to invali-
date the last received set of time stamps (if the exchange is broken for longer than 66 ms, the time stamps from a given
clock could roll over twice, invalidating time difference computations). In either of these situations, the next outgoing set of
time stamps is a special start-up set containing transmittal time only. When such a message is received, nothing is com-
puted from it, except the message time stamp and the received time stamp are saved for the next outgoing message (it is
neither necessary nor desirable to “reset” the local clock when such a message is received).
Error analysis shows that time stamp requirements are not very stringent because of the smoothing behavior of the phase
locked loop. The time stamp can be basically a sample count with enough bits to cover the worst round trip, including chan-
nel delay and processing delay. An 8 bit time stamp with 1 bit corresponding to 1/64 of a cycle will accommodate a round
trip delay of up to 4 cycles, which should be more than adequate.
The computation of round trip delay and phase offset from four time stamps is as follows:
a = Ti – 2 – Ti – 3
b = Ti – Ti – 1
δi = a + b (EQ 9.26)
θi = a – b-
-----------
2
The Ts are the time stamps, with Ti the newest. Delta is the round trip delay. Theta is the clock offset, and is the correct sign
for the feedback loop. Note that the time stamps are unsigned numbers that wrap around, while a and b can be positive or
9 negative; δi must be positive and θi can be positive or negative. Some care must be taken in the arithmetic to take into
account possible roll over of any of the time stamps. If Ti – 2 is greater than Ti – 1, there was a roll over in the clock respon-
sible for those two time stamps.
To correct for the roll over, subtract 256 from the round trip and subtract 128 from the phase angle. If Ti – 3 is greater than Ti,
add 256 to the round trip and add 128 to the phase angle. Also, if the above equations are computed using integer values
of time stamps, a conversion to phase angle in radians is required by multiplying by π / 32.
Time stamp values are snapshots of the local 256 bit sample counter taken at the time of the transmission or receipt of the
first message in a time stamp sequence. This could be done either in software or hardware, provided the jitter is limited to
less than plus or minus 130 μs. A fixed bias in the time stamp is acceptable, provided it is the same for all terminals.
Relay 1 Relay 2
COMMUNICATION PATH
Send T1i-3 Clocks mismatch
Store T1i-3
Send T2i-3
Store T2i-3
8.3 ms
Capture T2i-2
T2i-2
Capture T1i-2 T1i-2
8.3 ms
Send T1i-2
Send T2 i-2
8.3 ms
Store T1 i-2
Store T2 i-2
8.3 ms
Capture T1 i-1, T2 i
Capture T2 i-1, T1 i T1 i T2 i ( T2 i -3, T1i -2, T1i-1, T2 i )
( T1 i -3, T2 i-2, T2 i -1, T1i ) Calculate δ2, θ2.
Calculate δ1, θ1.
Speed up
Slow down
831729A2.CDR
t1 t2
Figure 9–2: ROUND TRIP DELAY AND CLOCK OFFSET COMPUTATION FROM TIME STAMPS
Filters are used in the phase locked loop to assure stability, to reduce phase and frequency noise. This is well known tech-
nology. The primary feedback mechanism shown in the Loop Block Diagram is phase angle information through the well
known proportional plus integral (PI) filter (the Z in the diagram refers to a unit delay, and 1 / (Z – 1) represents a simple
digital first order integrator). This loop is used to provide stability and zero steady state error.
A PI filter has two time parameters that determine dynamic behavior: the gain for the proportional term and the gain for the
integral. Depending on the gains, the transient behavior of the loop can be underdamped, critically damped, or over
damped. For this application, critically damped is a good choice.
This sets a constraint relating the two parameters. A second constraint is derived from the desired time constants of the
loop. By considering the effects of both phase and frequency noise in this application it can be shown that optimum behav-
ior results with a certain proportion between phase and frequency constraints.
A secondary input is formed through the frequency deviation input of the filter. Whenever frequency deviation information is
available, it is used for this input; otherwise, the input is zero. Because frequency is the derivative of phase information, the
appropriate filter for frequency deviation is an integrator, which is combined with the integrator of the PI filter for the phase.
It is very important to combine these two integrators into a single function because it can be shown if two separate integra-
tors are used, they can drift in opposite directions into saturation, because the loop would only drive their sum to zero.
In normal operation, frequency tracking at each terminal matches the tracking at all other terminals, because all terminals
will measure approximately the same frequency deviation. However, if there is not enough current at a terminal to compute
frequency deviation, frequency tracking at that terminal is accomplished indirectly via phase locking to other terminals. A
small phase deviation must be present for the tracking to occur.
Also shown in the loop is the clock itself, because it behaves like an integrator. The clock is implemented in hardware and
software with a crystal oscillator and a counter.
Delta frequency +
KF + 1/(Z–1)
+
+
KI New frequency
+
Delta phi time +
+ +
–
KP
1/(Z–1)
GPS channel
asymmetry
Clock
(sample timer) phi
831028A1.CDR
An algorithm is needed to match phaselets, detect lost messages, and detect communications channel failure. Channel fail-
ure is defined by a sequence of lost messages, where the length of the sequence is a design parameter. In any case, the
sequence should be no longer than the maximum sequence number (4 cycles) in order to be able to match up messages
when the channel is assumed to be operating normally.
A channel failure can be detected by a watchdog software timer that times the interval between consecutive incoming mes-
sages. If the interval exceeds a maximum limit, channel failure is declared and the channel recovery process is initiated.
While the channel is assumed to be operating normally, it is still possible for an occasional message to be lost, in which
case fault protection is suspended for the time period that depends on that message, and is resumed on the next occa-
sional message. A lost message is detected simply by looking at the sequence numbers of incoming messages. A lost
message will show up as a gap in the sequence.
Sequence numbers are also used to match messages for the protection computation. Whenever a complete set of current
measurements from all terminals with matching sequence numbers are available, the differential protection function is com-
puted using that set of measurements.
9.1.14 START-UP
Initialization in our peer-to-peer architecture is done independently at each terminal. Relays can be turned on in any order
with the power system either energized or de-energized. Synchronization and protection functions are accomplished auto-
matically whenever enough information is available.
After a relay completes other initialization tasks such as resetting of buffer pointers and determining relay settings, initial
values are computed for any state variables in the loop filters or the protection functions. The relay starts its clock at the
nominal power system frequency. Phaselet information is computed and transmitted.
• Outgoing messages over a given channel are treated in the same way as during the channel recovery process. The
special start-up message is sent each time containing only a single time step value.
• When incoming messages begin arriving over a channel, that channel is placed in service and the loop filters are
started up for that channel.
• Whenever the total clock uncertainty is less than a fixed threshold, the phase locking filter is declared locked and differ-
ential protection is enabled.
The average total channel delay in each direction is not critical, provided the total round trip delay is less than 4 power sys-
tem cycles. The jitter is important, and should be less than ±130 μs in each direction. The effect of a difference in the aver-
age delay between one direction and the other depends on the number of terminals. In the case of a 2 or 3 terminal system,
the difference is not critical, and can even vary with time. In the case of a 4 or more terminal system, variation in the differ-
ence limits the sensitivity of the system.
• The allowable margin of 130 μs jitter includes jitter in servicing the interrupt generated by an incoming message. For
both incoming and outgoing messages, the important parameter is the jitter between when the time stamp is read and
when the message begins to go out or to come in.
• The quality of the crystal driving the clock and software sampling is not critical, because of the compensation provided
by the phase and frequency tracking algorithm, unless it is desired to perform under or over frequency protection.
From the point of view of current differential protection only, the important parameter is the rate of drift of crystal fre-
quency, which should be less than 100 parts per million per minute.
• A 6 Mhz clock with a 16-bit hardware counter is adequate, provided the method is used for achieving the 32-bit resolu- 9
tion that is described in this document.
• An 8-bit time stamp is adequate provided time stamp messages are exchanged once per cycle.
• A 4-bit message sequence number is adequate.
Depending on the 87L settings, channel asymmetry (the difference in the transmitting and receiving paths channel delay)
cannot be higher than 1 to 1.5 ms if channel asymmetry compensation is not used. However, if the relay detects asymmetry
higher than 1.5 ms, the 87L DIFF CH ASYM DET FlexLogic™ operand is set high and the event and target are raised (if they
are enabled in the CURRENT DIFFERENTIAL menu) to provide an indication about potential danger.
GE's adaptive elliptical restraint characteristic is a good approximation to the cumulative effects of various sources of error
in determining phasors. Sources of error include power system noise, transients, inaccuracy in line charging current com-
putation, current sensor gain, phase and saturation error, clock error, and asynchronous sampling. Errors that can be con-
trolled are driven to zero by the system. For errors that cannot be controlled, all relays compute and sum the error for each
source of error for each phase. The relay computes the error caused by power system noise, CT saturation, harmonics,
and transients. These errors arise because power system currents are not always exactly sinusoidal. The intensity of these
errors varies with time; for example, growing during fault conditions, switching operations, or load variations. The system
treats these errors as a Gaussian distribution in the real and in the imaginary part of each phasor, with a standard deviation
that is estimated from the sum of the squares of the differences between the data samples and the sine function that is
used to fit them. This error has a spectrum of frequencies. Current transformer saturation is included with noise and tran-
sient error. The error for noise, harmonics, transients, and current transformer saturation is computed as follows. First, the
sum of the squares of the errors in the data samples is computed from the sum of squares information for the present
phaselet:
N⁄ 2– 1
∑
2
SumSquares 1_A ( k )
4
= ---- ( i 1_f_A ( k – p ) ) (EQ 9.28)
N p=0
2 2
I 1_MAG_A = ( I 1_RE_A ) + ( I 1_IM_A ) (EQ 9.29)
Finally, the local adaptive restraint term is computed as follows, for each local current:
2 4 2
( I 1_ADA_A ) = ---- ( SumSquares 1_A ( k ) – ( I 1_MAG_A ) ) (EQ 9.30)
N
Another source of the measurement errors is clock synchronization error, resulting in a clock uncertainty term. The L90
algorithm accounts for two terms of synchronization error corresponding to:
• Raw clock deviation computed from time stamps. There are several effects that cause it to not track exactly. First, the
ping-pong algorithm inherently produces slightly different estimates of clock deviation at each terminal. Second,
because the transmission of time stamps is spread out over several packets, the clock deviation estimate is not up to
date with other information it is combined with. Channel asymmetry also contributes to this term. The clock deviation
computation is indicated in equation 8.15 as θi. If 2 channels are used, clock deviation is computed for both channels
and then average of absolute values is computed. If GPS compensation is used, then GPS clock compensation is sub-
tracted from the clock deviation.
• Startup error. This term is used to estimate the initial startup transient of PFLLs. During startup conditions, a decaying
exponential is computed to simulate envelope of the error during startup
The clock uncertainty is expressed as:
clock_unc = clock_dev + start_up_error (EQ 9.31)
Current differential protection is inherently dependent on adequate CT performance at all terminals of the protected line,
especially during external faults. CT saturation, particularly when it happens at only one terminal of the line, introduces a
spurious differential current that may cause the differential protection to misoperate.
The L90 applies a dedicated mechanism to cope with CT saturation and ensure security of protection for external faults.
The relay dynamically increases the weight of the square of errors (the so-called ‘sigma’) portion in the total restraint quan-
tity, but for external faults only. The following logic is applied:
• First, the terminal currents are compared against a threshold of 3 pu to detect overcurrent conditions that may be
caused by a fault and may lead to CT saturation.
• For all the terminal currents that are above the 3 pu level, the relative angle difference is calculated. If all three termi-
nals see significant current, then all three pairs (1, 2), (2, 3), and (1, 3) are considered and the maximum angle differ-
ence is used in further calculations.
• Depending on the angle difference between the terminal currents, the value of sigma used for the adaptive restraint
current is increased by the multiple factor of 1, 5, or 2.5 to 5 as shown below. As seen from the figure, a factor of 1 is
used for internal faults, and a factor of 2.5 to 5 is used for external faults. This allows the relay to be simultaneously
sensitive for internal faults and robust for external faults with a possible CT saturation.
If more than one CT is connected to the relay (breaker-and-the half applications), the CT saturation mechanism is executed
between the maximum local current against the sum of all others, then between the maximum local and remote currents to
select the secure multiplier MULT. A Maximum of two (local and remote) is selected and then applied to adaptive restraint.
arg(I1/I2)=180 degrees
(external fault)
MULT=5
MULT=1
MULT=1
arg(I1/I2)= 0 degrees
831744A2.CDR
(internall fault)
The basic premise for the operation of differential protection schemes in general, and of the L90 line differential element in
particular, is that the sum of the currents entering the protected zone is zero. In the case of a power system transmission
line, this is not entirely true because of the capacitive charging current of the line. For short transmission lines the charging
current is a small factor and can therefore be treated as an unknown error. In this application the L90 can be deployed with-
out voltage sensors and the line charging current is included as a constant term in the total variance, increasing the differ- 9
ential restraint current. For long transmission lines the charging current is a significant factor, and should be computed to
provide increased sensitivity to fault current.
Compensation for charging current requires the voltage at the terminals be supplied to the relays. The algorithm calculates
C × dv ⁄ dt for each phase, which is then subtracted from the measured currents at both ends of the line. This is a simple
approach that provides adequate compensation of the capacitive current at the fundamental power system frequency. Trav-
elling waves on the transmission line are not compensated for, and contribute to restraint by increasing the measurement of
errors in the data set.
The underlying single phase model for compensation for a two and three terminal system are shown below.
Is Ir
Vs Vr
R L
C/2 C/2
831793A1.CDR
Figure 9–5: 2-TERMINAL TRANSMISSION LINE SINGLE PHASE MODEL FOR COMPENSATION
C/3
C/3
C/3
831019A1.CDR
Figure 9–6: 3-TERMINAL TRANSMISSION LINE SINGLE PHASE MODEL FOR COMPENSATION
Apportioning the total capacitance among the terminals is not critical for compensating the fundamental power system fre-
quency charging current as long as the total capacitance is correct. Compensation at other frequencies will be approximate.
If the VTs are connected in wye, the compensation is accurate for both balanced conditions (i.e. all positive, negative and
zero sequence components of the charging current are compensated). If the VTs are connected in delta, the compensation
is accurate for positive and negative sequence components of the charging current. Since the zero sequence voltage is not
available, the L90 cannot compensate for the zero sequence current.
The compensation scheme continues to work with the breakers open, provided the voltages are measured on the line side
of the breakers.
For very long lines, the distributed nature of the line leads to the classical transmission line equations which can be solved
for voltage and current profiles along the line. What is needed for the compensation model is the effective positive and zero
sequence capacitance seen at the line terminals.
Finally, in some applications the effect of shunt reactors needs to be taken into account. With very long lines shunt reactors
may be installed to provide some of the charging current required by the line. This reduces the amount of charging current
flowing into the line. In this application, the setting for the line capacitance should be the residual capacitance remaining
after subtracting the shunt inductive reactance from the total capacitive reactance at the power system frequency.
The differential element is completely dependent on receiving data from the relay at the remote end of the line, therefore,
upon startup, the differential element is disabled until the time synchronization system has aligned both relays to a common
time base. After synchronization is achieved, the differential is enabled. Should the communications channel delay time
increase, such as caused by path switching in a SONET system or failure of the communications power supply, the relay
will act as outlined in the next section.
9 The L90 incorporates an adaptive differential algorithm based on the traditional percent differential principle. In the tradi-
tional percent differential scheme, the operating parameter is based on the phasor sum of currents in the zone and the
restraint parameter is based on the scalar (or average scalar) sum of the currents in the protected zone - when the operat-
ing parameter divided by the restraint parameter is above the slope setting, the relay will operate. During an external fault,
the operating parameter is relatively small compared to the restraint parameter, whereas for an internal fault, the operating
parameter is relatively large compared to the restraint parameter. Because the traditional scheme is not adaptive, the ele-
ment settings must allow for the maximum amount of error anticipated during an out-of-zone fault, when CT errors may be
high and/or CT saturation may be experienced.
The major difference between the L90 differential scheme and a percent differential scheme is the use of an estimate of
errors in the input currents to increase the restraint parameter during faults, permitting the use of more sensitive settings
than those used in the traditional scheme. The inclusion of the adaptive feature in the scheme produces element character-
istic equations that appear to be different from the traditional scheme, but the differences are minimal during system
steady-state conditions. The element equations are shown in the Operating condition calculations section.
On startup of the relays, the channel status will be checked first. If channel status is OK, all relays will send a special
“startup” message and the synchronization process will be initiated. It will take about 5 to 7 seconds to declare PFLL status
as OK and to start performing current differential calculations. If one of the relays was powered off during the operation, the
synchronization process will restart from the beginning. Relays tolerate channel delay (resulting sometimes in step change
in communication paths) or interruptions up to four power cycles round trip time (about 66 ms at 60 Hz) without any deteri-
oration in performance. If communications are interrupted for more than four cycles, the following applies:
In two-terminal mode:
1. With second redundant channel, relays will not lose functionality at all if second channel is live.
2. With one channel only, relays have a five second time window. If the channel is restored within this time, it takes about
two to three power cycles of valid PFLL calculations (and if estimated error is still within margin) to declare that PFLL is
OK. If the channel is restored later than 5 seconds, PFLL at both relays will be declared as failed and the re-synchroni-
zation process will be initiated (about 5 to 7 seconds) after channel status becomes OK.
In three-terminal mode:
1. If one of the channels fails, the configuration reverts from master-master to master-slave where the master relay has
both channels live. The master relay PFLL keeps the two slave relays in synchronization, and therefore there is no
time limit for functionality. The PFLL of the slave relays will be suspended (that is, the 87L function will not be per-
formed at these relays but they can still trip via DTT from the master relay) until the channel is restored. If the esti-
mated error is within margin upon channel restoration and after two to three power cycles of valid PFLL calculations,
the PFLL will be declared as OK and the configuration will revert back to master-master.
2. If 2 channels fail, PFLL at all relays will be declared as failed and when the channels are back into service, the re-syn-
chronization process will be initiated (about 5 to 7 seconds) after channel status becomes OK.
Depending on the system configuration (number of terminals and channels), the 87L function operability depends on the
status of channel(s), status of synchronization, and status of channel(s) ID validation. All these states are available as Flex-
Logic™ operands, for viewing in actual values, logged in the event recorder (if events are enabled in 87L menu), and also
trigger targets (if targets are enabled in the 87L function). These FlexLogic™ operands can to be used to trigger alarms,
illuminate LEDs, and be captured in oscillography.
However, the 87L BLOCKED FlexLogic™ operand reflects whether the local current differential function is blocked due to
communications or settings problems. The state of this operand is based on the combination of conditions outlined above.
As such, it is recommended that it be used to enable backup protection if 87L is not available.
The 87L BLOCKED operand is set when the 87L function is enabled and any of the following three conditions apply:
1. At least one channel failed on a two or three-terminal single-channel system, or both channels failed on a two-terminal
two-channel system.
2. PFFL has failed or is suspended,
3. A channel ID failure has been detected on at least one channel in a two-terminal single-channel system or in a three-
terminal system, or a channel ID failure has been detected on both channels in a two-terminal dual-channel system.
All L90 communications alarms can be divided by major and minor alarms.
The major alarms are CHANNEL FAIL, PFLL FAIL, and CHANNEL ID FAIL. The relay is blocked automatically if any of these
9
conditions occur. Therefore, there is no need to assign these operands to a current differential block setting.
The minor alarms are CRC FAIL and LOST PACKET, which are indicators of a poor or noisy communications channel. If the
relay recognizes that a packet is lost or corrupted, the 87L feature is not processed at that protection pass. Instead, it waits
for the next valid packet.
Characteristics of differential elements can be shown in the complex plane. The operating characteristics of the L90 are
fundamentally dependant on the relative ratios of the local and remote current phasor magnitudes and the angles of I loc /
I rem as shown in the Restraint Characteristics figure.
The main factors affecting the trip-restraint decisions are:
1. Difference in angles (+ real represents pure internal fault when currents are essentially in phase, – real represents
external fault when currents are 180° apart).
2. The magnitude of remote current.
3. The magnitude of the local current.
4. Dynamically estimated errors in calculations.
5. Settings.
The following figure also shows the relay's capability to handle week-infeed conditions by increasing the restraint ellipse
when the remote current is relatively small (1.5 pu). Therefore, uncertainty is greater when compared with higher remote
currents (3 pu). The characteristic shown is also dependant on settings. The second graph shows how the relay's trip-
restraint calculation is made with respect to the variation in angle difference between local and remote currents. The char-
acteristic for 3 terminal mode is similar where both remote currents are combined together.
90
1 1
60
Restraint point (angle between Trip point (angle between
Iloc and Irem 180o) Iloc and Irem 0o) 30
Iloc 2
Iloc
0 Irem 0
Irem
-4 -3 -2 -1 1 2 3 4 Real 1 2 3 4
-30
-120
1 -150
Iloc Irem
-3
1 - For Irem =1.5 pu and angle 0-360o with respect to Iloc 831726A1.CDR
9-17
9
9.2 OPERATING CONDITION CHARACTERISTICS 9 THEORY OF OPERATION
Since the current at both ends is less than the breakpoint value of 5.0, the equation for two-terminal mode is used to calcu-
late restraint as follows.
2 2 2 2 2 2
I Rest = ( 2 ⋅ S 1 ⋅ I_L ) + ( 2 ⋅ S 1 ⋅ I_R ) + 2P + σ
2 2 2 2 2 (EQ 9.35)
= ( 2 ⋅ ( 0.1 ) ⋅ 4 ) + ( 2 ⋅ ( 0.1 ) ⋅ 0.8 ) + 2 ⋅ ( 0.5 ) + 0
= 0.8328
where σ = 0, assuming a pure sine wave.
The use of the CURRENT DIFF PICKUP, CURRENT DIFF RESTRAINT 1, CURRENT DIFF RESTRAINT 2, and CURRENT DIFF BREAK PT
settings are discussed in the Current differential section of chapter 5.
The following figure shows how the L90 settings affect the restraint characteristics. The local and remote currents are 180°
apart, which represents an external fault. The breakpoint between the two slopes indicates the point where the restraint
area is becoming wider to override uncertainties from CT saturation, fault noise, harmonics, etc. Increasing the slope per-
centage increases the width of the restraint area.
Iloc pu
20
OPERATE
16
RESTRAINT
OPERATE
0 Irem pu
4 8 12 16 20
0
831725A1.CDR
a) INTRODUCTION
Single pole operations make use of many features of the relay. At the minimum, the trip output, recloser, breaker control,
open pole detector, and phase selector must be fully programmed and in service; and either protection elements or digital
inputs representing fault detection must be available for successful operation. When single pole trip-and-reclose is required
overall control within the relay is performed by the trip output element. This element includes interfaces with pilot aided
schemes, the line pickup, breaker control, and breaker failure elements.
Single pole operations are based on use of the phase selector to identify the type of the fault, to eliminate incorrect fault
identification that can be made by distance elements in some circumstances and to provide trip initiation from elements that
are not capable of any fault type identification, such as high-set negative-sequence directional overcurrent element. The
scheme is also designed to make use of the advantages provided by communications channels with multiple-bit capacities
for fault identification.
Phase selector
Volts Reset
and output Fault locator
amps
Block specific protection elements
Volts
and
Trip output amps
Protection Setting
elements
Single-pole
Single-pole
trip request
Inputs Setting trip
Open
Pilot-
pole
aided
detector
schemes
Trip
A or B or C
Setting Setting
Setting Permission
Breaker 1 and 2
Inputs
Setting
Reset Breaker
control
Outputs
Three-pole Three-pole
trip trip
request
Line pickup Setting
CLOSE 1
CLOSE 2
CLOSE 1
CLOSE 2
Multi-phase
Operator
Void Force Three-pole
three-oole operation
Setting operation Setting
AR FORCE 3-P
Initiate
Reclose request Trip
Initiate
AR Initiate 3-Pole Recloser
Multi-phase
837026A5.CDR
b) SLG FAULT
At this moment the request to trip is placed for the trip output. As the fault is recognized as an AG fault, the TRIP PHASE A
operand is asserted by the trip output. This signal is passed to the breaker control scheme and results in tripping pole A of
the breaker.
Simultaneously with the TRIP PHASE A operand, the TRIP 1-POLE operand is asserted. This operand activates the open pole
detector. The latter detector responds to the TRIP PHASE A signal by declaring phase A open by asserting OPEN POLE OP
ΦA (even before it is actually opened). The TRIP PHASE A signal resets only after the breaker actually operates as indicated
by its auxiliary contact. At this moment the open pole detector responds to the breaker position and continues to indicate
phase A opened. This indication results in establishing blocking signals for distance elements (OPEN POLE BLK AB, OPEN
POLE BLK CA operands are asserted). If neutral and negative-sequence overcurrent elements are mapped into the trip out-
put to trigger single-pole tripping, they must be blocked with the OPEN POLE BLK N operand, specifically provided for this
purpose. The OPEN POLE BLK N operand must be assigned through the block setting of the overcurrent element. The two
latter operands block phase distance AB and CA elements, respectively (all zones); the OPEN POLE ΦA OP blocks the
ground distance AG elements (all zones). As a result, the Z1 OP and Z2 PKP operands that were picked-up reset immedi-
ately. The following distance elements remain operational guarding the line against evolving faults: BG, CG and BC.
The TRIP 1-POLE operand initiates automatically a single-pole autoreclose. The autoreclose is started and asserts the AR
RIP operand. This operand keeps blocking the phase selector so that it does not respond to any subsequent events. At the
same time the operand removes zero-sequence directional supervision from ground distance zones 2 and 3 so that they
could respond to a single-line-to-ground fault during open pole conditions.
The AR FORCE 3-P TRIP operand is asserted 1.25 cycles following autoreclose initiation. This operand acts as an enabler
for any existing trip request. In this case none of the protection elements is picked up at this time, therefore no more trips
are initiated.
When the recloser dead time interval is complete it signals the breaker control element to close the breaker. The breaker
control element operates output relays to close the breaker.
When pole A of the breaker closes this new status is reported to the breaker control element, which transfers this data to 9
the breaker failure, autorecloser, open pole detector and trip output elements. The response at breaker failure is dependent
on the programming of that element. The response at the autorecloser is not relevant to this discussion. At the open pole
detector, the blocking signals to protection elements are de-asserted.
If the fault was transient the reset time would expire at the autorecloser and the AR FORCE 3-P TRIP and RIP outputs would
be de-asserted, returning all features to the state described at the beginning of this description.
If the fault was permanent appropriate protection elements would detect it and place a trip request for the trip output ele-
ment. As the AR FORCE 3-P TRIP is still asserted, the request is executed as a three-pole trip.
The response of the system from this point is as described above for the second trip, except the autorecloser will go to lock-
out upon the next initiation (depending on the number of shots programmed).
The L90 uses phase relations between current symmetrical components for phase selection. First, the algorithm validates if
there is enough zero-sequence, positive-sequence, and negative-sequence currents for reliable analysis. The comparison
is adaptive; that is, the magnitudes of the three symmetrical components used mutually as restraints confirm if a given com-
ponent is large enough to be used for phase selection. Once the current magnitudes are validated, the algorithm analyzes
phase relations between the negative-sequence and positive-sequence currents and negative-sequence and zero-
sequence currents (when applicable) as illustrated below.
AB, CG,
BG ABG ABG
AG,
I2F AG I2F BCG
BC,
BCG
I1F I0F
CG CA, BG,
CAG CAG 837725A1.CDR
OPERAND DESCRIPTION
PHASE SELECT AG Asserted when a phase A to ground fault is detected.
PHASE SELECT BG Asserted when a phase B to ground fault is detected.
PHASE SELECT CG Asserted when a phase C to ground fault is detected.
PHASE SELECT AB Asserted when a phase A to B fault is detected.
PHASE SELECT BC Asserted when a phase B to C fault is detected.
PHASE SELECT CA Asserted when a phase C to A fault is detected.
PHASE SELECT ABG Asserted when a phase A to B to ground fault is detected.
PHASE SELECT BCG Asserted when a phase B to C to ground fault is detected.
PHASE SELECT CAG Asserted when a phase C to A to ground fault is detected.
If none of the fault types indicated above is determined, then three-phase fault conditions are checked to detect the pres-
ence of positive-sequence current and the absence of both zero-sequence and negative-sequence current. If these condi-
tions are met, then the PHASE SELECT 3P FlexLogic™ operand is asserted; otherwise, the PHASE SELECT VOID operand is
asserted, indicating that the phase selector failed to identify the fault type.
Finally, the states of the following additional FlexLogic™ operands are determined.
OPERAND DESCRIPTION
PHASE SELECT SLG Asserted if any of PHASE SELECT AG, PHASE SELECT BG, or PHASE SELECT CG
operands is active.
PHASE SELECT MULTI-P Asserted if neither the PHASE SELECT SLG nor PHASE SELECT VOID operands are being
asserted.
The phase selector operands are reset ½ cycle after the OPEN POLE OP FlexLogic™ operand is asserted or 500 ms after
the disturbance detector (50DD) initially operated. In the reset state, all phase selector FlexLogic™ operands are reset until
reset conditions are removed and the phase selector is ready for the next operation.
DELAY
FLEXLOGIC OPERAND
0.5 cycles
OPEN POLE OP RESET
0
DELAY
0 DELAY FLEXLOGIC OPERANDS
4 cycles 0 PHASE SELECT AG
FLEXLOGIC OPERAND AND START
500 ms PHASE SELECT BG
SRCn 50DD OP
PHASE SELECT CG
PHASE SELECT AB
FLEXLOGIC OPERAND
PHASE SELECTOR
PHASE SELECT BC
SRCn VT FUSE FAIL OP
PHASE SELECT CA
PHASE SELECT ABG
SETTING
PHASE SELECT BCG
DISTANCE SOURCE: PHASE SELECT CAG
PHASE SELECT 3P
I_0
PHASE SELECT SLG
I_1
PHASE SELECT MULTI-P
I_2
PHASE SELECT VOID
V_0
V_1
V_2
837027A5.CDR
The L90 uses two methods to determine fault type and fault location
• A multi-ended fault location algorithm using synchronized currents and voltage measurements from all line terminals.
• A single-ended method based on the measurement from local terminal relay only during channel failures.
a) DESCRIPTION
The multi-ended fault location method is based on synchronized voltage and current measurements at all ends of the trans-
mission line. This method makes it possible to compute the fault location without any assumptions or approximations. A
single composite voltage and single composite current signal represent voltage and current measurements at any line ter-
minal. These composite voltage and current signals are non-zero regardless of the fault type. The composite voltage at the
fault can be computed from each end of the line by subtracting the line drop to the fault from the voltage at that end.
The multi-ended algorithm executes separately on each terminal. All terminals compute the same fault location, since they
use the same equations applied to the same set of data. The algorithm is executed for both two-terminal and three-terminal
applications. The three-terminal algorithm executes at each terminal that has information from all three terminals. If there is
a communications failure on one channel, it will affect only one of the three terminals, since there are fault phasors from all
three terminals to compute the fault location. The three-terminal algorithm has two parts: one part that determines which
line segment is faulted, and another part that locates the fault on the faulted segment. Each terminal may report a slightly
different fault resistance. The algorithm achieves greater accuracy by removing the line charging current.
The fault location algorithm does not need to explicitly determine the composite voltage at the fault. Instead, it eliminates
the fault voltage from the equations for fault location by using other information instead.
For the purpose of fault location, the ABC quantities are represented by a single composite signal using the following base
equation.
1
S ( X ) = --- ( 2S ( A ) – bS ( B ) – b∗ S ( C ) ) (EQ 9.37)
3
In the above equation, b is a complex number defined as:
b = 1 + j tan ( α ) (EQ 9.38)
where α = 45°.
The expanded Clarke transform shown above is selected to yield non-zero operating signals under balanced and unbal-
anced conditions. This allows reducing the amount of exchanged information between devices and avoiding phase selec-
tion. The above defining equation applies to the wye connection of signals under ABC phase rotation. For delta connections
and ACB rotation, there is a small modification in this equation.
The following composite signals in (in per-unit values) are obtained from base equation shown above, taking into account
system phase rotation, CT nominal values, and VT nominal values and connections as set under the phase VT bank of the
first 87L source.
I LOC ( A, B, C ) → I LOC ( X ), I REM1 ( A, B, C ) → I REM1 ( X ), I REM2 ( A, B, C ) → I REM2 ( X )
(EQ 9.40)
V LOC ( A, B, C ) → V LOC ( X )
Composite currents are calculated locally at each terminal locally. Composite voltage is continuously transmitted to remote 9
terminals, where upon receipt it is labeled as VREM1(X) for channel 1 and VREM2(X) for channel 2. The transmitted composite
voltage signal is supervised by a VT fuse fail condition of the first source of 87L function. During VT fuse fail conditions,
transmitted voltage is substituted with zero, signaling to remote peers that multi-ended fault location should be inhibited.
The impedance for fault location calculation (in per-unit values) is calculated as follows.
CT sec
Z pu = Z sec × --------------- for wye-connected VTs
VT sec
(EQ 9.41)
CT sec
Z pu = 3 × Z sec × --------------- for delta-connected VTs
VT sec
Consequently, the positive-sequence line secondary impedance entered under in the fault locator menu yields following
signals used for calculation. For two-terminal applications, we have:
Z 1LINE → Z
(EQ 9.42)
L = corresponding line length
For three-terminal applications, we have:
Z 1LINE → Z LOC –T
Z REM1 –TAP → Z REM1 – T
(EQ 9.43)
Z REM2 –TAP → Z REM2 – T
L LOC – T, L REM1 –T, L REM2 –T = corresponding lengths of the three line segments
For two-terminal applications, fault calculations can be executed directly using the signals above. For three-terminal appli-
cations, it is first necessary to define the faulted line segment. This is done by estimating the tap voltage as seen from all
three line terminals.
V T ( LOC ) = V LOC ( X ) – Z LOC – T × I LOC ( X )
V T ( REM1 ) = V REM1 ( X ) – Z REM1 –T × I REM1 ( X ) (EQ 9.44)
V T ( REM2 ) = V REM2 ( X ) – Z REM2 –T × I REM2 ( X )
The faulted segment can be found by recognizing that the sum of the voltage drops around a loop through the unfaulted
segments is zero. The residual voltage phasors are computed for each loop. The loop with the lowest residual voltage con-
tains the two unfaulted segments. Therefore, the differences between each pair of estimates is calculated as follows.
ΔV LOC –REM1 = V T ( LOC ) – V T ( REM1 )
ΔV LOC –REM2 = V T ( LOC ) – V T ( REM2 ) (EQ 9.46)
ΔV REM1 –REM2 = V T ( REM1 ) – V T ( REM2 )
A similar set of equations is applied to determine whether the fault is between the tap and the local terminal or between the
tap and remote terminal 1.
Next, having all the data prepared, the following universal equation is used to calculate the fault location.
⎛V 1 ( X ) – V TAP ( X )
---------------------------------------- + I TAP ( X )⎞
⎜ Z ⎟
D pu = Re ⎜ -⎟
----------------------------------------------------------------
⎜ I FLT ( X ) ⎟ (EQ 9.49)
⎝ ⎠
D units = D pu × L
For two-terminal applications, the following equalities hold for the above equation.
V 1 ( X ) = V LOC ( X )
V TAP ( X ) = V REM1 ( X )
(EQ 9.50)
I TAP ( X ) = I REM1 ( X )
I FLT ( X ) = I LOC ( X ) + I REM1 ( X )
For two-terminal applications, the distance is reported from the local relay. In three-terminal applications, the distance is
reported from the terminal of a given line segment.
Phase rotation must be the same at all line terminals for correct operation of the multi-ended fault locator.
NOTE
b) EXAMPLE
Consider a three-terminal, 500 kV application with no charging current compensation or zero-sequence removal. The
phase rotation is ABC and the following CT and VT data is known.
The primary positive-sequence impedances and length for the line are shown below.
Table 9–3: LINE LENGTH AND POSITIVE-SEQUENCE IMPEDANCE FOR MULTI-ENDED EXAMPLE
VALUE RELAY 1 TO TAP RELAY 2 TO TAP RELAY 3 TO TAP
Impedance 21.29 Ω ∠80.5° 36.50 Ω ∠80.5° 16.73 Ω ∠80.5°
Length 70 km 120 km 55 km
channel 1 channel 1
Relay 1 Relay 2
70 km 120 km
channel 2 channel 2
55 km
Relay 3
channel 1 channel 2 831811A1.CDR
Assume the following signals are measured by the relays when the fault locator was triggered.
These measurement are shown below in per-unit values of the CT and VT nominal of the 87L source.
When subjected to the expanded Clarke transform in the previous sub-section, the local currents yield the following values
9 (in relay per-unit values):
• Relay 1: 1.3839 pu ∠–84.504°
• Relay 2: 5.4844 pu ∠–85.236°
• Relay 3: 1.2775 pu ∠–56.917°
When subjected to the expanded Clarke transform in the previous sub-section, the local voltages yield the following values
(in per-unit values of the nominal primary phase-to-ground voltage):
The line impedances entered in secondary ohms are recalculated as follows (refer to the previous sub-section for equa-
tions).
Using the data in the previous two tables, the tap voltages are calculated as follows (refer to the previous sub-section for
equations).
Applying the results of the table above to the equations in the previous sub-section, the algorithm arrives at the following:
• Relay 1 determines remote 1 to tap.
• Relay 2 determines local to tap.
• Relay 3 determines remote 2 to tap.
As a result, the relays use the following data for further calculations.
The data above are effectively identical. The difference in current magnitudes results from different per-unit bases at the
three relays (1200 A, 1000 A, and 1600 A). The difference in impedances results from different CT and VT ratios at the
three relays.
The tap voltage is the actual voltage at the tap (0.26558 × 500 kV / 3 = 76.67 kV). The V1 voltage is the voltage at relay 2
(0.30072 pu = 86.81 kV).
The tap current is the total feed from the tap towards the fault and is 2.9991 × 1200 A = 3.599 pu × 1000 A =
2.2494 pu × 1600 A = 3.599 kA. The fault current is 7.4992 pu × 1200 A = 8.999 pu × 1000 A = 5.6244 pu × 1600 A =
8.999 kA.
The data above results in the following fault locations.
• Relay 1 fault location = 0.4173 pu or 0.4173 × 120 km = 50.0704 km from its remote terminal 1 (relay 2)
• Relay 2 fault location = 0.4172 pu or 0.4172 × 120 km = 50.07 km from local terminal (relay 2)
• Relay 3 fault location = 0.4173 pu or 0.4173 × 120 km = 50.0704 km from its remote terminal 2 (relay 2)
The actual fault location in this example was 50.00km from relay 2 as shown below.
channel 1 AG channel 1
Relay 1 50 km Relay 2
70 km 120 km
channel 2 channel 2
9
55 km
Relay 3
channel 1 channel 2 831812A1.CDR
When the multi-ended fault locator cannot be executed due to communication channel problems or invalid signals from
remote terminals, then the single-ended method is used to report fault location.
Fault type determination is required for calculation of fault location – the algorithm uses the angle between the negative and
positive sequence components of the relay currents. To improve accuracy and speed of operation, the fault components of
the currents are used; that is, the pre-fault phasors are subtracted from the measured current phasors. In addition to the
angle relationships, certain extra checks are performed on magnitudes of the negative and zero-sequence currents.
The single-ended fault location method assumes that the fault components of the currents supplied from the local (A) and
remote (B) systems are in phase. The figure below shows an equivalent system for fault location.
distance to fault
Remote
Local bus bus
ZA IA mZ (1-m)Z IB ZB
EA VF RF EB
VA VB
842780A1.CDR
Inserting the IA and IB equations into the VA equation and solving for the fault resistance yields:
VA – m ⋅ Z ⋅ IA
R F = ----------------------------------- (EQ 9.54)
I BF⎞
I AF ⋅ ⎛ 1 + ------- -
⎝ I ⎠ AF
Assuming the fault components of the currents, IAF and IBF are in phase, and observing that the fault resistance, as imped-
ance, does not have any imaginary part gives:
VA – m ⋅ Z ⋅ IA
Im ⎛ -----------------------------------⎞ = 0 (EQ 9.55)
⎝ I AF ⎠
where: Im() represents the imaginary part of a complex number. Solving the above equation for the unknown m creates the
following fault location algorithm:
Im ( V A ⋅ I AF∗ ) 9
m = ---------------------------------------
- (EQ 9.56)
Im ( Z ⋅ I A ⋅ I AF∗ )
where * denotes the complex conjugate and I AF = I A – I Apre .
Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying
the two equations above (the superscripts denote phases, the subscripts denote stations).
For AG faults:
A A
VA = VA , I A = I A + K 0 ⋅ I 0A (EQ 9.57)
For BG faults:
B B
VA = VA , I A = I A + K 0 ⋅ I 0A (EQ 9.58)
For CG faults:
C BC
VA = VA , I A = I A + K 0 ⋅ I 0A (EQ 9.59)
where K0 is the zero sequence compensation factor (for the first six equations above)
For ABC faults, all three AB, BC, and CA loops are analyzed and the final result is selected based upon consistency of the
results
The element calculates the distance to the fault (with m in miles or kilometers) and the phases involved in the fault.
The relay allows locating faults from delta-connected VTs. If the FAULT REPORT 1 VT SUBSTITUTION setting is set to “None”,
and the VTs are connected in wye, the fault location is performed based on the actual phase to ground voltages. If the VTs
are connected in delta, fault location is suspended.
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “V0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and externally supplied neutral voltage:
1
V A = --- ( V N + V AB – V CA )
3
1
V B = --- ( V N + V BC – V AB ) (EQ 9.63)
3
1
V B = --- ( V N + V CA – V BC )
3
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “I0” and the VTs are connected in a wye configuration, the fault loca-
tion is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault loca-
tion is performed based on the delta voltages and zero-sequence voltage approximated based on the zero-sequence
current:
1
V A = --- ( V AB – V CA ) – Z SYS0 I 0
9 3
1
V B = --- ( V BC – V AB ) – Z SYS0 I 0 (EQ 9.64)
3
1
V B = --- ( V CA – V BC ) – Z SYS0 I 0
3
where ZSYS0 is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu.
SETTINGS
FAULT REPORT 1 Z1
MAG:
FAULT REPORT 1 Z1
ANGLE:
FAULT REPORT 1 Z0
MAG:
FAULT REPORT 1 Z0
ANGLE:
FAULT REPORT 1
LENGTH UNITS:
FAULT REPORT 1
LENGTH:
SHOT # FROM
AUTO RECLOSURE 827094A5.CDR
In general, proper CT selection is required to provide both adequate fault sensitivity and prevention of operation on high-
current external faults that could result from CT saturation. The use of high-quality CTs (such as class X) improves relay
stability during transients and CT saturation and can increase relay sensitivity. A current differential scheme is highly
dependent on adequate signals from the source CTs. Ideally, CTs selected for line current differential protection should be
based on the criteria described below. If the available CTs do not meet the described criteria, the L90 will still provide good
security for CT saturation for external faults. The L90 adaptive restraint characteristics, based on estimates of measure-
ment errors and CT saturation detection, allow the relay to be secure on external faults while maintaining excellent perfor-
mance for severe internal faults. Where CT characteristics do not meet criteria or where CTs at both ends may have
different characteristics, the differential settings should be adjusted as per section 9.2.1.
The capability of the CTs, and the connected burden, should be checked as follows:
1. The CTs should be class TPX or TPY (class TPZ should only be used after discussion with both the manufacturer of
the CT and GE Multilin) or IEC class 5P20 or better.
2. The CT primary current rating should be somewhat higher than the maximum continuous current, but not extremely
high relative to maximum load because the differential element minimum sensitivity setting is approximately 0.2 × CT
rating (the L90 relay allows for different CT ratings at each of the terminals).
3. The VA rating of the CTs should be above the Secondary Burden × CT Rated Secondary Current. The maximum sec-
ondary burden for acceptable performance is:
CT Rated VA
R b + R r < ------------------------------------------------------------2- (EQ 10.1)
( CT Secondary I rated )
V k > I fp × ⎛ ---
X- + 1⎞ × ( R + R + R ) for phase-phase faults
⎝R ⎠ CT L r
(EQ 10.2)
V k > I fg × ⎛ ---
X ⎞
⎝ R- + 1⎠ × ( R CT + 2R L + R r ) for phase-ground faults
This example illustrates how to check the performance of a class C400 ANSI/IEEE CT, ratios 2000/1800/1600/1500 : 5 A
connected at 1500:5. The burden and kneepoints are verified in this example.
Given the following values:
• maximum Ifp = 14 000 A
• maximum Ifg = 12 000 A
• impedance angle of source and line = 78°
• CT secondary leads are 75 m of AWG 10.
The following procedure verifies the burden. ANSI/IEEE class C400 requires that the CT can deliver 1 to 20 times the rated
secondary current to a standard B-4 burden (4 ohms or lower) without exceeding a maximum ratio error of 10%.
1. The maximum allowed burden at the 1500/5 tap is ( 1500 ⁄ 2000 ) × 4 = 3 Ω . 10
2. The RCT, Rr, and RL values are calculated as:
R CT = 0.75 Ω
0.2 VA
R r = ------------------ = 0.008 Ω
( 5 A )2 (EQ 10.3)
3.75 Ω
R L = 2 × 75 m × -------------------- = 2 × 0.26 Ω = 0.528 Ω
1000 m
3. This gives a total burden of:
Total Burden = R CT + R r + R L = 0.75 Ω + 0.008 Ω + 0.52 Ω = 1.28 Ω . (EQ 10.4)
To check the performance of an IEC CT of class 5P20, 15 VA, ratio 1500:5 A, assume the following values:
• maximum Ifp = 14 000 A
• maximum Ifg = 12 000 A
• impedance angle of source and line = 78°
• CT secondary leads are 75 m of AWG 10.
The IEC rating requires the CT deliver up to 20 times the rated secondary current without exceeding a maximum ratio error
of 5%, to a burden of:
15 VA = 0.6 Ω at the 5 A rated current
Burden = ---------------- (EQ 10.7)
( 5 A)2
The total Burden = Rr + Rl = 0.008 + 0.52 = 0.528 Ω, which is less than the allowed 0.6 Ω, which is OK.
The following procedure verifies the kneepoint voltage.
1. The maximum voltage available from the CT = ( 1500 ⁄ 2000 ) × 400 = 300 V .
2. The system X/R ratio = tan 78° = 4.71 .
3. The CT voltage for maximum phase fault is:
14000 A
V = ----------------------------------- × ( 4.71 + 1 ) × ( 0.75 + 0.26 + 0.008 Ω ) = 271.26 V (< 300 V, which is OK) (EQ 10.8)
ratio of 300:1
4. The CT voltage for maximum ground fault is:
12000 A
V = ----------------------------------- × ( 4.71 + 1 ) × ( 0.75 + 0.52 + 0.008 Ω ) = 291.89 V (< 300 V, which is OK) (EQ 10.9)
ratio of 300:1
Software is available from the GE Multilin website that is helpful in selecting settings for the specific appli-
cation. Checking the performance of selected element settings with respect to known power system fault
NOTE
parameters makes it relatively simple to choose the optimum settings for the application.
This software program is also very useful for establishing test parameters. It is strongly recommended this
program be downloaded.
The differential characteristic is defined by four settings: CURRENT DIFF PICKUP, CURRENT DIFF RESTRAINT 1, CURRENT DIFF
RESTRAINT 2, and CURRENT DIFF BREAK PT (breakpoint). As is typical for current-based differential elements, the settings
are a trade-off between operation on internal faults against restraint during external faults.
This setting established the sensitivity of the element to high impedance faults, and it is therefore desirable to choose a low
level, but this can cause a maloperation for an external fault causing CT saturation. The selection of this setting is influ-
enced by the decision to use charging current compensation. If charging current compensation is Enabled, pickup should
be set to a minimum of 150% of the steady-state line charging current, to a lower limit of 10% of CT rating. If charging cur-
rent compensation is Disabled, pickup should be set to a minimum of 250% of the steady-state line charging current to a
lower limit of 10% of CT rating.
If the CT at one terminal can saturate while the CTs at other terminals do not, this setting should be increased by approxi-
mately 20 to 50% (depending on how heavily saturated the one CT is while the other CTs are not saturated) of CT rating to
prevent operation on a close-in external fault.
This setting controls the element characteristic when current is below the breakpoint, where CT errors and saturation
effects are not expected to be significant. The setting is used to provide sensitivity to high impedance internal faults, or
when system configuration limits the fault current to low values. A setting of 10 to 20% is appropriate in most cases, but this
should be raised to 30% if the CTs can perform quite differently during faults.
This setting controls the element characteristic when current is above the breakpoint, where CT errors and saturation
effects are expected to be significant. The setting is used to provide security against high current external faults. A setting
of 30 to 40% is appropriate in most cases, but this should be raised to 70% if the CTs can perform quite differently during
faults.
Assigning the CURRENT DIFF RESTRAINT 1(2) settings to the same value reverts dual slope bias characteristics into
single slope bias characteristics.
NOTE
This setting controls the threshold where the relay changes from using the restraint 1 to the restraint 2 characteristics. Two
approaches can be considered.
1. Program the setting to 150 to 200% of the maximum emergency load current on the line, on the assumption that a
maintained current above this level is a fault.
2. Program the setting below the current level where CT saturation and spurious transient differential currents can be
expected.
The first approach gives comparatively more security and less sensitivity; the second approach provides less security for
more sensitivity.
10
10.2.6 CT TAP
If the CT ratios at the line terminals are different, the CURRENT DIFF CT TAP 1(2) setting must be used to correct the ratios to
a common base. In this case, a user should modify the CURRENT DIFF BREAK PT and CURRENT DIFF PICKUP settings
because the local current phasor is used as a reference to determine which differential equation is used, based on the
value of local and remote currents. If the setting is not modified, the responses of individual relays, especially during an
external fault, can be asymmetrical, as one relay can be below the breakpoint and the other above the breakpoint. There
are two methods to overcome this potential problem:
1. Set CURRENT DIFF RESTRAINT 1 and CURRENT DIFF RESTRAINT 2 to the same value (e.g. 40% or 50%). This converts the
relay characteristics from dual slope into single slope and the breakpoint becomes immaterial. Next, adjust differential
pickup at all terminals according to CT ratios, referencing the desired pickup to the line primary current (see below).
2. Set the breakpoints in each relay individually in accordance with the local CT ratio and the CT TAP setting. Next, adjust
the differential pickup setting according to the terminal CT ratios. The slope value must be identical at all terminals.
Consider a two-terminal configuration with the following CT ratios for relays 1 and 2.
CT ratio ( relay 1 ) = 1000 ⁄ 5
(EQ 10.10)
CT ratio ( relay 2 ) = 2000 ⁄ 5
To achieve maximum differential sensitivity, the minimum pickup is set as 0.2 pu at the terminal with the higher CT primary
current; in this case 2000:5 for relay 2. The other terminal pickup is adjusted accordingly. The pickup values are set as fol-
lows:
Pickup ( relay 1 ) = 0.4
(EQ 10.12)
Pickup ( relay 2 ) = 0.2
Choosing relay 1 as a reference with a breakpoint of 5.0, the break point at relay 2 is chosen as follows:
CT ratio ( relay 1 )
Breakpoint ( relay 2 ) = Breakpoint ( relay 1 ) × ----------------------------------------
CT ratio ( relay 2 )
(EQ 10.13)
1000 ⁄ 5
= 5.0 × -------------------- = 2.5
2000 ⁄ 5
Use the following equality the verify the calculated breakpoint:
Breakpoint ( relay 1 ) × CT ratio ( relay 1 ) = Breakpoint ( relay 2 ) × CT ratio ( relay 2 ) (EQ 10.14)
Therefore, we have a breakpoint of 5.0 for relay 1 and 2.5 for relay 2.
Now, consider a three-terminal configuration with the following CT ratios for relays 1, 2, and 3.
CT ratio ( relay 1 ) = 1000 ⁄ 5
CT ratio ( relay 2 ) = 2000 ⁄ 5 (EQ 10.15)
CT ratio ( relay 3 ) = 500 ⁄ 5
CT ratio ( relay 1 )
Breakpoint ( relay 3 ) = Breakpoint ( relay 1 ) × ----------------------------------------
CT ratio ( relay 3 )
(EQ 10.19)
1000 ⁄ 5
= 5.0 × -------------------- = 10.0
500 ⁄ 5
To verify the calculated values, we have:
Breakpoint ( relay 1 ) × CT ratio ( relay 1 ) = 5.0 × 1000 ⁄ 5 = 1000
Breakpoint ( relay 2 ) × CT ratio ( relay 2 ) = 2.5 × 2000 ⁄ 5 = 1000 (EQ 10.20)
Breakpoint ( relay 3 ) × CT ratio ( relay 3 ) = 10.0 × 5000 ⁄ 5 = 1000
10
10.2.7 BREAKER-AND-A-HALF
Assume a breaker-and-the-half configuration shown in the figure below. This section provides guidance on configuring the
L90 relay for this application. The L90 is equipped with two CT/VT modules: F8F and L8F.
1. CTs and VTs are connected to L90 CT/VT modules as follows:
– CT1 circuitry is connected to the F1 to F3 terminals of the F8F module (three-phase CT inputs, CT bank “F”).
– CT2 circuitry is connected to the F1 to F3 terminals of the L8F module (three-phase CT inputs, CT bank “L”).
– VT1 circuitry is connected to the F8 terminals of the F8F module (single-phase VT for synchrocheck 1, VT bank “F”).
– VT2 circuitry is connected to the F8 terminals of the L8F module (single-phase VT for synchrocheck 2, VT bank “L”).
– VT3 circuitry is connected to the F5 to F7 terminals of the F8F modules (three-phase VT for distance, metering, syn-
chrocheck, charging current compensation, etc.; VT bank “F”).
10
4. Sources are assigned accordingly in the specific element menus. For current differential, set CURRENT DIFF SIGNAL
SOURCE 1 to “SRC 1” and CURRENT DIFF SIGNAL SOURCE 2 to “SRC 2”.
For distance and backup overcurrent, make the following settings changes (EnerVista UR Setup example shown):
10
For breaker failure 1 and 2, make the following settings changes (EnerVista UR Setup example shown):
For synchrocheck 1 and 2, make the following settings changes (EnerVista UR Setup example shown):
10
In some cases, buses of the same substation are located quite far from each other or even separated by the line. In these
cases, it is challenging to apply conventional bus protection because of the CT cable length. In other cases, there are no
CTs available on the line side of the line to be protected. Taking full advantage of L90 capability to support up to 4 directly-
connected CTs, the relay can be applied to protect both line and buses as shown below. Proper CT/VT modules must be
ordered for such applications. The varying CT ratios at the breakers can be compensated locally by using the sources
mechanism and with the CT TAP settings between remote relays. If more than 4 but less than 8 CTs are to be connected to
the L90 at one bus, the 3-terminal system can be applied, provided the user does not exceed a total of 12 CTs.
831787A1.CDR
10
As indicated in the Settings chapter, the L90 provides three basic methods of applying channel asymmetry compensation
using GPS. Channel asymmetry can also be monitored with actual values and an indication signalled (FlexLogic™ oper-
ands 87L DIFF 1(2) MAX ASYM asserted) if channel asymmetry exceeds preset values. Depending on the implemented
relaying philosophy, the relay can be programmed to perform the following on the loss of the GPS signal:
1. Enable GPS compensation on the loss of the GPS signal at any terminal and continue to operate the 87L element
(using the memorized value of the last asymmetry) until a change in the channel round-trip delay is detected.
2. Enable GPS compensation on the loss of the GPS signal at any terminal and block the 87L element after a specified
time.
3. Continuously operate the 87L element but only enable GPS compensation when valid GPS signals are available. This
provides less sensitive protection on the loss of the GPS signal at any terminal and runs with higher pickup and
restraint settings.
Enable GPS compensation on the loss of the GPS signal at any terminal and continue to operate the 87L element until a
change in the channel round-trip delay is detected.
If GPS is enabled at all terminals and the GPS signal is present, the L90 compensates for the channel asymmetry. On the
loss of the GPS signal, the L90 stores the last measured value of the channel asymmetry per channel and compensates for
the asymmetry until the GPS clock is available. However, if the channel was switched to another physical path during GPS
loss conditions, the 87L element must be blocked, since the channel asymmetry cannot be measured and system is no lon-
ger accurately synchronized. The value of the step change in the channel is preset in L90 POWER SYSTEM settings menu
and signaled by the 87L DIFF 1(2) TIME CHNG FlexLogic™ operand. To implement this method, follow the steps below:
1. Enable Channel Asymmetry compensation by setting it to ON. Assign the GPS receiver failsafe alarm contact with the
setting Block GPS Time Ref.
2. Create FlexLogic™ similar to that shown below to block the 87L element on GPS loss if step change in the channel
delay occurs during GPS loss conditions or on a startup before the GPS signal is valid. For three-terminal systems, the
87L DIFF 1 TIME CHNG operand must be ORed with the 87L DIFF 2 TIME CHNG FlexLogic™ operand. The Block
87L (VO1) output is reset if the GPS signal is restored and the 87L element is ready to operate.
10
3 AND(2) OR(2)
4 87L DIFF GPS FAIL
AND(2)
5 87L DIFF 1 TIME CHNG
6 AND(2) Set
LATCH = BLOCK 87L (VO1)
7 TIMER 1 Reset
8 OR(2)
10 NOT AND(2)
11 87L DIFF GPS FAIL
12 NOT
13 AND(2)
14 TIMER 2
15 LATCH
3. Assign virtual output BLOCK 87L (VO1) to the 87L Current Differential Block setting. It can be used to enable backup
protection, raise an alarm, and perform other functions as per the given protection philosophy.
Enable GPS compensation on the loss of the GPS signal at any terminal and block the 87L element after a specified time.
This is a simple and conservative way of using the GPS feature. Follow steps 1 and 3 in compensation method 1. The Flex-
Logic™ is simple: 87L DIFF GPS FAIL-Timer-Virtual Output Block 87L (VO1). It is recommended that the timer be set no
higher than 10 seconds.
Continuously operate the 87L element but enable GPS compensation only when valid GPS signals are available. This pro-
vides less sensitive protection on GPS signal loss at any terminal and runs with higher pickup and restraint settings.
This approach can be used carefully if maximum channel asymmetry is known and doesn't exceed certain values (2.0 to
2.5 ms). The 87L DIFF MAX ASYM operand can be used to monitor and signal maximum channel asymmetry. Essentially,
the L90 switches to another setting group with higher pickup and restraint settings, sacrificing sensitivity to keep the 87L
function operational.
1. Create FlexLogic™ similar to that shown below to switch the 87L element to Settings Group 2 (with most sensitive set-
tings) if the L90 has a valid GPS time reference. If a GPS or 87L communications failure occurs, the L90 will switch
back to Settings Group 1 with less sensitive settings.
10
18 NOT AND(2)
19 87L DIFF GPS FAIL
Set
20 NOT LATCH = GPS ON-GR.2 (VO2)
21 AND(2)
Reset
24 OR(2)
25 TIMER 3
26 LATCH
2. Set the 87L element with different differential settings for Settings Groups 1 and 2 as shown below
3. Enable GPS compensation when the GPS signal is valid and switch to Settings Group 2 (with more sensitive settings)
as shown below.
10
Many high voltage lines have transformers tapped to the line serving as an economic approach to the supply of customer
load. A typical configuration is shown in the figure below.
Terminal 1 Terminal 2
831021A1.CDR
10
ation should also be given to a situation where the load impedance may enter into the relay characteristic for a time longer
than the chosen time delay, which could occur transiently during a system power swing. For this reason the power swing
blocking function should be used.
10
10
Traditionally, the reach setting of an underreaching distance function shall be set based on the net inductive impedance
between the potential source of the relay and the far-end busbar, or location for which the zone must not overreach. Faults
behind series capacitors on the protected and adjacent lines need to be considered for this purpose. For further illustration
a sample system shown in the figure below is considered.
voltage
SENDING RECEIVING
protection reactance
BUS BUS
level
0.5 pu 0.6 pu 0.5 pu 0.7 pu
-2 Ω -4 Ω -3 Ω -5 Ω
INFINITE
INFINITE
3Ω 10 Ω 7Ω
BUS
BUS
F2 A B B A F1
Protected Line
Figure 10–4: SAMPLE SERIES COMPENSATED SYSTEM
Assuming 20% security margin, the underreaching zone shall be set as follows.
At the Sending Bus, one must consider an external fault at F1 as the 5 Ω capacitor would contribute to the overreaching
effect. Any fault behind F1 is less severe as extra inductive line impedance increases the apparent impedance:
Reach Setting: 0.8 x (10 – 3 – 5) = 1.6 Ω if the line-side (B) VTs are used
Reach Setting: 0.8 x (10 – 4 – 3 – 5) = –1.6 Ω if the bus-side (A) VTs are used
The negative value means that an underreaching zone cannot be used as the circuit between the potential source of the
relay and an external fault for which the relay must not pick-up, is overcompensated, i.e. capacitive.
At the Receiving Bus, one must consider a fault at F2:
Reach Setting: 0.8 x (10 – 4 – 2) = 3.2 Ω if the line-side (B) VTs are used
Reach Setting: 0.8 x (10 – 4 – 3 – 2) = 0.8 Ω if the bus-side (A) VTs are used
Practically, however, to cope with the effect of sub-synchronous oscillations, one may need to reduce the reach even more.
As the characteristics of sub-synchronous oscillations are in complex relations with fault and system parameters, no solid
setting recommendations are given with respect to extra security margin for sub-synchronous oscillations. It is strongly rec-
ommended to use a power system simulator to verify the reach settings or to use an adaptive L90 feature for dynamic
reach control.
If the adaptive reach control feature is used, the PHS DIST Z1 VOLT LEVEL setting shall be set accordingly.
This setting is a sum of the overvoltage protection levels for all the series capacitors located between the relay potential
source and the far-end busbar, or location for which the zone must not overreach. The setting is entered in pu of the phase
VT nominal voltage (RMS, not peak value).
If a minimum fault current level (phase current) is causing a voltage drop across a given capacitor that prompts its air gap to
flash over or its MOV to carry practically all the current, then the series capacitor shall be excluded from the calculations
(the capacitor is immediately by-passed by its overvoltage protection system and does not cause any overreach problems).
If a minimum fault current does not guarantee an immediate capacitor by-pass, then the capacitor must be included in the
calculation: its overvoltage protection level, either air gap flash-over voltage or MOV knee-point voltage, shall be used
(RMS, not peak value).
Assuming none of the series capacitors in the sample system is guaranteed to get by-passed, the following calculations
apply:
For the Sending Bus: 0.5 + 0.7 = 1.2 pu if the line-side (B) VTs are used
0.6 + 0.5 + 0.7 = 1.8 pu if the bus-side (A) VTs are used
For the Receiving Bus: 0.6 + 0.5 = 1.1 pu if the line-side (B) VTs are used
0.6 + 0.5 + 0.5 = 1.6 pu if the bus-side (A) VTs are used 10
Ground directional overcurrent function (negative-sequence or neutral) uses an offset impedance to guarantee correct fault
direction discrimination. The following setting rules apply.
1. If the net impedance between the potential source and the local equivalent system is inductive, then there is no need
for an offset. Otherwise, the offset impedance shall be at least the net capacitive reactance.
2. The offset cannot be higher than the net inductive reactance between the potential source and the remote equivalent
system. For simplicity and extra security, the far-end busbar may be used rather than the remote equivalent system.
As the ground directional functions are meant to provide maximum fault resistance coverage, it is justified to assume that
the fault current is very low and none of the series capacitors is guaranteed to get by-passed. Consider settings of the neg-
ative-sequence directional overcurrent protection element for the Sample Series Compensated System.
For the Sending Bus relay, bus-side VTs:
• Net inductive reactance from the relay into the local system = –2 + 3 = 1 Ω > 0; there is no need for offset.
• Net inductive reactance from relay through far-end busbar = –4 + 10 – 3 = 3 Ω; the offset cannot be higher than 3 Ω.
• It is recommended to use 1.5 Ω offset impedance.
For the Sending Bus relay, line-side VTs:
• Net inductive reactance from relay into local system = –2 + 3 – 4 = –3 Ω < 0; an offset impedance ≥3 Ω must be used.
• Net inductive reactance from relay through far-end busbar = 10 – 3 = 7 Ω; the offset cannot be higher than 7 Ω.
• It is recommended to use 5 Ω offset impedance.
For the Receiving Bus relay, bus-side VTs:
• Net inductive reactance from relay into local system = –5 + 7 = 2 Ω > 0; there is no need for offset.
• Net inductive reactance from relay through far-end busbar = –3 + 10 – 4 = 3 Ω; the offset cannot be higher than 3 Ω.
• It is recommended to use 1.5 Ω offset impedance.
For the Receiving Bus relay, line-side VTs:
• Net inductive reactance from relay into local system = –3 – 5 + 7 = –1 Ω < 0; an offset impedance ≥1 Ω must be used.
• Net inductive reactance from relay through far-end busbar = 10 – 4 = 6 Ω; the offset cannot be higher than 6 Ω.
• It is recommended to use 3.5 Ω offset impedance.
10
The L90 protection system could be applied to lines with tapped transformer(s) even if the latter has its windings connected
in a grounded wye on the line side and the transformer(s) currents are not measured by the L90 protection system. The fol-
lowing approach is recommended.
If the setting SYSTEM SETUP ÖØ L90 POWER SYSTEM ÖØ ZERO-SEQ CURRENT REMOVAL is “Enabled”, all relays at the line ter-
minals are calculating zero-sequence for both local and remote currents and are removing this current from the phase cur-
rents. This ensures the differential current is immune to the zero-sequence current outfeed caused by the in-zone
transformer with a primary wye-connected winding solidly grounded neutral.
At all terminals the following is being performed:
I_L_0 = (I_L_A + I_L_B + I_L_C) / 3) : local zero-sequence current
I_R_0 = (I_R_A + I_R_B + I_R_C) / 3 : remote zero-sequence current
Now, the I_PHASE – I_0 values (for Local and Remote) are being used instead of pure phase currents for differential and
restraint current calculations. See the Theory of Operation chapter for additional details.
For example, the operating current in phase A is determined as:
I2op_A = |(I_L_A – I_L_0) + (I_R_A – I_R_0) |2 : squared operating current, phase A
where: I_L_A = “local” current phase A
I_R_A = “remote” current phase A
I_L_0 = local zero-sequence current
I_R_0 = remote zero-sequence current
I2op_A = operating (differential) squared current phase A
The restraint current is calculated in a similar way.
When the ZERO-SEQ CURRENT REMOVAL feature is enabled, the modified (I_0 removed) differential current in all
three phases is shown in the ACTUAL VALUES ÖØ METERING Ö 87L DIFFERENTIAL CURRENT menu. Local and remote
NOTE currents values are not changed.
As the tapped line may be energized from one terminal only, or there may be a low current flowing through the line, the
slope setting of the differential characteristic would not guarantee stability of the relay on transformer load currents. Conse-
quently, a pickup setting must be risen accordingly in order to prevent maloperation. The L90 forms its restraint current in a
unique way as explained in Chapter 8. Unlike traditional approaches, the effects of slope and pickup settings are combined:
the higher the slope, the lower the pickup setting required for the same restraining effect.
Assuming the line energized from one terminal and the current is below the lower break-point of the characteristic one
should consider the following stability conditions in order to select the pickup (P) and slope (S1) settings (ILOAD is a maxi-
mum total load current of the tapped transformer(s)).
• Two-terminal applications: • Three-terminal applications:
2 2 2 2
I op = I LOAD I op = I LOAD
2 2 2 2 2 4 22 2
I REST = 2S 1 I LOAD + 2P I REST = --- S 1 I LOAD + 2P
3
2 2 2 2
Stability condition: 2S 1 I LOAD + 2P > I LOAD 4 22 2 2
Stability condition: --- S 1 I LOAD + 2P > I LOAD
3
The above calculations should take into account the requirement for the pickup setting resulting from line charging currents.
Certainly, a security factor must be applied to the above stability conditions. Alternatively, distance supervision can be con-
sidered to prevent maloperation due to transformer load currents.
10
Distance supervision should be used to prevent maloperation of the L90 protection system during faults on the LV side of
the transformer(s). As explained earlier, the distance elements should be set to overreach all line terminals, and at the
same time safely underreach the LV busbars of all the tapped transformers. This may present some challenges, particularly
for long lines and large transformer tapped close to the substations. If the L90 system retrofits distance relays, there is a
good chance that one can set the distance elements to satisfy the imposed. If more than one transformer is tapped, partic-
ularly on parallel lines, and the LV sides are interconnected, detailed short circuit studies may be needed to determine the
distance settings.
External ground faults behind the line terminals will be seen by the overreaching distance elements. At the same time, the
tapped transformer(s), if connected in a grounded wye, will feed the zero-sequence current. This current is going to be
seen at one L90 terminal only, will cause a spurious differential signal, and consequently, may cause maloperation.
The L90 ensures stability in such a case by removing the zero-sequence current from the phase cur-rents prior to calculat-
ing the operating and restraining signals (SETTINGS ÖØ SYSTEM SETUP ÖØ L90 POWER SYSTEM ÖØ ZERO-SEQ CURRENT
REMOVAL = “Enabled”). Removing the zero-sequence component from the phase currents may cause the L90 to overtrip
healthy phases on internal ground fault. This is not a limitation, as the single-pole tripping is not recommended for lines with
tapped transformers.
10
As explained in the Theory of Operation chapter, two or three L90 relays are synchronized to each other and to system fre-
quency to provide digital differential protection and accurate measurements for other protection and control functions.
When an L90 system is starting up, the relays adjust their frequency aggressively to bring all relays into synchronization
with the system quickly. The tracking frequency can differ from nominal (or system frequency) by a few Hertz, especially
during the first second of synchronization. The 87L function is blocked during synchronization; therefore, the difference
between system frequency and relay sampling frequency does not affect 87L function. However, instantaneous elements
have additional error caused by the sensitivity of Fourier phasor estimation to the difference between signal frequency and
tracking frequency.
To secure instantaneous element operation, it is recommended either to use FlexLogic™ as shown below to block the
instantaneous elements during synchronization, or to use a different setting group with more conservative pickup for this
brief interval.
10
10
The communications system transmits and receives data between two or three terminals for the 87L function. The system
11
is designed to work with multiple channel options including direct and multiplexed optical fiber, G.703, and RS422. The
speed is 64 Kbaud in a transparent synchronous mode with automatic synchronous character detection and CRC insertion.
The Local Loopback Channel Test verifies the L90 communication modules are working properly. The Remote Loopback
Channel Test verifies the communication link between the relays meets requirements (BER less than 10–4). All tests are
verified by using the internal channel monitoring and the monitoring in the Channel Tests. All of the tests presented in this
section must be either OK or PASSED.
1. Verify that a type “W” module is placed in slot ‘W’ in both relays (e.g. W7J).
2. Interconnect the two relays using the proper media (e.g. single mode fiber cable) observing correct connection of
receiving (Rx) and transmitting (Tx) communications paths and turn power on to both relays.
3. Verify that the Order Code in both relays is correct.
4. Cycle power off/on in both relays.
5. Verify and record that both relays indicate In Service on the front display.
6. Make the following setting change in both relays: GROUPED ELEMENTS ÖØ GROUP 1 ÖØ CURRENT DIFFERENTIAL ELE-
MENTS Ö CURRENT DIFFERENTIAL Ö CURRENT DIFF FUNCTION: “Enabled”.
7. Verify and record that both relays have established communications with the following status checks:
ACTUAL VALUES ÖØ STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1 STATUS: “OK”
ACTUAL VALUES ÖØ STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 2 STATUS: “OK” (If used)
8. Make the following setting change in both relays: TESTING Ö TEST MODE: “Enabled”.
9. Make the following setting change in both relays:
TESTING ÖØ CHANNEL TESTS ÖØ LOCAL LOOPBACK TEST ÖØ LOCAL LOOPBACK CHANNEL NUMBER: "1"
10. Initiate the Local Loopback Channel Tests by making the following setting change:
TESTING ÖØ CHANNEL TESTS ÖØ LOCAL LOOPBACK TEST ÖØ LOCAL LOOPBACK FUNCTION: "Yes"
Expected result: In a few seconds “Yes” should change to “Local Loopback Test PASSED” and then to “No”, signify-
ing the test was successfully completed and the communication modules operated properly.
11. If Channel 2 is used, make the following setting change and repeat Step 10 for Channel 2 as performed for channel 1:
TESTING ÖØ CHANNEL TESTS ÖØ LOCAL LOOPBACK TEST ÖØ LOCAL LOOPBACK CHANNEL NUMBER: "2"
12. Verify and record that the Local Loopback Test was performed properly with the following status check:
ACTUAL VALUES ÖØ STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1(2) LOCAL LOOPBACK STATUS: "OK"
13. Make the following setting change in one of the relays:
TESTING ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK TEST ÖØ REMOTE LOOPBACK CHANNEL NUMBER: "1"
14. Initiate the Remote Loopback Channel Tests by making the following setting change:
TESTING ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK Ö REMOTE LOOPBACK FUNCTION: "Yes"
Expected result: The “Running Remote Loopback Test” message appears; within 60 to 100 sec. the “Remote Loop-
back Test PASSED” message appears for a few seconds and then changes to “No”, signifying the
test successfully completed and communications with the relay were successfully established. The
“Remote Loopback Test FAILED” message indicates that either the communication link quality does
not meet requirements (BER less than 10–4) or the channel is not established – check the communi-
cations link connections.
15. If Channel 2 is used, make the following setting change and repeat Step 14 for Channel 2 as performed for Channel 1:
TESTING ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK TEST ÖØ REMOTE LOOPBACK CHANNEL NUMBER: "2"
16. Verify and record the Remote Loopback Test was performed properly with the following status check:
ACTUAL VALUES ÖØ STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1(2) REMOTE LOOPBACK STATUS: "OK"
17. Verify and record that Remote Loopback Test fails during communications failures as follows: start test as per Steps 13
to 14 and in 2 to 5 seconds disconnect the fiber Rx cable on the corresponding channel.
11 Expected result: The "Running Remote Loopback Test" message appears. When the channel is momentarily cut off,
the "Remote Loopback Test FAILED" message is displayed. The status check should read as fol-
lows: ACTUAL VALUES Ø STATUS Ø CHANNEL TESTS Ö CHANNEL 1(2) LOCAL LOOPBACK STATUS: "Fail"
18. Re-connect the fiber Rx cable. Repeat Steps 13 to 14 and verify that Remote Loopback Test performs properly again.
19. Verify and record that Remote Loopback Test fails if communications are not connected properly by disconnecting the
fiber Rx cable and repeating Steps 13 to 14.
Expected result: The ACTUAL VALUES ÖØ STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1(2) REMOTE LOOPBACK TEST:
"Fail" message should be constantly on the display.
20. Repeat Steps 13 to 14 and verify that Remote Loopback Test is correct.
21. Make the following setting change in both relays: TESTING Ö TEST MODE: "Disabled"
During channel tests, verify in the ACTUAL VALUES ÖØ STATUS ÖØ CHANNEL TESTS Ö CHANNEL 1(2) LOST PACK-
ETS display that the values are very low – even 0. If values are comparatively high, settings of communica-
NOTE
tions equipment (if applicable) should be checked.
The 87L clock synchronization is based upon a peer-to-peer architecture in which all relays are Masters. The relays are
synchronized in a distributed fashion. The clocks are phase synchronized to each other and frequency synchronized to the
power system frequency. The performance requirement for the clock synchronization is a maximum error of ±130 μs.
All tests are verified by using PFLL status displays. All PFLL status displays must be either OK or Fail.
1. Ensure that Steps 1 through 7 inclusive of the previous section are completed.
2. Verify and record that both relays have established communications with the following checks after 60 to 120 seconds:
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1(2) STATUS: “OK”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK STATUS: “n/a”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ PFLL STATUS: “OK”
3. Disconnect the fiber Channel 1(2) Tx cable for less than 66 ms (not possible with direct fiber module).
Expected result: ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1(2) STATUS: “OK”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK STATUS: “n/a”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ PFLL STATUS: “OK”
If fault conditions are applied to the relay during these tests, it trips with a specified 87L operation time.
4. Disconnect the fiber Channel 1(2) Tx cable for more than 66 ms but less than 5 seconds.
Expected result: ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1(2) STATUS: “OK”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK STATUS: “n/a”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ PFLL STATUS: “OK”
If fault conditions are applied to the relay (after the channel is brought back) during these tests, it trips with a specified
87L operation time plus 50 to 80 ms required for establishing PFLL after such interruption.
5. Disconnect the fiber Channel 1(2) Tx cable for more than 5 seconds.
Expected result: ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ CHANNEL 1(2) STATUS: “OK”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK STATUS: “n/a”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ PFLL STATUS: “Fail”
6. Reconnect the fiber Channel 1(2) Tx cable and in 6 to 8 seconds confirm that the relays have re-established communi-
cations again with the following status checks:
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS Ö CHANNEL 1(2) STATUS: “OK”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ REMOTE LOOPBACK STATUS: “n/a”
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS ÖØ PFLL STATUS: “OK”
7. Apply a current of 0.5 pu at a frequency 1 to 3% higher or lower than nominal only to local relay phase A to verify that
frequency tracking will not affect PFLL when only one relay has a current input and both relays track frequency. Wait
200 seconds and verify the following: 11
ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS Ö PFLL STATUS: “OK”
ACTUAL VALUES ÖØ METERING ÖØ TRACKING FREQUENCY Ö TRACKING FREQUENCY: actual frequency at both relays
For 3-terminal configuration, the above-indicated tests should be carried out accordingly.
NOTE
The 87L element has adaptive restraint and dual slope characteristics. The pickup slope settings and the breakpoint set-
tings determine the element characteristics. The relay displays both local and remote current magnitudes and angles and
the differential current which helps with start-up activities. When a differential condition is detected, the output operands
from the element will be asserted along with energization of faceplate event indicators.
1. Ensure that relay will not issue any undesired signals to other equipment.
2. Ensure that relays are connected to the proper communication media, communications tests have been performed
and the CHANNEL and PFLL STATUS displays indicate OK.
3. Minimum pickup test with local current only:
• Ensure that all 87L setting are properly entered into the relay and connect a test set to the relay to inject current
into Phase A.
• Slowly increase the current until the relay operates and note the pickup value. The theoretical value of operating
current below the breakpoint is given by the following formula, where P is the pickup setting and S1 is the Slope 1
setting (in decimal format):
2
P
I op = 2 × ------------------2- (EQ 11.1)
1 – 2S 1
• Repeat the above test for different slope and pickup settings, if desired.
• Repeat the above tests for Phases B and C.
4. Minimum pickup test with local current and simulated remote current (pure internal fault simulation):
• Disconnect the local relay from the communications channel.
• Loop back the transmit signal to the receive input on the back of the relay.
• Wait until the CHANNEL and PFLL status displays indicate OK.
• Slowly increase the current until the relay operates and note the pickup value. The theoretical value of operating
current below breakpoint is given by the following formula:
2
2P
I op = -------------------------------------------------------------------------
- (EQ 11.2)
2 2 2
( 1 + TAP ) – 2S 1 ( 1 + TAP )
where TAP represents the CT Tap setting for the corresponding channel.
• Repeat the above test for different slope and pickup settings, if desired.
• During the tests, observe the current phasor at ACTUAL VALUES ÖØ METERING Ö 87L DIFF CURRENT Ö LOCAL IA.
This phasor should also be seen at ACTUAL VALUES ÖØ METERING Ö 87L DIFF CURRENT ÖØ TERMINAL 1(2) IA along
with a phasor of twice the magnitude at ACTUAL VALUES ÖØ METERING Ö 87L DIFF CURRENT ÖØ IA DIFF.
• Repeat the above tests for Phases B and C.
• Restore the communication circuits to normal.
Download the UR Test software from the GE Multilin website (http://www.GEindustrial.com/multilin) or contact GE
Multilin for information about the UR current differential test program which allows the user to simulate different
NOTE
operating conditions for verifying correct responses of the relays during commissioning activities.
5. Verify and record that both relays have established communications by performing the following status check thorough
the ACTUAL VALUES Ö STATUS ÖØ CHANNEL TESTS menu:
CHANNEL 1(2) STATUS: “OK”
6. At the remote relay, make the following changes in the SETTINGS ÖØ GROUPED ELEMENTS ÖØ LINE DIFFERENTIAL ELE-
MENTS ÖØ CURRENT DIFFERENTIAL menu:
CURRENT DIFF DTT: “Enabled”
7. At the Local relay, make the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUT N1 menu:
CONTACT OUTPUT N1 OPERATE: “87L DIFF RECVD DTT A”
CONTACT OUTPUT N2 OPERATE: “87L DIFF RECVD DTT B”
CONTACT OUTPUT N3 OPERATE: “87L DIFF RECVD DTT C”
8. At the Local relay, verify that ACTUAL VALUES Ö STATUS ÖØ CONTACT OUTPUTS ÖØ Cont Op N1 is in the “Off” state.
9. Apply current to phase A of the remote relay and increase until 87L operates.
10. At the Local relay, observe ACTUAL VALUES Ö STATUS ÖØ CONTACT OUTPUTS ÖØ Cont Op N1 is now in the “On” state.
11. Repeat steps 8 through 10 for phases A and B and observe Contact Outputs N2 and N3, respectively.
12. Repeat steps 8 through 11 with the Remote and Local relays inter-changed.
13. Make the following setting change in the SETTINGS ÖØ GROUPED ELEMENTS ÖØ LINE DIFFERENTIAL ELEMENTS Ö CUR-
RENT DIFFERENTIAL menu of both relays:
14. At the Remote relay, set SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUT N1 ÖØ CONTACT OUTPUT N1 OPERATE to
the CURRENT DIFF KEY DTT operand.
15. At the Local relay, observe under the ACTUAL VALUES Ö STATUS ÖØ CONTACT OUTPUTS menu that CONTACT OUTPUT
N1, N2 and N3 are “Off”.
16. At the Remote relay, set SETTINGS ÖØ TESTING ÖØ FORCE CONTACT INPUTS Ö FORCE Cont Ip N1 to “Closed”.
17. At the Local relay, observe under ACTUAL VALUES Ö STATUS ÖØ CONTACT OUTPUTS that CONTACT OUTPUT N1, N2 and
N3 are now “On”.
18. At both the Local and Remote relays, return all settings to normal.
b) FINAL TESTS
As proper operation of the relay is fundamentally dependent on the correct installation and wiring of the CTs, it must be con-
firmed that correct data is brought into the relays by an on-load test in which simultaneous measurements of current and
voltage phasors are made at all line terminals. These phasors and differential currents can be monitored at the ACTUAL VAL-
UES ÖØ METERING Ö 87L DIFFERENTIAL CURRENT menu where all current magnitudes and angles can be observed and con-
clusions of proper relay interconnections can be made.
A
Table A–1: FLEXANALOG DATA ITEMS (Sheet 1 of 11)
ADDRESS FLEXANALOG NAME UNITS DESCRIPTION
5688 Channel 1 Asymmetry --- Channel 1 asymmetry
5690 Channel 2 Asymmetry --- Channel 2 asymmetry
6144 SRC 1 Ia RMS Amps Source 1 phase A current RMS
6146 SRC 1 Ib RMS Amps Source 1 phase B current RMS
6148 SRC 1 Ic RMS Amps Source 1 phase C current RMS
6150 SRC 1 In RMS Amps Source 1 neutral current RMS
6152 SRC 1 Ia Mag Amps Source 1 phase A current magnitude
6154 SRC 1 Ia Angle Degrees Source 1 phase A current angle
6155 SRC 1 Ib Mag Amps Source 1 phase B current magnitude
6157 SRC 1 Ib Angle Degrees Source 1 phase B current angle
6158 SRC 1 Ic Mag Amps Source 1 phase C current magnitude
6160 SRC 1 Ic Angle Degrees Source 1 phase C current angle
6161 SRC 1 In Mag Amps Source 1 neutral current magnitude
6163 SRC 1 In Angle Degrees Source 1 neutral current angle
6164 SRC 1 Ig RMS Amps Source 1 ground current RMS
6166 SRC 1 Ig Mag Degrees Source 1 ground current magnitude
6168 SRC 1 Ig Angle Amps Source 1 ground current angle
6169 SRC 1 I_0 Mag Degrees Source 1 zero-sequence current magnitude
6171 SRC 1 I_0 Angle Amps Source 1 zero-sequence current angle
6172 SRC 1 I_1 Mag Degrees Source 1 positive-sequence current magnitude
6174 SRC 1 I_1 Angle Amps Source 1 positive-sequence current angle
6175 SRC 1 I_2 Mag Degrees Source 1 negative-sequence current magnitude
6177 SRC 1 I_2 Angle Amps Source 1 negative-sequence current angle
6178 SRC 1 Igd Mag Degrees Source 1 differential ground current magnitude
6180 SRC 1 Igd Angle Amps Source 1 differential ground current angle
6208 SRC 2 Ia RMS Amps Source 2 phase A current RMS
6210 SRC 2 Ib RMS Amps Source 2 phase B current RMS
6212 SRC 2 Ic RMS Amps Source 2 phase C current RMS
6214 SRC 2 In RMS Amps Source 2 neutral current RMS
6216 SRC 2 Ia Mag Amps Source 2 phase A current magnitude
6218 SRC 2 Ia Angle Degrees Source 2 phase A current angle
6219 SRC 2 Ib Mag Amps Source 2 phase B current magnitude
6221 SRC 2 Ib Angle Degrees Source 2 phase B current angle
6222 SRC 2 Ic Mag Amps Source 2 phase C current magnitude
6224 SRC 2 Ic Angle Degrees Source 2 phase C current angle
6225 SRC 2 In Mag Amps Source 2 neutral current magnitude
6227 SRC 2 In Angle Degrees Source 2 neutral current angle
6228 SRC 2 Ig RMS Amps Source 2 ground current RMS
6230 SRC 2 Ig Mag Degrees Source 2 ground current magnitude
6232 SRC 2 Ig Angle Amps Source 2 ground current angle
6233 SRC 2 I_0 Mag Degrees Source 2 zero-sequence current magnitude
6235 SRC 2 I_0 Angle Amps Source 2 zero-sequence current angle
6236 SRC 2 I_1 Mag Degrees Source 2 positive-sequence current magnitude
6238 SRC 2 I_1 Angle Amps Source 2 positive-sequence current angle
6239 SRC 2 I_2 Mag Degrees Source 2 negative-sequence current magnitude
A ADDRESS
6241
FLEXANALOG NAME
SRC 2 I_2 Angle
UNITS
Amps
DESCRIPTION
Source 2 negative-sequence current angle
6242 SRC 2 Igd Mag Degrees Source 2 differential ground current magnitude
6244 SRC 2 Igd Angle Amps Source 2 differential ground current angle
6272 SRC 3 Ia RMS Amps Source 3 phase A current RMS
6274 SRC 3 Ib RMS Amps Source 3 phase B current RMS
6276 SRC 3 Ic RMS Amps Source 3 phase C current RMS
6278 SRC 3 In RMS Amps Source 3 neutral current RMS
6280 SRC 3 Ia Mag Amps Source 3 phase A current magnitude
6282 SRC 3 Ia Angle Degrees Source 3 phase A current angle
6283 SRC 3 Ib Mag Amps Source 3 phase B current magnitude
6285 SRC 3 Ib Angle Degrees Source 3 phase B current angle
6286 SRC 3 Ic Mag Amps Source 3 phase C current magnitude
6288 SRC 3 Ic Angle Degrees Source 3 phase C current angle
6289 SRC 3 In Mag Amps Source 3 neutral current magnitude
6291 SRC 3 In Angle Degrees Source 3 neutral current angle
6292 SRC 3 Ig RMS Amps Source 3 ground current RMS
6294 SRC 3 Ig Mag Degrees Source 3 ground current magnitude
6296 SRC 3 Ig Angle Amps Source 3 ground current angle
6297 SRC 3 I_0 Mag Degrees Source 3 zero-sequence current magnitude
6299 SRC 3 I_0 Angle Amps Source 3 zero-sequence current angle
6300 SRC 3 I_1 Mag Degrees Source 3 positive-sequence current magnitude
6302 SRC 3 I_1 Angle Amps Source 3 positive-sequence current angle
6303 SRC 3 I_2 Mag Degrees Source 3 negative-sequence current magnitude
6305 SRC 3 I_2 Angle Amps Source 3 negative-sequence current angle
6306 SRC 3 Igd Mag Degrees Source 3 differential ground current magnitude
6308 SRC 3 Igd Angle Amps Source 3 differential ground current angle
6336 SRC 4 Ia RMS Amps Source 4 phase A current RMS
6338 SRC 4 Ib RMS Amps Source 4 phase B current RMS
6340 SRC 4 Ic RMS Amps Source 4 phase C current RMS
6342 SRC 4 In RMS Amps Source 4 neutral current RMS
6344 SRC 4 Ia Mag Amps Source 4 phase A current magnitude
6346 SRC 4 Ia Angle Degrees Source 4 phase A current angle
6347 SRC 4 Ib Mag Amps Source 4 phase B current magnitude
6349 SRC 4 Ib Angle Degrees Source 4 phase B current angle
6350 SRC 4 Ic Mag Amps Source 4 phase C current magnitude
6352 SRC 4 Ic Angle Degrees Source 4 phase C current angle
6353 SRC 4 In Mag Amps Source 4 neutral current magnitude
6355 SRC 4 In Angle Degrees Source 4 neutral current angle
6356 SRC 4 Ig RMS Amps Source 4 ground current RMS
6358 SRC 4 Ig Mag Degrees Source 4 ground current magnitude
6360 SRC 4 Ig Angle Amps Source 4 ground current angle
6361 SRC 4 I_0 Mag Degrees Source 4 zero-sequence current magnitude
6363 SRC 4 I_0 Angle Amps Source 4 zero-sequence current angle
6364 SRC 4 I_1 Mag Degrees Source 4 positive-sequence current magnitude
6366 SRC 4 I_1 Angle Amps Source 4 positive-sequence current angle
6367 SRC 4 I_2 Mag Degrees Source 4 negative-sequence current magnitude
6369 SRC 4 I_2 Angle Amps Source 4 negative-sequence current angle
A ADDRESS
6750
FLEXANALOG NAME
SRC 2 Vx RMS
UNITS
Volts
DESCRIPTION
Source 2 auxiliary voltage RMS
6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude
6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle
6755 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude
6757 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle
6758 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude
6760 SRC 2 V_1 Angle Degrees Source 2 positive-sequence voltage angle
6761 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude
6763 SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle
6784 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS
6786 SRC 3 Vbg RMS Volts Source 3 phase BG voltage RMS
6788 SRC 3 Vcg RMS Volts Source 3 phase CG voltage RMS
6790 SRC 3 Vag Mag Volts Source 3 phase AG voltage magnitude
6792 SRC 3 Vag Angle Degrees Source 3 phase AG voltage angle
6793 SRC 3 Vbg Mag Volts Source 3 phase BG voltage magnitude
6795 SRC 3 Vbg Angle Degrees Source 3 phase BG voltage angle
6796 SRC 3 Vcg Mag Volts Source 3 phase CG voltage magnitude
6798 SRC 3 Vcg Angle Degrees Source 3 phase CG voltage angle
6799 SRC 3 Vab RMS Volts Source 3 phase AB voltage RMS
6801 SRC 3 Vbc RMS Volts Source 3 phase BC voltage RMS
6803 SRC 3 Vca RMS Volts Source 3 phase CA voltage RMS
6805 SRC 3 Vab Mag Volts Source 3 phase AB voltage magnitude
6807 SRC 3 Vab Angle Degrees Source 3 phase AB voltage angle
6808 SRC 3 Vbc Mag Volts Source 3 phase BC voltage magnitude
6810 SRC 3 Vbc Angle Degrees Source 3 phase BC voltage angle
6811 SRC 3 Vca Mag Volts Source 3 phase CA voltage magnitude
6813 SRC 3 Vca Angle Degrees Source 3 phase CA voltage angle
6814 SRC 3 Vx RMS Volts Source 3 auxiliary voltage RMS
6816 SRC 3 Vx Mag Volts Source 3 auxiliary voltage magnitude
6818 SRC 3 Vx Angle Degrees Source 3 auxiliary voltage angle
6819 SRC 3 V_0 Mag Volts Source 3 zero-sequence voltage magnitude
6821 SRC 3 V_0 Angle Degrees Source 3 zero-sequence voltage angle
6822 SRC 3 V_1 Mag Volts Source 3 positive-sequence voltage magnitude
6824 SRC 3 V_1 Angle Degrees Source 3 positive-sequence voltage angle
6825 SRC 3 V_2 Mag Volts Source 3 negative-sequence voltage magnitude
6827 SRC 3 V_2 Angle Degrees Source 3 negative-sequence voltage angle
6848 SRC 4 Vag RMS Volts Source 4 phase AG voltage RMS
6850 SRC 4 Vbg RMS Volts Source 4 phase BG voltage RMS
6852 SRC 4 Vcg RMS Volts Source 4 phase CG voltage RMS
6854 SRC 4 Vag Mag Volts Source 4 phase AG voltage magnitude
6856 SRC 4 Vag Angle Degrees Source 4 phase AG voltage angle
6857 SRC 4 Vbg Mag Volts Source 4 phase BG voltage magnitude
6859 SRC 4 Vbg Angle Degrees Source 4 phase BG voltage angle
6860 SRC 4 Vcg Mag Volts Source 4 phase CG voltage magnitude
6862 SRC 4 Vcg Angle Degrees Source 4 phase CG voltage angle
6863 SRC 4 Vab RMS Volts Source 4 phase AB voltage RMS
6865 SRC 4 Vbc RMS Volts Source 4 phase BC voltage RMS
A ADDRESS
7227
FLEXANALOG NAME
SRC 2 Phase C PF
UNITS
---
DESCRIPTION
Source 2 phase C power factor
7232 SRC 3 P Watts Source 3 three-phase real power
7234 SRC 3 Pa Watts Source 3 phase A real power
7236 SRC 3 Pb Watts Source 3 phase B real power
7238 SRC 3 Pc Watts Source 3 phase C real power
7240 SRC 3 Q Vars Source 3 three-phase reactive power
7242 SRC 3 Qa Vars Source 3 phase A reactive power
7244 SRC 3 Qb Vars Source 3 phase B reactive power
7246 SRC 3 Qc Vars Source 3 phase C reactive power
7248 SRC 3 S VA Source 3 three-phase apparent power
7250 SRC 3 Sa VA Source 3 phase A apparent power
7252 SRC 3 Sb VA Source 3 phase B apparent power
7254 SRC 3 Sc VA Source 3 phase C apparent power
7256 SRC 3 PF --- Source 3 three-phase power factor
7257 SRC 3 Phase A PF --- Source 3 phase A power factor
7258 SRC 3 Phase B PF --- Source 3 phase B power factor
7259 SRC 3 Phase C PF --- Source 3 phase C power factor
7264 SRC 4 P Watts Source 4 three-phase real power
7266 SRC 4 Pa Watts Source 4 phase A real power
7268 SRC 4 Pb Watts Source 4 phase B real power
7270 SRC 4 Pc Watts Source 4 phase C real power
7272 SRC 4 Q Vars Source 4 three-phase reactive power
7274 SRC 4 Qa Vars Source 4 phase A reactive power
7276 SRC 4 Qb Vars Source 4 phase B reactive power
7278 SRC 4 Qc Vars Source 4 phase C reactive power
7280 SRC 4 S VA Source 4 three-phase apparent power
7282 SRC 4 Sa VA Source 4 phase A apparent power
7284 SRC 4 Sb VA Source 4 phase B apparent power
7286 SRC 4 Sc VA Source 4 phase C apparent power
7288 SRC 4 PF --- Source 4 three-phase power factor
7289 SRC 4 Phase A PF --- Source 4 phase A power factor
7290 SRC 4 Phase B PF --- Source 4 phase B power factor
7291 SRC 4 Phase C PF --- Source 4 phase C power factor
7552 SRC 1 Frequency Hz Source 1 frequency
7553 SRC 2 Frequency Hz Source 2 frequency
7554 SRC 3 Frequency Hz Source 3 frequency
7555 SRC 4 Frequency Hz Source 4 frequency
7680 SRC 1 Demand Ia Amps Source 1 phase A current demand
7682 SRC 1 Demand Ib Amps Source 1 phase B current demand
7684 SRC 1 Demand Ic Amps Source 1 phase C current demand
7686 SRC 1 Demand Watt Watts Source 1 real power demand
7688 SRC 1 Demand var Vars Source 1 reactive power demand
7690 SRC 1 Demand Va VA Source 1 apparent power demand
7696 SRC 2 Demand Ia Amps Source 2 phase A current demand
7698 SRC 2 Demand Ib Amps Source 2 phase B current demand
7700 SRC 2 Demand Ic Amps Source 2 phase C current demand
7702 SRC 2 Demand Watt Watts Source 2 real power demand
A ADDRESS
9346
FLEXANALOG NAME
Local IB Mag
UNITS
Amps
DESCRIPTION
Local terminal phase B current magnitude
9348 Local IC Mag Amps Local terminal phase C current magnitude
9350 Terminal 1 IA Mag Amps Remote terminal 1 phase A current magnitude
9352 Terminal 1 IB Mag Amps Remote terminal 1 phase B current magnitude
9354 Terminal 1 IC Mag Amps Remote terminal 1 phase C current magnitude
9356 Terminal 2 IA Mag Amps Remote terminal 2 phase A current magnitude
9358 Terminal 2 IB Mag Amps Remote terminal 2 phase B current magnitude
9360 Terminal 2 IC Mag Amps Remote terminal 2 phase C current magnitude
9362 Diff Curr IA Mag Amps Differential current phase A magnitude
9364 Diff Curr IB Mag Amps Differential current phase B magnitude
9366 Diff Curr IC Mag Amps Differential current phase C magnitude
9368 Local IA Angle Degrees Local terminal current phase A angle
9369 Local IB Angle Degrees Local terminal current phase B angle
9370 Local IC Angle Degrees Local terminal current phase C angle
9371 Terminal 1 IA Angle Degrees Remote terminal 1 current phase A angle
9372 Terminal 1 IB Angle Degrees Remote terminal 1 current phase B angle
9373 Terminal 1 IC Angle Degrees Remote terminal 1 current phase C angle
9374 Terminal 2 IA Angle Degrees Remote terminal 2 current phase A angle
9375 Terminal 2 IB Angle Degrees Remote terminal 2 current phase B angle
9376 Terminal 2 IC Angle Degrees Remote terminal 2 current phase C angle
9377 Diff Curr IA Angle Degrees Differential current phase A angle
9378 Diff Curr IB Angle Degrees Differential current phase B angle
9379 Diff Curr IC Angle Degrees Differential current phase C angle
9380 Op Square Curr IA Amps Phase A operating square current
9382 Op Square Curr IB Amps Phase B operating square current
9384 Op Square Curr IC Amps Phase C operating square current
9386 Rest Square Curr IA Amps Phase A restraint square current
9388 Rest Square Curr IB Amps Phase B restraint square current
9390 Rest Square Curr IC Amps Phase C restraint square current
9536 PMU 1 Va Mag Volts Phasor measurement unit 1 phase A voltage magnitude
9538 PMU 1 Va Angle Degrees Phasor measurement unit 1 phase A voltage angle
9539 PMU 1 Vb Mag Volts Phasor measurement unit 1 phase B voltage magnitude
9541 PMU 1 Vb Angle Degrees Phasor measurement unit 1 phase B voltage angle
9542 PMU 1 Vc Mag Volts Phasor measurement unit 1 phase C voltage magnitude
9544 PMU 1 Vc Angle Degrees Phasor measurement unit 1 phase C voltage angle
9545 PMU 1 Vx Mag Volts Phasor measurement unit 1 auxiliary voltage magnitude
9547 PMU 1 Vx Angle Degrees Phasor measurement unit 1 auxiliary voltage angle
9548 PMU 1 V1 Mag Volts Phasor measurement unit 1 positive-sequence voltage magnitude
9550 PMU 1 V1 Angle Degrees Phasor measurement unit 1 positive-sequence voltage angle
9551 PMU 1 V2 Mag Volts Phasor measurement unit 1 negative-sequence voltage magnitude
9553 PMU 1 V2 Angle Degrees Phasor measurement unit 1 negative-sequence voltage angle
9554 PMU 1 V0 Mag Volts Phasor measurement unit 1 zero-sequence voltage magnitude
9556 PMU 1 V0 Angle Degrees Phasor measurement unit 1 zero-sequence voltage angle
9557 PMU 1 Ia Mag Amps Phasor measurement unit 1 phase A current magnitude
9559 PMU 1 Ia Angle Degrees Phasor measurement unit 1 phase A current angle
9560 PMU 1 Ib Mag Amps Phasor measurement unit 1 phase B current magnitude
9562 PMU 1 Ib Angle Degrees Phasor measurement unit 1 phase B current angle
A ADDRESS
13562
FLEXANALOG NAME
RTD Inputs 11 Value
UNITS
---
DESCRIPTION
RTD input 11 actual value
13563 RTD Inputs 12 Value --- RTD input 12 actual value
13564 RTD Inputs 13 Value --- RTD input 13 actual value
13565 RTD Inputs 14 Value --- RTD input 14 actual value
13566 RTD Inputs 15 Value --- RTD input 15 actual value
13567 RTD Inputs 16 Value --- RTD input 16 actual value
13568 RTD Inputs 17 Value --- RTD input 17 actual value
13569 RTD Inputs 18 Value --- RTD input 18 actual value
13570 RTD Inputs 19 Value --- RTD input 19 actual value
13571 RTD Inputs 20 Value --- RTD input 20 actual value
13572 RTD Inputs 21 Value --- RTD input 21 actual value
13573 RTD Inputs 22 Value --- RTD input 22 actual value
13574 RTD Inputs 23 Value --- RTD input 23 actual value
13575 RTD Inputs 24 Value --- RTD input 24 actual value
13576 RTD Inputs 25 Value --- RTD input 25 actual value
13577 RTD Inputs 26 Value --- RTD input 26 actual value
13578 RTD Inputs 27 Value --- RTD input 27 actual value
13579 RTD Inputs 28 Value --- RTD input 28 actual value
13580 RTD Inputs 29 Value --- RTD input 29 actual value
13581 RTD Inputs 30 Value --- RTD input 30 actual value
13582 RTD Inputs 31 Value --- RTD input 31 actual value
13583 RTD Inputs 32 Value --- RTD input 32 actual value
13584 RTD Inputs 33 Value --- RTD input 33 actual value
13585 RTD Inputs 34 Value --- RTD input 34 actual value
13586 RTD Inputs 35 Value --- RTD input 35 actual value
13587 RTD Inputs 36 Value --- RTD input 36 actual value
13588 RTD Inputs 37 Value --- RTD input 37 actual value
13589 RTD Inputs 38 Value --- RTD input 38 actual value
13590 RTD Inputs 39 Value --- RTD input 39 actual value
13591 RTD Inputs 40 Value --- RTD input 40 actual value
13592 RTD Inputs 41 Value --- RTD input 41 actual value
13593 RTD Inputs 42 Value --- RTD input 42 actual value
13594 RTD Inputs 43 Value --- RTD input 43 actual value
13595 RTD Inputs 44 Value --- RTD input 44 actual value
13596 RTD Inputs 45 Value --- RTD input 45 actual value
13597 RTD Inputs 46 Value --- RTD input 46 actual value
13598 RTD Inputs 47 Value --- RTD input 47 actual value
13599 RTD Inputs 48 Value --- RTD input 48 actual value
24459 Active Setting Group --- Current setting group
32768 Tracking Frequency Hz Tracking frequency
39425 FlexElement 1 Value --- FlexElement™ 1 actual value
39427 FlexElement 2 Value --- FlexElement™ 2 actual value
39429 FlexElement 3 Value --- FlexElement™ 3 actual value
39431 FlexElement 4 Value --- FlexElement™ 4 actual value
39433 FlexElement 5 Value --- FlexElement™ 5 actual value
39435 FlexElement 6 Value --- FlexElement™ 6 actual value
39437 FlexElement 7 Value --- FlexElement™ 7 actual value
The UR-series relays support a number of communications protocols to allow connection to equipment such as personal
computers, RTUs, SCADA masters, and programmable logic controllers. The Modicon Modbus RTU protocol is the most
basic protocol supported by the UR. Modbus is available via RS232 or RS485 serial links or via ethernet (using the Mod-
bus/TCP specification). The following description is intended primarily for users who wish to develop their own master com-
munication drivers and applies to the serial Modbus RTU protocol. Note that:
• The UR always acts as a slave device, meaning that it never initiates communications; it only listens and responds to B
requests issued by a master computer.
• For Modbus®, a subset of the Remote Terminal Unit (RTU) protocol format is supported that allows extensive monitor-
ing, programming, and control functions using read and write register commands.
The Modbus® RTU protocol is hardware-independent so that the physical layer can be any of a variety of standard hard-
ware configurations including RS232 and RS485. The relay includes a faceplate (front panel) RS232 port and two rear ter-
minal communications ports that may be configured as RS485, fiber optic, 10Base-T, or 10Base-F. Data flow is half-duplex
in all configurations. See chapter 3 for details on communications wiring.
Each data byte is transmitted in an asynchronous format consisting of 1 start bit, 8 data bits, 1 stop bit, and possibly 1 parity
bit. This produces a 10 or 11 bit data frame. This can be important for transmission through modems at high bit rates (11 bit
data frames are not supported by many modems at baud rates greater than 300).
The baud rate and parity are independently programmable for each communications port. Baud rates of 300, 1200, 2400,
4800, 9600, 14400, 19200, 28800, 33600, 38400, 57600, or 115200 bps are available. Even, odd, and no parity are avail-
able. Refer to the Communications section of chapter 5 for further details.
The master device in any system must know the address of the slave device with which it is to communicate. The relay will
not act on a request from a master if the address in the request does not match the relay’s slave address (unless the
address is the broadcast address – see below).
A single setting selects the slave address used for all ports, with the exception that for the faceplate port, the relay will
accept any address when the Modbus® RTU protocol is used.
Communications takes place in packets which are groups of asynchronously framed byte data. The master transmits a
packet to the slave and the slave responds with a packet. The end of a packet is marked by dead-time on the communica-
tions line. The following describes general format for both transmit and receive packets. For exact details on packet format-
ting, refer to subsequent sections describing each function code.
• SLAVE ADDRESS: This is the address of the slave device that is intended to receive the packet sent by the master
and to perform the desired action. Each slave device on a communications bus must have a unique address to prevent
bus contention. All of the relay’s ports have the same address which is programmable from 1 to 254; see chapter 5 for
details. Only the addressed slave will respond to a packet that starts with its address. Note that the faceplate port is an
exception to this rule; it will act on a message containing any slave address.
A master transmit packet with slave address 0 indicates a broadcast command. All slaves on the communication link
take action based on the packet, but none respond to the master. Broadcast mode is only recognized when associated
with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored.
• FUNCTION CODE: This is one of the supported functions codes of the unit which tells the slave what action to per-
form. See the Supported Function Codes section for complete details. An exception response from the slave is indi-
cated by setting the high order bit of the function code in the response packet. See the Exception Responses section
for further details.
• DATA: This will be a variable number of bytes depending on the function code. This may include actual values, set-
tings, or addresses sent by the master to the slave or by the slave to the master.
• CRC: This is a two byte error checking code. The RTU version of Modbus® includes a 16-bit cyclic redundancy check
B (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device
receives a packet in which an error is indicated by the CRC, the slave device will not act upon or respond to the packet
thus preventing any erroneous operations. See the CRC-16 Algorithm section for details on calculating the CRC.
• DEAD TIME: A packet is terminated when no data is received for a period of 3.5 byte transmission times (about 15 ms
at 2400 bps, 2 ms at 19200 bps, and 300 µs at 115200 bps). Consequently, the transmitting device must not allow gaps
between bytes longer than this interval. Once the dead time has expired without a new byte transmission, all slaves
start listening for a new packet from the master except for the addressed slave.
The CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one contin-
uous binary number. This number is first shifted left 16 bits and then divided by a characteristic polynomial
(11000000000000101B). The 16-bit remainder of the division is appended to the end of the packet, MSByte first. The
resulting packet including CRC, when divided by the same polynomial at the receiver will give a zero remainder if no trans-
mission errors have occurred. This algorithm requires the characteristic polynomial to be reverse bit ordered. The most sig-
nificant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder.
A C programming language implementation of the CRC algorithm will be provided upon request.
Modbus® officially defines function codes from 1 to 127 though only a small subset is generally needed. The relay supports
some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail.
This function code allows the master to read one or more consecutive data registers (actual values or settings) from a relay.
Data registers are always 16-bit (two-byte) values transmitted with high order byte first. The maximum number of registers
that can be read in a single packet is 125. See the Modbus memory map table for exact details on the data registers.
Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The L90 interpretation
allows either function code to be used for reading one or more consecutive data registers. The data starting address will
determine the type of data being read. Function codes 03h and 04h are therefore identical.
The following table shows the format of the master and slave packets. The example shows a master device requesting
three register values starting at address 4050h from slave device 11h (17 decimal); the slave device responds with the val-
ues 40, 300, and 0 from registers 4050h, 4051h, and 4052h, respectively.
This function code allows the master to perform various operations in the relay. Available operations are shown in the Sum-
mary of operation codes table below.
The following table shows the format of the master and slave packets. The example shows a master device requesting the
slave device 11h (17 decimal) to perform a reset. The high and low code value bytes always have the values “FF” and “00”
respectively and are a remnant of the original Modbus definition of this function code.
B
Table B–4: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 05 FUNCTION CODE 05
OPERATION CODE - high 00 OPERATION CODE - high 00
OPERATION CODE - low 01 OPERATION CODE - low 01
CODE VALUE - high FF CODE VALUE - high FF
CODE VALUE - low 00 CODE VALUE - low 00
CRC - low DF CRC - low DF
CRC - high 6A CRC - high 6A
This function code allows the master to modify the contents of a single setting register in an relay. Setting registers are
always 16 bit (two byte) values transmitted high order byte first. The following table shows the format of the master and
slave packets. The example shows a master device storing the value 200 at memory map address 4051h to slave device
11h (17 dec).
This function code allows the master to modify the contents of a one or more consecutive setting registers in a relay. Setting
registers are 16-bit (two byte) values transmitted high order byte first. The maximum number of setting registers that can be
stored in a single packet is 60. The following table shows the format of the master and slave packets. The example shows
a master device storing the value 200 at memory map address 4051h, and the value 1 at memory map address 4052h to
slave device 11h (17 decimal).
B
Table B–7: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXMAPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 10 FUNCTION CODE 10
DATA STARTING ADDRESS - hi 40 DATA STARTING ADDRESS - hi 40
DATA STARTING ADDRESS - lo 51 DATA STARTING ADDRESS - lo 51
NUMBER OF SETTINGS - hi 00 NUMBER OF SETTINGS - hi 00
NUMBER OF SETTINGS - lo 02 NUMBER OF SETTINGS - lo 02
BYTE COUNT 04 CRC - lo 07
DATA #1 - high order byte 00 CRC - hi 64
DATA #1 - low order byte C8
DATA #2 - high order byte 00
DATA #2 - low order byte 01
CRC - low order byte 12
CRC - high order byte 62
Programming or operation errors usually happen because of illegal data in a packet. These errors result in an exception
response from the slave. The slave detecting one of these errors sends a response packet to the master with the high order
bit of the function code set to 1.
The following table shows the format of the master and slave packets. The example shows a master device sending the
unsupported function code 39h to slave device 11.
a) DESCRIPTION
The UR relay has a generic file transfer facility, meaning that you use the same method to obtain all of the different types of
files from the unit. The Modbus registers that implement file transfer are found in the "Modbus File Transfer (Read/Write)"
and "Modbus File Transfer (Read Only)" modules, starting at address 3100 in the Modbus Memory Map. To read a file from
the UR relay, use the following steps:
B 1. Write the filename to the "Name of file to read" register using a write multiple registers command. If the name is shorter
than 80 characters, you may write only enough registers to include all the text of the filename. Filenames are not case
sensitive.
2. Repeatedly read all the registers in "Modbus File Transfer (Read Only)" using a read multiple registers command. It is
not necessary to read the entire data block, since the UR relay will remember which was the last register you read. The
"position" register is initially zero and thereafter indicates how many bytes (2 times the number of registers) you have
read so far. The "size of..." register indicates the number of bytes of data remaining to read, to a maximum of 244.
3. Keep reading until the "size of..." register is smaller than the number of bytes you are transferring. This condition indi-
cates end of file. Discard any bytes you have read beyond the indicated block size.
4. If you need to re-try a block, read only the "size of.." and "block of data", without reading the position. The file pointer is
only incremented when you read the position register, so the same data block will be returned as was read in the pre-
vious operation. On the next read, check to see if the position is where you expect it to be, and discard the previous
block if it is not (this condition would indicate that the UR relay did not process your original read request).
The UR relay retains connection-specific file transfer information, so files may be read simultaneously on multiple Modbus
connections.
b) OTHER PROTOCOLS
All the files available via Modbus may also be retrieved using the standard file transfer mechanisms in other protocols (for
example, TFTP or MMS).
Command and setting passwords each have a 30 minute timer. Each timer starts when you enter the particular password,
and is re-started whenever you use it. For example, writing a setting re-starts the setting password timer and writing a com-
mand register or forcing a coil re-starts the command password timer. The value read at memory location 4010 can be used
to confirm whether a command password is enabled or disabled (a value of 0 represents disabled). The value read at mem-
ory location 4011 can be used to confirm whether a setting password is enabled or disabled.
Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which
the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the
B passwords must be re-entered after disconnecting and re-connecting on TCP/IP.
B 0421
0422
Virtual Input 34 State
Virtual Input 35 State
0 to 1
0 to 1
---
---
1
1
F108
F108
0 (Off)
0 (Off)
0423 Virtual Input 36 State 0 to 1 --- 1 F108 0 (Off)
0424 Virtual Input 37 State 0 to 1 --- 1 F108 0 (Off)
0425 Virtual Input 38 State 0 to 1 --- 1 F108 0 (Off)
0426 Virtual Input 39 State 0 to 1 --- 1 F108 0 (Off)
0427 Virtual Input 40 State 0 to 1 --- 1 F108 0 (Off)
0428 Virtual Input 41 State 0 to 1 --- 1 F108 0 (Off)
0429 Virtual Input 42 State 0 to 1 --- 1 F108 0 (Off)
042A Virtual Input 43 State 0 to 1 --- 1 F108 0 (Off)
042B Virtual Input 44 State 0 to 1 --- 1 F108 0 (Off)
042C Virtual Input 45 State 0 to 1 --- 1 F108 0 (Off)
042D Virtual Input 46 State 0 to 1 --- 1 F108 0 (Off)
042E Virtual Input 47 State 0 to 1 --- 1 F108 0 (Off)
042F Virtual Input 48 State 0 to 1 --- 1 F108 0 (Off)
0430 Virtual Input 49 State 0 to 1 --- 1 F108 0 (Off)
0431 Virtual Input 50 State 0 to 1 --- 1 F108 0 (Off)
0432 Virtual Input 51 State 0 to 1 --- 1 F108 0 (Off)
0433 Virtual Input 52 State 0 to 1 --- 1 F108 0 (Off)
0434 Virtual Input 53 State 0 to 1 --- 1 F108 0 (Off)
0435 Virtual Input 54 State 0 to 1 --- 1 F108 0 (Off)
0436 Virtual Input 55 State 0 to 1 --- 1 F108 0 (Off)
0437 Virtual Input 56 State 0 to 1 --- 1 F108 0 (Off)
0438 Virtual Input 57 State 0 to 1 --- 1 F108 0 (Off)
0439 Virtual Input 58 State 0 to 1 --- 1 F108 0 (Off)
043A Virtual Input 59 State 0 to 1 --- 1 F108 0 (Off)
043B Virtual Input 60 State 0 to 1 --- 1 F108 0 (Off)
043C Virtual Input 61 State 0 to 1 --- 1 F108 0 (Off)
043D Virtual Input 62 State 0 to 1 --- 1 F108 0 (Off)
043E Virtual Input 63 State 0 to 1 --- 1 F108 0 (Off)
043F Virtual Input 64 State 0 to 1 --- 1 F108 0 (Off)
Digital Counter States (Read Only Non-Volatile) (8 modules)
0800 Digital Counter 1 Value -2147483647 to --- 1 F004 0
2147483647
0802 Digital Counter 1 Frozen -2147483647 to --- 1 F004 0
2147483647
0804 Digital Counter 1 Frozen Time Stamp 0 to 4294967295 --- 1 F050 0
0806 Digital Counter 1 Frozen Time Stamp us 0 to 4294967295 --- 1 F003 0
0808 ...Repeated for Digital Counter 2
0810 ...Repeated for Digital Counter 3
0818 ...Repeated for Digital Counter 4
0820 ...Repeated for Digital Counter 5
0828 ...Repeated for Digital Counter 6
0830 ...Repeated for Digital Counter 7
0838 ...Repeated for Digital Counter 8
FlexStates (Read Only)
0900 FlexState Bits (16 items) 0 to 65535 --- 1 F001 0
Element States (Read Only)
1000 Element Operate States (64 items) 0 to 65535 --- 1 F502 0
B 26BA
26BB
IEC 61850 GGIO5 uinteger input 11 operand
IEC 61850 GGIO5 uinteger input 12 operand
---
---
---
---
---
---
F612
F612
0
0
26BC IEC 61850 GGIO5 uinteger input 13 operand --- --- --- F612 0
26BD IEC 61850 GGIO5 uinteger input 14 operand --- --- --- F612 0
26BE IEC 61850 GGIO5 uinteger input 15 operand --- --- --- F612 0
26BF IEC 61850 GGIO5 uinteger input 16 operand --- --- --- F612 0
IEC 61850 received integers (read only actual values)
26F0 IEC 61850 received uinteger 1 0 to 4294967295 --- 1 F003 0
26F2 IEC 61850 received uinteger 2 0 to 4294967295 --- 1 F003 0
26F4 IEC 61850 received uinteger 3 0 to 4294967295 --- 1 F003 0
26F6 IEC 61850 received uinteger 4 0 to 4294967295 --- 1 F003 0
26F8 IEC 61850 received uinteger 5 0 to 4294967295 --- 1 F003 0
26FA IEC 61850 received uinteger 6 0 to 4294967295 --- 1 F003 0
26FC IEC 61850 received uinteger 7 0 to 4294967295 --- 1 F003 0
26FE IEC 61850 received uinteger 8 0 to 4294967295 --- 1 F003 0
2700 IEC 61850 received uinteger 9 0 to 4294967295 --- 1 F003 0
2702 IEC 61850 received uinteger 10 0 to 4294967295 --- 1 F003 0
2704 IEC 61850 received uinteger 11 0 to 4294967295 --- 1 F003 0
2706 IEC 61850 received uinteger 12 0 to 4294967295 --- 1 F003 0
2708 IEC 61850 received uinteger 13 0 to 4294967295 --- 1 F003 0
270A IEC 61850 received uinteger 14 0 to 4294967295 --- 1 F003 0
270C IEC 61850 received uinteger 15 0 to 4294967295 --- 1 F003 0
270E IEC 61850 received uinteger 16 0 to 4294967295 --- 1 F003 0
Expanded FlexStates (Read Only)
2B00 FlexStates, one per register (256 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Digital Input/Output states (Read Only)
2D00 Contact Input States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
2D80 Contact Output States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
2E00 Virtual Output States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Remote Input/Output Status (Read Only)
2F00 Remote Device States, one per register (16 items) 0 to 1 --- 1 F155 0 (Offline)
2F80 Remote Input States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
Oscillography Values (Read Only)
3000 Oscillography Number of Triggers 0 to 65535 --- 1 F001 0
3001 Oscillography Available Records 0 to 65535 --- 1 F001 0
3002 Oscillography Last Cleared Date 0 to 400000000 --- 1 F050 0
3004 Oscillography Number Of Cycles Per Record 0 to 65535 --- 1 F001 0
Oscillography Commands (Read/Write Command)
3005 Oscillography Force Trigger 0 to 1 --- 1 F126 0 (No)
3011 Oscillography Clear Data 0 to 1 --- 1 F126 0 (No)
Fault Report Indexing (Read Only Non-Volatile)
3020 Number of Fault Reports 0 to 65535 --- 1 F001 0
Fault Report Actuals (Read Only Non-Volatile) (15 modules)
3030 Fault Report 1 Time 0 to 4294967295 --- 1 F050 0
3032 Fault Report 2 Time 0 to 4294967295 --- 1 F050 0
3034 Fault Report 3 Time 0 to 4294967295 --- 1 F050 0
3036 Fault Report 4 Time 0 to 4294967295 --- 1 F050 0
3038 Fault Report 5 Time 0 to 4294967295 --- 1 F050 0
303A Fault Report 6 Time 0 to 4294967295 --- 1 F050 0
B 34FC
34FD
RTD Input 13 Value
RTD Input 14 Value
-32768 to 32767
-32768 to 32767
°C
°C
1
1
F002
F002
0
0
34FE RTD Input 15 Value -32768 to 32767 °C 1 F002 0
34FF RTD Input 16 Value -32768 to 32767 °C 1 F002 0
3500 RTD Input 17 Value -32768 to 32767 °C 1 F002 0
3501 RTD Input 18 Value -32768 to 32767 °C 1 F002 0
3502 RTD Input 19 Value -32768 to 32767 °C 1 F002 0
3503 RTD Input 20 Value -32768 to 32767 °C 1 F002 0
3504 RTD Input 21 Value -32768 to 32767 °C 1 F002 0
3505 RTD Input 22 Value -32768 to 32767 °C 1 F002 0
3506 RTD Input 23 Value -32768 to 32767 °C 1 F002 0
3507 RTD Input 24 Value -32768 to 32767 °C 1 F002 0
3508 RTD Input 25 Value -32768 to 32767 °C 1 F002 0
3509 RTD Input 26 Value -32768 to 32767 °C 1 F002 0
350A RTD Input 27 Value -32768 to 32767 °C 1 F002 0
350B RTD Input 28 Value -32768 to 32767 °C 1 F002 0
350C RTD Input 29 Value -32768 to 32767 °C 1 F002 0
350D RTD Input 30 Value -32768 to 32767 °C 1 F002 0
350E RTD Input 31 Value -32768 to 32767 °C 1 F002 0
350F RTD Input 32 Value -32768 to 32767 °C 1 F002 0
3510 RTD Input 33 Value -32768 to 32767 °C 1 F002 0
3511 RTD Input 34 Value -32768 to 32767 °C 1 F002 0
3512 RTD Input 35 Value -32768 to 32767 °C 1 F002 0
3513 RTD Input 36 Value -32768 to 32767 °C 1 F002 0
3514 RTD Input 37 Value -32768 to 32767 °C 1 F002 0
3515 RTD Input 38 Value -32768 to 32767 °C 1 F002 0
3516 RTD Input 39 Value -32768 to 32767 °C 1 F002 0
3517 RTD Input 40 Value -32768 to 32767 °C 1 F002 0
3518 RTD Input 41 Value -32768 to 32767 °C 1 F002 0
3519 RTD Input 42 Value -32768 to 32767 °C 1 F002 0
351A RTD Input 43 Value -32768 to 32767 °C 1 F002 0
351B RTD Input 44 Value -32768 to 32767 °C 1 F002 0
351C RTD Input 45 Value -32768 to 32767 °C 1 F002 0
351D RTD Input 46 Value -32768 to 32767 °C 1 F002 0
351E RTD Input 47 Value -32768 to 32767 °C 1 F002 0
351F RTD Input 48 Value -32768 to 32767 °C 1 F002 0
Passwords (Read/Write Command)
4000 Command Password Setting 0 to 4294967295 --- 1 F003 0
Passwords (Read/Write Setting)
4002 Setting Password Setting 0 to 4294967295 --- 1 F003 0
Passwords (Read/Write)
4008 Command Password Entry 0 to 4294967295 --- 1 F003 0
400A Setting Password Entry 0 to 4294967295 --- 1 F003 0
Passwords (read only actual values)
4010 Command password status 0 to 1 --- 1 F102 0 (Disabled)
4011 Setting password status 0 to 1 --- 1 F102 0 (Disabled)
Passwords (read/write settings)
4012 Control password access timeout 5 to 480 minutes 1 F001 5
4013 Setting password access timeout 5 to 480 minutes 1 F001 30
B 40C0
40C1
DNP IIN time synchronization bit period
DNP message fragment size
1 to 10080
30 to 2048
min
---
1
1
F001
F001
1440
240
40C2 DNP client address 3 0 to 4294967295 --- 1 F003 0
40C4 DNP client address 4 0 to 4294967295 --- 1 F003 0
40C6 DNP client address 5 0 to 4294967295 --- 1 F003 0
40C8 DNP number of paired binary output control points 0 to 32 --- 1 F001 0
40C9 DNP TCP connection timeout 10 to 65535 --- 1 F001 120
40CA Reserved (22 items) 0 to 1 --- 1 F001 0
40E0 TCP port number for the IEC 60870-5-104 protocol 1 to 65535 --- 1 F001 2404
40E1 IEC 60870-5-104 protocol function 0 to 1 --- 1 F102 0 (Disabled)
40E2 IEC 60870-5-104 protocol common address of ASDU 0 to 65535 --- 1 F001 0
40E3 IEC 60870-5-104 protocol cyclic data transmit period 1 to 65535 s 1 F001 60
40E4 IEC 60870-5-104 current default threshold 0 to 65535 --- 1 F001 30000
40E6 IEC 60870-5-104 voltage default threshold 0 to 65535 --- 1 F001 30000
40E8 IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EA IEC 60870-5-104 energy default threshold 0 to 65535 --- 1 F001 30000
40EC IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EE IEC 60870-5-104 other default threshold 0 to 65535 --- 1 F001 30000
40F0 IEC 60870-5-104 client address (5 items) 0 to 4294967295 --- 1 F003 0
4104 IEC 60870-5-104 redundancy port 0 to 1 --- 1 F126 0 (No)
4005 Reserved (59 items) 0 to 1 --- 1 F001 0
4140 DNP object 1 default variation 1 to 2 --- 1 F001 2
4141 DNP object 2 default variation 1 to 3 --- 1 F001 2
4142 DNP object 20 default variation 0 to 3 --- 1 F523 0 (1)
4143 DNP object 21 default variation 0 to 3 --- 1 F524 0 (1)
4144 DNP object 22 default variation 0 to 3 --- 1 F523 0 (1)
4145 DNP object 23 default variation 0 to 3 --- 1 F523 0 (1)
4146 DNP object 30 default variation 1 to 5 --- 1 F001 1
4147 DNP object 32 default variation 0 to 5 --- 1 F525 0 (1)
Ethernet switch (Read/Write Setting)
4148 Ethernet switch IP address 0 to 4294967295 --- 1 F003 3232235778
414A Ethernet switch Modbus IP port number 1 to 65535 --- 1 F001 502
414B Ethernet switch Port 1 Events 0 to 1 --- 1 F102 0 (Disabled)
414C Ethernet switch Port 2 Events 0 to 1 --- 1 F102 0 (Disabled)
414D Ethernet switch Port 3 Events 0 to 1 --- 1 F102 0 (Disabled)
414E Ethernet switch Port 4 Events 0 to 1 --- 1 F102 0 (Disabled)
414F Ethernet switch Port 5 Events 0 to 1 --- 1 F102 0 (Disabled)
4150 Ethernet switch Port 6 Events 0 to 1 --- 1 F102 0 (Disabled)
Ethernet switch (Read Only Actual Values)
4151 Ethernet switch MAC address --- --- 1 F072 0
4154 Ethernet switch Port 1 Status 0 to 2 --- 1 F134 0 (Fail)
4155 Ethernet switch Port 2 Status 0 to 2 --- 1 F134 0 (Fail)
4156 Ethernet switch Port 3 Status 0 to 2 --- 1 F134 0 (Fail)
4157 Ethernet switch Port 4 Status 0 to 2 --- 1 F134 0 (Fail)
4158 Ethernet switch Port 5 Status 0 to 2 --- 1 F134 0 (Fail)
4159 Ethernet switch Port 6 Status 0 to 2 --- 1 F134 0 (Fail)
415A Switch Firmware Version 0.00 to 99.99 --- 0.01 F001 0
Simple Network Time Protocol (Read/Write Setting)
4168 Simple Network Time Protocol (SNTP) function 0 to 1 --- 1 F102 0 (Disabled)
B 42A4
42A6
...Repeated for User-Programmable LED 19
...Repeated for User-Programmable LED 20
42A8 ...Repeated for User-Programmable LED 21
42AA ...Repeated for User-Programmable LED 22
42AC ...Repeated for User-Programmable LED 23
42AE ...Repeated for User-Programmable LED 24
42B0 ...Repeated for User-Programmable LED 25
42B2 ...Repeated for User-Programmable LED 26
42B4 ...Repeated for User-Programmable LED 27
42B6 ...Repeated for User-Programmable LED 28
42B8 ...Repeated for User-Programmable LED 29
42BA ...Repeated for User-Programmable LED 30
42BC ...Repeated for User-Programmable LED 31
42BE ...Repeated for User-Programmable LED 32
42C0 ...Repeated for User-Programmable LED 33
42C2 ...Repeated for User-Programmable LED 34
42C4 ...Repeated for User-Programmable LED 35
42C6 ...Repeated for User-Programmable LED 36
42C8 ...Repeated for User-Programmable LED 37
42CA ...Repeated for User-Programmable LED 38
42CC ...Repeated for User-Programmable LED 39
42CE ...Repeated for User-Programmable LED 40
42D0 ...Repeated for User-Programmable LED 41
42D2 ...Repeated for User-Programmable LED 42
42D4 ...Repeated for User-Programmable LED 43
42D6 ...Repeated for User-Programmable LED 44
42D8 ...Repeated for User-Programmable LED 45
42DA ...Repeated for User-Programmable LED 46
42DC ...Repeated for User-Programmable LED 47
42DE ...Repeated for User-Programmable LED 48
Installation (Read/Write Setting)
43E0 Relay Programmed State 0 to 1 --- 1 F133 0 (Not Programmed)
43E1 Relay Name --- --- --- F202 “Relay-1”
User Programmable Self Tests (Read/Write Setting)
4441 User Programmable Detect Ring Break Function 0 to 1 --- 1 F102 1 (Enabled)
4442 User Programmable Direct Device Off Function 0 to 1 --- 1 F102 1 (Enabled)
4443 User Programmable Remote Device Off Function 0 to 1 --- 1 F102 1 (Enabled)
4444 User Programmable Primary Ethernet Fail Function 0 to 1 --- 1 F102 0 (Disabled)
4445 User Programmable Secondary Ethernet Fail Function 0 to 1 --- 1 F102 0 (Disabled)
4446 User Programmable Battery Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4447 User Programmable SNTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4448 User Programmable IRIG-B Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4449 User Programmable Ethernet Switch Fail Function 0 to 1 --- 1 F102 0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480 Phase CT 1 Primary 1 to 65000 A 1 F001 1
4481 Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4482 Ground CT 1 Primary 1 to 65000 A 1 F001 1
4483 Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4484 ...Repeated for CT Bank 2
B 4713
4714
Breaker 1 phase A / three-pole opened
Breaker 1 phase B opened
0 to 65535
0 to 65535
---
---
1
1
F300
F300
0
0
4715 Breaker 1 phase C opened 0 to 65535 --- 1 F300 0
4716 Breaker 1 operate time 0 to 2 s 0.001 F001 70
4717 Breaker 1 events 0 to 1 --- 1 F102 0 (Disabled)
4718 Reserved --- --- --- --- ---
4719 ...Repeated for breaker 2
4732 ...Repeated for breaker 3
474B ...Repeated for breaker 4
Synchrocheck (Read/Write Setting) (2 modules)
47A0 Synchrocheck 1 Function 0 to 1 --- 1 F102 0 (Disabled)
47A1 Synchrocheck 1 V1 Source 0 to 5 --- 1 F167 0 (SRC 1)
47A2 Synchrocheck 1 V2 Source 0 to 5 --- 1 F167 1 (SRC 2)
47A3 Synchrocheck 1 Maximum Voltage Difference 0 to 400000 V 1 F060 10000
47A5 Synchrocheck 1 Maximum Angle Difference 0 to 100 degrees 1 F001 30
47A6 Synchrocheck 1 Maximum Frequency Difference 0 to 2 Hz 0.01 F001 100
47A7 Synchrocheck 1 Dead Source Select 0 to 5 --- 1 F176 1 (LV1 and DV2)
47A8 Synchrocheck 1 Dead V1 Maximum Voltage 0 to 1.25 pu 0.01 F001 30
47A9 Synchrocheck 1 Dead V2 Maximum Voltage 0 to 1.25 pu 0.01 F001 30
47AA Synchrocheck 1 Live V1 Minimum Voltage 0 to 1.25 pu 0.01 F001 70
47AB Synchrocheck 1 Live V2 Minimum Voltage 0 to 1.25 pu 0.01 F001 70
47AC Synchrocheck 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
47AD Synchrocheck 1 Events 0 to 1 --- 1 F102 0 (Disabled)
47AE Synchrocheck 1 Block 0 to 65535 --- 1 F300 0
47AF Synchrocheck 1 Frequency Hysteresis 0 to 0.1 Hz 0.01 F001 6
47B0 ...Repeated for Synchrocheck 2
Demand (Read/Write Setting)
47D0 Demand Current Method 0 to 2 --- 1 F139 0 (Thrm. Exponential)
47D1 Demand Power Method 0 to 2 --- 1 F139 0 (Thrm. Exponential)
47D2 Demand Interval 0 to 5 --- 1 F132 2 (15 MIN)
47D3 Demand Input 0 to 65535 --- 1 F300 0
Demand (Read/Write Command)
47D4 Demand Clear Record 0 to 1 --- 1 F126 0 (No)
Flexcurves A and B (Read/Write Settings)
4800 FlexCurve A (120 items) 0 to 65535 ms 1 F011 0
48F0 FlexCurve B (120 items) 0 to 65535 ms 1 F011 0
Modbus User Map (Read/Write Setting)
4A00 Modbus Address Settings for User Map (256 items) 0 to 65535 --- 1 F001 0
User Displays Settings (Read/Write Setting) (16 modules)
4C00 User-Definable Display 1 Top Line Text --- --- --- F202 ““
4C0A User-Definable Display 1 Bottom Line Text --- --- --- F202 ““
4C14 Modbus Addresses of Display 1 Items (5 items) 0 to 65535 --- 1 F001 0
4C19 Reserved (7 items) --- --- --- F001 0
4C20 ...Repeated for User-Definable Display 2
4C40 ...Repeated for User-Definable Display 3
4C60 ...Repeated for User-Definable Display 4
4C80 ...Repeated for User-Definable Display 5
4CA0 ...Repeated for User-Definable Display 6
4CC0 ...Repeated for User-Definable Display 7
B 5556
5569
...Repeated for RTD Input 19
...Repeated for RTD Input 20
557C ...Repeated for RTD Input 21
558F ...Repeated for RTD Input 22
55A2 ...Repeated for RTD Input 23
55B5 ...Repeated for RTD Input 24
55C8 ...Repeated for RTD Input 25
55DB ...Repeated for RTD Input 26
55EE ...Repeated for RTD Input 27
5601 ...Repeated for RTD Input 28
5614 ...Repeated for RTD Input 29
5627 ...Repeated for RTD Input 30
563A ...Repeated for RTD Input 31
564D ...Repeated for RTD Input 32
5660 ...Repeated for RTD Input 33
5673 ...Repeated for RTD Input 34
5686 ...Repeated for RTD Input 35
5699 ...Repeated for RTD Input 36
56AC ...Repeated for RTD Input 37
56BF ...Repeated for RTD Input 38
56D2 ...Repeated for RTD Input 39
56E5 ...Repeated for RTD Input 40
56F8 ...Repeated for RTD Input 41
570B ...Repeated for RTD Input 42
571E ...Repeated for RTD Input 43
5731 ...Repeated for RTD Input 44
5744 ...Repeated for RTD Input 45
5757 ...Repeated for RTD Input 46
576A ...Repeated for RTD Input 47
577D ...Repeated for RTD Input 48
Flexlogic Timers (Read/Write Setting) (32 modules)
5800 FlexLogic™ Timer 1 Type 0 to 2 --- 1 F129 0 (millisecond)
5801 FlexLogic™ Timer 1 Pickup Delay 0 to 60000 --- 1 F001 0
5802 FlexLogic™ Timer 1 Dropout Delay 0 to 60000 --- 1 F001 0
5803 Reserved (5 items) 0 to 65535 --- 1 F001 0
5808 ...Repeated for FlexLogic™ Timer 2
5810 ...Repeated for FlexLogic™ Timer 3
5818 ...Repeated for FlexLogic™ Timer 4
5820 ...Repeated for FlexLogic™ Timer 5
5828 ...Repeated for FlexLogic™ Timer 6
5830 ...Repeated for FlexLogic™ Timer 7
5838 ...Repeated for FlexLogic™ Timer 8
5840 ...Repeated for FlexLogic™ Timer 9
5848 ...Repeated for FlexLogic™ Timer 10
5850 ...Repeated for FlexLogic™ Timer 11
5858 ...Repeated for FlexLogic™ Timer 12
5860 ...Repeated for FlexLogic™ Timer 13
5868 ...Repeated for FlexLogic™ Timer 14
5870 ...Repeated for FlexLogic™ Timer 15
B 5B00
5B01
Neutral Time Overcurrent 1 Function
Neutral Time Overcurrent 1 Signal Source
0 to 1
0 to 5
---
---
1
1
F102
F167
0 (Disabled)
0 (SRC 1)
5B02 Neutral Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5B03 Neutral Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5B04 Neutral Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5B05 Neutral Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5B06 Neutral Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5B07 Neutral Time Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5B08 Neutral Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5B09 Neutral Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5B0A Reserved (6 items) 0 to 1 --- 1 F001 0
5B10 ...Repeated for Neutral Time Overcurrent 2
5B20 ...Repeated for Neutral Time Overcurrent 3
5B30 ...Repeated for Neutral Time Overcurrent 4
5B40 ...Repeated for Neutral Time Overcurrent 5
5B50 ...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5C01 Neutral Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5C02 Neutral Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5C04 Neutral Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5C06 Neutral Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5C07 Neutral Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5C08 Reserved (8 items) 0 to 1 --- 1 F001 0
5C10 ...Repeated for Neutral Instantaneous Overcurrent 2
5C20 ...Repeated for Neutral Instantaneous Overcurrent 3
5C30 ...Repeated for Neutral Instantaneous Overcurrent 4
5C40 ...Repeated for Neutral Instantaneous Overcurrent 5
5C50 ...Repeated for Neutral Instantaneous Overcurrent 6
5C60 ...Repeated for Neutral Instantaneous Overcurrent 7
5C70 ...Repeated for Neutral Instantaneous Overcurrent 8
5C80 ...Repeated for Neutral Instantaneous Overcurrent 9
5C90 ...Repeated for Neutral Instantaneous Overcurrent 10
5CA0 ...Repeated for Neutral Instantaneous Overcurrent 11
5CB0 ...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00 Ground Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5D03 Ground Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5D07 Ground Time Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5D08 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5D09 Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5D0A Reserved (6 items) 0 to 1 --- 1 F001 0
B 5F9C
5FA4
Setting Group 3 Name
Setting Group 4 Name
---
---
---
---
---
---
F203
F203
(none)
(none)
5FAC Setting Group 5 Name --- --- --- F203 (none)
5FB4 Setting Group 6 Name --- --- --- F203 (none)
Current Differential 87L (Read/Write Grouped Setting)
6000 87L Current Differential Function 0 to 1 --- 1 F102 0 (Disabled)
6001 87L Current Differential Block 0 to 65535 --- 1 F300 0
6002 87L Current Differential Signal Source 1 0 to 5 --- 1 F167 0 (SRC 1)
6003 87L Minimum Phase Current Sensitivity 0.1 to 4 pu 0.01 F001 20
6004 87L Current Differential Tap Setting 0.2 to 5 --- 0.01 F001 100
6005 87L Current Differential Phase Percent Restraint 1 1 to 50 % 1 F001 30
6006 87L Current Differential Phase Percent Restraint 2 1 to 70 % 1 F001 50
6007 87L Current Differential Phase Dual Slope Breakpoint 0 to 20 pu 0.1 F001 10
6008 87L Current Differential Ground Function 0 to 1 --- 1 F102 0 (Disabled)
6009 87L Current Differential Ground Pickup 0.05 to 1 pu 0.01 F001 10
600A 87L Current Differential Ground Restraint 1 to 50 % 1 F001 25
600B 87L Current Differential Ground Delay 0 to 5 seconds 0.01 F001 10
600C 87L Current Differential Key DTT 0 to 1 --- 1 F102 1 (Enabled)
600D 87L Current Differential External Key DTT 0 to 65535 --- 1 F300 0
600E 87L Current Differential Target 0 to 2 --- 1 F109 0 (Self-reset)
600F 87L Current Differential Event 0 to 1 --- 1 F102 0 (Disabled)
6010 87L Current Differential Tap 2 Setting 0.2 to 5 --- 0.01 F001 100
6011 87L Current Differential Signal Source 2 0 to 6 --- 1 F211 0 (None)
6012 87L Current Differential Signal Source 3 0 to 6 --- 1 F211 0 (None)
6014 87L Current Differential Signal Source 4 0 to 6 --- 1 F211 0 (None)
Wattmetric ground fault settings (read/write grouped, 2 modules)
6050 Wattmetric ground fault 1 function 0 to 1 --- 1 F102 0 (Disabled)
6051 Wattmetric ground fault 1 source 0 to 5 --- 1 F167 0 (SRC 1)
6052 Wattmetric ground fault 1 voltage 0 to 1 --- 1 F234 0 (Calculated VN)
6053 Wattmetric ground fault 1 overvoltage pickup 0.02 to 3.00 pu 0.01 F001 20
6054 Wattmetric ground fault 1 current 0 to 1 --- 1 F235 (Calculated IN)
6055 Wattmetric ground fault 1 overcurrent pickup 0.002 to 30.000 pu 0.001 F001 60
6056 Wattmetric ground fault 1 overcurrent pickup delay 0 to 600 s 0.01 F001 20
6057 Wattmetric ground fault 1 power pickup 0.001 to 1.2 pu 0.001 F001 100
6058 Wattmetric ground fault 1 ECA 0 to 360 ° Lag 1 F001 0
6059 Wattmetric ground fault 1 power pickup delay 0 to 600 s 0.01 F001 20
605A Wattmetric ground fault 1 curve 0 to 5 --- 1 F236 0 (Definite Time)
605B Wattmetric ground fault 1 multiplier 0.01 to 2 s 0.01 F001 100
605C Wattmetric ground fault 1 block 0 to 65535 --- 1 F300 0
605D Wattmetric ground fault 1 target 0 to 2 --- 1 F109 0 (Self-reset)
605E Wattmetric ground fault 1 events 0 to 1 --- 1 F102 0 (Disabled)
605F Wattmetric ground fault 1 reference power 0.001 to 1.2 pu 0.001 F001 500
6060 Reserved --- --- --- --- ---
6061 ...Repeated for wattmetric ground fault 2
Wattmetric ground fault actual values (read only)
6072 Wattmetric ground fault 1 operating power 0.000 to 1000000.000 W 0.001 F060 0
6074 Wattmetric ground fault 2 operating power 0.000 to 1000000.000 W 0.001 F060 0
CT Failure Detector (Read/Write Setting)
6124 CT Fail Function 0 to 1 --- 1 F102 0 (Disabled)
B 65D1
65D2
Power Swing Detect Trip Mode
Power Swing Detect Block
0 to 1
0 to 65535
---
---
1
1
F514
F300
0 (Delayed)
0
65D3 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
65D4 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
65D5 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho Shape)
65D6 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
65D7 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
65D8 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
65D9 Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
65DA Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DB Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DC Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DD Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DE Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DF Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
Load Encroachment (Read/Write Grouped Setting)
6700 Load Encroachment Function 0 to 1 --- 1 F102 0 (Disabled)
6701 Load Encroachment Source 0 to 5 --- 1 F167 0 (SRC 1)
6702 Load Encroachment Minimum Voltage 0 to 3 pu 0.001 F001 250
6703 Load Encroachment Reach 0.02 to 250 ohms 0.01 F001 100
6704 Load Encroachment Angle 5 to 50 degrees 1 F001 30
6705 Load Encroachment Pickup Delay 0 to 65.535 s 0.001 F001 0
6706 Load Encroachment Reset Delay 0 to 65.535 s 0.001 F001 0
6707 Load Encroachment Block 0 to 65535 --- 1 F300 0
6708 Load Encroachment Target 0 to 2 --- 1 F109 0 (Self-reset)
6709 Load Encroachment Events 0 to 1 --- 1 F102 0 (Disabled)
670A Reserved (6 items) 0 to 65535 --- 1 F001 0
Trip Output (Read/Write Setting)
67E0 Trip Mode 0 to 2 --- 1 F195 0 (Disabled)
67E1 Trip 3-Pole Input1 0 to 65535 --- 1 F300 0
67E2 Trip 3-Pole Input2 0 to 65535 --- 1 F300 0
67E3 Trip 3-Pole Input3 0 to 65535 --- 1 F300 0
67E4 Trip 3-Pole Input4 0 to 65535 --- 1 F300 0
67E5 Trip 3-Pole Input5 0 to 65535 --- 1 F300 0
67E6 Trip 3-Pole Input6 0 to 65535 --- 1 F300 0
67E7 Trip 1-Pole Input1 0 to 65535 --- 1 F300 0
67E8 Trip 1-Pole Input2 0 to 65535 --- 1 F300 0
67E9 Trip 1-Pole Input3 0 to 65535 --- 1 F300 0
67EA Trip 1-Pole Input4 0 to 65535 --- 1 F300 0
67EB Trip 1-Pole Input5 0 to 65535 --- 1 F300 0
67EC Trip 1-Pole Input6 0 to 65535 --- 1 F300 0
67ED Trip Reclose Input1 0 to 65535 --- 1 F300 0
67EE Trip Reclose Input2 0 to 65535 --- 1 F300 0
67EF Trip Reclose Input3 0 to 65535 --- 1 F300 0
67F0 Trip Reclose Input4 0 to 65535 --- 1 F300 0
67F1 Trip Reclose Input5 0 to 65535 --- 1 F300 0
67F2 Trip Reclose Input6 0 to 65535 --- 1 F300 0
67F3 Trip Force 3-Pole 0 to 65535 --- 1 F300 0
67F4 Trip Pilot Priority 0 to 65.535 s 0.001 F001 0
B 68AF
68B0
Autoreclose Transfer Time
Autoreclose Event
0 to 655.35
0 to 1
s
---
0.01
1
F001
F102
400
0 (Disabled)
68B1 Autoreclose 3P Dead Time 3 0 to 655.35 s 0.01 F001 200
68B2 Autoreclose 3P Dead Time 4 0 to 655.35 s 0.01 F001 400
68B3 Autoreclose Bus Fault Initiate 0 to 65535 s 0.01 F300 0
68B4 Autoreclose Initiate Mode 0 to 1 --- 1 F610 0 (Protection AND CB)
68B5 Reserved (11 items) --- --- --- F001 0
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 65535 --- 1 F300 0
7007 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7008 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7009 Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to Ground)
700A Reserved (6 items) 0 to 1 --- 1 F001 0
7013 ...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040 Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7041 Phase Overvoltage 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7042 Phase Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7043 Phase Overvoltage 1 Delay 0 to 600 s 0.01 F001 100
7044 Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7045 Phase Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7046 Phase Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7047 Phase Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7048 Reserved (8 items) 0 to 1 --- 1 F001 0
Distance (Read/Write Grouped Setting)
7060 Distance Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7061 Memory Duration 5 to 25 cycles 1 F001 10
7062 Force Self-Polarization 0 to 65535 --- 1 F300 0
7062 Force Memory Polarization 0 to 65535 --- 1 F300 0
Phase Distance (Read/Write Grouped Setting) (5 modules)
7070 Phase Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7071 Phase Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200
7072 Phase Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
7073 Phase Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
7074 Phase Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
7075 Phase Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
7076 Phase Distance Zone 1 Block 0 to 65535 --- 1 F300 0
7077 Phase Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7078 Phase Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7079 Phase Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
707A Phase Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
707B Phase Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
707C Phase Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
B 72A1
72A2
Negative Sequence Directional Overcurrent 1 Source
Negative Sequence Directional Overcurrent 1 Type
0 to 5
0 to 1
---
---
1
1
F167
F179
0 (SRC 1)
0 (Neg Sequence)
72A3 Neg Sequence Directional Overcurrent 1 Forward ECA 0 to 90 ° Lag 1 F002 75
72A4 Neg Seq Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
72A5 Neg Sequence Directional Overcurrent 1 Forward Pickup 0.015 to 30 pu 0.05 F001 5
72A6 Neg Seq Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
72A7 Neg Sequence Directional Overcurrent 1 Reverse Pickup 0.015 to 30 pu 0.05 F001 5
72A8 Negative Sequence Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
72A9 Negative Sequence Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
72AA Negative Sequence Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
72AB Negative Sequence Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
72AC Neg Seq Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
72AD Reserved (3 items) 0 to 1 --- 1 F001 0
72B0 ...Repeated for Neg Seq Directional Overcurrent 2
Breaker Arcing Current Settings (Read/Write Setting)
72C0 Breaker 1 Arcing Current Function 0 to 1 --- 1 F102 0 (Disabled)
72C1 Breaker 1 Arcing Current Source 0 to 5 --- 1 F167 0 (SRC 1)
72C2 Breaker 1 Arcing Current Initiate A 0 to 65535 --- 1 F300 0
72C3 Breaker 1 Arcing Current Initiate B 0 to 65535 --- 1 F300 0
72C4 Breaker 1 Arcing Current Initiate C 0 to 65535 --- 1 F300 0
72C5 Breaker 1 Arcing Current Delay 0 to 65.535 s 0.001 F001 0
72C6 Breaker 1 Arcing Current Limit 0 to 50000 kA2-cyc 1 F001 1000
72C7 Breaker 1 Arcing Current Block 0 to 65535 --- 1 F300 0
72C8 Breaker 1 Arcing Current Target 0 to 2 --- 1 F109 0 (Self-reset)
72C9 Breaker 1 Arcing Current Events 0 to 1 --- 1 F102 0 (Disabled)
72CA ...Repeated for Breaker 2 Arcing Current
72D4 ...Repeated for Breaker 3 Arcing Current
72DE ...Repeated for Breaker 4 Arcing Current
dcmA Inputs (Read/Write Setting) (24 modules)
7300 dcmA Inputs 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7301 dcmA Inputs 1 ID --- --- --- F205 “DCMA I 1"
7307 Reserved 1 (4 items) 0 to 65535 --- 1 F001 0
730B dcmA Inputs 1 Units --- --- --- F206 “mA”
730E dcmA Inputs 1 Range 0 to 6 --- 1 F173 6 (4 to 20 mA)
730F dcmA Inputs 1 Minimum Value -9999.999 to 9999.999 --- 0.001 F004 4000
7311 dcmA Inputs 1 Maximum Value -9999.999 to 9999.999 --- 0.001 F004 20000
7313 Reserved (5 items) 0 to 65535 --- 1 F001 0
7318 ...Repeated for dcmA Inputs 2
7330 ...Repeated for dcmA Inputs 3
7348 ...Repeated for dcmA Inputs 4
7360 ...Repeated for dcmA Inputs 5
7378 ...Repeated for dcmA Inputs 6
7390 ...Repeated for dcmA Inputs 7
73A8 ...Repeated for dcmA Inputs 8
73C0 ...Repeated for dcmA Inputs 9
73D8 ...Repeated for dcmA Inputs 10
73F0 ...Repeated for dcmA Inputs 11
7408 ...Repeated for dcmA Inputs 12
7420 ...Repeated for dcmA Inputs 13
B 7B89
7B8A
User Programmable Pushbutton 1 Set
User Programmable Pushbutton 1 Hold
0 to 65535
0 to 10
---
s
1
0.1
F300
F001
0
1
7B8B ...Repeated for User Programmable Pushbutton 2
7BB6 ...Repeated for User Programmable Pushbutton 3
7BE1 ...Repeated for User Programmable Pushbutton 4
7C0C ...Repeated for User Programmable Pushbutton 5
7C37 ...Repeated for User Programmable Pushbutton 6
7C62 ...Repeated for User Programmable Pushbutton 7
7C8D ...Repeated for User Programmable Pushbutton 8
7CB8 ...Repeated for User Programmable Pushbutton 9
7CE3 ...Repeated for User Programmable Pushbutton 10
7D0E ...Repeated for User Programmable Pushbutton 11
7D39 ...Repeated for User Programmable Pushbutton 12
7D64 ...Repeated for User Programmable Pushbutton 13
7D8F ...Repeated for User Programmable Pushbutton 14
7DBA ...Repeated for User Programmable Pushbutton 15
7DE5 ...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00 Neutral Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F01 Neutral Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F02 Neutral Overvoltage 1 Pickup 0 to 3.00 pu 0.001 F001 300
7F03 Neutral Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F04 Neutral Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F05 Neutral Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7F06 Neutral Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F07 Neutral Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F08 Neutral Overvoltage 1 Curves 0 to 3 --- 1 F116 0 (Definite Time)
7F09 Reserved (8 items) 0 to 65535 --- 1 F001 0
7F10 ...Repeated for Neutral Overvoltage 2
7F20 ...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30 Auxiliary Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F31 Auxiliary Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F32 Auxiliary Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7F33 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F34 Auxiliary Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F35 Auxiliary Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7F36 Auxiliary Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F37 Auxiliary Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F38 Reserved (8 items) 0 to 65535 --- 1 F001 0
7F40 ...Repeated for Auxiliary Overvoltage 2
7F50 ...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60 Auxiliary Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F61 Auxiliary Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F62 Auxiliary Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 700
7F63 Auxiliary Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7F64 Auxiliary Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7F65 Auxiliary Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
B 8A12
8A14
Reserved (2 items)
...Repeated for Digital Element 2
--- --- --- F001 0
B 90F0
9104
...Repeated for FlexElement™ 13
...Repeated for FlexElement™ 14
9118 ...Repeated for FlexElement™ 15
912C ...Repeated for FlexElement™ 16
Fault Report Settings (Read/Write Setting) (up to 5 modules)
9200 Fault Report 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
9201 Fault Report 1 Trigger 0 to 65535 --- 1 F300 0
9202 Fault Report 1 Z1 Magnitude 0.01 to 250 ohms 0.01 F001 300
9203 Fault Report 1 Z1 Angle 25 to 90 degrees 1 F001 75
9204 Fault Report 1 Z0 Magnitude 0.01 to 650 ohms 0.01 F001 900
9205 Fault Report 1 Z0 Angle 25 to 90 degrees 1 F001 75
9206 Fault Report 1 Line Length Units 0 to 1 --- 1 F147 0 (km)
9207 Fault Report 1 Line Length 0 to 2000 0.1 F001 1000
9208 Fault Report 1 VT Substitution 0 to 2 --- 1 F270 0 (None)
9208 Fault Report 1 System Z0 Magnitude 0.01 to 650.00 ohms 0.01 F001 900
9208 Fault Report 1 System Z0 Angle 25 to 90 degrees 1 F001 75
920B ...Repeated for Fault Report 2
9216 ...Repeated for Fault Report 3
9221 ...Repeated for Fault Report 4
922C ...Repeated for Fault Report 5
dcmA Outputs (Read/Write Setting) (24 modules)
9300 dcmA Output 1 Source 0 to 65535 --- 1 F600 0
9301 dcmA Output 1 Range 0 to 2 --- 1 F522 0 (–1 to 1 mA)
9302 dcmA Output 1 Minimum –90 to 90 pu 0.001 F004 0
9304 dcmA Output 1 Maximum –90 to 90 pu 0.001 F004 1000
9306 ...Repeated for dcmA Output 2
930C ...Repeated for dcmA Output 3
9312 ...Repeated for dcmA Output 4
9318 ...Repeated for dcmA Output 5
931E ...Repeated for dcmA Output 6
9324 ...Repeated for dcmA Output 7
932A ...Repeated for dcmA Output 8
9330 ...Repeated for dcmA Output 9
9336 ...Repeated for dcmA Output 10
933C ...Repeated for dcmA Output 11
9342 ...Repeated for dcmA Output 12
9348 ...Repeated for dcmA Output 13
934E ...Repeated for dcmA Output 14
9354 ...Repeated for dcmA Output 15
935A ...Repeated for dcmA Output 16
9360 ...Repeated for dcmA Output 17
9366 ...Repeated for dcmA Output 18
936C ...Repeated for dcmA Output 19
9372 ...Repeated for dcmA Output 20
9378 ...Repeated for dcmA Output 21
937E ...Repeated for dcmA Output 22
9384 ...Repeated for dcmA Output 23
938A ...Repeated for dcmA Output 24
B A287
A288
Selector 1 Bit1
Selector 1 Bit2
0 to 65535
0 to 65535
---
---
1
1
F300
F300
0
0
A289 Selector 1 Bit Mode 0 to 1 --- 1 F083 0 (Time-out)
A28A Selector 1 Bit Acknowledge 0 to 65535 --- 1 F300 0
A28B Selector 1 Power Up Mode 0 to 2 --- 1 F084 0 (Restore)
A28C Selector 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A28D Selector 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A28E Reserved (10 items) --- --- 1 F001 0
A298 ...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300 DNP/IEC 60870-5-104 Binary Input Points (256 items) 0 to 65535 --- 1 F300 0
A400 DNP/IEC 60870-5-104 Analog Input Points (256 items) 0 to 65535 --- 1 F300 0
Flexcurves C and D (Read/Write Setting)
A600 FlexCurve C (120 items) 0 to 65535 ms 1 F011 0
A680 FlexCurve D (120 items) 0 to 65535 ms 1 F011 0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700 Non-Volatile Latch 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A701 Non-Volatile Latch 1 Type 0 to 1 --- 1 F519 0 (Reset Dominant)
A702 Non-Volatile Latch 1 Set 0 to 65535 --- 1 F300 0
A703 Non-Volatile Latch 1 Reset 0 to 65535 --- 1 F300 0
A704 Non-Volatile Latch 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A705 Non-Volatile Latch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A706 Reserved (4 items) --- --- --- F001 0
A70A ...Repeated for Non-Volatile Latch 2
A714 ...Repeated for Non-Volatile Latch 3
A71E ...Repeated for Non-Volatile Latch 4
A728 ...Repeated for Non-Volatile Latch 5
A732 ...Repeated for Non-Volatile Latch 6
A73C ...Repeated for Non-Volatile Latch 7
A746 ...Repeated for Non-Volatile Latch 8
A750 ...Repeated for Non-Volatile Latch 9
A75A ...Repeated for Non-Volatile Latch 10
A764 ...Repeated for Non-Volatile Latch 11
A76E ...Repeated for Non-Volatile Latch 12
A778 ...Repeated for Non-Volatile Latch 13
A782 ...Repeated for Non-Volatile Latch 14
A78C ...Repeated for Non-Volatile Latch 15
A796 ...Repeated for Non-Volatile Latch 16
Digital Counter (Read/Write Setting) (8 modules)
A800 Digital Counter 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A801 Digital Counter 1 Name --- --- --- F205 “Counter 1"
A807 Digital Counter 1 Units --- --- --- F206 (none)
A80A Digital Counter 1 Block 0 to 65535 --- 1 F300 0
A80B Digital Counter 1 Up 0 to 65535 --- 1 F300 0
A80C Digital Counter 1 Down 0 to 65535 --- 1 F300 0
A80D Digital Counter 1 Preset –2147483647 to --- 1 F004 0
2147483647
A80F Digital Counter 1 Compare –2147483647 to --- 1 F004 0
2147483647
A811 Digital Counter 1 Reset 0 to 65535 --- 1 F300 0
B AD67
AD73
IEC 61850 logical node PDIFx name prefix (6 items)
IEC 61850 logical node MMXNx name prefix (6 items)
0 to 65534
0 to 65534
---
---
1
1
F206
F206
(none)
(none)
ADE2 IEC 61850 logical node CSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AE3C IEC 61850 logical node XSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
IEC 61850 XSWI configuration (read/write settings)
AECF Operand for IEC 61850 XSWI1.ST.Loc status 0 to 65535 --- 1 F300 0
AED0 Command to clear XSWI1 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AED1 Repeated for IEC 61850 XSWI2
AED3 Repeated for IEC 61850 XSWI3
AED5 Repeated for IEC 61850 XSWI4
AED7 Repeated for IEC 61850 XSWI5
AED9 Repeated for IEC 61850 XSWI6
AEDB Repeated for IEC 61850 XSWI7
AEDD Repeated for IEC 61850 XSWI8
AEDF Repeated for IEC 61850 XSWI9
AEE1 Repeated for IEC 61850 XSWI10
AEE3 Repeated for IEC 61850 XSWI11
AEE5 Repeated for IEC 61850 XSWI12
AEE7 Repeated for IEC 61850 XSWI13
AEE9 Repeated for IEC 61850 XSWI14
AEEB Repeated for IEC 61850 XSWI15
AEED Repeated for IEC 61850 XSWI16
AEEF Repeated for IEC 61850 XSWI17
AEF1 Repeated for IEC 61850 XSWI18
AEF3 Repeated for IEC 61850 XSWI19
AEF5 Repeated for IEC 61850 XSWI20
AEF7 Repeated for IEC 61850 XSWI21
AEF9 Repeated for IEC 61850 XSWI22
AEFB Repeated for IEC 61850 XSWI23
AEFD Repeated for IEC 61850 XSWI24
IEC 61850 GGIO4 general analog configuration settings (read/write)
AF00 Number of analog points in GGIO4 4 to 32 --- 4 F001 4
IEC 61850 GGIO4 analog input points configuration settings (read/write)
AF10 IEC 61850 GGIO4 analog input 1 value --- --- --- F600 0
AF11 IEC 61850 GGIO4 analog input 1 deadband 0.001 to 100 % 0.001 F003 100000
AF13 IEC 61850 GGIO4 analog input 1 minimum –1000000000000 to --- 0.001 F060 0
1000000000000
AF15 IEC 61850 GGIO4 analog input 1 maximum –1000000000000 to --- 0.001 F060 1000000
1000000000000
AF17 ...Repeated for IEC 61850 GGIO4 analog input 2
AF1E ...Repeated for IEC 61850 GGIO4 analog input 3
AF25 ...Repeated for IEC 61850 GGIO4 analog input 4
AF2C ...Repeated for IEC 61850 GGIO4 analog input 5
AF33 ...Repeated for IEC 61850 GGIO4 analog input 6
AF3A ...Repeated for IEC 61850 GGIO4 analog input 7
AF41 ...Repeated for IEC 61850 GGIO4 analog input 8
AF48 ...Repeated for IEC 61850 GGIO4 analog input 9
AF4F ...Repeated for IEC 61850 GGIO4 analog input 10
AF56 ...Repeated for IEC 61850 GGIO4 analog input 11
AF5D ...Repeated for IEC 61850 GGIO4 analog input 12
B B0C2
B0C4
IEC 61850 MMXU TotVAr Deadband 1
IEC 61850 MMXU TotVA Deadband 1
0.001 to 100
0.001 to 100
%
%
0.001
0.001
F003
F003
10000
10000
B0C6 IEC 61850 MMXU TotPF Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C8 IEC 61850 MMXU Hz Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CA IEC 61850 MMXU PPV.phsAB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CC IEC 61850 MMXU PPV.phsBC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CE IEC 61850 MMXU PPV.phsCA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D0 IEC 61850 MMXU PhV.phsADeadband 1 0.001 to 100 % 0.001 F003 10000
B0D2 IEC 61850 MMXU PhV.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D4 IEC 61850 MMXU PhV.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D6 IEC 61850 MMXU A.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D8 IEC 61850 MMXU A.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0DA IEC 61850 MMXU A.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0DC IEC 61850 MMXU A.neut Deadband 1 0.001 to 100 % 0.001 F003 10000
B0DE IEC 61850 MMXU W.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E0 IEC 61850 MMXU W.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E2 IEC 61850 MMXU W.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E4 IEC 61850 MMXU VAr.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E6 IEC 61850 MMXU VAr.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E8 IEC 61850 MMXU VAr.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0EA IEC 61850 MMXU VA.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0EC IEC 61850 MMXU VA.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0EE IEC 61850 MMXU VA.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F0 IEC 61850 MMXU PF.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F2 IEC 61850 MMXU PF.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F4 IEC 61850 MMXU PF.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F6 ...Repeated for Deadband 2
B12C ...Repeated for Deadband 3
B162 ...Repeated for Deadband 4
B198 ...Repeated for Deadband 5
B1CE ...Repeated for Deadband 6
IEC 61850 Report Settings (Read/Write Setting) (14 modules)
B280 IEC 61850 Report Control 1 RptID --- --- --- F209
B2A1 IEC 61850 Report Control 1 OptFlds 0 to 65535 --- 1 F001 0
B2A2 IEC 61850 Report Control 1 BufTm 0 to 4294967295 --- 1 F003 0
B2A4 IEC 61850 Report Control 1 TrgOps 0 to 65535 --- 1 F001 0
B2A5 IEC 61850 Report Control 1 IntgPd 0 to 4294967295 --- 1 F003 0
B2A7 ...Repeated for Report 2
B2CE ...Repeated for Report 3
B2F5 ...Repeated for Report 4
B31C ...Repeated for Report 5
B343 ...Repeated for Report 6
B36A ...Repeated for Report 7
B391 ...Repeated for Report 8
B3B8 ...Repeated for Report 9
B3DF ...Repeated for Report 10
B406 ...Repeated for Report 11
B42D ...Repeated for Report 12
B454 ...Repeated for Report 13
B BBB8
BBC0
...Repeated for Contact Input 24
...Repeated for Contact Input 25
BBC8 ...Repeated for Contact Input 26
BBD0 ...Repeated for Contact Input 27
BBD8 ...Repeated for Contact Input 28
BBE0 ...Repeated for Contact Input 29
BBE8 ...Repeated for Contact Input 30
BBF0 ...Repeated for Contact Input 31
BBF8 ...Repeated for Contact Input 32
BC00 ...Repeated for Contact Input 33
BC08 ...Repeated for Contact Input 34
BC10 ...Repeated for Contact Input 35
BC18 ...Repeated for Contact Input 36
BC20 ...Repeated for Contact Input 37
BC28 ...Repeated for Contact Input 38
BC30 ...Repeated for Contact Input 39
BC38 ...Repeated for Contact Input 40
BC40 ...Repeated for Contact Input 41
BC48 ...Repeated for Contact Input 42
BC50 ...Repeated for Contact Input 43
BC58 ...Repeated for Contact Input 44
BC60 ...Repeated for Contact Input 45
BC68 ...Repeated for Contact Input 46
BC70 ...Repeated for Contact Input 47
BC78 ...Repeated for Contact Input 48
BC80 ...Repeated for Contact Input 49
BC88 ...Repeated for Contact Input 50
BC90 ...Repeated for Contact Input 51
BC98 ...Repeated for Contact Input 52
BCA0 ...Repeated for Contact Input 53
BCA8 ...Repeated for Contact Input 54
BCB0 ...Repeated for Contact Input 55
BCB8 ...Repeated for Contact Input 56
BCC0 ...Repeated for Contact Input 57
BCC8 ...Repeated for Contact Input 58
BCD0 ...Repeated for Contact Input 59
BCD8 ...Repeated for Contact Input 60
BCE0 ...Repeated for Contact Input 61
BCE8 ...Repeated for Contact Input 62
BCF0 ...Repeated for Contact Input 63
BCF8 ...Repeated for Contact Input 64
BD00 ...Repeated for Contact Input 65
BD08 ...Repeated for Contact Input 66
BD10 ...Repeated for Contact Input 67
BD18 ...Repeated for Contact Input 68
BD20 ...Repeated for Contact Input 69
BD28 ...Repeated for Contact Input 70
BD30 ...Repeated for Contact Input 71
BD38 ...Repeated for Contact Input 72
B BF80
BF8C
...Repeated for Virtual Input 29
...Repeated for Virtual Input 30
BF98 ...Repeated for Virtual Input 31
BFA4 ...Repeated for Virtual Input 32
BFB0 ...Repeated for Virtual Input 33
BFBC ...Repeated for Virtual Input 34
BFC8 ...Repeated for Virtual Input 35
BFD4 ...Repeated for Virtual Input 36
BFE0 ...Repeated for Virtual Input 37
BFEC ...Repeated for Virtual Input 38
BFF8 ...Repeated for Virtual Input 39
C004 ...Repeated for Virtual Input 40
C010 ...Repeated for Virtual Input 41
C01C ...Repeated for Virtual Input 42
C028 ...Repeated for Virtual Input 43
C034 ...Repeated for Virtual Input 44
C040 ...Repeated for Virtual Input 45
C04C ...Repeated for Virtual Input 46
C058 ...Repeated for Virtual Input 47
C064 ...Repeated for Virtual Input 48
C070 ...Repeated for Virtual Input 49
C07C ...Repeated for Virtual Input 50
C088 ...Repeated for Virtual Input 51
C094 ...Repeated for Virtual Input 52
C0A0 ...Repeated for Virtual Input 53
C0AC ...Repeated for Virtual Input 54
C0B8 ...Repeated for Virtual Input 55
C0C4 ...Repeated for Virtual Input 56
C0D0 ...Repeated for Virtual Input 57
C0DC ...Repeated for Virtual Input 58
C0E8 ...Repeated for Virtual Input 59
C0F4 ...Repeated for Virtual Input 60
C100 ...Repeated for Virtual Input 61
C10C ...Repeated for Virtual Input 62
C118 ...Repeated for Virtual Input 63
C124 ...Repeated for Virtual Input 64
Virtual Outputs (Read/Write Setting) (96 modules)
C130 Virtual Output 1 Name --- --- --- F205 “Virt Op 1 “
C136 Virtual Output 1 Events 0 to 1 --- 1 F102 0 (Disabled)
C137 Reserved --- --- --- F001 0
C138 ...Repeated for Virtual Output 2
C140 ...Repeated for Virtual Output 3
C148 ...Repeated for Virtual Output 4
C150 ...Repeated for Virtual Output 5
C158 ...Repeated for Virtual Output 6
C160 ...Repeated for Virtual Output 7
C168 ...Repeated for Virtual Output 8
C170 ...Repeated for Virtual Output 9
C178 ...Repeated for Virtual Output 10
B C358
C360
...Repeated for Virtual Output 70
...Repeated for Virtual Output 71
C368 ...Repeated for Virtual Output 72
C370 ...Repeated for Virtual Output 73
C378 ...Repeated for Virtual Output 74
C380 ...Repeated for Virtual Output 75
C388 ...Repeated for Virtual Output 76
C390 ...Repeated for Virtual Output 77
C398 ...Repeated for Virtual Output 78
C3A0 ...Repeated for Virtual Output 79
C3A8 ...Repeated for Virtual Output 80
C3B0 ...Repeated for Virtual Output 81
C3B8 ...Repeated for Virtual Output 82
C3C0 ...Repeated for Virtual Output 83
C3C8 ...Repeated for Virtual Output 84
C3D0 ...Repeated for Virtual Output 85
C3D8 ...Repeated for Virtual Output 86
C3E0 ...Repeated for Virtual Output 87
C3E8 ...Repeated for Virtual Output 88
C3F0 ...Repeated for Virtual Output 89
C3F8 ...Repeated for Virtual Output 90
C400 ...Repeated for Virtual Output 91
C408 ...Repeated for Virtual Output 92
C410 ...Repeated for Virtual Output 93
C418 ...Repeated for Virtual Output 94
C420 ...Repeated for Virtual Output 95
C428 ...Repeated for Virtual Output 96
Mandatory (Read/Write Setting)
C430 Test Mode Function 0 to 1 --- 1 F245 0 (Disabled)
C431 Force VFD and LED 0 to 1 --- 1 F126 0 (No)
C432 Test Mode Forcing 0 to 65535 --- 1 F300 1
Clear commands (read/write)
C433 Clear All Relay Records Command 0 to 1 --- 1 F126 0 (No)
Synchrophasor actual values (read only)
C435 Synchrophasors active 0 to 1 --- 1 F126 0 (No)
Contact Outputs (Read/Write Setting) (64 modules)
C440 Contact Output 1 Name --- --- --- F205 “Cont Op 1"
C446 Contact Output 1 Operation 0 to 65535 --- 1 F300 0
C447 Contact Output 1 Seal In 0 to 65535 --- 1 F300 0
C448 Latching Output 1 Reset 0 to 65535 --- 1 F300 0
C449 Contact Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)
C44A Latching Output 1 Type 0 to 1 --- 1 F090 0 (Operate-dominant)
C44B Reserved --- --- --- F001 0
C44C ...Repeated for Contact Output 2
C458 ...Repeated for Contact Output 3
C464 ...Repeated for Contact Output 4
C470 ...Repeated for Contact Output 5
C47C ...Repeated for Contact Output 6
C488 ...Repeated for Contact Output 7
B D24C
D250
...Repeated for Remote Output 12
...Repeated for Remote Output 13
D254 ...Repeated for Remote Output 14
D258 ...Repeated for Remote Output 15
D25C ...Repeated for Remote Output 16
D260 ...Repeated for Remote Output 17
D264 ...Repeated for Remote Output 18
D268 ...Repeated for Remote Output 19
D26C ...Repeated for Remote Output 20
D270 ...Repeated for Remote Output 21
D274 ...Repeated for Remote Output 22
D278 ...Repeated for Remote Output 23
D27C ...Repeated for Remote Output 24
D280 ...Repeated for Remote Output 25
D284 ...Repeated for Remote Output 26
D288 ...Repeated for Remote Output 27
D28C ...Repeated for Remote Output 28
D290 ...Repeated for Remote Output 29
D294 ...Repeated for Remote Output 30
D298 ...Repeated for Remote Output 31
D29C ...Repeated for Remote Output 32
Remote Output UserSt Pairs (Read/Write Setting) (32 modules)
D2A0 Remote Output UserSt 1 Operand 0 to 65535 --- 1 F300 0
D2A1 Remote Output UserSt 1 Events 0 to 1 --- 1 F102 0 (Disabled)
D2A2 Reserved (2 items) 0 to 1 --- 1 F001 0
D2A4 ...Repeated for Remote Output 2
D2A8 ...Repeated for Remote Output 3
D2AC ...Repeated for Remote Output 4
D2B0 ...Repeated for Remote Output 5
D2B4 ...Repeated for Remote Output 6
D2B8 ...Repeated for Remote Output 7
D2BC ...Repeated for Remote Output 8
D2C0 ...Repeated for Remote Output 9
D2C4 ...Repeated for Remote Output 10
D2C8 ...Repeated for Remote Output 11
D2CC ...Repeated for Remote Output 12
D2D0 ...Repeated for Remote Output 13
D2D4 ...Repeated for Remote Output 14
D2D8 ...Repeated for Remote Output 15
D2DC ...Repeated for Remote Output 16
D2E0 ...Repeated for Remote Output 17
D2E4 ...Repeated for Remote Output 18
D2E8 ...Repeated for Remote Output 19
D2EC ...Repeated for Remote Output 20
D2F0 ...Repeated for Remote Output 21
D2F4 ...Repeated for Remote Output 22
D2F8 ...Repeated for Remote Output 23
D2FC ...Repeated for Remote Output 24
D300 ...Repeated for Remote Output 25
B D353
D354
IEC 61850 GGIO2.CF.SPCSO52.ctlModel Value
IEC 61850 GGIO2.CF.SPCSO53.ctlModel Value
0 to 2
0 to 2
---
---
1
1
F001
F001
2
2
D355 IEC 61850 GGIO2.CF.SPCSO54.ctlModel Value 0 to 2 --- 1 F001 2
D356 IEC 61850 GGIO2.CF.SPCSO55.ctlModel Value 0 to 2 --- 1 F001 2
D357 IEC 61850 GGIO2.CF.SPCSO56.ctlModel Value 0 to 2 --- 1 F001 2
D358 IEC 61850 GGIO2.CF.SPCSO57.ctlModel Value 0 to 2 --- 1 F001 2
D359 IEC 61850 GGIO2.CF.SPCSO58.ctlModel Value 0 to 2 --- 1 F001 2
D35A IEC 61850 GGIO2.CF.SPCSO59.ctlModel Value 0 to 2 --- 1 F001 2
D35B IEC 61850 GGIO2.CF.SPCSO60.ctlModel Value 0 to 2 --- 1 F001 2
D35C IEC 61850 GGIO2.CF.SPCSO61.ctlModel Value 0 to 2 --- 1 F001 2
D35D IEC 61850 GGIO2.CF.SPCSO62.ctlModel Value 0 to 2 --- 1 F001 2
D35E IEC 61850 GGIO2.CF.SPCSO63.ctlModel Value 0 to 2 --- 1 F001 2
Remote Device Status (Read Only) (16 modules)
D380 Remote Device 1 StNum 0 to 4294967295 --- 1 F003 0
D382 Remote Device 1 SqNum 0 to 4294967295 --- 1 F003 0
D384 ...Repeated for Remote Device 2
D388 ...Repeated for Remote Device 3
D38C ...Repeated for Remote Device 4
D390 ...Repeated for Remote Device 5
D394 ...Repeated for Remote Device 6
D398 ...Repeated for Remote Device 7
D39C ...Repeated for Remote Device 8
D3A0 ...Repeated for Remote Device 9
D3A4 ...Repeated for Remote Device 10
D3A8 ...Repeated for Remote Device 11
D3AC ...Repeated for Remote Device 12
D3B0 ...Repeated for Remote Device 13
D3B4 ...Repeated for Remote Device 14
D3B8 ...Repeated for Remote Device 15
D3BC ...Repeated for Remote Device 16
D3C0 ...Repeated for Remote Device 17
D3C4 ...Repeated for Remote Device 18
D3C8 ...Repeated for Remote Device 19
D3CC ...Repeated for Remote Device 20
D3D0 ...Repeated for Remote Device 21
D3D4 ...Repeated for Remote Device 22
D3D8 ...Repeated for Remote Device 23
D3DC ...Repeated for Remote Device 24
D3E0 ...Repeated for Remote Device 25
D3E4 ...Repeated for Remote Device 26
D3E8 ...Repeated for Remote Device 27
D3EC ...Repeated for Remote Device 28
D3F0 ...Repeated for Remote Device 29
D3F4 ...Repeated for Remote Device 30
D3F8 ...Repeated for Remote Device 31
D3FC ...Repeated for Remote Device 32
Phasor Measurement Unit Communication (Read/Write Setting)
D400 PMU 1 Communication Port 1 Type 0 to 3 --- 1 F545 0 (Network)
D401 PMU 1 Communication Port 2 Type 0 to 3 --- 1 F545 0 (Network)
B EA8C
EA8D
PMU 1 Ia Calibration Angle
PMU 1 Ib Calibration Angle
-5 to 5
-5 to 5
°
°
0.05
0.05
F002
F002
0
0
EA8E PMU 1 Ic Calibration Angle -5 to 5 ° 0.05 F002 0
EA8F PMU 1 Ig Calibration Angle -5 to 5 ° 0.05 F002 0
EA90 PMU 1 Sequence Voltage Shift Angle -180 to 180 ° 30 F002 0
EA91 PMU 1 Sequence Current Shift Angle -180 to 180 ° 30 F002 0
Phasor Measurement Unit Triggering (Read/Write Setting)
EAB0 PMU 1 User Trigger 0 to 65535 --- 1 F300 0
Phasor Measurement Unit Current Trigger (Read/Write Setting)
EAB4 PMU 1 Current Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EAB5 PMU 1 Current Trigger Pickup 0.1 to 30 pu 0.001 F001 1800
EAB6 PMU 1 Current Trigger Pickup Time 0 to 600 s 0.01 F001 10
EAB7 PMU 1 Current Trigger Dropout Time 0 to 600 s 0.01 F001 100
EAB8 PMU 1 Current Trigger Block (3 items) 0 to 65535 --- 1 F300 0
EABB PMU 1 Current Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EABC PMU 1 Current Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EAD8 PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EAD9 PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 25
EADA PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 25
EADB PMU 1 df/dt Trigger Pickup Time 0 to 600 s 0.01 F001 10
EADC PMU 1 df/dt Trigger Dropout Time 0 to 600 s 0.01 F001 100
EADD PMU 1 df/dt Trigger Block (3 items) 0 to 65535 --- 1 F300 0
EAE0 PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EAE1 PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EB00 PMU 1 Frequency Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB01 PMU 1 Frequency Trigger Low Frequency 20 to 70 Hz 0.01 F001 4900
EB02 PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0.01 F001 6100
EB03 PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0.01 F001 10
EB04 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0.01 F001 100
EB05 PMU 1 Frequency Trigger Block (3 items) 0 to 65535 --- 1 F300 0
EB08 PMU 1 Frequency Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EB09 PMU 1 Frequency Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Power Trigger (Read/Write Setting)
EB28 PMU 1 Power Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB29 PMU 1 Power Trigger Active 0.25 to 3 pu 0.001 F001 1250
EB2A PMU 1 Power Trigger Reactive 0.25 to 3 pu 0.001 F001 1250
EB2B PMU 1 Power Trigger Apparent 0.25 to 3 pu 0.001 F001 1250
EB2C PMU 1 Power Trigger Pickup Time 0 to 600 s 0.01 F001 10
EB2D PMU 1 Power Trigger Dropout Time 0 to 600 s 0.01 F001 100
EB2E PMU 1 Power Trigger Block (3 items) 0 to 65535 --- 1 F300 0
EB31 PMU 1 Power Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EB32 PMU 1 Power Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
EB54 PMU 1 Voltage Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB55 PMU 1 Voltage Trigger Low Voltage 0.25 to 1.25 pu 0.001 F001 800
EB56 PMU 1 Voltage Trigger High Voltage 0.75 to 1.75 pu 0.001 F001 1200
EB57 PMU 1 Voltage Trigger Pickup Time 0 to 600 s 0.01 F001 10
F001 F040
UR_UINT16 UNSIGNED 16 BIT INTEGER UR_UINT48 48-BIT UNSIGNED INTEGER
B F002
UR_SINT16 SIGNED 16 BIT INTEGER
F050
UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January
1, 1970.
F003
UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register. F051
Low order word is stored in the second register. UR_UINT32 DATE in SR format (alternate format for F050)
First 16 bits are Month/Day (MM/DD/xxxx). Month: 1=January,
2=February,...,12=December; Day: 1 to 31 in steps of 1
F004
Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1
UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register/
Low order word is stored in the second register. F052
UR_UINT32 TIME in SR format (alternate format for F050)
First 16 bits are Hours/Minutes (HH:MM:xx.xxx).
F005
Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm;
UR_UINT8 UNSIGNED 8 BIT INTEGER
Minutes: 0 to 59 in steps of 1
Last 16 bits are Seconds (xx:xx:.SS.SSS): 0=00.000s,
F006 1=00.001,...,59999=59.999s)
UR_SINT8 SIGNED 8 BIT INTEGER
F060
F011 FLOATING_POINT IEEE FLOATING POINT (32 bits)
UR_UINT16 FLEXCURVE DATA (120 points)
A FlexCurve is an array of 120 consecutive data points (x, y) which
F070
are interpolated to generate a smooth curve. The y-axis is the user
HEX2 2 BYTES - 4 ASCII DIGITS
defined trip or operation time setting; the x-axis is the pickup ratio
and is pre-defined. Refer to format F119 for a listing of the pickup
ratios; the enumeration value for the pickup ratio indicates the off-
F071
set into the FlexCurve base address where the corresponding time HEX4 4 BYTES - 8 ASCII DIGITS
value is stored.
F072
F012
HEX6 6 BYTES - 12 ASCII DIGITS
DISPLAY_SCALE DISPLAY SCALING
(unsigned 16-bit integer)
MSB indicates the SI units as a power of ten. LSB indicates the F073
number of decimal points to display. HEX8 8 BYTES - 16 ASCII DIGITS
Example: Current values are stored as 32 bit numbers with three
decimal places and base units in Amps. If the retrieved value is
F074
12345.678 A and the display scale equals 0x0302 then the dis-
HEX20 20 BYTES - 40 ASCII DIGITS
played value on the unit is 12.35 kA.
F081
F013
ENUMERATION: AUTORECLOSE 1P/3P BKR FAIL OPTION
POWER_FACTOR (SIGNED 16 BIT INTEGER)
0 = Continue, 1 = Lockout
Positive values indicate lagging power factor; negative values
indicate leading.
F082 F103
ENUMERATION: AUTORECLOSE SINGLE-PHASE / ENUMERATION: CURVE SHAPES
THREE-PHASE BREAKER SEQUENCE
bitmask curve shape bitmask curve shape
0 = 1, 1 = 2, 2 = 1 & 2, 3 = 1 – 2, 4 = 2 – 1
0 IEEE Mod Inv 9 IAC Inverse
1 IEEE Very Inv 10 IAC Short Inv
F083 2 IEEE Ext Inv 11 I2t
ENUMERATION: SELECTOR MODES 3 IEC Curve A 12 Definite Time B
0 = Time-Out, 1 = Acknowledge 4 IEC Curve B 13 FlexCurve™ A
5 IEC Curve C 14 FlexCurve™ B
6 IEC Short Inv 15 FlexCurve™ C
F084
7 IAC Ext Inv 16 FlexCurve™ D
ENUMERATION: SELECTOR POWER UP
8 IAC Very Inv
0 = Restore, 1 = Synchronize, 2 = Sync/Restore
F104
F085 ENUMERATION: RESET TYPE
ENUMERATION: POWER SWING SHAPE
0 = Instantaneous, 1 = Timed, 2 = Linear
0 = Mho Shape, 1 = Quad Shape
F105
F086 ENUMERATION: LOGIC INPUT
ENUMERATION: DIGITAL INPUT DEFAULT STATE
0 = Disabled, 1 = Input 1, 2 = Input 2
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On
F106
F090 ENUMERATION: PHASE ROTATION
ENUMERATION: LATCHING OUTPUT TYPE
0 = ABC, 1 = ACB
0 = Operate-dominant, 1 = Reset-dominant
F108
F100 ENUMERATION: OFF/ON
ENUMERATION: VT CONNECTION TYPE
0 = Off, 1 = On
0 = Wye; 1 = Delta
F109
F101 ENUMERATION: CONTACT OUTPUT OPERATION
ENUMERATION: MESSAGE DISPLAY INTENSITY
0 = Self-reset, 1 = Latched, 2 = Disabled
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%
F110
F102 ENUMERATION: CONTACT OUTPUT LED CONTROL
ENUMERATION: DISABLED/ENABLED
0 = Trip, 1 = Alarm, 2 = None
0 = Disabled; 1 = Enabled
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112 F119
ENUMERATION: RS485 BAUD RATES ENUMERATION: FLEXCURVE™ PICKUP RATIOS
bitmask value bitmask value bitmask value mask value mask value mask value mask value
0 300 4 9600 8 115200 0 0.00 30 0.88 60 2.90 90 5.90
1 1200 5 19200 9 14400 1 0.05 31 0.90 61 3.00 91 6.00
2 2400 6 38400 10 28800 2 0.10 32 0.91 62 3.10 92 6.50
B 3 4800 7 57600 11 33600 3 0.15 33 0.92 63 3.20 93 7.00
4 0.20 34 0.93 64 3.30 94 7.50
5 0.25 35 0.94 65 3.40 95 8.00
F113
6 0.30 36 0.95 66 3.50 96 8.50
ENUMERATION: PARITY
7 0.35 37 0.96 67 3.60 97 9.00
0 = None, 1 = Odd, 2 = Even
8 0.40 38 0.97 68 3.70 98 9.50
9 0.45 39 0.98 69 3.80 99 10.00
F114 10 0.48 40 1.03 70 3.90 100 10.50
ENUMERATION: IRIG-B SIGNAL TYPE 11 0.50 41 1.05 71 4.00 101 11.00
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
bitmask element
F124
71 Ground Instantaneous Overcurrent 8
ENUMERATION: LIST OF ELEMENTS
72 Ground Instantaneous Overcurrent 9
F127 F138
ENUMERATION: LATCHED OR SELF-RESETTING ENUMERATION: OSCILLOGRAPHY FILE TYPE
0 = Latched, 1 = Self-Reset 0 = Data File, 1 = Configuration File, 2 = Header File
F128 F139
ENUMERATION: CONTACT INPUT THRESHOLD ENUMERATION: DEMAND CALCULATIONS
B 0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC 0 = Thermal Exponential, 1 = Block Interval, 2 = Rolling Demand
F129 F140
ENUMERATION: FLEXLOGIC TIMER TYPE ENUMERATION: CURRENT, SENS CURRENT, VOLTAGE,
DISABLED
0 = millisecond, 1 = second, 2 = minute
0 = Disabled, 1 = Current 46 A, 2 = Voltage 280 V,
3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A,
F130 6 = Notched 2 A
ENUMERATION: SIMULATION MODE
0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault
F141
ENUMERATION: SELF TEST ERRORS
F131
Bitmask Error
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 Any Self Tests
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze 1 IRIG-B Failure
2 Port 1 Offline
Bitmask Error
F146
33 ---
ENUMERATION: MISCELLANEOUS EVENT CAUSES
34 ---
35 --- bitmask definition
36 Watchdog Error 0 Events Cleared
37 Low On Memory 1 Oscillography Triggered
38 --- 2 Date/time Changed
43 Module Failure 01 3 Default Settings Loaded B
44 Module Failure 02 4 Test Mode Forcing On
45 Module Failure 03 5 Test Mode Forcing Off
46 Module Failure 04 6 Power On
47 Module Failure 05 7 Power Off
48 Module Failure 06 8 Relay In Service
49 Module Failure 07 9 Relay Out Of Service
50 Module Failure 08 10 Watchdog Reset
51 Module Failure 09 11 Oscillography Clear
52 Incompatible Hardware 12 Reboot Command
53 Module Failure 10 13 Led Test Initiated
54 Module Failure 11 14 Flash Programming
55 Module Failure 12 15 Fault Report Trigger
16 User Programmable Fault Report Trigger
17 ---
F142
ENUMERATION: EVENT RECORDER ACCESS FILE TYPE 18 Reload CT/VT module Settings
19 ---
0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause
20 Ethernet Port 1 Offline
21 Ethernet Port 2 Offline
F143 22 Ethernet Port 3 Offline
UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number) 23 Ethernet Port 4 Offline
A bit value of 0 = no error, 1 = error 24 Ethernet Port 5 Offline
25 Ethernet Port 6 Offline
26 Test Mode Isolated
F144
27 Test Mode Forcible
ENUMERATION: FORCED CONTACT INPUT STATE
28 Test Mode Disabled
0 = Disabled, 1 = Open, 2 = Closed
29 Temperature Warning On
30 Temperature Warning Off
F145 31 Unauthorized Access
ENUMERATION: ALPHABET LETTER 32 System Integrity Recovery
33 System Integrity Recovery 06
bitmask type bitmask type bitmask type bitmask type
34 System Integrity Recovery 07
0 null 7 G 14 N 21 U
1 A 8 H 15 O 22 V
2 B 9 I 16 P 23 W F147
3 C 10 J 17 Q 24 X ENUMERATION: LINE LENGTH UNITS
4 D 11 K 18 R 25 Y 0 = km, 1 = miles
5 E 12 L 19 S 26 Z
6 F 13 M 20 T
F148 F155
ENUMERATION: FAULT TYPE ENUMERATION: REMOTE DEVICE STATE
bitmask fault type bitmask fault type 0 = Offline, 1 = Online
0 NA 6 AC
1 AG 7 ABG
F156
2 BG 8 BCG
ENUMERATION: REMOTE INPUT BIT PAIRS
B 3
4
CG
AB
9
10
ACG
ABC bitmask value bitmask value
5 BC 11 ABCG 0 NONE 35 UserSt-3
1 DNA-1 36 UserSt-4
2 DNA-2 37 UserSt-5
F151
3 DNA-3 38 UserSt-6
ENUMERATION: RTD SELECTION
4 DNA-4 39 UserSt-7
bitmask RTD# bitmask RTD# bitmask RTD# 5 DNA-5 40 UserSt-8
0 NONE 17 RTD 17 33 RTD 33 6 DNA-6 41 UserSt-9
1 RTD 1 18 RTD 18 34 RTD 34 7 DNA-7 42 UserSt-10
2 RTD 2 19 RTD 19 35 RTD 35 8 DNA-8 43 UserSt-11
3 RTD 3 20 RTD 20 36 RTD 36 9 DNA-9 44 UserSt-12
4 RTD 4 21 RTD 21 37 RTD 37 10 DNA-10 45 UserSt-13
5 RTD 5 22 RTD 22 38 RTD 38 11 DNA-11 46 UserSt-14
6 RTD 6 23 RTD 23 39 RTD 39 12 DNA-12 47 UserSt-15
7 RTD 7 24 RTD 24 40 RTD 40 13 DNA-13 48 UserSt-16
8 RTD 8 25 RTD 25 41 RTD 41 14 DNA-14 49 UserSt-17
9 RTD 9 26 RTD 26 42 RTD 42 15 DNA-15 50 UserSt-18
10 RTD 10 27 RTD 27 43 RTD 43 16 DNA-16 51 UserSt-19
11 RTD 11 28 RTD 28 44 RTD 44 17 DNA-17 52 UserSt-20
12 RTD 12 29 RTD 29 45 RTD 45 18 DNA-18 53 UserSt-21
13 RTD 13 30 RTD 30 46 RTD 46 19 DNA-19 54 UserSt-22
14 RTD 14 31 RTD 31 47 RTD 47 20 DNA-20 55 UserSt-23
15 RTD 15 32 RTD 32 48 RTD 48 21 DNA-21 56 UserSt-24
16 RTD 16 22 DNA-22 57 UserSt-25
23 DNA-23 58 UserSt-26
24 DNA-24 59 UserSt-27
F152
ENUMERATION: SETTING GROUP 25 DNA-25 60 UserSt-28
26 DNA-26 61 UserSt-29
0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3
27 DNA-27 62 UserSt-30
4 = Group 4, 5 = Group 5, 6 = Group 6
28 DNA-28 63 UserSt-31
29 DNA-29 64 UserSt-32
F153 30 DNA-30 65 Dataset Item 1
ENUMERATION: DISTANCE TRANSFORMER CONNECTION
31 DNA-31 66 Dataset Item 2
bitmask type bitmask type bitmask type 32 DNA-32 67 Dataset Item 3
0 None 5 Dy9 10 Yd7 33 UserSt-1 ↓ ↓
1 Dy1 6 Dy11 11 Yd9 34 UserSt-2 128 Dataset Item 64
2 Dy3 7 Yd1 12 Yd11
3 Dy5 8 Yd3
F157
4 Dy7 9 Yd5
ENUMERATION: BREAKER MODE
0 = 3-Pole, 1 = 1-Pole
F154
ENUMERATION: DISTANCE DIRECTION
F158
0 = Forward, 1 = Reverse, 2 = Non-Directional
ENUMERATION: SCHEME CALIBRATION TEST
0 = Normal, 1 = Symmetry 1, 2 = Symmetry 2, 3 = Delay 1
4 = Delay 2
F159 F174
ENUMERATION: BREAKER AUX CONTACT KEYING ENUMERATION: TRANSDUCER RTD INPUT TYPE
0 = 52a, 1 = 52b, 2 = None 0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel,
2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
F166
ENUMERATION: AUXILIARY VT CONNECTION TYPE F175
0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca
ENUMERATION: PHASE LETTERS B
0 = A, 1 = B, 2 = C
F167
ENUMERATION: SIGNAL SOURCE F176
ENUMERATION: SYNCHROCHECK DEAD SOURCE SELECT
0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4,
4 = SRC 5, 5 = SRC 6
bitmask synchrocheck dead source
0 None
F168 1 LV1 and DV2
ENUMERATION: INRUSH INHIBIT FUNCTION 2 DV1 and LV2
0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd 3 DV1 or DV2
4 DV1 Xor DV2
5 DV1 and DV2
F170
ENUMERATION: LOW/HIGH OFFSET and GAIN
TRANSDUCER INPUT/OUTPUT SELECTION F177
0 = LOW, 1 = HIGH ENUMERATION: COMMUNICATION PORT
0 = None, 1 = COM1-RS485, 2 = COM2-RS485,
3 = Front Panel-RS232, 4 = Network - TCP, 5 = Network - UDP
F171
ENUMERATION: TRANSDUCER CHANNEL INPUT TYPE
0 = dcmA IN, 1 = Ohms IN, 2 = RTD IN, 3 = dcmA OUT, F178
4 = RRTD IN ENUMERATION: DATA LOGGER RATES
0 = 1 sec, 1 = 1 min, 2 = 5 min, 3 = 10 min, 4 = 15 min,
5 = 20 min, 6 = 30 min, 7 = 60 min, 8 = 15 ms, 9 = 30 ms,
F172 10 = 100 ms, 11 = 500 ms
ENUMERATION: SLOT LETTERS
F180
F173 ENUMERATION: PHASE/GROUND
ENUMERATION: DCMA INPUT/OUTPUT RANGE
0 = PHASE, 1 = GROUND
bitmask dcmA input/output range
0 0 to –1 mA
F181
1 0 to 1 mA ENUMERATION: ODD/EVEN/NONE
2 –1 to 1 mA
0 = ODD, 1 = EVEN, 2 = NONE
3 0 to 5 mA
4 0 to 10 mA
5 0 to 20 mA
6 4 to 20 mA
F184 F192
ENUMERATION: REMOTE DEVICE GOOSE DATASET ENUMERATION: ETHERNET OPERATION MODE
0 = Half-Duplex, 1 = Full-Duplex
value GOOSE dataset
0 Off
1 GooseIn 1 F194
ENUMERATION: DNP SCALE
2 GooseIn 2
3 GooseIn 3 0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000,
4 GooseIn 4 7 = 100000, 8 = 0.001
5 GooseIn 5
6 GooseIn 6 F195
7 GooseIn 7 ENUMERATION: SINGLE POLE TRIP MODE
8 GooseIn 8
0 = Disabled, 1 = 3 Pole Only, 2 = 3 Pole & 1 Pole
F185 F196
ENUMERATION: PHASE A,B,C, GROUND SELECTOR ENUMERATION: NEUTRAL DIRECTIONAL OVERCURRENT
0 = A, 1 = B, 2 = C, 3 = G OPERATING CURRENT
0 = Calculated 3I0, 1 = Measured IG
F186
ENUMERATION: MEASUREMENT MODE F199
0 = Phase to Ground, 1 = Phase to Phase ENUMERATION: DISABLED/ENABLED/CUSTOM
0 = Disabled, 1 = Enabled, 2 = Custom
F190
ENUMERATION: SIMULATED KEYPRESS F200
TEXT40: 40-CHARACTER ASCII TEXT
bitmsk keypress bitmsk keypress
0 --- 23 Reset 20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
use between real keys
24 User 1
1 1 25 User 2 F201
2 2 26 User 3 TEXT8: 8-CHARACTER ASCII PASSCODE
3 3 27 User-programmable key 1
4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
4 4 28 User-programmable key 2
5 5 29 User-programmable key 3
6 6 30 User-programmable key 4 F202
TEXT20: 20-CHARACTER ASCII TEXT
7 7 31 User-programmable key 5
8 8 32 User-programmable key 6 10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
9 9 33 User-programmable key 7
10 0 34 User-programmable key 8
F203
11 Decimal Point 35 User-programmable key 9 TEXT16: 16-CHARACTER ASCII TEXT
12 Plus/Minus 36 User-programmable key 10
13 Value Up 37 User-programmable key 11
14 Value Down 38 User-programmable key 12 F204
TEXT80: 80-CHARACTER ASCII TEXT
F205 F231
TEXT12: 12-CHARACTER ASCII TEXT ENUMERATION: POLARIZING VOLTAGE
0 = Calculated V0, 1 = Measured VX
F206
TEXT6: 6-CHARACTER ASCII TEXT
F232
ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS
F207
FOR TRANSMISSION B
TEXT4: 4-CHARACTER ASCII TEXT
value GOOSE dataset item
0 None
F208 1 GGIO1.ST.Ind1.q
TEXT2: 2-CHARACTER ASCII TEXT 2 GGIO1.ST.Ind1.stVal
3 GGIO1.ST.Ind2.q
4 GGIO1.ST.Ind2.stVal
F211
ENUMERATION: SOURCE SELECTION ↓ ↓
255 GGIO1.ST.Ind128.q
0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4,
256 GGIO1.ST.Ind128.stVal
5 = SRC 5, 6 = SRC 6
257 MMXU1.MX.TotW.mag.f
258 MMXU1.MX.TotVAr.mag.f
F213 259 MMXU1.MX.TotVA.mag.f
TEXT32: 32-CHARACTER ASCII TEXT
260 MMXU1.MX.TotPF.mag.f
261 MMXU1.MX.Hz.mag.f
F220 262 MMXU1.MX.PPV.phsAB.cVal.mag.f
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY 263 MMXU1.MX.PPV.phsAB.cVal.ang.f
264 MMXU1.MX.PPV.phsBC.cVal.mag.f
value priority
265 MMXU1.MX.PPV.phsBC.cVal.ang.f
0 Disabled
266 MMXU1.MX.PPV.phsCA.cVal.mag.f
1 Normal
267 MMXU1.MX.PPV.phsCA.cVal.ang.f
2 High Priority
268 MMXU1.MX.PhV.phsA.cVal.mag.f
269 MMXU1.MX.PhV.phsA.cVal.ang.f
value current
F260
0 Calculated IN ENUMERATION: DATA LOGGER MODE
1 Measured IG
0 = Continuous, 1 = Trigger
F237
F270
ENUMERATION: REAL TIME CLOCK MONTH
ENUMERATION: FAULT REPORT VT SUBSTITUTION
value month
Value Description
0 January
0 None
1 February
1 I_0
2 March
2 V_0
3 April
4 May
5 June F300
6 July UR_UINT16: FLEXLOGIC™ BASE TYPE (6-bit type)
7 August The FlexLogic™ BASE type is 6 bits and is combined with a 9 bit
8 September descriptor and 1 bit for protection element to form a 16 bit value.
9 October The combined bits are of the form: PTTTTTTDDDDDDDDD,
where P bit if set, indicates that the FlexLogic™ type is associated
10 November
with a protection element state and T represents bits for the BASE
11 December type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
F238 [PTTTTTT] and the values in round brackets indicate the descrip-
tor range.
ENUMERATION: REAL TIME CLOCK DAY
[0] Off(0) – this is boolean FALSE value
value day [0] On (1) – this is boolean TRUE value
0 Sunday [2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
B [32] END
[34] NOT (1 INPUT)
F504
BITFIELD: 3-PHASE ELEMENT STATE
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 inputs) bitmask element state
[40] OR (2 to 16 inputs) 0 Pickup
[42] AND (2 to 16 inputs) 1 Operate
[44] NOR (2 to 16 inputs)
2 Pickup Phase A
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32) 3 Pickup Phase B
[50] ASSIGN VIRTUAL OUTPUT (1 to 96) 4 Pickup Phase C
[52] SELF-TEST ERROR (see F141 for range) 5 Operate Phase A
[56] ACTIVE SETTING GROUP (1 to 6) 6 Operate Phase B
[62] MISCELLANEOUS EVENTS (see F146 for range)
7 Operate Phase C
[64 to 127] ELEMENT STATES
F400 F505
UR_UINT16: CT/VT BANK SELECTION BITFIELD: CONTACT OUTPUT STATE
F510 F518
BITFIELD: 87L ELEMENT STATE ENUMERATION: FLEXELEMENT™ UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes
bitmask 87L Element State
0 Operate A
1 Operate B F519
2 Operate C ENUMERATION: NON-VOLATILE LATCH
3 Received DTT 0 = Reset-Dominant, 1 = Set-Dominant B
4 Operate
5 Key DTT
6 PFLL FAIL F521
ENUMERATION: GROUND DISTANCE POLARIZING CURRENT
7 PFLL OK
8 Channel 1 FAIL 0 = Zero-Sequence; 1 = Negative-Sequence
9 Channel 2 FAIL
10 Channel 1 Lost Packet
F522
11 Channel 2 Lost Packet ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE
12 Channel 1 CRC Fail
0 = –1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mA
13 Channel 2 CRC Fail
F523
F511 ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
BITFIELD: 3-PHASE SIMPLE ELEMENT STATE VARIATION
0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C
bitmask default variation
0 1
F513 1 2
ENUMERATION: POWER SWING MODE 2 5
0 = Two Step, 1 = Three Step 3 6
F514 F524
ENUMERATION: POWER SWING TRIP MODE ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION
F515 1 2
ENUMERATION ELEMENT INPUT MODE 2 9
3 10
0 = Signed, 1 = Absolute
F516 F525
ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION
ENUMERATION ELEMENT COMPARE MODE
0 = Level, 1 = Delta bitmask default variation
0 1
1 2
F517
2 3
ENUMERATION: ELEMENT DIRECTION OPERATION
3 4
0 = Over, 1 = Under
4 5
5 7
F530 F544
ENUMERATION: FRONT PANEL INTERFACE KEYPRESS ENUMERATION: PMU RECORDING/REPORTING RATE
value keypress value keypress value keypress
value rate value rate
0 None 15 3 33 User PB 3
0 1/second 6 15/second
1 Menu 16 Enter 34 User PB 4
1 2/second 7 20second
2 Message Up 17 Message 35 User PB 5
2 4/second 8 25/second
B 3 7 ~
18
Down
0 ~
36 User PB 6 3 5/second 9 30/second
F531 F547
ENUMERATION: LANGUAGE ENUMERATION: PMU REPORTING FORMAT
0 = English, 1 = French, 2 = Chinese, 3 = Russian 0 = Integer, 1 = Floating
F540 F600
ENUMERATION: PMU POST-FILTER UR_UINT16: FLEXANALOG PARAMETER
0 = None, 1 = Symm-3-Point, 2 = Symm-5-Point, Corresponds to the Modbus address of the value used when this
3 = Symm-7-Point parameter is selected. Only certain values may be used as Flex-
Analogs (basically all metering quantities used in protection).
F542
ENUMERATION: PMU TRIGGERING MODE F605
ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
0 = Automatic Overwrite, 1 = Protected
STATUS
F607 F610
ENUMERATION: OPEN POLE DETECTOR MODE ENUMERATION: SINGLE-POLE AUTORECLOSE INITIATION
MODE
Enumeration Open Pole Mode
0 Accelerated Enumeration Initiation Mode
F608
B
ENUMERATION: OPEN POLE DETECTION FUNCTION F611
ENUMERATION: GOOSE RETRANSMISSION SCHEME
Enumeration Open Pole Detection
0 I AND V AND CBaux Enumeration Configurable GOOSE retransmission scheme
The IEC 61850 standard is the result of electric utilities and vendors of electronic equipment to produce standardized com-
munications systems. IEC 61850 is a series of standards describing client/server and peer-to-peer communications, sub-
station design and configuration, testing, environmental and project standards. The complete set includes:
• IEC 61850-1: Introduction and overview
• IEC 61850-2: Glossary
• IEC 61850-3: General requirements
• IEC 61850-4: System and project management
• IEC 61850-5: Communications and requirements for functions and device models
• IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs
• IEC 61850-7-1: Basic communication structure for substation and feeder equipment - Principles and models
C
• IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract communication service
interface (ACSI)
• IEC 61850-7-3: Basic communication structure for substation and feeder equipment – Common data classes
• IEC 61850-7-4: Basic communication structure for substation and feeder equipment – Compatible logical node classes
and data classes
• IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2)
and to ISO/IEC 8802-3
• IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over serial unidirectional multi-
drop point to point link
• IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3
• IEC 61850-10: Conformance testing
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with
any IEC 61850 implementation obtain this document set.
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer
of real-time data. This protocol has been in existence for several of years and provides a set of services suitable for the
transfer of data within a substation LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser-
vices in IEC 61850-8-1.
The L90 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks.
The TP4/CLNP profile requires the L90 to have a network address or Network Service Access Point (NSAP) to establish a
communication link. The TCP/IP profile requires the L90 to have an IP address to establish communications. These
addresses are located in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK menu. Note that the L90
supports IEC 61850 over the TP4/CLNP or TCP/IP stacks, and also operation over both stacks simultaneously. It is possi-
ble to have up to five simultaneous connections (in addition to DNP and Modbus/TCP (non-IEC 61850) connections).
• Client/server: This is a connection-oriented type of communication. The connection is initiated by the client, and com-
munication activity is controlled by the client. IEC 61850 clients are often substation computers running HMI programs
or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, trans-
former tap changers, or bay controllers.
• Peer-to-peer: This is a non-connection-oriented, high speed type of communication usually between substation equip-
ment such as protection relays. GSSE and GOOSE are methods of peer-to-peer communication.
• Substation configuration language (SCL): A substation configuration language is a number of files used to describe
the configuration of substation equipment. Each configured device has an IEC Capability Description (ICD) file. The
substation single line information is stored in a System Specification Description (SSD) file. The entire substation con-
figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ-
ual ICD files and the SSD file.
IEC 61850 defines an object-oriented approach to data and services. An IEC 61850 physical device can contain one or
more logical device(s). Each logical device can contain many logical nodes. Each logical node can contain many data
objects. Each data object is composed of data attributes and data attribute components. Services are available at each
level for performing various functions, such as reading, writing, control commands, and reporting.
Each L90 IED represents one IEC 61850 physical device. The physical device contains one logical device, and the logical
device contains many logical nodes. The logical node LPHD1 contains information about the L90 IED physical device. The
logical node LLN0 contains information about the L90 IED logical device.
C The GGIO1 logical node is available in the L90 to provide access to as many 128 digital status points and associated time-
stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status
points for access by clients.
It is intended that clients use GGIO1 in order to access digital status values from the L90. Configuration settings are pro-
vided to allow the selection of the number of digital status indications available in GGIO1 (8 to 128), and to allow the choice
of the L90 FlexLogic™ operands that drive the status of the GGIO1 status indications. Clients can utilize the IEC 61850
buffered and unbuffered reporting features available from GGIO1 in order to build sequence of events (SOE) logs and HMI
display screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the
chances of missing data state changes. Unbuffered reporting should generally be used for local status display.
The GGIO2 logical node is available to provide access to the L90 virtual inputs. Virtual inputs are single-point control
(binary) values that can be written by clients. They are generally used as control inputs. GGIO2 provides access to the vir-
tual inputs through the IEC 61850 standard control model (ctlModel) services:
• Status only.
• Direct control with normal security.
• SBO control with normal security.
Configuration settings are available to select the control model for each point. Each virtual input used through GGIO2
should have its VIRTUAL INPUT 1(64) FUNCTION setting programmed as “Enabled” and its corresponding GGIO2 CF SPSCO1(64)
CTLMODEL setting programmed to the appropriate control configuration.
C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE DATA
The GGIO3 logical node is available to provide access for clients to values received via configurable GOOSE messages.
The values of the digital status indications and analog values in GGIO3 originate in GOOSE messages sent from other
devices.
The GGIO4 logical node provides access to as many as 32 analog value points, as well as associated timestamps and
quality flags. The data content must be configured before the data can be used. GGIO4 provides analog values for access
by clients.
It is intended that clients use GGIO4 to access generic analog values from the L90. Configuration settings allow the selec-
tion of the number of analog values available in GGIO4 (4 to 32) and the choice of the FlexAnalog™ values that determine
the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available
from GGIO4 in order to obtain the analog values provided by GGIO4.
A limited number of measured analog values are available through the MMXU logical nodes.
Each MMXU logical node provides data from a L90 current and voltage source. There is one MMXU available for each con-
figurable source (programmed in the SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES menu). MMXU1 provides data
from L90 source 1, and MMXU2 provides data from L90 source 2.
MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a
read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3.
The selection of appropriate deadband settings for the L90 is described in chapter 5 of this manual.
IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes pro-
vide the following data for each source:
• MMXU1.MX.TotW: three-phase real power
• MMXU1.MX.TotVAr: three-phase reactive power
C
• MMXU1.MX.TotVA: three-phase apparent power
• MMXU1.MX.TotPF: three-phase power factor
• MMXU1.MX.Hz: frequency
• MMXU1.MX.PPV.phsAB: phase AB voltage magnitude and angle
• MMXU1.MX.PPV.phsBC: phase BC voltage magnitude and angle
• MMXU1.MX.PPV.phsCA: Phase CA voltage magnitude and angle
• MMXU1.MX.PhV.phsA: phase AG voltage magnitude and angle
• MMXU1.MX.PhV.phsB: phase BG voltage magnitude and angle
• MMXU1.MX.PhV.phsC: phase CG voltage magnitude and angle
• MMXU1.MX.A.phsA: phase A current magnitude and angle
• MMXU1.MX.A.phsB: phase B current magnitude and angle
• MMXU1.MX.A.phsC: phase C current magnitude and angle
• MMXU1.MX.A.neut: ground current magnitude and angle
• MMXU1.MX.W.phsA: phase A real power
• MMXU1.MX.W.phsB: phase B real power
• MMXU1.MX.W.phsC: phase C real power
• MMXU1.MX.VAr.phsA: phase A reactive power
• MMXU1.MX.VAr.phsB: phase B reactive power
• MMXU1.MX.VAr.phsC: phase C reactive power
• MMXU1.MX.VA.phsA: phase A apparent power
• MMXU1.MX.VA.phsB: phase B apparent power
• MMXU1.MX.VA.phsC: phase C apparent power
• MMXU1.MX.PF.phsA: phase A power factor
• MMXU1.MX.PF.phsB: phase B power factor
• MMXU1.MX.PF.phsC: phase C power factor
The following list describes the protection elements for all UR-series relays. The L90 relay will contain a subset of protec-
tion elements from this list.
• PDIF: bus differential, transformer instantaneous differential, transformer percent differential
IEC 61850 buffered and unbuffered reporting is provided in the GGIO1 logical nodes (for binary status values) and MMXU1
to MMXU6 (for analog measured values). Report settings can be configured using the EnerVista UR Setup software, sub-
station configurator software, or via an IEC 61850 client. The following items can be configured:
• TrgOps: Trigger options. The following bits are supported by the L90:
– Bit 1: data-change
– Bit 4: integrity
– Bit 5: general interrogation
• OptFlds: Option Fields. The following bits are supported by the L90:
– Bit 1: sequence-number
– Bit 2: report-time-stamp
C
– Bit 3: reason-for-inclusion
– Bit 4: data-set-name
– Bit 5: data-reference
– Bit 6: buffer-overflow (for buffered reports only)
– Bit 7: entryID (for buffered reports only)
– Bit 8: conf-revision
– Bit 9: segmentation
• IntgPd: Integrity period.
• BufTm: Buffer time.
MMS file services are supported to allow transfer of oscillography, event record, or other files from a L90 relay.
The timestamp values associated with all IEC 61850 data items represent the time of the last change of either the value or
quality flags of the data item. To accomplish this functionality, all IEC 61850 data items must be regularly scanned for data
changes, and the timestamp updated when a change is detected, regardless of the connection status of any IEC 61850 cli-
ents. For applications where there is no IEC 61850 client in use, the IEC 61850 SERVER SCANNING setting can be pro-
grammed as “Disabled”. If a client is in use, this setting should be programmed as “Enabled” to ensure the proper
generation of IEC 61850 timestamps.
The logical device name is used to identify the IEC 61850 logical device that exists within the L90. This name is composed
of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of
the two character strings programmed in the IEDNAME and LD INST settings. The default values for these strings are “IED-
Name” and “LDInst”. These values should be changed to reflect a logical naming convention for all IEC 61850 logical
devices in the system.
C.3.5 LOCATION
The LPHD1 logical node contains a data attribute called location (LPHD1.DC.PhyNam.location). This is a character string
meant to describe the physical location of the L90. This attribute is programmed through the LOCATION setting and its
default value is “Location”. This value should be changed to describe the actual physical location of the L90.
IEC 61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of:
• a five or six-character name prefix.
• a four-character standard name (for example, MMXU, GGIO, PIOC, etc.).
• a one or two-character instantiation index.
Complete names are of the form xxxxxxPIOC1, where the xxxxxx character string is configurable. Details regarding the
logical node naming rules are given in IEC 61850 parts 6 and 7-2. It is recommended that a consistent naming convention
be used for an entire substation project.
C A built-in TCP/IP connection timeout of two minutes is employed by the L90 to detect ‘dead’ connections. If there is no data
traffic on a TCP connection for greater than two minutes, the connection will be aborted by the L90. This frees up the con-
nection to be used by other clients. Therefore, when using IEC 61850 reporting, clients should configure report control
block items such that an integrity report will be issued at least every 2 minutes (120000 ms). This ensures that the L90 will
not abort the connection. If other MMS data is being polled on the same connection at least once every 2 minutes, this tim-
eout will not apply.
The L90 relay makes available a number of non-IEC 61850 data items. These data items can be accessed through the
“UR” MMS domain. IEC 61850 data can be accessed through the standard IEC 61850 logical device. To access the non-
IEC data items, the INCLUDE NON-IEC DATA setting must be “Enabled”.
The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a L90 relay with an
MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc.
IEC 61850 specifies two types of peer-to-peer data transfer services: Generic Substation State Events (GSSE) and Generic
Object Oriented Substation Events (GOOSE). GSSE services are compatible with UCA 2.0 GOOSE. IEC 61850 GOOSE
services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ethertype Application ID configuration. The sup-
port for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given
a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Because of the additional
features of GOOSE services versus GSSE services, it is recommended that GOOSE be used wherever backwards com-
patibility with GSSE (or UCA 2.0 GOOSE) is not required.
Devices that transmit GSSE and/or GOOSE messages also function as servers. Each GSSE publisher contains a “GSSE
control block” to configure and control the transmission. Each GOOSE publisher contains a “GOOSE control block” to con-
figure and control the transmission. The transmission is also controlled via device settings. These settings can be seen in
the ICD and/or SCD files, or in the device configuration software or files.
IEC 61850 recommends a default priority value of 4 for GOOSE. Ethernet traffic that does not contain a priority tag has a
C
default priority of 1. More details are specified in IEC 61850 part 8-1.
IEC 61850 recommends that the Ethertype Application ID number be configured according to the GOOSE source. In the
L90, the transmitted GOOSE Application ID number must match the configured receive Application ID number in the
receiver. A common number may be used for all GOOSE transmitters in a system. More details are specified in IEC 61850
part 8-1.
IEC 61850 Generic Substation Status Event (GSSE) communication is compatible with UCA GOOSE communication.
GSSE messages contain a number of double point status data items. These items are transmitted in two pre-defined data
structures named DNA and UserSt. Each DNA and UserSt item is referred to as a ‘bit pair’. GSSE messages are transmit-
ted in response to state changes in any of the data points contained in the message. GSSE messages always contain the
same number of DNA and UserSt bit pairs. Depending the on the configuration, only some of these bit pairs may have val-
ues that are of interest to receiving devices.
The GSSE FUNCTION, GSSE ID, and GSSE DESTINATION MAC ADDRESS settings are used to configure GSSE transmission.
GSSE FUNCTION is set to “Enabled” to enable the transmission. If a valid multicast Ethernet MAC address is entered for the
GSSE DESTINATION MAC ADDRESS setting, this address will be used as the destination MAC address for GSSE messages. If
a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the L90 will use the source Ether-
net MAC address as the destination, with the multicast bit set.
The L90 supports two types of IEC 61850 Generic Object Oriented Substation Event (GOOSE) communication: fixed
GOOSE and configurable GOOSE. All GOOSE messages contain IEC 61850 data collected into a dataset. It is this dataset
that is transferred using GOOSE message services. The dataset transferred using the L90 fixed GOOSE is the same data
that is transferred using the GSSE feature; that is, the DNA and UserSt bit pairs. The FlexLogic™ operands that determine
the state of the DNA and UserSt bit pairs are configurable via settings, but the fixed GOOSE dataset always contains the
same DNA/UserSt data structure. Upgrading from GSSE to GOOSE services is simply a matter of enabling fixed GOOSE
and disabling GSSE. The remote inputs and outputs are configured in the same manner for both GSSE and fixed GOOSE.
It is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between UR-
series IEDs. Configurable GOOSE may be used for implementations that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers.
The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the L90.
The L90 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data
transfer between devices.
Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.
Dataset 1 should be used for high-speed transmission of data that is required for applications such as transfer tripping,
blocking, and breaker fail initiate. At least one digital status value needs to be configured in dataset 1 to enable transmis-
sion of all data configured for dataset 1. Configuring analog data only to dataset 1 will not activate transmission.
Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every
100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any
changes have been made. If any changes in the data items are detected, these changes will be transmitted through a
GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.
For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no
changes in the data items are detected.
The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes-
sages due to an oscillation being created that is triggering a message.
C The L90 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be
caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station
components. If erroneously oscillation is detected, the L90 will stop sending GOOSE messages from the dataset for a min-
imum period of one second. Should the oscillation persist after the one second time-out period, the L90 will continue to
block transmission of the dataset. The L90 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error mes-
sage on the front panel display, where XXX denotes the data item detected as oscillating.
The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup-
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
1. Configure the transmission dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
The general steps required for reception configuration are:
1. Configure the reception dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ
IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE
GOOSE 1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:
– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception
dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION
ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGU-
RABLE GOOSE 1 settings menu:
– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE DEVICES
ÖØ REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
– Set REMOTE DEVICE 1 ETYPE APPID to match the Ethertype application ID from the transmitting device. This is “0” in
the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the data by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE INPUTS ÖØ REMOTE INPUT 1
settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The L90 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
Ethernet capable devices each contain a unique identifying address called a Media Access Control (MAC) address. This
address cannot be changed and is unique for each Ethernet device produced worldwide. The address is six bytes in length
and is usually represented as six hexadecimal values (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as
the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can
be different for each Ethernet frame depending on the intended destination of the frame.
A special type of destination address called a multicast address is used when the Ethernet frame can be received by more
than one device. An Ethernet MAC address is multicast when the least significant bit of the first byte is set (for example, 01
00 00 00 00 00 is a multicast address).
GSSE and GOOSE messages must have multicast destination MAC addresses.
By default, the L90 is configured to use an automated multicast MAC scheme. If the L90 destination MAC address setting
is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina-
tion MAC will be the same as the local MAC address, but with the multicast bit set. Thus, if the local MAC address is 00 A0
F4 01 02 03, then the destination MAC address will be 01 A0 F4 01 02 03.
GSSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in IEC
C 61850 part 8-1 as GsID. This is a programmable 65-character string. This string should be chosen to provide a descriptive
name of the originator of the GSSE message.
GOOSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in
IEC 61850 part 8-1 as GoID. This programmable 65-character string should be a descriptive name of the originator of the
GOOSE message. GOOSE messages also contain two additional character strings used for identification of the message:
DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block.
These strings are automatically populated and interpreted by the L90; no settings are required.
The L90 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1. An ICD file is generated for the L90 by the EnerVista UR Setup software that describe the capabilities of the IED.
2. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3. The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.
Import
System
specification data SSD file
System specification tool
System configurator
System Configuration
(network, cross-
communications, IED setting
modification, etc.)
SCD file
EnerVista UR Setup
Ethernet
842790A1.CDR
Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED. For example, the IED name
and logical device instance can be specified to uniquely identify the IED within the substation, or transmission GOOSE
datasets created so that the system configurator can configure the cross-communication links to send GOOSE messages
from the IED. Once the IEC 61850 settings are configured, the ICD creation process will recognize the changes and gener-
ate an ICD file that contains the updated settings.
Some of the IED settings will be modified during they system configuration process. For example, a new IP address may be
assigned, line items in a Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be
changed. While all new configurations will be mapped to the L90 settings file when importing an SCD file, all unchanged
settings will preserve the same values in the new settings file.
These settings can be configured either directly through the relay panel or through the EnerVista UR Setup software (pre-
ferred method). The full list of IEC 61850 related settings for are as follows:
• Network configuration: IP address, IP subnet mask, and default gateway IP address (access through the Settings >
Product Setup > Communications > Network menu tree in EnerVista UR Setup).
• Server configuration: IED name and logical device instance (access through the Settings > Product Setup > Com-
munications > IEC 61850 > Server Configuration menu tree in EnerVista UR Setup).
• Logical node prefixes, which includes prefixes for all logical nodes except LLN0 (access through the Settings > Prod-
uct Setup > Communications > IEC 61850 > Logical Node Prefixes menu tree in EnerVista UR Setup).
• MMXU deadbands, which includes deadbands for all available MMXUs. The number of MMXUs is related to the num-
ber of CT/VT modules in the relay. There are two MMXUs for each CT/VT module. For example, if a relay contains two
CT/VT modules, there will be four MMXUs available (access through the Settings > Product Setup > Communica-
tions > IEC 61850 > MMXU Deadbands menu tree in EnerVista UR Setup).
• GGIO1 status configuration, which includes the number of status points in GGIO1 as well as the potential internal map-
pings for each GGIO1 indication. However only the number of status points will be used in the ICD creation process
(access through the Settings > Product Setup > Communications > IEC 61850 > GGIO1 Status Configuration
menu tree in EnerVista UR Setup).
• GGIO2 control configuration, which includes ctlModels for all SPCSOs within GGIO2 (access through the Settings >
Product Setup > Communications > IEC 61850 > GGIO2 Control Configuration menu tree in EnerVista UR
Setup).
• Configurable transmission GOOSE, which includes eight configurable datasets that can be used for GOOSE transmis-
sion. The GOOSE ID can be specified for each dataset (it must be unique within the IED as well as across the whole
substation), as well as the destination MAC address, VLAN priority, VLAN ID, ETYPE APPID, and the dataset items.
C
The selection of the dataset item is restricted by firmware version; for version 5.7x, only GGIO1.ST.Indx.stVal and
GGIO1.ST.Indx.q are valid selection (where x is between 1 to N, and N is determined by number of GGIO1 status
points). Although configurable transmission GOOSE can also be created and altered by some third-party system con-
figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly
within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com-
munications > IEC 61850 > GSSE/GOOSE Configuration > Transmission > Tx Configurable GOOSE menu tree
in EnerVista UR Setup).
• Configurable reception GOOSE, which includes eight configurable datasets that can be used for GOOSE reception.
However, unlike datasets for transmission, datasets for reception only contains dataset items, and they are usually cre-
ated automatically by process of importing the SCD file (access through the Settings > Product Setup > Communi-
cations > IEC 61850 > GSSE/GOOSE Configuration > Reception > Rx Configurable GOOSE menu tree in
EnerVista UR Setup).
• Remote devices configuration, which includes remote device ID (GOOSE ID or GoID of the incoming transmission
GOOSE dataset), ETYPE APPID (of the GSE communication block for the incoming transmission GOOSE), and
DATASET (which is the name of the associated reception GOOSE dataset). These settings are usually done automat-
ically by process of importing SCD file (access through the Settings > Inputs/Outputs > Remote Devices menu tree
in EnerVista UR Setup).
• Remote inputs configuration, which includes device (remote device ID) and item (which dataset item in the associated
reception GOOSE dataset to map) values. Only the items with cross-communication link created in SCD file should be
mapped. These configurations are usually done automatically by process of importing SCD file (access through the
Settings > Inputs/Outputs > Remote Inputs menu tree in EnerVista UR Setup).
The SCL language is based on XML, and its syntax definition is described as a W3C XML Schema. ICD is one type of SCL
file (which also includes SSD, CID and SCD files). The ICD file describes the capabilities of an IED and consists of four
major sections:
• Header
• Communication
• IEDs
• DataTypeTemplates
SCL
Communication
DataTypeTemplates
842795A1.CDR
Communication
SubNetwork (name)
Address
P (type)
Text
Other P elements
Address
P (type)
Text
Services
AccessPoint (name)
Server
Authentication (none) C
LDevice (inst)
DataSet (name)
DOI (name)
DataSet (name)
DOI (name)
The DataTypeTemplates node defines instantiable logical node types. A logical node type is an instantiable template of the
data of a logical node. A LnodeType is referenced each time that this instantiable type is needed with an IED. A logical
node type template is built from DATA (DO) elements, which again have a DO type, which is derived from the DATA classes
(CDC). DOs consist of attributes (DA) or of elements of already defined DO types (SDO). The attribute (DA) has a func-
tional constraint, and can either have a basic type, be an enumeration, or a structure of a DAType. The DAType is built from
BDA elements, defining the structure elements, which again can be BDA elements of have a base type such as DA.
DataTypeTemplates
DO (name, type)
Other DO elements
DAType (id)
EnumType (id)
An ICD file can be created directly from a connected L90 IED or from an offline L90 settings file with the EnerVista UR
Setup software using the following procedure:
1. Right-click the connected UR-series relay or settings file and select Create ICD File.
2. The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click
OK to generate the file.
The time to create an ICD file from the offline L90 settings file is typically much quicker than create an ICD file directly from
the relay.
System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their
own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI
version 4.6 or above and ASE Visual SCL Beta 0.12).
Although the configuration tools vary from one vendor to another, the procedure is pretty much the same. First, a substation
project must be created, either as an empty template or with some system information by importing a system specification
file (SSD). Then, IEDs are added to the substation. Since each IED is represented by its associated ICD, the ICD files are
imported into the substation project, and the system configurator validates the ICD files during the importing process. If the
ICD files are successfully imported into the substation project, it may be necessary to perform some additional minor steps
to attach the IEDs to the substation (see the system configurator manual for details).
Once all IEDs are inserted into the substation, further configuration is possible, such as:
• assigning network addresses to individual IEDs
• customizing the prefixes of logical nodes
• creating cross-communication links (configuring GOOSE messages to send from one IED to others)
When system configurations are complete, the results are saved to an SCD file, which contains not only the configuration
for each IED in the substation, but also the system configuration for the entire substation. Finally, the SCD file is passed
back to the IED configurator (vendor specific tool) to update the new configuration into the IED.
The SCD file consists of at least five major sections:
• Header
• Substation
• Communication
• IED section (one or more)
• DataTypeTemplates
The root file structure of an SCD file is illustrated below.
SCL
C Substation
Communication
DataTypeTemplates
842791A1.CDR
Substation
PowerSystemResource
GeneralEquipment
EquipmentContainer
VoltageLevel Bay
Voltage
PowerSystemResource
Function SubFunction
GeneralEquipment
842792A1.CDR
The Communication node describes the direct communication connection possibilities between logical nodes by means of
logical buses (sub-networks) and IED access ports. The communication section is structured as follows.
Communication
SubNetwork (name)
ConnectedAP (IED 1)
Address
P (type)
Text
Other P elements
P (type)
Other P elements
ConnectedAP (IED 2)
Address
P (type)
Text
Other P elements
Address
P (type)
Text
Other P elements
Other GSE elements
AccessPoint (name)
Server
Authentication (none)
LDevice (inst)
DataSet elements
C ReportControl elements
DOI elements
Inputs
GSEControl elements
842794A1.CDR
The following procedure describes how to update the L90 with the new configuration from an SCD file with the EnerVista
UR Setup software.
1. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
3. The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and
name for the URS (UR-series relay settings) file.
If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set-
tings file for each IED.
4. After the URS file is created, modify any settings (if required).
5. To update the relay with the new settings, right-click on the settings file in the settings tree and select the Write Set-
tings File to Device item.
6. The software will prompt for the target device. Select the target device from the list provided and click Send. The new
settings will be updated to the selected device.
c1: shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
NOTE M: Mandatory
c2: shall be "M" if support for LOGICAL-NODE model has been declared
c3: shall be "M" if support for DATA model has been declared
NOTE c4: shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared
c5: shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
In the table below, the acronym AA refers to Application Associations (TP: Two Party / MC: Multicast). The c6 to c10 entries
are defined in the notes following the table.
The UR-series of relays supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantia-
tion of each logical node is determined by the product order code. For example. the logical node “PDIS” (distance protec-
tion) is available only in the D60 Line Distance Relay.
This document is adapted from the IEC 60870-5-104 standard. For ths section the boxes indicate the following: 4 – used in
standard direction;
– not used; – cannot be selected in IEC 60870-5-104 standard.
1. SYSTEM OR DEVICE:
System Definition
Controlling Station Definition (Master)
4 Controlled Station Definition (Slave)
2. NETWORK CONFIGURATION:
Point-to-Point Multipoint
Multiple Point-to-Point Multipoint Star
3. PHYSICAL LAYER
Transmission Speed (control direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s: D
100 bits/sec. 2400 bits/sec. 2400 bits/sec.
200 bits/sec. 4800 bits/sec. 4800 bits/sec.
300 bits/sec. 9600 bits/sec. 9600 bits/sec.
600 bits/sec. 19200 bits/sec.
1200 bits/sec. 38400 bits/sec.
56000 bits/sec.
64000 bits/sec.
Transmission Speed (monitor direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s:
100 bits/sec. 2400 bits/sec. 2400 bits/sec.
200 bits/sec. 4800 bits/sec. 4800 bits/sec.
300 bits/sec. 9600 bits/sec. 9600 bits/sec.
600 bits/sec. 19200 bits/sec.
1200 bits/sec. 38400 bits/sec.
56000 bits/sec.
64000 bits/sec.
4. LINK LAYER
Link Transmission Procedure: Address Field of the Link:
Balanced Transmision Not Present (Balanced Transmission Only)
Unbalanced Transmission One Octet
Two Octets
Structured
Unstructured
Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low priority) with the
indicated causes of transmission:
The standard assignment of ADSUs to class 2 messages is used as follows:
5. APPLICATION LAYER
Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in this companion
stanadard.
Common Address of ADSU:
One Octet
4 Two Octets
Information Object Address:
One Octet 4 Structured
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the set
<30> to <40> are used.
Process information in control direction
4 <45> := Single command C_SC_NA_1
D
<46> := Double command C_DC_NA_1
<47> := Regulating step command C_RC_NA_1
<48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point value C_SE_NC_1
<51> := Bitstring of 32 bits C_BO_NA_1
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
System information in monitor direction
4 <70> := End of initialization M_EI_NA_1
File transfer
<120> := File Ready F_FR_NA_1
<121> := Section Ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory (blank or X, available only in monitor [standard] direction) C_CD_NA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<1> M_SP_NA_1 X X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<10> M_ME_TA_1 D
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X
<59> C_DC_TA_1
<60> C_RC_TA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
D <61>
<62>
C_SE_TA_1
C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
<70> M_EI_NA_1*) X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<107> C_TS_TA_1
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1 X X X
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*)
Spontaneous Transmission:
4 Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of an information
object. The particular information object addresses for which double transmission is enabled are defined in a project-
specific list.
Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1
Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1
Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1
Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1
Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1
Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
4 Global D
4 Group 1 4 Group 5 4 Group 9 4 Group 13
4 Group 2 4 Group 6 4 Group 10 4 Group 14
4 Group 3 4 Group 7 4 Group 11 4 Group 15
4 Group 4 4 Group 8 4 Group 12 4 Group 16
Clock synchronization:
4 Clock synchronization (optional, see Clause 7.6)
Command transmission:
4 Direct command transmission
Direct setpoint command transmission
4 Select and execute command
Select and execute setpoint command
4 C_SE ACTTERM used
4 No additional definition
4 Short pulse duration (duration determined by a system parameter in the outstation)
4 Long pulse duration (duration determined by a system parameter in the outstation)
4 Persistent output
4 Counter read
4 Counter freeze without reset
APPENDIX E DNP COMMUNICATIONSE.1DEVICE PROFILE DOCUMENT E.1.1 DNP V3.00 DEVICE PROFILE
The following table provides a ‘Device Profile Document’ in the standard format defined in the DNP 3.0 Subset Definitions
Document.
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Control Relay Output Block (Object 12)
Binary Counters (Object 20)
E
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
File Transfer (Object 70)
Internal Indications (Object 80)
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: configurable up to 2048
Received: 292 Received: 2048
Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms
Explanation of ‘Sometimes’: Object 12 points are mapped to UR Virtual Inputs. The persistence of Virtual Inputs is
determined by the VIRTUAL INPUT X TYPE settings. Both “Pulse On” and “Latch On” operations perform the same func-
tion in the UR; that is, the appropriate Virtual Input is put into the “On” state. If the Virtual Input is set to “Self-Reset”,
it will reset after one pass of FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off”
operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate
Virtual Input into the “On” state.
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events when no
specific variation requested: specific variation requested:
Never
Never
4 Only time-tagged 4 Binary Input Change With Time
Only non-time-tagged
Binary Input Change With Relative Time
Configurable
Configurable (attach explanation)
The following table identifies the variations, function codes, and qualifiers supported by the L90 in both request messages
and in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or
28. For change-event objects, qualifiers 17 or 28 are always responded.
3 Binary Input Change with Relative Time 1 (read) 06 (no range, or all)
07, 08 (limited quantity)
10 0 Binary Output Status (Variation 0 is used to 1 (read) 00, 01(start-stop)
request default variation) 06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
12 1 Control Relay Output Block 3 (select) 00, 01 (start-stop) 129 (response) echo of request
4 (operate) 07, 08 (limited quantity)
5 (direct op) 17, 28 (index)
6 (dir. op, noack)
20 0 Binary Counter 1 (read) 00, 01(start-stop)
(Variation 0 is used to request default 7 (freeze) 06(no range, or all)
variation) 8 (freeze noack) 07, 08(limited quantity)
9 (freeze clear) 17, 28(index)
10 (frz. cl. noack)
22 (assign class)
1 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
7 (freeze) 06 (no range, or all) 17, 28 (index)
8 (freeze noack) 07, 08 (limited quantity) (see Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the L90 is not restarted, but the DNP process is restarted.
The DNP binary input data points are configured through the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT
LISTS Ö BINARY INPUT / MSP POINTS menu. Refer to the Communications section of Chapter 5 for additional details. When a
freeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counter
point.
Supported Control Relay Output Block fields: Pulse On, Pulse Off, Latch On, Latch Off, Paired Trip, Paired Close.
E.2.3 COUNTERS
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is per-
formed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.
BINARY COUNTERS
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear),
10 (freeze and clear, noack), 22 (assign class)
Static Variation reported when variation 0 requested: 1 (32-Bit Binary Counter with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Change Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3
FROZEN COUNTERS
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
E Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3
A counter freeze command has no meaning for counters 8 and 9. L90 Digital Counter values are represented as 32-bit inte-
gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative
counter values.
The DNP analog input data points are configured through the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT
LISTS Ö ANALOG INPUT / MME POINTS menu. Refer to the Communications section of Chapter 5 for additional details.
It is important to note that 16-bit and 32-bit variations of analog inputs are transmitted through DNP as signed numbers.
Even for analog input points that are not valid as negative values, the maximum positive representation is 32767 for 16-bit
values and 2147483647 for 32-bit values. This is a DNP requirement.
The deadbands for all Analog Input points are in the same units as the Analog Input quantity. For example, an Analog Input
quantity measured in volts has a corresponding deadband in units of volts. This is in conformance with DNP Technical Bul-
letin 9809-001: Analog Input Reporting Deadband. Relay settings are available to set default deadband values according to
data type. Deadbands for individual Analog Input Points can be set using DNP Object 34.
2-17 2-17 Update Updated PROTECTION ELEMENTS section for changes to line current differential specifications
2-22 2-22 Update Updated MONITORING specifications section
2-23 2-23 Update Updated INPUTS specifications section
2-27 2-27 Update Updated ENVIRONMENTAL specifications section
2-27 2-28 Update Updated TYPE TESTS specifications section
5-8 5-8 Update Updated PASSWORD SECURITY section (now titled SECURITY)
--- 5-31 Add Added ETHERNET SWITCH sub-section
5-44 5-45 Update Updated USER-PROGRAMMABLE PUSHBUTTONS section
5-62 5-64 Update Updated BREAKERS section
--- 5-68 Add Added DISCONNECT SWITCHES section
5-90 5-96 Update Updated FLEXLOGIC OPERANDS table
B-9 B-9 Update Update MODBUS MEMORY MAP section for revision 5.5x
In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay
providing the warrantor determined that it is defective and it is returned with all transportation
charges prepaid to an authorized service centre or the factory. Repairs or replacement under war-
ranty will be made without charge.
Warranty shall not apply to any relay which has been subject to misuse, negligence, accident,
incorrect installation or use not in accordance with instructions nor any unit that has been altered
outside a GE Multilin authorized factory outlet.
F GE Multilin is not liable for special, indirect or consequential damages or for loss of profit or for
expenses sustained as a result of a relay malfunction, incorrect application or adjustment.
For complete text of Warranty (including limitations and disclaimers), refer to GE Multilin Standard
Conditions of Sale.
Index
I
L
I2T CURVES .................................................................. 5-162
IAC CURVES ................................................................. 5-161 L90 POWER SYSTEM
IEC 60870-5-104 PROTOCOL Modbus registers .......................................................... B-25
interoperability document .................................................D-1 L90 TRIP
Modbus registers ........................................................... B-22 Modbus registers .......................................................... B-31
points list ........................................................................D-9 LAMPTEST ........................................................................ 7-3
settings ......................................................................... 5-32 LANGUAGE ..................................................................... 5-12
IEC 61850 GOOSE ANALOGS LASER MODULE .............................................................. 3-29
settings ....................................................................... 5-273 LATCHING OUTPUTS
IEC 61850 GOOSE UINTEGERS application example .......................................... 5-265, 5-266
settings ....................................................................... 5-274 error messages ................................................................ 7-9
IEC 61850 PROTOCOL settings ....................................................................... 5-264
device ID ..................................................................... 5-268 specifications ................................................................. 2-24
DNA2 assignments ...................................................... 5-270 LED INDICATORS ......................... 4-14, 4-15, 4-16, 4-22, 5-45
error messages ............................................................... 7-9 LED TEST
Modbus registers .............. B-47, B-48, B-49, B-50, B-51, B-61 FlexLogic™ operand .................................................... 5-108
remote device settings ................................................. 5-267 settings ......................................................................... 5-43
remote inputs .............................................................. 5-268 specifications ................................................................. 2-21
settings ......................................................................... 5-21 LINE
UserSt-1 bit pair .......................................................... 5-270 pickup ......................................................................... 5-127
IEC CURVES ................................................................. 5-160 LINE DIFFERENTIAL ELEMENTS ................................... 5-122
IED .................................................................................... 1-2 LINE PICKUP
IED SETUP ........................................................................ 1-5 FlexLogic™ operands ................................................... 5-103
IEEE C37.94 COMMUNICATIONS ................... 3-36, 3-38, 3-40 logic ............................................................................ 5-128
IEEE CURVES ............................................................... 5-159 Modbus registers .......................................................... B-37
IMPORTANT CONCEPTS ................................................... 1-4 settings ....................................................................... 5-127
IN SERVICE INDICATOR .......................................... 1-17, 7-6 specifications ................................................................. 2-17
INCOMPATIBLE HARDWARE ERROR ................................ 7-7 LINK POWER BUDGET .................................................... 2-27
INPUTS LOAD ENCROACHMENT
AC current .............................................................2-23, 5-59 FlexLogic™ operands ................................................... 5-103
AC voltage ............................................................2-23, 5-60 Modbus registers .......................................................... B-34
contact inputs ........................................... 2-23, 5-261, 5-282 settings ............................................................ 5-156, 5-157
dcmA inputs ..........................................................2-23, 3-22 specifications ................................................................. 2-20
direct inputs ................................................................ 5-271 LOCAL LOOPBACK ........................................................ 5-284
IRIG-B ..................................................................2-23, 3-26 LOGIC GATES ............................................................... 5-110
remote inputs .................................2-23, 5-267, 5-268, 5-269 LOOP FILTER BLOCK DIAGRAM ...................................... 9-10
RTD inputs ............................................................2-23, 3-22 LOOPBACK ........................................................... 2-13, 5-284
virtual ......................................................................... 5-263 LOST PASSWORD ...................................... 5-9, 5-10, 8-2, 8-3
INSPECTION CHECKLIST ................................................. 1-1 LV FAULT ...................................................................... 10-13
INSTALLATION
communications ............................................................ 3-24
CT inputs ..............................................................3-12, 3-13
RS485 ........................................................................... 3-25 M
settings ......................................................................... 5-57
MAINTENANCE COMMANDS ............................................. 7-3
UNIT NOT PROGRAMMED ........................................ 5-57, 7-7 FlexLogic™ operands ................................................... 5-108
UNPACKING THE RELAY ................................................... 1-1 Modbus registers ........................................................... B-54
UPDATING ORDER CODE ................................................. 7-3 settings ........................................................................ 5-266
URPC VOLTAGE BANKS ............................................................5-60
see entry for ENERVISTA UR SETUP VOLTAGE DEVIATIONS ...................................................2-28
USER-DEFINABLE DISPLAYS VOLTAGE ELEMENTS .................................................... 5-196
example ........................................................................ 5-57 VOLTAGE METERING
invoking and scrolling .................................................... 5-55 Modbus registers ........................................................... B-12
Modbus registers ..................................................B-21, B-26 specifications .................................................................2-22
settings ................................................................ 5-55, 5-57 values ............................................................................6-15
specifications ................................................................. 2-21 VOLTAGE RESTRAINT CHARACTERISTIC ..................... 5-163
USER-PROGRAMMABLE LEDs VT FUSE FAILURE
custom labeling ............................................................. 4-22 logic ............................................................................ 5-241
defaults ......................................................................... 4-16 Modbus registers ........................................................... B-45
description............................................................ 4-15, 4-16 settings ........................................................................ 5-241
Modbus registers ...........................................................B-23 VT INPUTS ....................................................... 3-13, 5-6, 5-60
settings ......................................................................... 5-45 VT WIRING ......................................................................3-13
specifications ................................................................. 2-21 VTFF
USER-PROGRAMMABLE PUSHBUTTONS FlexLogic™ operands ................................................... 5-106
FlexLogic™ operands .................................................. 5-109 see VT FUSE FAILURE
Modbus registers ..................................................B-27, B-39
settings ......................................................................... 5-49
specifications ................................................................. 2-21
USER-PROGRAMMABLE SELF TESTS W
Modbus registers ...........................................................B-24
WARRANTY ...................................................................... F-8
settings ......................................................................... 5-46
WATT-HOURS ......................................................... 2-22, 6-17
USERST-1 BIT PAIR ...................................................... 5-270
WATTMETRIC ZERO-SEQUENCE DIRECTIONAL
actual values ..................................................................6-20
FlexLogic™ operands ................................................... 5-107
V Modbus registers ........................................................... B-32
settings ........................................................................ 5-177
VAR-HOURS ........................................................... 2-22, 6-17 specifications .................................................................2-19
VIBRATION TESTING ...................................................... 2-28 WEB SERVER PROTOCOL ...............................................5-32
VIRTUAL INPUTS WEBSITE .......................................................................... 1-1
actual values ................................................................... 6-3 WIRING DIAGRAM ...........................................................3-10
commands ....................................................................... 7-1
FlexLogic™ operands .................................................. 5-107
logic ............................................................................ 5-263
Modbus registers ................................................... B-9, B-53 Z
settings ....................................................................... 5-263
ZERO SEQUENCE CORE BALANCE .................................3-13
VIRTUAL OUTPUTS
ZERO-SEQUENCE CURRENT REMOVAL .........................5-66
actual values ................................................................... 6-5