Paralleling Disimilar Generators - Part 1 PDF
Paralleling Disimilar Generators - Part 1 PDF
TM
CLIENT CUMMINS
Dissimilar CD Brien S.
JOB DESCRIPTION White Paper
generators AD
FLAT 8.5” x 11”
CW Don F.
BLEED 1/8”
3 FOLDED
FILE 100%
DS
AM Christie G.
COLOR CMYK
PM Katie D.
c M Y K CLIENT Cummins
System-level issues “knows” the kW capacity of the generator sets available
on line can automatically compensate for the difference
Before looking at generator set compatibility, in sizes by using different sequencing when different
it’s worthwhile to consider several system-level combinations of equipment are available.
problems that come about due to use of dissimilar
How much difference in size is “practical”? That is a
generator sets.
matter of considerable discussion in the industry. We
If generator sets are of dissimilar sizes, there can be know that it’s technically possible to parallel anything
impacts on the system design. An emergency system with anything, but where it’s practical is less clear. In
with generator sets that have matching kW ratings general, you probably will have a manageable system
can support a higher first priority load than a system when the smallest generator set is no less than 30% of
that has generator sets with dissimilar kW ratings. the capacity of the largest generator set in the system.
For example, an emergency system with two 500 kW If there is a larger disparity in equipment sizes, it might
generator sets will handle a first priority load as large as be easier to make the larger machine bigger, and forget
500 kW. A system with one 750 kW generator set and about paralleling altogether.
one 250 kW generator set, while having the same total
It’s useful to note that there are often large kW size
power rating, should be limited to a 250 kW first priority
load, because if the first generator set closing to the bus differences in prime power applications, such as are used
is the 250 kW machine, any load greater than 250 kW in remote, isolated cities and towns. In those applications,
could cause it to be overloaded. loads during the daylight hours are often much higher
than in the evenings. A pair of 350 kW generator sets
When faced with the use of dissimilar-sized generator
may be running during the day, and only a 50 kW set
sets, some designers will insert bus isolation ties
running at night. This is less of an issue in prime power
between generator sets in order to prevent overloading
applications because the load profile does not quickly
on startup. This, however, sets up another series
of issues because of the added complexity in the change, and the systems generally have no automatic
sequence of operation and usually the need for more load management systems.
synchronizers in the system. Manual operation and
As a technical matter, the smallest power circuit breaker
failure mode effects are also more difficult to deal with
that we can provide is an 800 amp frame. So it can
as tiebreakers are inserted into a system.
be costly to parallel smaller generator sets. In those
Changes in sequence of operation may be necessary cases it’s possible to source 5-cycle operating molded
due to use of dissimiliar-sized machines. It is not case breakers for use in paralleling the generator.
advisable to design a system sequence of operation These breakers are smaller, available in fixed frame
contingent on synchronizing generator sets within configurations so less space is needed for the equipment,
10 seconds. Many manufacturers cannot provide
and less expensive, but they are available only from a
equipment that is certain to be paralleled in 10 seconds,
limited number of suppliers. In some cases motor starting
so in situations where local codes require service to
contactors might be used for paralleling applications
emergency loads within 10 or 15 seconds, the system
designer must choose between preventing smaller where smaller generator sets are used, but the contactors
machines from closing to the bus first (minimizing the must generally be protected by current limiting fuses for a
advantage of redundancy offered by many systems), safe design.
or making sure that first priority loads can always be
served by the smallest machine in the system.
Compatible engines
From a load shed perspective, the problem is less
The real power (kW) provided by a generator set
difficult, but still needs a bit of thought. If there is an
operating in parallel with others is a direct function
under-frequency condition on the bus, the system will
of engine real power output. Compatible engines
need to drop load. With dissimilar-sized machines,
can share load nearly equally, at all load levels, while
it is desirable to drop load in large enough steps to
operating at steady state load levels and during
relieve the 250 kW set in the event that the 500 kW
transient loading conditions. Conversely, if incompatible
unit becomes the unit that is not available. Cascading
engines are paralleled, load sharing problems can
type load shedding systems continue to drop load until
02 Power Topic #9015
www.cumminspower.com
www.cumminspower.com
www.cumminspower.com
50
0 100
PERCENT LOAD
Figure 2 - Droop governing.
www.cumminspower.com
ALARM ALARM
EC EC
ENGINE
ENGINE
GOV GOV
CB CB
POWER
TO
LOAD
Figure 3 - A block diagram of a simple isolated bus paralleling system showing interface of generator sets, paralleling functions and master control system.
Note that the only interface between the generator sets is the load sharing signals.
Isochronous kW and kVAR Analog control systems are often faster responding
than digital communication/control systems and can
load sharing often be made to be compatible between different
manufacturers. Cummins manufactures an analog load
Isochronous load sharing control systems are active
sharing interface module (ILSI) that can be used for
control systems that calculate the percentage of real
interface of Cummins PowerCommand® systems with
and reactive load on a specific generator set, compare
other load sharing controls that use analog signals.
those values to the percentage of real and reactive
Digital communication/control systems generally
load on the system, and then provide control to the
have less susceptibility to external interference than
fuel and excitation system of the generator to drive
analog signals, but every supplier has a different
the percentage of load on the generator to the same
communication algorithm that makes it difficult to add
value as the percentage of load on the system. Load
dissimilar equipment to an existing system.
sharing is critical to paralleling compatibility because
the load sharing communication is the only point where
generator controls interact with each other when Cross current compensation
operating on an isolated bus.
Cross current is a flow of electrical current between
To provide load sharing functions, each generator set generator sets that is caused by dissimilar excitation
in the system must have controls that will calculate the levels in those sets. Cross current compensation is a
total percent of kW and kVAR load on the machine, and term describing operation of paralleled generator sets
then have a means to compare that value to that of the
without intentional voltage droop. This is achieved by
system as a whole. Several approaches are available
insertion of a droop current transformer (CT), usually on
in the marketplace to provide this interface. In general,
“B” phase of each generator, and interconnecting the
they can be broken into two large groups:
CTs to provide an identical voltage bias to each AVR in
Systems that use analog signals for load sharing the system. The system works best when the voltage
ystems that use digital communication signals for
S regulators are all of the same manufacturer and model.
load sharing (such as CAN, RS485 or Ethernet) Not all voltage regulators work together in this mode,
06 Power Topic #9015
www.cumminspower.com
www.cumminspower.com
Recommendations
When paralleling dissimilar generator sets, a
designer should:
erify that the existing generator set can carry full load
V
with good voltage and frequency regulation.
eview the transient performance of all the generator
R
sets in the system and verify that the load steps
(particularly load rejection) of all the gensets will not
result in objectionable levels of reverse power.
erify that the pitch of all alternators is the same.
V
Specify 2/3 pitch on all generator sets to avoid
problems with this. Take mitigating steps if dissimilar
alternators cannot be avoided.
In addition:
1
Modbus is a registered trademark of Group Schneider.
08 Power Topic #9015
www.cumminspower.com