Features: Regulated Converters

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Features

• Medically certified 2MOPP module, BF ready


• Class II installations (without FG)
• IP68 waterproof encapsulation AC/DC Converter
Regulated • Operation altitude certified up to 5000m
• No external components necessary
Converters • Energy Efficiency Level IV RACM30-ER
Description 30 Watt 3Y
EAR

The RACM30-SER series comprises reliable and highly efficient power conversion modules in a potted
IP68 waterproof encapsulation to withstand harsh operating conditions. With a certified operation up Round
3 wa
rranty

to 5000m altitude and less than 2”x2” of required board space, these modules are designed to power
compact applications in medical healthcare, household, sanitary, smart building, and automation pro-
cesses. The product family is covered by medical, household, and ITE safety standards. More than 6dB
Shape Single
margin to EMI emissions class B limits eases integration without the need for any external components. Output

Selection Guide
Part Input Output Output Efficiency
Number Voltage Range Voltage (1) Current typ. (2)
(VAC) (VDC) (A) (%)
RACM30-12SER (3) 90-264 12 2.5 89
RACM30-24SER (3) 90-264 24 1.25 89

Notes:
Note1: Other output voltages on request
Note2: Efficiency is tested at nominal input (115/230VAC) and full load at +25°C ambient

C US
TEBA XEBA

2MOPP
Model Numbering 250VAC

RACM30-__ SER (3) IEC/EN60950-1 (pending)


UL60950-1 (pending)
IEC/EN60601-1 (pending)
Output Power Single
UL60601-1 (pending)
Output Voltage IEC/EN60335-1 (pending)
IEC/EN61558-2-16 (pending)

Notes:
Note3: Other connection types on reqeuest

www.recom-power.com REV.: 0/2017 MED-1


RACM30-ER
AC/DC Converter Series
Specifications (measured @ ta= 25°C, nom. Vin (115/230VAC), full load after warm-up unless otherwise stated)
BASIC CHARACTERISTICS
Parameter Condition Min. Typ. Max.
Internal Input Filter Pi type
Input Voltage Range 90VAC 230VAC 264VAC
115VAC 1000mA
Input Current
230VAC 290mA
115VAC 60A
Inrush Current
230VAC 95A
No load Power Consumption 75mW
Input Frequency Range 47Hz 63Hz
Minimum Load 0%
Power Factor 0.55
115VAC 75ms
Start-up Time
230VAC 150ms
Rise Time 115VAC / 230VAC 10ms
115VAC 15ms
Hold-up Time
230VAC 55ms
Internal Operating Frequency 100% load at nominal Vin 100kHz
Output Ripple and Noise 75mVp-p
Efficiency vs. Load
RACM30-12SER RACM30-24SER
100 100
90 90
80 80
70 70
Efficiency [%]

Efficiency [%]

60 60
50 50
40 40
30 30
20 85VAC 20 85VAC
115VAC 115VAC
10 230VAC 10 230VAC
264VAC 264VAC
0 0
0 25 50 75 100 0 25 50 75 100
Output Load [%] Output Load [%]

REGULATIONS
Parameter Condition Value
Output Accuracy ±3.0% max.
Line Regulation low line to high line, full load 1.0% max.
Load Regulation 0% to 100% load 1.0% max.
Transient Response 100% load step change ±3.0% max.

continued on next page

MED-2 REV.: 0/2017 www.recom-power.com


RACM30-ER
AC/DC Converter Series
Specifications (measured @ ta= 25°C, nom. Vin (115/230VAC), full load after warm-up unless otherwise stated)
Accuracy vs. Load
(@ min Vin to max. Vin)
RACM30-12SER RACM30-24SER
+3.0 +3.0
+2.0 +2.0
Deviation [%]

Deviation [%]
+1.0 +1.0
0 0
-1.0 -1.0
-2.0 -2.0
-3.0 -3.0
0 25 50 75 100 0 25 50 75 100
Output Load [%] Output Load [%]

PROTECTIONS
Parameter Type Value
Input Fuse internal (line & neutral) T2A, slow blow
Short Circuit Protection (SCP) continuous, auto recovery
12Vout 17VDC, Latch OFF
Over Voltage Protection (OVP)
24Vout 35VDC, Latch OFF
Over Voltage Category (OVC) OVCII
90VAC 140% of nominal output current, auto recovery
Over Current Protection (OCP) < 1 minute Hiccup Mode
264VAC 170% of nominal output current, auto recovery
Over Temperature Protection (OTP) 95°C ambient thermal shutdown, auto recovery
Class of Equipment Class II
Isolation Voltage (3)
I/P to O/P tested for 1 minute 4.4kVAC
Insulation Grade reinforced
Leakage Current 100µA max.
Means of Protection 260VAC working voltage 2MOPP
Medical Device Classification Type BF

Notes:
Note3: For repeat Hi-Pot testing, reduce the time and/or the test voltage

ENVIRONMENTAL
Parameter Condition Value
without derating -20°C to +50°C
Operating Temperature Range (natural convection 0.1m/s)
with derating -20°C to +70°C
Maximum Case Temperature +85°C
Operating Altitude 5000m
Operating Humidity non-condensing 95% RH max.
Pollution Degree PD2
according to MIL-HDBK- +25°C 538 x 103 hours
MTBF
217F, G.B. +50°C 107 x 103 hours
Design Lifetime E-Cap limitation 130 x 103 hours

continued on next page

www.recom-power.com REV.: 0/2017 MED-3


RACM30-ER
AC/DC Converter Series
Specifications (measured @ ta= 25°C, nom. Vin (115/230VAC), full load after warm-up unless otherwise stated)

Derating Graph
(@ Chamber and natural convection 0.1m/s) 100

80

Output Power [%]


60
50
40

20

0
-20 -10 0 10 20 30 40 50 60 70 80 90

Ambient Temperature [°C]

SAFETY AND CERTIFICATIONS


Certificate Type (Safety) Report / File Number Standard
IEC60950-1:2005, 2nd Edition +Am2:2013
Information Technology Equipment, General Requirements for Safety (CB Scheme)
EN60950-1:2006 + A2:2013
UL60950-1, 2nd Edition:2014
Information Technology Equipment, General Requirements for Safety
CAN/CSA C22.2 No. 60950-1, 2nd Edition:2014
Medical Electric Equipment, General Requirements for Safety and Essential IEC60601-1:2005, AM1:2012
Performance (CB Scheme) EN60601-1:2006 + A12:2014
Medical Electric Equipment, General Requirements for Safety and Essential
CAN/CSA-C22.2 No. 60601-1:14, 3rd Edition 2014
Performance
Household and similar electrical appliances - Safety IEC60335-1:2010
Part 1: General requirements (CB Scheme) EN60335-1:2012 + A11:2014
RoHs 2 (2+) RoHs 10/10, AM2015

EMC Compliance Condition Standard / Criterion


Electromagnetic compatibility of multimedia equipment - Emission requirements EN55022: 2010, Class B
Information technology equipment - Immunity characteristics - Limits and
EN55024: 2010
methods of measurement
Electromagnetic compatibility - Requirements for household appliances, electric EN55014-1: 2006 + A2:2011
tools and similar apparatus - Part 1: Emission EN55014-2: 1997 + A2:2008
Medical electrical equipment - Part 1-2: General requirements for basic safety
and essential performance - Collateral standard: Electromagnetic compatibility - EN60601-1-2, 2007
Requirements and tests
ESD Electrostatic discharge immunity test ±8kV Air; ±6kV Contact EN61000-4-2, Criteria A
Radiated, radio-frequency, electromagnetic field immunity test 3V/m, 80-2500MHz EN61000-4-3, Criteria A
Fast Transient and Burst Immunity ±2kV EN61000-4-4, Criteria A
Surge Immunity L-N ±1kV EN61000-4-5, Criteria A
Immunity to conducted disturbances, induced by radio-frequency fields 3V r.m.s. EN61000-4-6, Criteria A
Power Magnetic Field Immunity 3A/m EN61000-4-8, Criteria A
Voltage Dips and Interruption 100/230VAC EN61000-4-11
Voltage Fluctuations and Flicker in Public Low-Voltage Systems EN61000-3-3

MED-4 REV.: 0/2017 www.recom-power.com


RACM30-ER
AC/DC Converter Series
Specifications (measured @ ta= 25°C, nom. Vin (115/230VAC), full load after warm-up unless otherwise stated)
DIMENSION and PHYSICAL CHARACTERISTICS
Parameter Type Value
Case non-conductive black plastic, (UL94V-0)
Material Potting polyurethane, (UL94V-0)
PCB FR4, (UL94V-0)
Package Dimension (LxWxH) 53.0 x 51.0 x 33.5mm
Package Weight 128g max.

Dimension Drawing (mm)

FC 12.5
.1
57

FC 20.5

tc
51.0

embossed logo
Ø 3.2
FC 20.5

FC 12.5
53.0

2.0°
33.5
3.5

0.88 ±0.01 0.60 ±0.02

FC 25.0
2.24 Pin Connections
0.0.8+0.03
-0
Pin # Single
1 +Vout
2 knurled pins 2 -Vout
1 6.10 3 VAC in (N)
4 VAC in (L)
12.0
40.33

Bottom View tc= case temperature measuring point


FC = fixing centers
36.60
31.60

FC 41.0

NC= no connection
Tolerance: xx.x= ±0.5mm
7.10 xx.xx= ±0.25mm
4 3 Max. tightening torque fixing screws: 0.3Nm

15.30

www.recom-power.com REV.: 0/2017 MED-5


RACM30-ER
AC/DC Converter Series
Specifications (measured @ ta= 25°C, nom. Vin (115/230VAC), full load after warm-up unless otherwise stated)
PACKAGING INFORMATION
Parameter Type Value
Packaging Dimension (LxWxH) carton 310.0 x 220.0 x 100.0mm
Packaging Quantity 10pcs
Storage Temperature Range -30°C to +80°C
Storage Humidtiy non-condensing 95% RH max.

The product information and specifications may be subject to changes even without prior written notice.The product has been designed for various applications; its suitability lies in the responsibility of each customer. The
products are not authorized for use in safety-critical applications without RECOM’s explicit written consent. A safety-critical application is an application where a failure may reasonably be expected to endanger or cause
loss of life, inflict bodily harm or damage property. The applicant shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized
use of RECOM products in such safety-critical applications.
MED-6 REV.: 0/2017 www.recom-power.com
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

RECOM:
RACM30-24SER RACM30-12SER

You might also like