ACM220series DIP PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

ACM220 Series

Access Power Controllers


with Power Supplies

Installation Guide
Models Include:
• AL400ACM220 • AL600ACM220
- 12VDC @ 4A - 12VDC or 24VDC @ 6A.
or 24VDC @ 3A - Fused Outputs
- Fused Outputs

• AL1012ACM220 • AL1024ACM220
- 12VDC @ 10A. - 24VDC @ 10A.
- Fused Outputs - Fused Outputs

For a red enclosure add an “R” suffix to the part #, e.g. AL1024ACMR220

Rev. 010213
Overview:
These units distribute and switch power to access control systems and accessories. They convert a nominal 220VAC
(working range 198VAC - 256VAC), 50/60Hz input into eight (8) independently controlled 12VDC or 24VDC fuse
protected outputs. These power outputs can be converted to dry form “C” contacts. Outputs are activated by an open col-
lector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button,
PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes,
Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface
enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm discon-
nect feature is individually selectable for any or all of the eight (8) outputs.

ACM Series Configuration Reference Chart:


220VAC
12VDC 24VDC 50/60Hz
Total Total Individual Input Power Supply Power Supply
Altronix Output Output Fused Output (current Board Input Board Battery
Model Number Current Current Outputs Rating draw) Fuse Rating Fuse Rating
AL400ACM220 4A 3A 1.2A 15A/32V
AL600ACM220 6A 6A 1.5A 5A/250V ---------
8 2.5A
AL1012ACM220 10A --------- 2.2A
15A/32V
AL1024ACM220 --------- 10A 3A 6.3A/250V

Specifications:
Input: Features (cont’d):
• Power supply input options: • Fire Alarm disconnect input options:
a) One (1) common power input for ACM8 and lock a) Normally open (NO) or normally closed (NC)
power (factory installed). dry contact input.
b) Two (2) isolated power inputs - One (1) to power the b) Polarity reversal input from FACP signaling circuit.
ACM8 and one (1) for lock accessory power (external • Alarm output relay indicates that FACP input is
power supply is required). Current is determined by triggered (form “C” contact rated @ 1A 28VDC
the power supply connected, not to exceed a not evaluated by UL).
maximum of 10A total. • Short circuit and thermal overload protection.
• Eight (8) Access Control System trigger inputs. Visual Indicators:
Input options: • Red LEDs indicate outputs are triggered
a) Eight (8) normally open (NO) inputs. (relays energized).
b) Eight (8) open collector inputs. • Green LED indicates FACP disconnect is triggered.
c) Any combination of the above. • AC input and DC output LED indicators.
Output: Battery Backup:
• 12VDC or 24VDC outputs. • Built-in charger for sealed lead acid or gel type batteries.
• Power-limited outputs. • AL400XB2V, AL600XB220, and AL1012XB220
• Eight (8) independently controlled outputs. (Power Supply Board) maximum charge current 0.7A.
Output options: AL1024XB2V (Power Supply Board) maximum
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs. charge current 3.6A.
b) Eight (8) form “C” 5A rated relay outputs • Automatic switch over to stand-by battery when AC fails.
c) Any combination of the above. • AC input and DC output LED indicators.
• Eight (8) auxiliary power outputs (unswitched) • Zero voltage drop when unit switches over to battery
• Output fuses are rated @ 3.5A. backup (AC failure condition).
• Filtered and electronically regulated outputs • Battery fail and battery presence supervision
(built-in power supply). (form “C” contact).
Features: Enclosure Dimensions (H x W x D approx.):
• Fire Alarm disconnect (latching or non-latching) is • 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
individually selectable for any or all of the • Enclosure accommodates up to two (2) 12AH batteries.
eight (8) outputs.

- 2 -­ ACM220 series
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 10).
Secure enclosure to earth ground. It is recommended to first review the following tables to facilitate installation:
Output Voltage and Stand-by Specifications Charts (pg. 3)
Typical Application Diagram (pg. 5)
LED Diagnostics (pg. 5-6)
Terminal Identification Tables (pg. 7)
Hook-up Diagrams (pg. 8)
2. Set output voltage:
AL400ACM220 and AL600ACM220 - set desired DC output voltage by setting switch SW1 to the appropriate
position on the power supply board. AL1012ACM220 is factory set at 12VDC and AL1024ACM220 is factory set at
24VDC (Output Voltage and Stand-by Specification Charts below).

Output Voltage and Stand-by Specification Charts:


AL400ACM220
Voltage Switch Position Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
12VDC SW1 - ON 40AH 3.5A / 3.5A 0.5A / 3.5A
24VDC SW1 - OFF 40AH 2.75A / 2.75A 0.75A / 2.75A

AL600ACM220
Voltage Switch Position Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
12VDC SW1 - ON 40AH 5.5A / 5.5A 0.5A / 5.5A
24VDC SW1 - OFF 40AH 5.75A / 5.75A 0.75A / 5.75A

AL1012ACM220
Voltage Switch Position Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
12VDC N/A 40AH 9.5A / 9.5A 0.5A / 9.5A

AL1024ACM220 (refer to AL1024ACM220 Battery Size Calculation Worksheet, pg. 9).


Voltage
24VDC
Stand-by
Battery
12AH
15 mins. Stand-by /
5 mins. Alarm
7.7A / 9.7A
4 hr. Stand-by /
5 mins. Alarm
1.2A / 9.7A
24 hr. Stand-by /
5 mins. Alarm
------------
60 hr. Stand-by /

Ground Lug
5 mins. Alarm
------------
Pow
24VDC 65AH ------------ 7.7A / 9.7A 1.2A / 9.7A Door 200mA / 9.7A CAUTION
For continue
3. Connect AC (Fig. 2, pg. 6): fuse
Connect AC circuit (220VAC, 50/60Hz) as follows: Green branch wire connects to earth (safety) ground .
Line and Neutral to the connector on power supply board marked [L, N] respectively (Fig. 2, pg. 6).
Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
4. Measure voltage before connecting devices. This helps avoiding potential damage.
5. Output options (Fig. 1, pg. 5): L G

The unit will provide either eight (8) switched power outputs, eight (8) dry form “C” outputs, or any
combination of both switched power and form “C” outputs, plus eight (8) unswitched auxiliary power outputs.
(a) Switched Power outputs:
Connect the negative (–) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation
Wire
connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation
Strap
connect the positive (+) input of the device being powered to the terminal marked [NO].
(from
Enclosure
ACM220 series
to Door) - 3 -­

F1
(b) Form “C” outputs:
When form “C” outputs are desired the corresponding output fuse (1-8) must be removed. Connect negative (–) of
the power supply directly to the locking device. Connect the positive (+) of the power supply to the terminal
marked [C]. For Fail-Safe operation connect the positive (+) of the device being powered to the terminal
marked NC]. For Fail-Secure operation connect the positive (+) of the device being powered to the
terminal marked [NO].
(c) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (–) of the
device being powered to the terminal marked [COM]. Output can be used to provide power for card readers,
keypads etc.
6. Input trigger options (Fig. 1, pg. 5):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs.
Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (–)
to the terminal marked [GND].
7. Fire Alarm Interface options (Figs. 4 through 8, pg. 8):
A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will
trigger selected outputs. To enable FACP Disconnect for an output turn the corresponding switch [SW1-SW8] OFF.
To disable FACP disconnect for an output turn the corresponding switch [SW1-SW8] ON.
(a) Normally Open [NO] input:
For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up (Fig. 6, pg. 8).
(b) Normally Closed [NC] input:
For non-latching hook-up (Fig. 7, pg. 8). For latching hook-up (Fig. 8, pg. 8).
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked [+ INP –].
Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm condition).
Jumper located next to TRG LED must be cut (Fig. 1a, pg. 5 and Fig. 4, pg. 8).
8. FACP Dry form “C” output (Fig. 1b, pg. 5):
Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C]
FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
9. Battery Connections (Fig. 2, pg. 6):
For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of
output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked
[+ BAT -] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation.
10. Battery and AC Supervision output (Fig. 2, pg. 6):
It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory
relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail &
Low/No Battery reporting. Cut “AC delay” jumper to delay report 6 hour.
Note: A tamper switch must be installed and connected to the appropriate notification device to report a
trouble condition when the enclosure door is open.
11. Multiple power supply inputs (Fig. 1, pg. 5):
When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) must
be cut (Fig. 1c, pg. 5 and Fig. 3 pg. 8). Connect power for the ACM8 to the terminals marked [– Power +] and
connect power for the locking devices to the terminals marked [– Control +]. When using DC power supplies polarity
must be observed. When using AC power supplies polarity needs not to be observed (Fig. 1d, pg. 5).
Note: For UL compliance the additional power supply must be power-limited, UL Listed for Access Control
Systems and accessories.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Output Voltage and Stand-by Specification Charts, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery
terminals and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.
Note: AL400XB2V, AL600XB220, AL1012XB220 (Power Supply Board) maximum charge current is 0.7A.
AL1024XB220 (Power Supply Board) maximum charge current is 3.6A.
Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.

- 4 -­ ACM220 series
Typical Application Diagram:
Fig. 1
Fig. 1a
Intact = Dry Input
Normally Open (N.O.) Cut = Wet Input
Door Releasing
Device FACP FACP
Keypad
Access Control Panel TRG (Fire Alarm
Control
C Panel)
Output
Relay NO FACP Dry Fig. 1b
NC Form "C" Output

NO C NC
FACP

NO C NC + INP --- T + RET -

FACP
INTERFACE
TRG
IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8

F1 F2 F3 F4 F5 F6 F7 F8
ON ON

FACP
SW1-SW8
1 2 3 4 1 2 3 4

FACP Interface
Disabled

ON

1
MAIN

10A 250V

LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8


Enabled

ON

1
Mag. J3 J2 J1

--- + --- +
Power Control
Lock

NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM


OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8

AC or DC AC or DC
Power Power
Supply Supply
(req'd.) (optional)

UL Listed
Power Supply
Electric For this application
Strike corresponding
fuse F8 must be
removed. MAG.
Electromagnetic
Door Holders LOCK
Fig. 1d Fig. 1c
J3
Intact = DC Input Intact = One P/S Input
Cut = AC Input Cut = Dual P/S Input
J2 J1

--- +
Control
NC C NO COM
OUTPUT 8

LED Diagnostics:
Power Supply Board
LED
Power Supply Status
Red (DC) Green (AC)
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output.

Red (Bat) Battery Status


ON Normal operating condition.
OFF Battery fail/low battery.

ACM8 Access Power Controller


LED ON OFF
LED 1 - LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized.
Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
ACM220 series - 5 -­
Fig. 2

ON

Power Supply Board


OFF --- 24V
ON --- 12V

Ground Lug
SW1

- DC +
Door CAUTION: De-energize unit prior to servicing.
For continued protection against fire hazard replace
fuse with the same type and rating. Observe
polarity

+ BAT -
Battery and AC
Supervision Circuit
AC DELAY

L G N BAT FAIL AC FAIL

Unswitched
220VAC
power mains
Wire Insulating
Strap Barrier
(from Inputs
Enclosure

NO C NC + INP --- T + RET -


to Door)

INTERFACE
TRG
IN GND IN GND IN GND IN GND
1 2 3 4
IN GND IN GND IN GND IN GND
5 6 7 8
Fire
Alarm
F1 F2 F3 F4 F5 F6 F7 F8
ON ON
Interface

FACP
1 2 3 4 1 2 3 4

3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V

MAIN

10A 250V

LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8

J3 J2 J1

--- + --- +
Power Control
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8

DC Output to devices

Optional Rechargeable Optional Rechargeable


Stand-by Battery Stand-by Battery

CAUTION: Optional rechargeable stand-by batteries must match


the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

- 6 -­ ACM220 series
Terminal Identification Tables:
Power Supply Board
Terminal
Function/Description
Legend
L, N Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral.
AL400ACM220 - 12VDC @ 4A or 24VDC @ 3A to ACM8 board (power-limited).
AL600ACM220 - 12VDC/24VDC @ 6A to ACM8 board (non power-limited).
+ DC –
AL1012ACM220 - 12VDC @ 10A to ACM8 board (non power-limited).
AL1024ACM220 - 24VDC @ 10A to ACM8 board (non power-limited).
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay
AC FAIL normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is
NC, C, NO reported within 1 minute of event. To delay reporting of up to 6 hrs.,
cut “AC delay” jumper and reset power to unit.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
power is present. Contact rating 1A @ 28VDC. A removed battery is reported within 5 minutes. Battery
BAT FAIL reconnection is reported within 1 minute.
NC, C, NO Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ACM220),
24VDC output threshold set @ approximately 21VDC (N/A for AL1012ACM220).
Stand-by battery connections. AL400XB2V, AL600XB220 and AL1012XB220
+ BAT – (Power Supply Board) maximum charge current is 0.7A.
AL1024XB2V (Power Supply Board) maximum charge current is 3.6A.

ACM8 Access Power Controller


Terminal Legend Function/Description
– Power + 12VDC or 24VDC input from power supply board.
These terminals can be connected to a separate power limited, UL Listed power supply to
– Control +
provide isolated operating power for the ACM8 (jumpers J1 and J2 must be removed).
TRIGGER
From normally open and/or open collector sink trigger inputs
INPUT 1 - INPUT 8
(request to exit buttons, exit pir’s, etc.).
IN, GND
12 to 24 volts AC/DC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
OUTPUT 1 - Fail-Secure [NO positive (+) & COM Negative (-)],
OUTPUT 8 Auxiliary output [C positive (+) & COM Negative (-)]
NC, C, NO, COM (When using AC power supplies polarity need not be observed),
NC, C, NO become form “C” 5A 24VAC/VDC rated dry outputs when fuses are removed.
Contacts shown in a non-triggered state.
FACP INTERFACE Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
T, + INPUT – normally closed from an FACP output circuit (Fig. 4 through 8, pg. 8).
FACP INTERFACE Form “C” relay contact rated @ 1A 28VDC for alarm reporting.
NC, C, NO (This output has not been evaluated by UL).

ACM220 series - 7 -­
Hook-Up Diagrams:
Fig. 3 Optional hook-up using two (2) isolated Fig. 4 Polarity reversal input from FACP signaling circuit
power supply inputs: output (polarity is referenced in alarm condition):
CUT JUMPERS CUT
J1 AND J2 JUMPER
FACP
FACP
TRG OUTPUT EOL
J2 J1

INTERFACE
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(ACM8 POWER)
-- FROM FACP
OUTPUT
+
ISOLATED POWER INPUT CIRCUIT
12 OR 24 VAC OR VDC
(LOCK POWER)

NO C NC
FACP
Fig. 5 Normally Open - Non-Latching FACP Fig. 6 Normally Open FACP Latching trigger input
trigger input: with reset:
(This output has not been evaluated by UL)
FACP FACP

TRG TRG
INTERFACE

N.O. TRIGGER N.O.


INPUT TRIGGER
INPUT
N.C. RESET
SWITCH
NO C NC

NC
JUMPER
FACP

NO C

Fig. 7 Normally Closed - Non-Latching FACP Fig. 8 Normally Closed - Latching FACP trigger input
trigger input: with reset:
(This output has not been evaluated by UL)
FACP FACP

TRG TRG
N.C. RESET
INTERFACE

SWITCH
N.C. DRY
TRIGGER
INPUT

JUMPER N.C. TRIGGER


JUMPER INPUT
NO C NC
FACP

- 8 -­ ACM220 series
AL1024ACM220 Battery Size Calculation Worksheet:

A. AL1024ACM220 internal current consumption (stand-by) ___________________ 0.35A

B. Load current consumption (stand-by) ___________________ A

C. Stand-by time required (Hours) ___________________ H

D. Battery capacity required for stand-by (A+B)*C ___________________ AH

E. AL1024ACM220 internal power consumption (Alarm) ___________________ 0.35A

F. Load current consumption (Alarm) ___________________ A

G. Alarm duration (Hours, example: 15 Min. = 0.25 Hour) (Alarm) ___________________ H

H. Battery capacity required for Alarm (E+F)*G ___________________ AH

I. Total calculated battery capacity D+H ___________________ AH

J. Battery capacity required I*1.8 (safety factor) ___________________ AH

Note: AL1024ACM220 power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceed 36AH. You have to reduce either stand-by current consumption or stand-by time in
order to comply with requirement.

To determine actual battery size please round line [J] to the nearest larger standard battery size.

ACM220 series - 9 -­
Enclosure Dimensions (H x W x D approximate):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5” 4.615” 4.615” 1.5”
(38.1mm) (117.22mm) (117.22mm) (38.1mm)

1.75”
(44.45mm)

1.375”
(34.925mm)

1.125”
(28.575mm)

4.5” 12.23” 4.5”


1.25” (114.3mm) 1.1” (310.64mm) 1.1” (114.3mm) 1.25”
(31.75mm) (27.94mm) (27.94mm) (31.75mm)

0.91” 0.91”
1.5” (23.114mm) (23.114mm) 1.5”
(38.1mm) (38.1mm)

2.0” 15.5”
(50.8mm) (393.7mm)

2.0”
(50.8mm)

5.0” 5.0”
(127.0mm) (127.0mm)

0.79”
1.1” (20.06mm)
1.25” (27.94mm) 1.25”
(31.75mm) (31.75mm)

1.75”
(44.45mm)

1.5” 4.615” 4.615” 1.5”


(38.1mm) (117.22mm) (117.22mm) (38.1mm)

- 10 -­ ACM220 series
Notes:

ACM220 series - 11 -­
Notes:

Altronix is not responsible for any typographical errors.


140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
web site: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IIACM220 series I13Q MEMBER
- 12 -­ ACM220 series

You might also like