MG07B302 Design Guide FC 280
MG07B302 Design Guide FC 280
MG07B302 Design Guide FC 280
Design Guide
VLT® Midi Drive FC 280
vlt-drives.danfoss.com
Contents Design Guide
Contents
1 Introduction 5
1.1 Purpose of the Design Guide 5
1.2 Additional Resources 5
1.3 Definitions 5
1.4 Document and Software Version 8
1.5 Approvals and Certifications 8
1.6 Safety 9
2 Product Overview 10
2.1 Enclosure Size Overview 10
2.2 Electrical Installation 12
2.2.1 Motor Connection 14
2.2.2 AC Mains Connection 15
2.2.3 Control Terminal Types 16
2.2.4 Wiring to Control Terminals 17
2.3 Control Structures 18
2.3.1 Control Modes 18
2.3.2 Control Principle 19
2.3.3 Control Structure in VVC+ 19
2.3.4 Internal Current Control in VVC+ Mode 21
2.3.5 Local (Hand On) and Remote (Auto On) Control 21
2.4 Reference Handling 22
2.4.1 Reference Limits 23
2.4.2 Scaling of Preset References and Bus References 24
2.4.3 Scaling of Analog and Pulse References and Feedback 24
2.4.4 Dead Band Around Zero 25
2.5 PID Control 28
2.5.1 Speed PID Control 28
2.5.2 Process PID Control 31
2.5.3 Process Control Relevant Parameters 32
2.5.4 Example of Process PID Control 33
2.5.5 Process Controller Optimization 35
2.5.6 Ziegler Nichols Tuning Method 36
2.6 EMC Emission and Immunity 36
2.6.1 General Aspects of EMC Emission 36
2.6.2 EMC Emission 38
2.6.3 EMC Immunity 40
2.7 Galvanic Isolation 41
2.8 Ground Leakage Current 41
3 Application Examples 48
3.1 Introduction 48
3.1.1 Encoder Connection 48
3.1.2 Encoder Direction 48
3.1.3 Closed-loop Drive System 48
3.2 Application Examples 49
3.2.1 AMA 49
3.2.2 Speed 49
3.2.3 Start/Stop 50
3.2.4 External Alarm Reset 51
3.2.5 Motor Thermistor 51
3.2.6 SLC 51
7 Specifications 80
7.1 Electrical Data 80
7.2 Mains Supply 83
7.3 Motor Output and Motor Data 83
7.4 Ambient Conditions 84
7.5 Cable Specifications 84
7.6 Control Input/Output and Control Data 85
7.7 Connection Tightening Torques 88
7.8 Fuses and Circuit Breakers 89
7.9 Efficiency 90
7.10 Acoustic Noise 91
7.11 dU/dt Conditions 91
7.12 Special Conditions 92
7.12.1 Manual Derating 93
7.12.2 Automatic Derating 95
7.13 Enclosure Sizes, Power Ratings, and Dimensions 96
Index 99
1 Introduction 1 1
PM,N RefMAX
Rated motor power (nameplate data in kW or hp). Determines the relationship between the reference input at
100% full scale value (typically 10 V, 20 mA) and the
TM,N resulting reference. The maximum reference value is set in
Rated torque (motor). parameter 3-03 Maximum Reference.
UM RefMIN
Instantaneous motor voltage. Determines the relationship between the reference input at
UM,N 0% value (typically 0 V, 0 mA, 4 mA) and the resulting
Rated motor voltage (nameplate data). reference. The minimum reference value is set in
parameter 3-02 Minimum Reference.
Break-away torque
Torque
175ZA078.10
1.3.5 Miscellaneous
Pull-out
Analog inputs
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
• Current input: 0–20 mA and 4–20 mA.
• Voltage input: 0–10 V DC.
Analog outputs
The analog outputs can supply a signal of 0–20 mA, or 4–
20 mA.
RPM Automatic motor adaptation, AMA
Illustration 1.1 Break-away Torque The AMA algorithm determines the electrical parameters
for the connected motor at standstill.
Brake resistor
ηVLT The brake resistor is a module capable of absorbing the
The efficiency of the frequency converter is defined as the brake power generated in regenerative braking. This
ratio between the power output and the power input. regenerative brake power increases the DC-link voltage,
Start-disable command and a brake chopper ensures that the power is transmitted
A start-disable command belonging to the control to the brake resistor.
commands in group 1. See Table 1.1 for more details. CT characteristics
Stop command Constant torque characteristics used for all applications
A stop command belonging to the control commands in such as conveyor belts, displacement pumps, and cranes.
group 1. See Table 1.1 for more details. Digital inputs
The digital inputs can be used for controlling various
1.3.4 References functions of the frequency converter.
Digital outputs
Analog reference The frequency converter features 2 solid-state outputs that
A signal transmitted to the analog inputs 53 or 54 can be can supply a 24 V DC (maximum 40 mA) signal.
voltage or current.
DSP
Binary reference Digital signal processor.
A signal transmitted via the serial communication port.
PCD THD
Process control data. Total harmonic distortion states the total contribution of
harmonic distortion.
PFC
Power factor correction. Thermistor
A temperature-dependent resistor placed where the
temperature is monitored (frequency converter or motor).
This manual is regularly reviewed and updated. All 1.5.3 EMC Directive
suggestions for improvement are welcome. Table 1.2 shows
the document version and the corresponding software Electromagnetic compatibility (EMC) means that electro-
version. magnetic interference between pieces of equipment does
not hinder their performance. The basic protection
Software requirement of the EMC Directive 2014/30/EU states that
Edition Remarks
version devices that generate electromagnetic interference (EMI) or
More information for POWERLINK and whose operation could be affected by EMI must be
MG07B3 1.3
software update. designed to limit the generation of electromagnetic
interference and shall have a suitable degree of immunity
Table 1.2 Document and Software Version
to EMI when properly installed, maintained, and used as
intended.
1.5 Approvals and Certifications
Frequency converters are designed in compliance with the A frequency converter can be used as standalone device or
directives described in this section. as part of a more complex installation. Devices in either of
these cases must bear the CE mark. Systems must not be
CE marked but must comply with the basic protection
requirements of the EMC directive.
1.5.4 UL Compliance 1 1
UL-listed
Illustration 1.2 UL
1.6 Safety
Frequency converters contain high-voltage components
and have the potential for fatal injury if handled
improperly. Only qualified personnel are allowed to install
and operate the equipment. Do not attempt repair work
without first removing power from the frequency converter
and waiting the designated duration of time for stored
electrical energy to dissipate.
2 Product Overview
2 2
2.1 Enclosure Size Overview
Enclosure size depends on power range. For details about dimensions, refer to chapter 7.13 Enclosure Sizes, Power Ratings,
and Dimensions.
Enclosure K1 K2 K3 K4 K5
size
130BA870.10
130BA809.10
130BA810.10
130BA810.10
130BA810.10
Enclosure
IP20 IP20 IP20 IP20 IP20
protection1)
Power
range
[kW (hp)] 0.37–2.2 (0.5–3.0) 3.0–5.5 (5.0–7.5) 7.5 (10) 11–15 (15–20) 18.5–22 (25–30)
3-phase
380–480 V
Power
range
[kW (hp)] 0.37–1.5 (0.5–2.0) 2.2 (3.0) 3.7 (5.0) – –
3-phase
200–240 V
Power
range
[kW (hp)]
0.37–1.5 (0.5–2.0) 2.2 (3.0) – – –
single-
phase
200–240 V
Enclosure size is used throughout this guide whenever procedures or components differ between frequency converters
based on physical size.
130BF709.10
1 2 3
MADE IN
Danfoss A/S, 6430 Nordborg, Denmark DENMARK
CAUTION / ATTENTION:
See manual for special condition/mains fuse
Voir manual de conditions speciales/fusibles
WARNING / AVERTISSEMENT:
Stored charge, wait 4 min.
Charge résiduelle, attendez 4 min.
130BE202.18
RFI
91 (L1/N) (U) 96
Power 92 (L2/L) (V) 97
input 93 (L3) (W) 98
95 PE (PE) 99
Motor
Switch mode
power supply 1)
(-DC) 88 5)
10 V DC 24 V DC (+DC/R+) 89
5)
Brake
15 mA 100 mA resistor
50 (+10 V OUT) + - + -
+10 V DC (R-) 81
0−10 V DC 53 (A IN) 2)
Relay 1
03
0−10 V DC 54 (A IN) 250 V AC, 3 A
0/4−20 mA 02
12 (+24 V OUT)
13 (+24 V OUT)
P 5-00
24 V (NPN)
18 (D IN) 0 V (PNP)
24 V (NPN)
19 (D IN) 0 V (PNP) (A OUT) 42 Analog output
0/4−20 mA
24 V (NPN)
27 (D IN/OUT) 0 V (PNP)
3)
24 V ON = Terminated
1 2
ON
OFF = Open
0V 5V
24 V (NPN)
29 (D IN) 0 V (PNP)
S801 0V
RS485
(N RS485) 69 RS485
24 V (NPN) interface
32 (D IN) 0 V (PNP) (P RS485) 68
24 V (NPN)
33 (D IN) 0V (COM RS485) 61
0 V (PNP)
(PNP) = Source
37 (STO1)4) (NPN) = Sink
38 (STO2)4)
A = Analog, D = Digital
1) Built-in brake chopper is only available on 3-phase units.
2) Terminal 53 can also be used as digital input.
3) Switch S801 (bus terminal) can be used to enable termination on the RS485 port (terminals 68 and 69).
4) Refer to chapter 4 Safe Torque Off (STO) for the correct STO wiring.
5) The S2 (single-phase 200–240 V) frequency converter does not support load sharing application.
130BF228.10
6
2 2
7
8
9
10
11
1 12
90
13
2 14
3
15
u
4
v 16
4
w
4 PE
L1 17
L2
L3
PE
18
130BD531.10
2 2 WARNING V
W
98
INDUCED VOLTAGE U 97
96
Induced voltage from output motor cables that run
together can charge equipment capacitors, even when
the equipment is turned off and locked out. Failure to
run output motor cables separately or use shielded
cables could result in death or serious injury.
• Run output motor cables separately.
• Use shielded cables.
130BE804.10
130BE232.11
2 2
Illustration 2.5 Mains, Motor, and Grounding Connection for Illustration 2.7 Mains, Motor, and Grounding Connection for 3-
Single-phase Units (K1, K2) phase Units (K4, K5)
2 2 Illustration 2.8 shows the removable frequency converter Parameter 5-13 [14] Jog Digital input.
connectors. Terminal functions and default settings are 29 Terminal 29
summarized in Table 2.3 and Table 2.4. Digital Input
Parameter 5-14
[0] No
32 Terminal 32 Digital input, 24 V
130BE212.10
operation
Digital Input encoder. Terminal
Parameter 5-15 33 can be used for
[0] No pulse input.
33 Terminal 33
1 2 operation
Digital Input
Functional safety
37, 38 – STO
inputs.
3
Analog inputs/outputs
Programmable
Illustration 2.8 Control Terminal Locations analog output. The
analog signal is 0–
Parameter 6-91 20 mA or 4–
[0] No
1 2
42 Terminal 42 20 mA at a
operation
130BE214.10
37 38 12 13 18 19 27 29 32 33 61 68 69
Analog Output maximum of
500 Ω. Can also
be configured as
digital outputs.
3
10 V DC analog
42 53 54 50 55
supply voltage.
15 mA maximum
50 – +10 V DC
commonly used
Illustration 2.9 Terminal Numbers
for potentiometer
or thermistor.
Analog input. Only
See chapter 7.6 Control Input/Output and Control Data for Parameter voltage mode is
terminal ratings details. 53 group 6-1* – supported. It can
Analog input 53 also be used as
Default digital input.
Terminal Parameter Description
setting Analog input.
Parameter
Digital I/O, pulse I/O, encoder Selectable
54 group 6-2* –
24 V DC supply between voltage
Analog input 54
voltage. Maximum or current mode.
12, 13 – +24 V DC output current is Common for
100 mA for all 55 – – digital and analog
24 V loads. inputs.
Parameter 5-10
18 Terminal 18 [8] Start Table 2.3 Terminal Descriptions - Digital Inputs/Outputs,
Digital Input Analog Inputs/Outputs
Digital inputs.
Parameter 5-11
19 Terminal 19 [10] Reversing
Digital Input
Parameter 5-01
Terminal 27 Selectable for
Mode either digital
Parameter 5-12 input, digital
27 Terminal 27 output, or pulse
Digital Input DI [2] Coast output. The
Parameter 5-30 inverse default setting is
Terminal 27 DO [0] No digital input.
Digital Output operation
VLT® Midi Drive FC 280 is a general-purpose frequency converter for variable speed applications. The control principle is
based on VVC+.
2 2
FC 280 frequency converters can handle asynchronous motors and permanent magnet synchronous motors up to 22 kW
(30 hp).
The current-sensing principle in FC 280 frequency converters is based on the current measurement by a resistor in the DC
link. The ground fault protection and short circuit behavior are handled by the same resistor.
130BD974.10
Brake resistor
R+ R-
Load sharing + 82 81
89(+)
L1 91
L2 92
Inrush U 96
L3 93
V 97
M
W 98
RFI switch
Load sharing -
88(-)
P 4-19
130BD371.10
Max. output freq.
P 1-00 P 1-00
P 4-14
Config. mode Config. mode
Motor speed +f max.
high limit (Hz)
High P 3-** Motor
controller
Ref.
Ramp -f max.
Low
+ P 4-12
P 4-19
S Process Motor speed
Max. output freq.
_ low limit (Hz)
P 7-0* +f max.
Illustration 2.11 Control Structure in VVC+ Open-loop Configurations and Closed-loop Configurations
In the configuration shown in Illustration 2.11, parameter 1-01 Motor Control Principle is set to [1] VVC+ and
parameter 1-00 Configuration Mode is set to [0] Speed open loop. The resulting reference from the reference handling system
is received and fed through the ramp limitation and speed limitation before being sent to the motor control. The output of
the motor control is then limited by the maximum frequency limit.
2 2 If parameter 1-00 Configuration Mode is set to [1] Speed closed loop, the resulting reference is passed from the ramp
limitation and speed limitation into a speed PID control. The speed PID control parameters are in parameter group 7-0*
Speed PID Ctrl. The resulting reference from the speed PID control is sent to the motor control limited by the frequency limit.
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of speed or
pressure in the controlled application. The process PID parameters are in parameter groups 7-2* Process Ctrl. Feedb and 7-3*
Process PID Ctrl.
Hand Auto
Off Reset
on on
130BD374.10
Relative scaling ref.
No function
P 3-18
Analog ref.
Pulse ref.
P 3-14
Preset relative ref.
P 3-00 P 1-00
(0) Ref./feedback range Configuration mode
(1)
(4)
P 3-10
Scale to
(5) -max ref./ Hz
P 5-1x(28)/P 5-1x(29) +max ref.
(6) 100%
Input command:
(7) Catch up/ slow down
-100% Torque P 16-01
Y Remote
Relative Catch up/ ref.
P 3-04 Scale to
X+X*Y slow Nm
(0) X
/100 down
max ref.
P 3-12 %
No function (1)
D1 Catchup Slowdown
value Process
Analog ref. P 5-1x(15) %
Preset '1'
Ref.resource 1
±100% unit
Local bus ref. Freeze ref.
&
DigiPot increase/
decrease
ref.
P 5-1x(21)/P 5-1x(22)
Speed up/ speed down
No function
200% Ref. in %
Pulse ref.
P 3-16
DigiPot
No function
Analog ref.
Ref. resource 3
Pulse ref.
P 3-17
The remote reference is calculated once in every scan 2.4.1 Reference Limits
interval and initially consists of 2 types of reference
inputs:
1. X (the external reference): A sum (see
Parameter 3-00 Reference Range, parameter 3-02 Minimum
Reference, and parameter 3-03 Maximum Reference define 2 2
parameter 3-04 Reference Function) of up to 4 the allowed range of the sum of all references. The sum of
externally selected references, comprising any all references is clamped when necessary. The relation
combination (determined by the setting of between the resulting reference (after clamping) and the
parameter 3-15 Reference 1 Source, sum of all references are shown in Illustration 2.15 and
parameter 3-16 Reference 2 Source, and Illustration 2.16.
parameter 3-17 Reference 3 Source) of a fixed
preset reference (parameter 3-10 Preset Reference),
P 3-00 Reference Range= [0] Min-Max
130BA184.10
variable analog references, variable digital pulse
references, and various fieldbus references in any Resulting reference
unit the frequency converter is monitoring ([Hz],
[RPM], [Nm], and so on).
2. Y (the relative reference): A sum of 1 fixed preset P 3-03
reference (parameter 3-14 Preset Relative Reference)
Forward
and 1 variable analog reference
(parameter 3-18 Relative Scaling Reference
P 3-02
Resource) in [%].
The 2 types of reference inputs are combined in the
following formula:
Sum of all
Remote reference=X+X*Y/100%.
-P 3-02 references
If relative reference is not used, set parameter 3-18 Relative
Scaling Reference Resource to [0] No function and
Reverse
parameter 3-14 Preset Relative Reference to 0%. The digital
-P 3-03
inputs on the frequency converter can activate both the
catch up/slow down function and the freeze reference
function. The functions and parameters are described in Illustration 2.15 Sum of All References When Reference Range
the VLT® Midi Drive FC 280 Programming Guide. is Set to 0
The scaling of analog references is described in parameter
groups 6-1* Analog Input 53 and 6-2* Analog Input 54, and
the scaling of digital pulse references is described in
130BA185.10
P 3-00 Reference Range =[1]-Max-Max
parameter group 5-5* Pulse Input.
Reference limits and ranges are set in parameter group 3-0* Resulting reference
Reference Limits.
P 3-03
Sum of all
references
-P 3-03
130BA186.11
P 3-00 Reference Range= [0] Min to Max
References and Feedback
2 2 Resulting reference
References and feedback are scaled from analog and pulse
inputs in the same way. The only difference is that a
reference above or below the specified minimum and
P 3-03 maximum endpoints (P1 and P2 in Illustration 2.18) are
clamped while feedbacks above or below are not.
Resource output
130BD431.10
Sum of all [Hz]
P 3-02 references
High reference/
feedback value 50 P2
The endpoints P1 and P2 are defined in Table 2.5 depending on the choice of input.
Input Analog 53
voltage mode
Analog 54
voltage mode
Analog 54
current mode
Pulse input 29 Pulse input 33
2 2
P1=(Minimum input value, minimum reference value)
Minimum reference value Parameter 6-14 Te Parameter 6-24 Te Parameter 6-24 Ter Parameter 5-52 Ter Parameter 5-57 Term. 33
rminal 53 Low rminal 54 Low minal 54 Low Ref./ m. 29 Low Ref./ Low Ref./Feedb. Value
Ref./Feedb. Value Ref./Feedb. Value Feedb. Value Feedb. Value
Minimum input value Parameter 6-10 Te Parameter 6-20 Te Parameter 6-22 Ter Parameter 5-50 Ter Parameter 5-55 Term. 33
rminal 53 Low rminal 54 Low minal 54 Low m. 29 Low Low Frequency [Hz]
Voltage [V] Voltage [V] Current [mA] Frequency [Hz]
P2=(Maximum input value, maximum reference value)
Maximum reference value Parameter 6-15 Te Parameter 6-25 Te Parameter 6-25 Ter Parameter 5-53 Ter Parameter 5-58 Term. 33
rminal 53 High rminal 54 High minal 54 High Ref./ m. 29 High Ref./ High Ref./Feedb. Value
Ref./Feedb. Value Ref./Feedb. Value Feedb. Value Feedb. Value
Maximum input value Parameter 6-11 Te Parameter 6-21 Te Parameter 6-23 Ter Parameter 5-51 Ter Parameter 5-56 Term. 33
rminal 53 High rminal 54 High minal 54 High m. 29 High High Frequency [Hz]
Voltage [V] Voltage [V] Current [mA] Frequency [Hz]
Sometimes, the reference (in rare cases also the feedback) should have a dead band around 0 to ensure that the machine is
stopped when the reference is near 0.
To make the dead band active and to set the amount of dead band, do the following:
• Set either the minimum reference value (see Table 2.5 for relevant parameter) or maximum reference value at 0. In
other words, either P1 or P2 must be on the X-axis in Illustration 2.19.
• Ensure that both points defining the scaling graph are in the same quadrant.
Resource output
130BD446.10
Quadrant 2 Quadrant 1
[Hz] or “No unit”
High reference/feedback 50 P2
value forward
P1
Resource input
Low reference/feedback 0
[mA]
value 1 16 20
Terminal X high
Terminal low
-50 reverse
Quadrant 3 Quadrant 4
Illustration 2.19 Size of Dead Band
Case 1: Positive reference with dead band, digital input to trigger reverse, part I
Illustration 2.20 shows how reference input with limits inside minimum to maximum limits clamps.
2 2 General Reference
130BD454.10
General Motor
parameters: parameters:
Limited to: -200%- +200%
Reference Range: Min - Max Motor speed direction:Both directions
Minimum Reference: 0 Hz (0,0%) (-40 Hz- +40 Hz)
Motor speed Low limit: 0 Hz
Maximum Reference: 20 Hz (100,0%) Motor speed high limit: 8 Hz
Analog input 53
Low reference 0 Hz Ext. reference Reference Limited to:
+
High reference 20 Hz Range: algorithm
0%- +100%
Low voltage 1 V 0.0% (0 Hz)
Ext. Reference (0 Hz- +20 Hz)
High voltage 10 V 100.0% (20 Hz)
Absolute
0 Hz 1 V
Ext. source 1
20 Hz 10V Reference
Range:
Range:
0.0% (0 Hz) Reference is scaled
according to min 0.0% (0 Hz)
100.0% (20 Hz)
max reference giving a 100.0% (20 Hz)
speed.!!!
Dead band
Hz
20
Scale to Hz
speed 20
V
1 10
V
1 10
Speed
setpoint
Range: -20
Digital input 19 -20 Hz
Digital input Low No reversing +20 Hz
High Reversing
Motor PID
Motor Range:
control -8 Hz Motor
+8 Hz
Illustration 2.20 Clamping of Reference Input with Limits inside Minimum to Maximum
Case 2: Positive reference with dead band, digital input to trigger reverse, part II
Illustration 2.21 shows how reference input with limits outside -maximum to +maximum limits clamps to the input low and
high limits before adding to external reference, and how the external reference is clamped to -maximum to +maximum by
the reference algorithm. 2 2
130BD433.11
General Reference General Motor
parameters: parameters:
Limited to: -200%- +200%
Reference Range: -Max - Max Motor speed direction: Both directions
Minimum Reference: Don't care (-40 Hz- +40 Hz)
Motor speed Low limit: 0 Hz
Maximum Reference: 20 Hz (100.0%) Motor speed high limit: 10 Hz
Analog input 53
Low reference 0 Hz + Ext. reference Reference Limited to:
High reference 20 Hz Range: algorithm -100%- +100%
Ext. Reference Low voltage 1 V 0.0% (0 Hz) (-20 Hz- +20 Hz)
High voltage 10 V 150.0% (30 Hz)
Absolute
0 Hz 1 V Ext. source 1
30 Hz 10 V Reference
Range:
Range:
0.0% (0 Hz) Reference is scaled
150.0% (30 Hz) according to 0.0% (0 Hz)
max reference giving a 100.0% (20 Hz)
speed.!!!
Dead band
30 Hz
Scale to
speed 20 Hz
V
1 10
V
1 10
Speed
setpoint
Range: -20 Hz
Digital input 19 -20 Hz
Digital input Low No reversing +20 Hz
High Reversing
Motor PID
Motor Range:
control –10 Hz Motor
+10 Hz
Illustration 2.21 Clamping of Reference Input with Limits outside -Maximum to +Maximum
130BD372.11
L2
L3
N
PE
F1
12
91 92 93 95
27
L1 L2 L3 PE
18
50
53
55
U V W PE
32
33
96 97 98 99
M 24 Vdc
Follow the steps in Table 2.8 to program the speed control (see explanation of settings in the programming guide)
In Table 2.8, it is assumed that all other parameters and switches remain at their default setting.
Set acceptable limits for the motor speed and frequency. Parameter 4-12 Motor 0 Hz
Speed Low Limit [Hz]
2 2
Parameter 4-14 Motor 50 Hz
Speed High Limit [Hz]
Parameter 4-19 Max 60 Hz
Output Frequency
4) Configure the speed control and select the motor control principle:
Activation of speed control Parameter 1-00 Configu- [1] Speed closed loop
ration Mode
Selection of motor control principle Parameter 1-01 Motor [1] VVC+
Control Principle
5) Configure and scale the reference to the speed control:
Set up analog input 53 as a reference source. Parameter 3-15 Reference 1 Not necessary (default)
Source
Scale analog input 53 0 Hz (0 V) to 50 Hz (10 V) Parameter group 6-1* Not necessary (default)
Analog Input 1
6) Configure the 24 V HTL encoder signal as feedback for the motor control and the speed control:
Set up digital input 32 and 33 as encoder inputs. Parameter 5-14 Terminal [82] Encoder input B
32 Digital Input
Parameter 5-15 Terminal [83] Encoder input A
33 Digital Input
Select terminal 32/33 as speed PID feedback. Parameter 7-00 Speed PID [1] 24 V Encoder
Feedback Source
7) Tune the speed control PID parameters:
Use the tuning guidelines when relevant or tune manually. Parameter group 7-0*
Speed PID Ctrl.
8) Finish:
Save the parameter setting to the LCP for safe keeping. Parameter 0-50 LCP Copy [1] All to LCP
The process PID control can be used to control application parameters that can be measured by a sensor (for example
pressure, temperature, flow) and affected by the connected motor through a pump, fan, or other connected devices. 2 2
Table 2.9 shows the control configurations in which the process control is possible. Refer to chapter 2.3 Control Structures to
see where the speed control is active.
NOTICE
The process control PID works under the default parameter setting, but tuning the parameters is recommended to
optimize the application control performance.
Process PID
130BA178.10
P 7-38
Feed forward 100%
Reference + 0%
Handling % [unit] % % 0%
_ [unit] [speed] To motor
PID Scale to
speed control
-100%
Feedback *(-1)
Handling 100%
% [unit]
-100%
P 7-30 P 4-10
normal/inverse Motor speed
direction
Illustration 2.23 Process PID Control Diagram
130BF102.10
L2
L3
Illustration 2.24 is an example of a process PID control used
in a ventilation system:
N
PE
2 2
F1
130BA218.10
Cold air
100kW
Heat 13
91 92 93 95
generating
process 27
L1 L2 L3 PE
18
50
Temperature 53
W n °C
transmitter 55
U V W PE
Temperature
54
Fan speed
96 97 98 99 Transmitter
Heat
2 2
If the motor turns opposite of required direction: Parameter 4-10 Select correct motor shaft direction.
1. Change motor direction in Motor Speed
parameter 4-10 Motor Speed Direction. Direction
2 2
Set terminal 53 low voltage. Parameter 6-10 0V
Set terminal 53 high voltage. Terminal 53 10 V
Set terminal 54 low feedback value. Low Voltage -5 °C (23 °F)
Set terminal 54 high feedback value. Parameter 6-11 35 °C (95 °F)
Set feedback source. Terminal 53 [2] Analog input 54
High Voltage
Parameter 6-24
Terminal 54
Low Ref./Feedb.
Value
Parameter 6-25
Terminal 54
High Ref./
Feedb. Value
Parameter 7-20
Process CL
Feedback 1
Resource
6) Basic PID settings:
Process PID normal/inverse. Parameter 7-30 [0] Normal
Process PID
Normal/
Inverse Control
Process PID anti wind-up. Parameter 7-31 [1] On
Process PID
Anti Windup
Process PID start speed. Parameter 7-32 300 RPM
Process PID
Start Speed
Save parameters to LCP. Parameter 0-50 [1] All to LCP
LCP Copy
2.5.5 Process Controller Optimization the integration time until the feedback signal
stabilizes, followed by an increase of 15–50%.
After configuring the basic settings as described in 4. Only use parameter 7-35 Process PID Differentiation
chapter 2.5.5 Programming Order, optimize the proportional Time for fast-acting systems (differentiation time).
gain, the integration time, and the differentiation time The typical value is 4 times the set integration
(parameter 7-33 Process PID Proportional Gain, time. Use the differentiator when the setting of
parameter 7-34 Process PID Integral Time, and the proportional gain and the integration time
parameter 7-35 Process PID Differentiation Time). In most has been fully optimized. Make sure that the
processes, complete the following procedure: lowpass filter dampens the oscillations on the
feedback signal sufficiently.
1. Start the motor.
NOTICE
2. Set parameter 7-33 Process PID Proportional Gain If necessary, start/stop can be activated several times to
to 0.3 and increase it until the feedback signal provoke a variation of the feedback signal.
again begins to vary continuously. Reduce the
value until the feedback signal has stabilized.
Lower the proportional gain by 40–60%.
3. Set parameter 7-34 Process PID Integral Time to
20 s and reduce the value until the feedback
signal again begins to vary continuously. Increase
2.5.6 Ziegler Nichols Tuning Method 4. Use Table 2.12 to calculate the necessary PID
control parameters.
NOTICE y(t)
130BA183.10
Do not use the Ziegler Nichols Tuning method in
applications that could be damaged by the oscillations
created by marginally stable control settings.
Burst transient is conducted at frequencies in the range 150 kHz to 30 MHz. Airborne interference from the frequency
converter system in the range 30 MHz to 1 GHz is generated from the frequency converter, motor cable, and motor.
Capacitive currents in the motor cable coupled with a high dU/dt from the motor voltage generate leakage currents.
Using a shielded motor cable increases the leakage current (see Illustration 2.27) because shielded cables have higher
capacitance to ground than unshielded cables. If the leakage current is not filtered, it causes greater interference on the
mains in the radio frequency range below approximately 5 MHz. Since the leakage current (I1) is carried back to the unit
through the shield (I3), there is only a small electro-magnetic field (I4) from the shielded motor cable.
The shield reduces the radiated interference but increases the low-frequency interference on the mains. Connect the motor
cable shield to the frequency converter enclosure and the motor enclosure. This is best done by using integrated shield
clamps to avoid twisted shield ends (pigtails). The shield clamps increase the shield impedance at higher frequencies, which
reduces the shield effect and increases the leakage current (I4).
Mount the shield on the enclosure at both ends if a shielded cable is used for the following purposes:
• Fieldbus
• Network
• Relay
• Control cable
• Signal interface
• Brake 2 2
In some situations, however, it is necessary to break the shield to avoid current loops.
175ZA062.12
z L1 CS CS
U
I1
z L2 V
z L3 W
z PE PE I2 CS
1
I3
2
CS CS CS
I4 I4
3 4 5 6
1 Ground cable
2 Shield
3 AC mains supply
4 Frequency converter
5 Shielded motor cable
6 Motor
If placing the shield on a mounting plate for the frequency converter, use a metal mounting plate to convey the shield
currents back to the unit. Ensure good electrical contact from the mounting plate through the mounting screws to the
frequency converter chassis.
When using unshielded cables, some emission requirements are not complied with, although the immunity requirements are
observed.
To reduce the interference level from the entire system (unit and installation), make motor and brake cables as short as
possible. Avoid placing cables with a sensitive signal level alongside mains, motor, and brake cables. Radio interference
higher than 50 MHz (airborne) is especially generated by the control electronics.
2 2 The test results in Table 2.13 have been obtained using a system with a frequency converter (with the mounting plate), a
motor, and shielded motor cables.
Filter type
Supply voltage/rated power Class A2/EN 55011 Class A1/EN 55011 Class B/EN 55011
(internal)
3x380–480 V 3x200–240 V 1x200–240 V Conducted Radiated Conducted Radiated Conducted Radiated
0.37–22 kW
– – 25 m (82 ft) Yes1) – – – –
(0.5–30 hp)
0.37–4 kW
A2 filter – – 25 m (82 ft) Yes1) – – – –
(0.5–5.4 hp)
0.37–2.2 kW
– – – – – – – –
(0.5–3 hp)
0.37–7.5 kW 25 m
– – 25 m (82 ft) Yes1) Yes – –
(0.5–10 hp) (82 ft)
11–22 kW 50 m
A1 filter – – 50 m (164 ft) Yes1) Yes – –
(15–30 hp) (164 ft)
0.37–2.2 kW 40 m 15 m
– – 40 m (131 ft) Yes1) Yes –
(0.5–3 hp) (131 ft) (49.2 ft)
0.37–22 kW
– – – – – – – –
A2 filter (0.5–30 hp)
EMC 0.37–4 kW
– – – – – – – –
screw (0.5–5.4 hp)
removed2) 0.37–2.2 kW
– – – – – – – –
(0.5–3 hp)
0.37–7.5 kW
– – 5 m (16.4 ft) Yes1) – – – –
A1 filter (0.5–10 hp)
EMC 11–22 kW
– – 5 m (16.4 ft) Yes1) – – – –
screw (15–30 hp)
removed2) 0.37–2.2 kW
– – 5 m (16.4 ft) Yes1) – – – –
(0.5–3 hp)
The test results in Table 2.14 have been obtained using a system with a frequency converter (with the mounting plate), an
external filter, a motor, and shielded motor cables. 3-phase 380–480 V frequency converter should be with internal A1 filter.
Filter type
Supply voltage/rated power Class A2/EN 55011 Class A1/EN 55011 Class B/EN 55011
(external)
2 2
3x380–480 V 3x200–240 V 1x200–240 V Conducted Radiated Conducted Radiated Conducted Radiated
0.37–22 kW 100 m 25 m
– – 100 m (328 ft) Yes1) Yes –
(0.5–30 hp) (328 ft) (82 ft)
0.37–4 kW
EMC filter – – – – – – – –
(0.5–5.4 hp)
0.37–2.2 kW 100 m 40 m
– – 100 m (328 ft) Yes1) Yes –
(0.5–3 hp) (328 ft) (131 ft)
0.37–7.5 kW
– – – – – – – –
(0.5–10 hp)
11–22 kW 40 m
– – 150 m (492 ft) Yes1) Yes – –
dU/dt (15–30 hp) (131 ft)
filter 0.37–4 kW
– – – – – – – –
(0.5–5.4 hp)
0.37–2.2 kW
– – – – – – – –
(0.5–3 hp)
0.37–7.5 kW 50 m
– – 50 m (164 ft) Yes1) Yes – –
(0.5–10 hp) (164 ft)
11–15 kW 50 m
– – 150 m (492 ft) Yes1) Yes – –
(15–20 hp) (164 ft)
Sine-wave 18.5–22 kW 100 m
– – 150 m (492 ft) Yes1) Yes – –
filter (25–30 hp) (328 ft)
0.37–4 kW
– – – – – – – –
(0.5–5.4 hp)
0.37–2.2 kW 50 m
– – 50 m (164 ft) Yes1) Yes – –
(0.5–3 hp) (164 ft)
0.37–15 kW 100 m
– – 150 m (492 ft) Yes1) Yes – –
(0.5–20 hp) (328 ft)
EMC filter 18.5–22 kW
– – – – – – – –
+ (25–30 hp)
sine-wave 0.37–4 kW
– – – – – – – –
filter (0.5–5.4 hp)
0.37–2.2 kW 100 m
– – 150 m (492 ft) Yes1) Yes – –
(0.5–3 hp) (328 ft)
2 2 VLT® Midi Drive FC 280 complies with the industrial environment requirements, which are higher than the requirements for
the home and office environments. Therefore, FC 280 also complies with the lower requirements for home and office
environments with a large safety margin.
To document immunity against burst transient from electrical phenomena, the following immunity tests have been made on
a system consisting of:
• A frequency converter (with options if relevant).
• A shielded control cable.
• A control box with potentiometer, motor cable, and motor.
The tests were performed in accordance with the following basic standards:
• EN 61000-4-2 (IEC 61000-4-2) Electrostatic discharges (ESD): Simulation of electrostatic discharges from human
beings.
• EN 61000-4-3 (IEC 61000-4-3) Radiated immunity: Amplitude modulated simulation of the effects of radar and
radio communication equipment and mobile communications equipment.
• EN 61000-4-4 (IEC 61000-4-4) Burst transients: Simulation of interference caused by switching a contactor, relay,
or similar devices.
• EN 61000-4-5 (IEC 61000-4-5) Surge transients: Simulation of transients caused by, for example, lightning that
strikes near installations.
• EN 61000-4-6 (IEC 61000-4-6) Conducted immunity: Simulation of the effect from radio-transmission equipment
joined by connection cables.
FC 280 follows IEC 61800-3 standard. See Table 2.15 for details.
Galvanic (ensured) isolation is obtained by fulfilling Follow national and local codes regarding protective
requirements for higher isolation and by providing the grounding of equipment with a leakage current >3.5 mA.
relevant creapage/clearance distances. These requirements Frequency converter technology implies high frequency
are described in the EN 61800-5-1 standard. switching at high power. This switching generates a
leakage current in the ground connection. A fault current
in the frequency converter at the output power terminals
The components that make up the electrical isolation, as
might contain a DC component, which can charge the
shown in Illustration 2.28, also comply with the
filter capacitors and cause a transient ground current.
requirements for higher isolation and the relevant test as
The ground leakage current is made up of several contri-
described in EN 61800-5-1.
butions and depends on various system configurations
The PELV galvanic isolation can be shown in 3 locations
including RFI filtering, shielded motor cables, and
(see Illustration 2.28):
frequency converter power.
130BB955.12
Leakage current
terminals must be PELV, for example, the thermistor must
be reinforced/double insulated. a
130BD447.11
4 3 2 1
b
130BB956.12
130BB958.12
Leakage current
2 2
THDv=0%
THDv=5%
50 Hz 150 Hz f sw Frequency
Mains 3rd harmonics Cable
Illustration 2.31 Mains Contributions to Leakage Current
130BB957.11
Leakage current [mA]
Using RCDs
For more details, refer to the RCD Application Note.
Where residual current devices (RCDs), also known as earth
leakage circuit breakers (ELCBs), are used, comply with the 2.9 Brake Functions
following:
2.9.1 Mechanical Holding Brake
• Use RCDs of type B only, which are capable of
detecting AC and DC currents.
A mechanical holding brake mounted directly on the
• Use RCDs with an inrush delay to prevent faults motor shaft normally performs static braking.
caused by transient ground currents.
• Dimension RCDs according to the system configu- NOTICE
ration and environmental considerations.
When the holding brake is included in a safety chain, a
frequency converter cannot provide a safe control of a
mechanical brake. Include a redundancy circuitry for the
brake control in the total installation.
130BA167.10
Load
The threshold can be adjusted in parameter 2-14 Brake 2.9.4 Control with Brake Function
voltage reduce, with 70 V range.
2 2 NOTICE
The brake is protected against short-circuiting of the brake
resistor, and the brake transistor is monitored to ensure
The greater the reduction value, the faster the reaction that short-circuiting of the transistor is detected. A relay/
to a generator overload. Should only be used if there are digital output can be used for protecting the brake resistor
problems with overvoltage in the DC-link voltage. from overloading caused by a fault in the frequency
converter.
In addition, the brake enables readout of the momentary
NOTICE power and the mean power for the latest 120 s. The brake
Make sure that the brake resistor can cope with a can also monitor the power energizing and make sure that
voltage of 410 V or 800 V. it does not exceed a limit selected in parameter 2-12 Brake
Power Limit (kW).
Danfoss recommends calculating the brake resistance Rrec
according to the following formula. The recommended NOTICE
brake resistance guarantees that the frequency converter is
Monitoring the brake power is not a safety function. A
able to brake at the highest braking torque (Mbr(%)) of
thermal switch is required to prevent the brake power
160%.
from exceeding the limit. The brake resistor circuit is not
ground leakage protected.
U 2dc x 100x 0.83
Rrec Ω =
Pmotor x Mbr ( % ) xηVLT x ηmotor Overvoltage control (OVC) (exclusive brake resistor) can be
ηmotor is typically at 0.80 (≤7.5 kW (10 hp)); 0.85 (11–22 kW selected as an alternative brake function in
(15–30 hp)) parameter 2-17 Over-voltage Control. This function is active
ηVLT is typically at 0.97 for all units. The function ensures that a trip can be
avoided if the DC-link voltage increases. This is done by
For FC 280, Rrec at 160% braking torque is written as: increasing the output frequency to limit the voltage from
the DC link. It is a useful function, for example if the ramp-
396349 down time is too short to avoid tripping of the frequency
480V : Rrec = Ω 1) converter. In this situation, the ramp-down time is
Pmotor
397903 extended.
480V : Rrec = Ω 2)
Pmotor
1) For frequency converters ≤7.5 kW (10 hp) shaft output. NOTICE
2) For frequency converters 11–22 kW (15–30 hp) shaft OVC can be activated when running a PM motor (when
output. parameter 1-10 Motor Construction is set to [1] PM non-
salient SPM).
NOTICE
The resistance of the brake resistor should not be higher 2.10 Motor Insulation
than the value recommended by Danfoss. For brake
resistors with a higher ohmic value, the 160% braking Modern design of motors for use with frequency
torque may not be achieved because the frequency converters have a high degree of insulation to account for
converter might cut out for safety reasons. new generation high-efficiency IGBTs with high dU/dt. For
The resistance should be bigger than Rmin. retrofit in old motors it is necessary to confirm the motor
insulation or to mitigate with a dU/dt filter or if necessary
a sine-wave filter.
NOTICE
If a short circuit in the brake transistor occurs, prevent
power dissipation in the brake resistor by using a mains
2.10.1 Sine-wave Filters
switch or contactor to disconnect the mains for the
frequency converter. The frequency converter can control When a frequency converter controls a motor, resonance
the contactor. noise is heard from the motor. This noise, which is the
result of the motor design, occurs every time an inverter
switch in the frequency converter is activated. The
NOTICE frequency of the resonance noise thus corresponds to the
Do not touch the brake resistor because it can get hot switching frequency of the frequency converter.
during braking. To avoid fire risk, place the brake resistor
in a secure environment.
Danfoss supplies a sine-wave filter to dampen the acoustic Par. 13-51 Par. 13-52
130BB671.13
SL Controller Event SL Controller Action
motor noise.
The filter reduces the ramp-up time of the voltage, the Running
Warning
Coast 2 2
Start timer
peak load voltage UPEAK, and the ripple current ΔI to the Torque limit Set Do X low
motor, which means that current and voltage become Digital input X 30/2 Select set-up 2
... ...
almost sinusoidal. So, the acoustic motor noise is reduced
to a minimum. Par. 13-43
Logic Rule Operator 2
Start
130BA062.14
event P13-01
State 1
13-51.0
13-52.0 State 2
Stop 13-51.1
event P13-02 13-52.1
Stop
event P13-02
State 4
13-51.3
13-52.3
State 3
13-51.2
13-52.2
Stop
event P13-02
Illustration 2.35 Sequence with 3 Events/Actions
130BB672.10
Comparator Operator
Par. 13-10
and the DC link capacitors when a certain voltage level is
Comparator Operand reached.
= To select the method used for controlling the DC-link
Par. 13-12 TRUE longer than. voltage level, see parameter 2-10 Brake Function and
Comparator Value ... parameter 2-17 Over-voltage Control.
...
Mains drop-out
Illustration 2.36 Comparators During a mains drop-out, the frequency converter keeps
running until the DC-link voltage drops below the
minimum stop level, which is:
Logic rules • 314 V for 3x380–480 V.
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
• 202 V for 3x200–240 V.
using the logical operators and, or, and not. • 225 V for 1x200–240 V.
Par. 13-41 Par. 13-43 The mains voltage before the drop-out and the motor load
130BB673.10
Par. 13-40
Logic Rule Operator 1 Logic Rule Operator 2 determines how long it takes for the inverter to coast.
Logic Rule Boolean 1
Par. 13-42
Static overload in VVC+ mode
Logic Rule Boolean 2 ... When the frequency converter is overloaded, the torque
... ... limit in parameter 4-16 Torque Limit Motor Mode/
...
parameter 4-17 Torque Limit Generator Mode is reached, the
Par. 13-44 control unit reduces the output frequency to reduce the
Logic Rule Boolean 3
load.
Illustration 2.37 Logic Rules
If the overload is excessive, a overcurrent which makes the
frequency converter cut out after approximately 5–10 s
may occur.
2.12 Extreme Running Conditions Operation within the torque limit is limited in time (0–60 s)
Short circuit (motor phase-to-phase) in parameter 14-25 Trip Delay at Torque Limit.
The frequency converter is protected against short circuits
by current measurement in each of the 3 motor phases or 2.12.1 Motor Thermal Protection
in the DC link. A short circuit between 2 output phases
causes an overcurrent in the frequency converter. The To protect the application from serious damage, VLT® Midi
frequency converter is turned off individually when the Drive FC 280 offers several dedicated features.
short-circuit current exceeds the allowed value (alarm 16,
trip lock). Torque limit
Switching on the output The torque limit protects the motor from being overloaded
Switching on the output between the motor and the independent of the speed. Torque limit is controlled in
frequency converter is fully allowed, and does not damage parameter 4-16 Torque Limit Motor Mode and
the frequency converter. However, fault messages may parameter 4-17 Torque Limit Generator Mode.
appear. Parameter 14-25 Trip Delay at Torque Limit controls the time
before the torque limit warning trips.
Motor-generated overvoltage
The voltage in the DC link is increased when the motor Current limit
acts as a generator. This occurs in following cases: Parameter 4-18 Current Limit controls the current limit, and
parameter 14-24 Trip Delay at Current Limit controls the
• The load drives the motor (at constant output
time before the current limit warning trips.
frequency from the frequency converter).
Minimum speed limit
• If the inertia moment is high during deceleration
Parameter 4-12 Motor Speed Low Limit [Hz] sets the
(ramp-down), the friction is low and the ramp-
minimum output speed that the frequency converter can
down time is too short for the energy to be
provide.
dissipated as a loss in the frequency converter,
the motor, and the installation.
175ZA052.12
t [s]
2000
1000
600
500
400
300
200
fOUT = 1 x f M,N(par. 1-23)
100
fOUT = 2 x f M,N
60
50 fOUT = 0.2 x f M,N
40
30
20 IM
10
1.0 1.2 1.4 1.6 1.8 2.0 IMN(par. 1-24)
Illustration 2.38 ETR
3 Application Examples
3.1 Introduction
130BA646.10
CW
3 3
A
3.1.1 Encoder Connection
B
The purpose of this guideline is to ease the set-up of
encoder connection to the frequency converter. Before
setting up the encoder, the basic settings for a closed-loop
speed control system are shown.
130BE805.11
+24 V DC
+24 V DC
CCW
GND
A
B
12 13 18 19 27 29 32 33 55
B
Illustration 3.2 24 V Incremental Encoder, Maximum Cable
Length 5 m (16.4 ft)
3.2.2 Speed
130BE728.10
Parameters
Function Setting
130BE204.11
FC
Parameter 6-10 T
+24 V
+24 V
12
13
erminal 53 Low
Voltage
0.07 V*
3 3
D IN 18
Parameter 6-11 T
D IN 19
erminal 53 High 10 V*
D IN 27
Voltage
D IN 29
Parameter 6-14 T
D IN 32
33
erminal 53 Low 0
D IN
Brake resistor Ref./Feedb. Value
Parameter 6-15 T
erminal 53 High 50
+10 V 50
+ Ref./Feedb. Value
Transmission A IN 53
A IN 54 Parameter 6-19 T
[1] Voltage
COM 55 erminal 53 mode
-
A OUT 42 * = Default value
0 ~10 V
Notes/comments:
Motor Gearbox
Illustration 3.3 Basic Set-up for Closed-loop Speed Control Table 3.2 Analog Speed Reference (Voltage)
Parameters
3.2 Application Examples 130BF097.10 Function Setting
FC Parameter 6-22 T
3.2.1 AMA +24 V 12 erminal 54 Low 4 mA*
+24 V 13 Current
Parameters D IN 18
Parameter 6-23 T
D IN 19
Function Setting erminal 54 High 20 mA*
130BF096.10
FC D IN 27
Parameter 1-29 A Current
+24 V 12 [1] Enable D IN 29
utomatic Motor Parameter 6-24 T
+24 V 13 complete D IN 32
Adaptation erminal 54 Low 0
D IN 18 AMA D IN 33
(AMA) Ref./Feedb. Value
D IN 19
D IN 27 Parameter 5-12 T Parameter 6-25 T
*[2] Coast
D IN 29 erminal 27 erminal 54 High 50
inverse +10 V 50
D IN 32 Digital Input + Ref./Feedb. Value
A IN 53
D IN 33 * = Default value Parameter 6-29 T
A IN 54
Notes/comments: Set [0] Current
COM 55 erminal 54 mode
parameter group 1-2* Motor -
A OUT 42 * = Default value
4 - 20mA
+10 V 50 Data according to motor
Notes/comments:
A IN 53 specifications.
A IN 54 NOTICE
COM 55
If terminal 13 and 27 are
A OUT 42
not connected, set Table 3.3 Analog Speed Reference (Current)
parameter 5-12 Terminal 27
Digital Input to [0] No
operation.
Parameters Speed
130BB840.12
Function Setting Reference
130BE208.11
FC
Parameter 6-10 T
+24 V 12
erminal 53 Low 0.07 V*
+24 V 13
Voltage Start (18)
D IN 18
3 3 D IN
D IN
19
27
Parameter 6-11 T
erminal 53 High 10 V*
Freeze ref (27)
Speed up (29)
D IN 29 Voltage
Speed down (32)
D IN 32 Parameter 6-14 T
D IN 33 erminal 53 Low 0 Illustration 3.4 Speed Up/Speed Down
Ref./Feedb. Value
Parameter 6-15 T
erminal 53 High 50
+10 V 50 3.2.3 Start/Stop
A IN 53 ≈ 5kΩ Ref./Feedb. Value
A IN 54 Parameter 6-19 T
[1] Voltage Parameters
COM 55 erminal 53 mode
Function Setting
130BF098.10
A OUT 42 * = Default value FC
+24 V 12 Parameter 5-10 Ter
Notes/comments:
+24 V 13 minal 18 Digital [8] Start
D IN 18 Input
D IN 19 Parameter 5-11 Ter
D IN 27 *[10]
Table 3.4 Speed Reference (Using a Manual Potentiometer) minal 19 Digital
D IN 29 Reversing
Input
D IN 32
Parameters Parameter 5-12 Ter [0] No
D IN 33
Function Setting minal 27 Digital operation
130BF100.10
FC
Parameter 5-10 T Input
+24 V 12
erminal 18 *[8] Start Parameter 5-14 Ter [16] Preset
+24 V 13 +10 V 50
Digital Input A IN minal 32 Digital ref bit 0
D IN 18 53
D IN 19
Parameter 5-12 T [19] Freeze A IN 54 Input
D IN 27 erminal 27 Reference COM 55 Parameter 5-15 Ter [17] Preset
D IN 29 Digital Input A OUT 42 minal 33 Digital ref bit 1
D IN 32 Parameter 5-13 T [21] Speed Up Input
D IN 33 erminal 29 Parameter 3-10 Pre
Digital Input set Reference
Parameter 5-14 T [22] Speed Preset ref. 0 25%
+10 V 50 erminal 32 Down Preset ref. 1 50%
A IN 53 Digital Input Preset ref. 2 75%
A IN 54 * = Default value Preset ref. 3 100%
COM 55 Notes/comments: * = Default value
A OUT 42 Notes/comments:
Parameters Parameters
Function Setting Function Setting
130BE211.11
130BF099.10
FC FC Parameter 4-30
Parameter 5-11 T +24 V 12 Motor Feedback [1] Warning
+24 V 12
+24 V
D IN
13
18
erminal 19
Digital Input
[1] Reset +24 V
D IN
13
18
Loss Function
Parameter 4-31 3 3
* = Default value Motor Feedback 50
D IN 19 D IN 19
Speed Error
D IN 27 Notes/comments: D IN 27
Parameter 4-32
D IN 29 D IN 29 Motor Feedback 5 s
D IN 32 D IN 32 Loss Timeout
D IN 33 D IN 33 Parameter 7-00 S
[1] 24 V
peed PID
encoder
Feedback Source
Parameter 5-70 T
+10 V 50 erm 32/33 Pulses 1024*
+10 V 50
A IN
A IN 53 Per Revolution
53
A IN 54 Parameter 13-00
A IN 54
COM 55
SL Controller [1] On
COM 55 Mode
A OUT A OUT 42
42 Parameter 13-01
[19] Warning
Start Event
Parameter 13-02
[44] Reset key
01 Stop Event
02 Parameter 13-10
R1
[21] Warning
03 Comparator
Table 3.7 External Alarm Reset no.
Operand
Parameter 13-11
Comparator *[1] ≈
3.2.5 Motor Thermistor Operator
Parameter 13-12
NOTICE Comparator
Value
61
5.1 Introduction
5.1.1 Overview
RS485 is a 2-wire bus interface compatible with multi-drop network topology. The nodes can be connected as a bus, or via
drop cables from a common trunk line. A total of 32 nodes can be connected to 1 network segment.
Repeaters divide network segments, see Illustration 5.1.
drop cable 5 5
130BB795.10
61 68 69
COMM. GND
P
N NOTICE
Observe relevant national and local regulations, for
example regarding protective earth connection. To avoid
Illustration 5.2 Network Connection coupling of high-frequency noise between the cables,
keep the RS485 communication cable away from motor
5 5 5.1.3 Hardware Set-up
and brake resistor cables. Normally, a distance of
200 mm (8 in) is sufficient. Maintain the greatest possible
distance between the cables, especially where cables run
To terminate the RS485 bus, use the terminator switch on in parallel over long distances. When crossing is
the main control board of the frequency converter. unavoidable, the RS485 cable must cross motor and
brake resistor cables at an angle of 90°.
The factory setting for the switch is OFF.
5.2 FC Protocol
5.1.4 Parameter Settings for Modbus
Communication 5.2.1 Overview
Parameter 8-33 Pari Set the parity and number of stop bits.
ty / Stop Bits NOTICE
The default selection depends on the
protocol selected in
parameter 8-30 Protocol.
The physical layer is RS485, thus utilizing the RS485 port 5.4 FC Protocol Message Framing Structure
built into the frequency converter. The FC protocol
supports different telegram formats: 5.4.1 Content of a Character (byte)
• A short format of 8 bytes for process data. Each character transferred begins with a start bit. Then 8
data bits are transferred, corresponding to a byte. Each
• A long format of 16 bytes that also includes a
character is secured via a parity bit. This bit is set at 1
parameter channel.
when it reaches parity. Parity is when there are an equal
• A format used for texts. number of 1s in the 8 data bits and the parity bit in total.
A stop bit completes a character, consisting of 11 bits in
5.2.2 FC with Modbus RTU all.
195NA036.10
bus reference of the frequency converter.
Start 0 1 2 3 4 5 6 7 Even Stop
bit Parity bit
The control word allows the Modbus master to control
Illustration 5.3 Content of a Character
several important functions of the frequency converter:
• Start.
• Stop of the frequency converter in various ways: 5.4.2 Telegram Structure
- Coast stop.
- Quick stop. Each telegram has the following structure:
• Start character (STX) = 02 hex.
- DC brake stop.
• A byte denoting the telegram length (LGE).
- Normal (ramp) stop.
• A byte denoting the frequency converter address
• Reset after a fault trip. (ADR).
• Run at various preset speeds. Several data bytes (variable, depending on the type of
• Run in reverse. telegram) follow.
195NA099.10
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
STX LGE ADR DATA BCC
and where possible, write values to them. Accessing the
parameters offers a range of control options, including Illustration 5.4 Telegram Structure
controlling the setpoint of the frequency converter when
its internal PI controller is used.
To enable the FC protocol for the frequency converter, set The telegram length is the number of data bytes plus the
the following parameters. address byte ADR and the data control byte BCC.
130BB918.10
PKE IND PWEhigh PWElow
The slave returns the address byte unchanged to the
master in the response telegram.
Parameter
commands
5.4.6 The Data Field
and replies
Parameter
number
The structure of data blocks depends on the type of
Illustration 5.8 PKE Field
telegram. There are 3 telegram types, and the type applies
for both control telegrams (master⇒slave) and response
telegrams (slave⇒master).
Bits 12–15 transfer parameter commands from master to
slave and return processed slave responses to the master.
The 3 types of telegram are:
STX LGE ADR PKE IND PWEhigh PWElow PCD1 PCD2 BCC
15 14 13 12
0 0 0 0 No response.
Illustration 5.6 Parameter Block
0 0 0 1 Parameter value transferred (word).
Parameter value transferred (double
0 0 1 0
word).
Text block
0 1 1 1 Command cannot be performed.
The text block is used to read or write texts via the data
1 1 1 1 Text transferred.
block.
Table 5.6 Response
130BA270.10
STX LGE ADR PKE IND Ch1 Ch2 Chn PCD1 PCD2 BCC
Illustration 5.7 Text Block If the command cannot be performed, the slave sends
0111 Command cannot be performed response and issues
the following fault reports in Table 5.7.
Fault code FC specification parameter 0-01 Language, select the data value by entering
0 Illegal parameter number. the value in the PWE block. Serial communication is only
1 Parameter cannot be changed. capable of reading parameters containing data type 9 (text
2 Upper or lower limit is exceeded. string).
3 Subindex is corrupted.
4 No array. Parameter 15-40 FC Type to parameter 15-53 Power Card
5 Wrong data type. Serial Number contain data type 9.
6 Not used. For example, read the unit size and mains voltage range in
7 Not used. parameter 15-40 FC Type. When a text string is transferred
9 Description element is not available.
(read), the length of the telegram is variable, and the texts
are of different lengths. The telegram length is defined in
11 No parameter write access.
5 5
the 2nd byte of the telegram (LGE). When using text
15 No text available.
transfer, the index character indicates whether it is a read
17 Not applicable while running.
or a write command.
18 Other errors.
100 –
To read a text via the PWE block, set the parameter
>100 –
command (AK) to F hex. The index character high-byte
130 No bus access for this parameter.
must be 4.
131 Write to factory set-up is not possible.
132 No LCP access.
252 Unknown viewer.
5.4.11 Data Types Supported by the
253 Request is not supported.
Frequency Converter
254 Unknown attribute.
Unsigned means that there is no operational sign in the
255 No error.
telegram.
Table 5.7 Slave Report
Data types Description
5.4.8 Parameter Number (PNU) 3 Integer 16
4 Integer 32
Bits 0–11 transfer parameter numbers. The function of the 5 Unsigned 8
relevant parameter is defined in the parameter description 6 Unsigned 16
in the VLT® Midi Drive FC 280 Programming Guide. 7 Unsigned 32
9 Text string
5.4.10 Parameter Value (PWE) Parameter 4-12 Motor Speed Low Limit [Hz] has a conversion
factor of 0.1. To preset the minimum frequency to 10 Hz,
The parameter value block consists of 2 words (4 bytes), transfer the value 100. A conversion factor of 0.1 means
and the value depends on the defined command (AK). The that the value transferred is multiplied by 0.1. The value
master prompts for a parameter value when the PWE block 100 is thus perceived as 10.0.
contains no value. To change a parameter value (write),
write the new value in the PWE block and send from the
master to the slave.
130BA093.10
119E H 0000 H 0000 H 03E8 H
5 5
Table 5.9 Conversion
PKE IND PWE high PWE low
PCD 1 PCD 2 Read the value in parameter 3-41 Ramp 1 Ramp Up Time.
Control telegram (master⇒slave control word) Reference value
Control telegram (slave⇒master) status word Present output PKE = 1155 hex - Read parameter value in
frequency parameter 3-41 Ramp 1 Ramp Up Time:
• IND = 0000 hex.
Table 5.10 Process Words (PCD)
• PWEHIGH = 0000 hex.
5.5 Examples • PWELOW = 0000 hex.
130BA094.10
5.5.1 Writing a Parameter Value
1155 H 0000 H 0000 H 0000 H
PKE = E19E hex - Write single word in If the value in parameter 3-41 Ramp 1 Ramp Up Time is
parameter 4-14 Motor Speed High Limit [Hz]: 10 s, the response from the slave to the master is shown in
• IND = 0000 hex. Illustration 5.12.
Data value 1000, corresponding to 100 Hz, see PKE IND PWE high PWE low
chapter 5.4.12 Conversion.
Illustration 5.12 Response
5 5
supports the interfaces defined in this manual. It is the frequency converter.
assumed that the user has full knowledge of the
capabilities and limitations of the controller. The control word allows the Modbus master to control
several important functions of the frequency converter:
5.6.2 Overview • Start.
• Various stops:
Regardless of the type of physical communication
networks, this section describes the process that a - Coast stop.
controller uses to request access to another device. This - Quick stop.
process includes how the Modbus RTU responds to
- DC brake stop.
requests from another device, and how errors are detected
and reported. It also establishes a common format for the - Normal (ramp) stop.
layout and contents of telegram fields. • Reset after a fault trip.
5 5
Closed-loop mode: Frequency
• The quantity of items to be handled.
converter feedback signal.
• The count of actual data bytes in the field. Parameter write control (master to
slave).
5.8.7 CRC Check Field 0 = Parameter changes are written
to the RAM of the frequency
65 Master to slave
Telegrams include an error-checking field, operating based converter.
on a cyclic redundancy check (CRC) method. The CRC field 1 = Parameter changes are written
checks the contents of the entire telegram. It is applied to the RAM and EEPROM of the
regardless of any parity check method used for the frequency converter.
individual characters of the telegram. The transmitting 66–65536 Reserved. –
device calculates the CRC value and appends the CRC as
the last field in the telegram. The receiving device Table 5.15 Coil Register
recalculates a CRC during receipt of the telegram and
Coil 0 1
compares the calculated value to the actual value received
01 Preset reference lsb
in the CRC field. 2 unequal values result in bus timeout.
02 Preset reference msb
The error-checking field contains a 16-bit binary value
implemented as 2 8-bit bytes. After the implementation, 03 DC brake No DC brake
the low-order byte of the field is appended first, followed 04 Coast stop No coast stop
by the high-order byte. The CRC high-order byte is the last 05 Quick stop No quick stop
byte sent in the telegram. 06 Freeze frequency No freeze frequency
07 Ramp stop Start
Coil 0 1
33 Control not ready Control ready
34 Frequency converter not Frequency converter ready
ready
35 Coast stop Safety closed
36 No alarm Alarm
37 Not used Not used
38 Not used Not used
39 Not used Not used
40 No warning Warning
41 Not at reference At reference
5 5 42
43
Hand mode
Out of frequency range
Auto mode
In frequency range
44 Stopped Running
45 Not used Not used
46 No voltage warning Voltage warning
47 Not in current limit Current limit
48 No thermal warning Thermal warning
Examples
Reading parameter 3-12 Catch up/slow Down Value (16 bit):
The holding register 3120 holds the parameters value. A
value of 1352 (decimal), means that the parameter is set to
12.52%.
Reading parameter 3-14 Preset Relative Reference (32 bit):
The holding registers 3410 and 3411 hold the parameters
5.10.2 Force/Write Single Coil (05 hex) Field name Example (hex)
Slave address 01 (frequency converter address)
Description Function 0F (write multiple coils)
This function forces the coil to either ON or OFF. When Coil address HI 00
broadcast, the function forces the same coil references in Coil address LO 10 (coil address 17)
all attached slaves. Quantity of coils HI 00
Query Quantity of coils LO 10 (16 coils)
The query telegram specifies the coil 65 (parameter write Byte count 02
control) to be forced. Coil addresses start at 0, that is, coil Force data HI
20
65 is addressed as 64. Force data = 00 00 hex (OFF) or FF (Coils 8–1)
00 hex (ON). Force data LO
00 (reference = 2000 hex)
Field name Example (hex)
(Coils 16–9)
Error check (CRC) –
5 5
Slave address 01 (Frequency converter address)
Function 05 (write single coil) Table 5.26 Query
Coil address HI 00
Coil address LO 40 (64 decimal) Coil 65 Response
Force data HI FF The normal response returns the slave address, function
Force data LO 00 (FF 00 = ON)
code, starting address, and quantity of coils forced.
Error check (CRC) – Field name Example (hex)
Slave address 01 (frequency converter address)
Table 5.24 Query
Function 0F (write multiple coils)
Response Coil address HI 00
The normal response is an echo of the query, returned Coil address LO 10 (coil address 17)
after the coil state has been forced. Quantity of coils HI 00
Quantity of coils LO 10 (16 coils)
Field name Example (hex) Error check (CRC) –
Slave address 01
Function 05 Table 5.27 Response
Force data HI FF
Force data LO 00 5.10.4 Read Holding Registers (03 hex)
Quantity of coils HI 00
Quantity of coils LO 01 Description
Error check (CRC) – This function reads the contents of holding registers in the
slave.
Table 5.25 Response
Query
The query telegram specifies the starting register and
5.10.3 Force/Write Multiple Coils (0F hex) quantity of registers to be read. Register addresses start at
0, that is, registers 1–4 are addressed as 0–3.
Description
Example: Read parameter 3-03 Maximum Reference, register
This function forces each coil in a sequence of coils to
03030.
either on or off. When broadcasting, the function forces
the same coil references in all attached slaves.
Field name Example (hex)
Query
Slave address 01
The query telegram specifies the coils 17–32 (speed
Function 03 (Read holding registers)
setpoint) to be forced.
Starting address HI 0B (Register address 3029)
NOTICE Starting address LO D5 (Register address 3029)
Coil addresses start at 0, that is, coil 17 is addressed as Number of points HI 00
16. 02 – (parameter 3-03 Maximum
Number of points LO Reference is 32 bits long, that is, 2
registers)
Error check (CRC) –
5 5 Byte count
Data HI (register 3030)
04
00 Slave address
Field name Example (hex)
01
Data LO (register 3030) 16 Function 10
Data HI (register 3031) E3 Starting address HI 04
Data LO (register 3031) 60 Starting address LO 07
Error check (CRC) – Number of registers HI 00
Number of registers LO 02
Table 5.29 Response Byte count 04
Write data HI (Register 4: 1049) 00
5.10.5 Preset Single Register (06 hex) Write data LO (Register 4: 1049) 00
Write data HI (Register 4: 1050) 02
Description Write data LO (Register 4: 1050) E2
This function presets a value into a single holding register. Error check (CRC) –
Query
Table 5.32 Query
The query telegram specifies the register reference to be
preset. Register addresses start at 0, that is, register 1 is
Response
addressed as 0.
The normal response returns the slave address, function
Example: Write to parameter 1-00 Configuration Mode, code, starting address, and quantity of registers preset.
register 1000.
Field name Example (hex)
Field name Example (hex) Slave address 01
Slave address 01 Function 10
Function 06 Starting address HI 04
Register address HI 03 (register address 999) Starting address LO 19
Register address LO E7 (register address 999) Number of registers HI 00
Preset data HI 00 Number of registers LO 02
Preset data LO 01 Error check (CRC) –
Error check (CRC) –
Table 5.33 Response
Table 5.30 Query
Response
The normal response is an echo of the query, returned
after the register contents have been passed.
130BA274.11
Bit 03, Coasting
CTW Speed ref. Bit 03 = 0: The frequency converter immediately releases
the motor (the output transistors are shut off), and it
coasts to a standstill.
Bit
no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit 03 = 1: If the other starting conditions are met, the
frequency converter starts the motor.
Illustration 5.13 Control Word According to FC Profile
In parameter 8-50 Coasting Select, define how bit 03 gates
with the corresponding function on a digital input.
5 5
Bit Bit value = 0 Bit value = 1 Bit 04, Quick stop
00 Reference value External selection lsb Bit 04 = 0: Makes the motor speed ramp down to stop (set
01 Reference value External selection msb in parameter 3-81 Quick Stop Ramp Time).
02 DC brake Ramp
Bit 05, Hold output frequency
03 Coasting No coasting Bit 05 = 0: The present output frequency (in Hz) freezes.
04 Quick stop Ramp Change the frozen output frequency only with the digital
Hold output inputs programmed to [21] Speed up and [22] Speed down
05 Use ramp
frequency (parameter 5-10 Terminal 18 Digital Input to
06 Ramp stop Start parameter 5-13 Terminal 29 Digital Input).
07 No function Reset
08 No function Jog
NOTICE
09 Ramp 1 Ramp 2
If freeze output is active, the frequency converter can
only be stopped in 1 of the following ways:
10 Data invalid Data valid
11 Relay 01 open Relay 01 active • Bit 03 coast stop.
12 Relay 02 open Relay 02 active • Bit 02 DC brake.
13 Parameter set-up Selection lsb
15 No function Reverse
• Digital input programmed to [5] DC brake
inverse, [2] Coast inverse, or [3] Coast and reset
Table 5.34 Control Word According to FC Profile inv (parameter 5-10 Terminal 18 Digital Input to
parameter 5-13 Terminal 29 Digital Input).
Explanation of the control bits
Bits 00/01
Bits 00 and 01 are used to select among the 4 reference Bit 06, Ramp stop/start
values, which are preprogrammed in parameter 3-10 Preset Bit 06 = 0: Causes a stop and makes the motor speed
Reference according to Table 5.35. ramp down to stop via the selected ramp-down parameter.
Bit 06 = 1: Allows the frequency converter to start the
Programmed
Bit Bit motor if the other starting conditions are met.
reference Parameter
01 00 In parameter 8-53 Start Select, define how bit 06 ramp stop/
value
1 Parameter 3-10 Preset Reference [0] 0 0 start gates with the corresponding function on a digital
2 Parameter 3-10 Preset Reference [1] 0 1
input.
3 Parameter 3-10 Preset Reference [2] 1 0 Bit 07, Reset
4 Parameter 3-10 Preset Reference [3] 1 1 Bit 07 = 0: No reset.
Bit 07 = 1: Resets a trip. Reset is activated on the leading
Table 5.35 Control Bits signal edge, that is, when changing from logic 0 to logic 1.
Bit 08, Jog
NOTICE Bit 08 = 1: Parameter 3-11 Jog Speed [Hz] determines the
In parameter 8-56 Preset Reference Select, define how bit output frequency.
00/01 gates with the corresponding function on the
Bit 09, Selection of ramp 1/2
digital inputs.
Bit 09 = 0: Ramp 1 is active (parameter 3-41 Ramp 1 Ramp
Up Time to parameter 3-42 Ramp 1 Ramp Down Time).
Bit 09 = 1: Ramp 2 (parameter 3-51 Ramp 2 Ramp Up Time
to parameter 3-52 Ramp 2 Ramp Down Time) is active.
Bit 10, Data not valid/Data valid 5.11.2 Status Word According to FC Profile
Tell the frequency converter whether to use or ignore the (STW)
control word.
Bit 10 = 0: The control word is ignored. Set parameter 8-30 Protocol to [0] FC.
Bit 10 = 1: The control word is used. This function is
relevant because the telegram always contains the control
Follower-master
130BA273.11
word, regardless of the telegram type. If the control word
is not needed when updating or reading parameter, turn it STW Output freq.
off.
Bit 11, Relay 01 Bit
Bit 11 = 0: Relay not activated. no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Speed reference value is transmitted to the frequency converter in a relative value in %. The value is transmitted in the form
of a 16-bit word. The integer value 16384 (4000 hex) corresponds to 100%. Negative figures are formatted using 2’s
complement. The actual output frequency (MAV) is scaled in the same way as the bus reference.
Master-slave
130BA276.11
16bit
Follower-slave
5 5 STW
Actual output
frequency
-100% 0% 100%
130BA277.10
(C000hex) (0hex) (4000hex)
Par.3-00 set to
Reverse Forward
(1) -max- +max
Par.3-03 0 Par.3-03
0% 100%
(0hex) (4000hex)
Par.3-00 set to
Forward
(0) min-max
Par.3-02 Par.3-03
130BF710.10
1 3 7 11 13 16 18 20 24 29 134B0792
MCM 1011)
FC-280PK37T4E20H1BXCXXXSXXXXAX VLT® Control Panel LCP 21 (Numeric) 132B0254
VLT® Control Panel LCP 102 (Graphical) 130B1107
Illustration 6.1 Type Code
Graphical LCP adapter 132B0281
Power Pm (HO) Rmin Rbr. nom Rrec Pbr avg Ordering Period Cable Thermal Maximum
rating number cross- relay brake torque
section1) with resistor
3-phase [kW (hp)] [Ω] [Ω] [Ω] [kW (hp)] 175Uxxxx [s] [mm2 [A] [%]
380–480 V (AWG)]
(T4)
Table 6.4 FC 280 - Mains: 3-phase 380–480 V (T4), 10% Duty Cycle
Power Pm (HO) Rmin Rbr. nom Rrec Pbr avg Ordering Period Cable Thermal Maximum
rating number cross- relay brake torque
section1) with resistor
3-phase [kW (hp)] [Ω] [Ω] [Ω] [kW (hp)] 175Uxxxx [s] [mm2 [A] [%]
200–240 V (AWG)]
(T2)
0.030
PK37 0.37 (0.5) 225 263.22 250 3006 120 1.5 (16) 0.6 140
(0.040)
0.045
PK55 0.55 (0.75) 151 176.90 168 3011 120 1.5 (16) 0.7 142
(0.060)
0.062
PK75 0.75 (1.0) 110 129.92 123 3016 120 1.5 (16) 0.8 143
(0.083)
0.092
P1K1 1.1 (1.5) 73 86.77 82 3021 120 1.5 (16) 0.9 139
(0.120)
0.190
P2K2 2.2 (3.0) 35 42.06 39 3031 120 1.5 (16) 1.9 140
(0.255)
0.327
P3K7 3.7 (5.0) 20 24.47 23 3326 120 1.5 (16) 3.5 145
(0.439)
Table 6.5 FC 280 - Mains: 3-phase 200–240 V (T2), 10% Duty Cycle
1) All cabling must comply with national and local regulations on cable cross-sections and ambient temperature.
Power Pm (HO) Rmin Rbr. nom Rrec Pbr avg Ordering Period Cable Thermal Maximum
rating number cross- relay brake torque
section1) with resistor
3-phase [kW (hp)] [Ω] [Ω] [Ω] [kW (hp)] 175Uxxxx [s] [mm2] [A] [%]
380–480 V
(T4)
0.127
PK37 0.37 (0.5) 890 1041.98 989 3101 120 1.5 (16) 0.4 139
(0.170)
0.191
PK55 0.55 (0.75) 593 693.79 659 3308 120 1.5 (16) 0.5 131
(0.256)
0.260
PK75 0.75 (1.0) 434 508.78 483 3309 120 1.5 (16) 0.7 129
(0.349)
Table 6.6 FC 280 - Mains: 3-phase 380–480 V (T4), 40% Duty Cycle
Power Pm (HO) Rmin Rbr. nom Rrec Pbr avg Ordering Period Cable Thermal Maximum
rating number cross- relay brake torque
section1) with resistor
3-phase [kW (hp)] [Ω] [Ω] [Ω] [kW (hp)] 175Uxxxx [s] [mm2 [A] [%]
200–240 V (AWG)]
(T2)
0.129
PK37 0.37 (0.5) 225 263.22 250 3096 120 1.5 (16) 0.8 140
(0.173)
0.192
PK55 0.55 (0.75) 151 176.90 168 3008 120 1.5 (16) 0.9 142
(0.257)
0.261
PK75 0.75 (1.0) 110 129.92 123 3300 120 1.5 (16) 1.3 143
(0.350)
0.391
P1K1 1.1 (1.5) 73 86.77 82 3301 120 1.5 (16) 2 139
(0.524)
0.807
P2K2 2.2 (3.0) 35 42.06 39 3303 120 1.5 (16) 4.2 140
(1.082)
1.386
P3K7 3.7 (5.0) 20 24.47 23 3305 120 1.5 (16) 6.8 145
(1.859)
Table 6.7 FC 280 - Mains: 3-phase 200–240 V (T2), 40% Duty Cycle
1) All cabling must comply with national and local regulations on cable cross-sections and ambient temperature.
Suggested parameter settings for operation with sine-wave filter are as follows:
• Set [1] Sine-Wave Filter in parameter 14-55 Output Filter.
• Set suitable value for individual filter in parameter 14-01 Switching Frequency. When [1] Sine-Wave Filter is set in
parameter 14-55 Output Filter, the options which are lower than 5 kHz in parameter 14-01 Switching Frequency are
removed automatically.
For K1T4, K2T4 and K3T4 with internal A1 filter, with external EMC filters listed in Table 6.10, the maximum shielded cable
length of 100 m (328 ft) according to EN/IEC 61800-3 C2 (EN 55011 A1), or 25 m (82 ft) according to EN/IEC 61800-3 C1 (EN
55011 B) can be achieved.
130BF872.10
e1
a1
c1
C
A
a1 e1
am a2
fm
f1
6 6
bm
b1
B
4-Dm 6-D1
6-D1
For K4T4 and K5T4 with internal A1 filter, with external EMC filters listed in Table 6.11, the maximum shielded cable length
of 100 m (328 ft) according to EN/IEC 61800-3 C2 (EN 55011 A1), or 25 m (82 ft) according to EN/IEC 61800-3 C1 (EN 55011
B) can be achieved.
D l1
130BC247.10
C
L1
H K
A
B
G 6 6
F
7 Specifications
Estimated power loss at rated maximum load [W]1) 37.7 46.2 56.2 76.8 97.5 121.6
Torque characteristics
Starting torque (constant torque) Maximum 160% for 60 s1)
Overload torque (constant torque) Maximum 160% for 60 s1)
Starting current Maximum 200% for 1 s
Torque rise time in VVC+ mode (independent of fsw) Maximum 50 ms
1) Percentage relates to the nominal torque. It is 150% for 11–22 kW (15–30 hp) frequency converters.
7 7
EMC standards, immunity EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61326-3-1
Energy efficiency class 5) IE2
1) Refer to chapter 7.12 Special Conditions for:
• Derating for high ambient temperature.
• Derating for high altitude.
2) For PROFIBUS, PROFINET, EtherNet/IP, and POWERLINK variant of VLT® Midi Drive FC 280, to prevent the control card from
overtemperature, avoid full digital/analog I/O load at ambient temperature higher than 45 °C (113 °F).
3) Ambient temperature for K1S2 with derating is maximun 50 °C (122 °F).
4) Ambient temperature for K1S2 at full constant output current is maximun 40 °C (104 °F).
5) Determined according to EN 50598-2 at:
• Rated load.
• 90% rated frequency.
• Switching frequency factory setting.
• Switching pattern factory setting.
• Open type: Surrounding air temperature 45 °C (113 °F).
• Type 1 (NEMA kit): Ambient temperature 45 °C (113 °F).
STO inputs
7 7
Terminal number 37, 38
Voltage level 0–30 V DC
Voltage level, low <1.8 V DC
Voltage level, high >20 V DC
Maximum voltage on input 30 V DC
Minimum input current (each pin) 6 mA
Analog inputs
Number of analog inputs 2
Terminal number 531), 54
Modes Voltage or current
Mode select Software
Voltage level 0–10 V
Input resistance, Ri Approximately 10 kΩ
Maximum voltage -15 V to +20 V
Current level 0/4 to 20 mA (scaleable)
Input resistance, Ri Approximately 200 Ω
Maximum current 30 mA
Resolution for analog inputs 11 bit
Accuracy of analog inputs Maximum error 0.5% of full scale
Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminal 53 supports only voltage mode and can also be used as digital input.
PELV isolation
130BE837.10
7 7 37
Control Mains
38
High
voltage Motor
33
Functional
isolation
RS485 DC bus
NOTICE
HIGH ALTITUDE
For installation at altitudes above 2000 m (6562 ft), contact Danfoss hotline regarding PELV.
Pulse inputs
Programmable pulse inputs 2
Terminal number pulse 29, 33
Maximum frequency at terminal 29, 33 32 kHz (push-pull driven)
Maximum frequency at terminal 29, 33 5 kHz (open collector)
Minimum frequency at terminal 29, 33 4 Hz
Voltage level See the section on digital input
Maximum voltage on input 28 V DC
Input resistance, Ri Approximately 4 kΩ
Pulse input accuracy Maximum error: 0.1% of full scale
Digital outputs
Programmable digital/pulse outputs 1
Terminal number 271)
Voltage level at digital/frequency output 0–24 V
Maximum output current (sink or source) 40 mA
Maximum load at frequency output 1 kΩ
Maximum capacitive load at frequency output 10 nF
Minimum output frequency at frequency output 4 Hz
Maximum output frequency at frequency output 32 kHz
Accuracy of frequency output Maximum error: 0.1% of full scale
Resolution of frequency output 10 bit
1) Terminal 27 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Analog outputs
Number of programmable analog outputs 1
Terminal number 42
Current range at analog output
Maximum resistor load to common at analog output
0/4–20 mA
500 Ω
7 7
Accuracy on analog output Maximum error: 0.8% of full scale
Resolution on analog output 10 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number 12, 13
Maximum load 100 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV). However, the supply has the same potential as the
analog and digital inputs and outputs.
Relay outputs
Programmable relay outputs 1
Relay 01 01–03 (NC), 01–02 (NO)
Maximum terminal load (AC-1)1) on 01–02 (NO) (resistive load) 250 V AC, 3 A
Maximum terminal load (AC-15)1) on 01–02 (NO) (inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–02 (NO) (resistive load) 30 V DC, 2 A
Maximum terminal load (DC-13)1) on 01–02 (NO) (inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 01–03 (NC) (resistive load) 250 V AC, 3 A
Maximum terminal load (AC-15)1)on 01–03 (NC) (inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–03 (NC) (resistive load) 30 V DC, 2 A
Minimum terminal load on 01–03 (NC), 01–02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation.
7 7 Control characteristics
Resolution of output frequency at 0–500 Hz ±0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, and 33) ≤2 ms
Speed control range (open loop) 1:100 of synchronous speed
Speed accuracy (open loop) ±0.5% of nominal speed
Speed accuracy (closed loop) ±0.1% of nominal speed
All control characteristics are based on a 4-pole asynchronous motor.
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE
RISK
Malfunction or failing to follow the recommendations
may result in personal risk and damage to the frequency
converter and other equipment.
• Select fuses according to recommendations.
Possible damage can be limited to be inside the
frequency converter.
Non-UL circuit
UL fuse
Enclosure size Power [kW (hp)] Non-UL fuse breaker
(Bussmann, class T)
(Eaton)
0.37 (0.5)
0.55–0.75 gG-10 JJS-6
(0.74–1.0)
K1 PKZM0-16
1.1–1.5
JJS-10
(1.48–2.0) gG-20
2.2 (3.0) JJS-15
3-phase 380–480 V 3.0–5.5
K2 PKZM0-20
(4.0–7.5) gG-25 JJS-25
K3 7.5 (10) PKZM0-25
11–15
K4 gG-50 – JJS-50
(15–20)
18.5–22
K5 gG-80 – JJS-80
(25–30)
0.37 (0.5) gG-10 JJN-6
7 7 K1
0.55 (0.74)
0.75 (1.0) PKZM0-16
JJN-10
JJN-15
gG-20
3-phase 200–240 V 1.1 (1.48)
JJN-20
1.5 (2.0)
K2 2.2 (3.0) PKZM0-20
gG-25 JJN-25
K3 3.7 (5.0) PKZM0-25
0.37 (0.5) gG-10 JJN-6
0.55 (0.74) JJN-10
K1 0.75 (1.0) PKZM0-16 JJN-15
Single-phase 200–240 V gG-20
1.1 (1.48)
JJN-20
1.5 (2.0)
K2 2.2 (3.0) gG-25 PKZM0-20 JJN-25
130BB252.11
1.0
Efficiency of the frequency converter (ηVLT) 0.99
Relative Efficiency
The load on the frequency converter has little effect on its 0.98
0.97
efficiency. In general, the efficiency is the same at the
0.96
rated motor frequency fM,N. This rule also applies even if 0.95
the motor supplies 100% of the rated shaft torque or only 0.94
75%, for example if there is part loads. 0.93
0.92
This also means that the efficiency of the frequency 0% 50% 100% 150% 200%
converter does not change even if other U/f characteristics % Speed
are selected. 100% load 75% load 50% load 25% load
However, the U/f characteristics influence the efficiency of Illustration 7.2 Typical Efficiency Curves
the motor.
The efficiency declines a little when the switching
frequency is set to a value above the default value. If the Efficiency of the motor (ηMOTOR)
mains voltage is 480 V, or if the motor cable is longer than The efficiency of a motor connected to the frequency
30 m (98.4 ft), the efficiency is also slightly reduced. converter depends on the magnetizing level. In general,
the efficiency is as good as with mains operation. The
Frequency converter efficiency calculation efficiency of the motor depends on the type of motor.
Calculate the efficiency of the frequency converter at
different loads based on Illustration 7.2. Multiply the factor In the range of 75–100% of the rated torque, the efficiency
in Illustration 7.2 by the specific efficiency factor listed in of the motor is practically constant, both when controlled
the specification tables in chapter 7.1 Electrical Data: by the frequency converter and when running directly on
mains.
In small motors, the influence from the U/f characteristic If the peak voltage is too high, motors without phase coil
on efficiency is marginal. However, in motors from 11 kW insulation are affected. The longer the motor cable, the
(14.8 hp) and up, the advantages are significant. higher the rise time and peak voltage.
In general, the switching frequency does not affect the
efficiency of small motors. Motors from 11 kW (14.8 hp) Switching of the IGBTs cause peak voltage on the motor
and up have their efficiency improved 1–2% because the terminals. The VLT® Midi Drive FC 280 complies with IEC
sine shape of the motor current is almost perfect at high 60034-25 regarding motors designed to be controlled by
switching frequency. frequency converters. The FC 280 also complies with IEC
60034-17 regarding Norm motors controlled by frequency
Efficiency of the system (ηSYSTEM)
converters.
To calculate the system efficiency, the efficiency of the
The following dU/dt data are measured at the motor
frequency converter (ηVLT) is multiplied by the efficiency of
terminal side:
the motor (ηMOTOR):
ηSYSTEM = ηVLT x ηMOTOR
Cable Mains
7.10 Acoustic Noise length voltage Rise time UPEAK dU/dt
[m (ft)] [V] [μsec] [kV] [kV/μsec]
The acoustic noise from the frequency converter comes
5 (16.4) 400 0.0904 0.718 6.41
from 3 sources:
• DC intermediate circuit coils.
50 (164)
5 (16.4)
400
480
0.292
0.108
1.05
0.835
2.84
6.20
7 7
• Integral fan. 50 (164) 480 0.32 1.25 3.09
• RFI filter choke.
Table 7.8 dU/dt Data for FC 280, 2.2 kW (3.0 hp), 3x380–480 V
The typical values measured at a distance of 1 m (3.3 ft)
from the unit: Cable Mains
length voltage Rise time UPEAK dU/dt
Enclosure size 80% fan Full fan speed Background [m (ft)] [V] [μsec] [kV] [kV/μsec]
[kW (hp)] speed [dBA] [dBA] noise 5 (16.4) 400 0.096 0.632 5.31
K1 50 (164) 400 0.306 0.99 2.58
0.37–2.2 41.4 42.7 33 5 (16.4) 480 0.118 0.694 4.67
(0.5–3.0) 50 (164) 480 0.308 1.18 3.05
K2
50.3 54.3 32.9
3.0–5.5 (4.0–7.5) Table 7.9 dU/dt Data for FC 280, 5.5 kW (7.5 hp), 3x380–480 V
K3
51 54.2 33 Cable Mains
7.5 (10)
K4 length voltage Rise time UPEAK dU/dt
59 61.1 32.9 [m (ft)] [V] [μsec] [kV] [kV/μsec]
11–15 (15–20)
K5 5 (16.4) 400 0.128 0.732 4.54
64.6 65.6 32.9 50 (164) 400 0.354 1.01 2.27
18.5–22 (25–30)
5 (16.4) 480 0.134 0.835 5.03
Table 7.7 Typical Measured Values 50 (164) 480 0.36 1.21 2.69
7.11 dU/dt Conditions Table 7.10 dU/dt Data for FC 280, 7.5 kW (10 hp), 3x380–480 V
• The cross-section of the motor cable. 50 (164) 400 0.738 1.07 1.15
5 (16.4) 480 0.334 0.99 2.36
• The length of the motor cable.
50 (164) 480 0.692 1.25 1.44
• Whether the motor cable is shielded or not.
Table 7.11 dU/dt Data for FC 280, 15 kW (20 hp), 3x380–480 V
• Inductance.
The natural induction causes an overshoot UPEAK in the
motor voltage before it stabilizes itself at a level
depending on the voltage in the DC link. The rise time and
the peak voltage UPEAK affect the service life of the motor.
Cable Mains
length voltage Rise time UPEAK dU/dt
[m (ft)] [V] [μsec] [kV] [kV/μsec]
5 (16.4) 240 0.0712 0.484 5.44
50 (164) 240 0.224 0.594 2.11
Table 7.13 dU/dt Data for FC 280, 1.5 kW (2.0 hp), 3x200–240 V
7 7 Cable
length
Mains
voltage Rise time UPEAK dU/dt
[m (ft)] [V] [μsec] [kV] [kV/μsec]
5 (16.4) 240 0.072 0.468 5.25
50 (164) 240 0.208 0.592 2.28
Table 7.14 dU/dt Data for FC 280, 2.2 kW (3.0 hp), 3x200–240 V
Cable Mains
length voltage Rise time UPEAK dU/dt
[m (ft)] [V] [μsec] [kV] [kV/μsec]
5 (16.4) 240 0.092 0.526 4.56
50 (164) 240 0.28 0.6 1.72
Table 7.15 dU/dt Data for FC 280, 3.7 kW (5.0 hp), 3x200–240 V
Cable Mains
length voltage Rise time UPEAK dU/dt
[m (ft)] [V] [μsec] [kV] [kV/μsec]
5 (16.4) 240 0.088 0.414 3.79
50 (164) 240 0.196 0.593 2.41
Table 7.16 dU/dt Data for FC 280, 1.5 kW (2.0 hp), 1x200–240 V
Cable Mains
length voltage Rise time UPEAK dU/dt
[m (ft)] [V] [μsec] [kV] [kV/μsec]
5 (16.4) 240 0.112 0.368 2.64
50 (164) 240 0.116 0.362 2.51
Table 7.17 dU/dt Data for FC 280, 2.2 kW (3.0 hp), 1x200–240 V
130BE891.10
100%
Manual derating must be considered for: 90%
130BE889.10
100% 0%
0 2 4 6 8 10 12 14 16
90%
(2) Switching Frequency [kHz]
80%
70%
(1) Output current
(1) Output Current
60%
50%
(2) Switching frequency [kHz]
45C
40%
30%
50C
55C
Illustration 7.5 K3T4 Derating Curve 7 7
20%
10%
130BE892.10
0% 100%
0 2 4 6 8 10 12 14 16
90%
(2) Switching Frequency [kHz]
80%
70%
(1) Output Current
0%
100% 0 2 4 6 8 10 12 14 16
90% (2) Switching Frequency [kHz]
80%
70% (1) Output current
(1) Output Current
130BE893.10
130BF106.10
100% 100%
90% 90%
80% 80%
70% 70%
(1) Output Current
100%
130BF107.10
90% 100%
80% 90%
70% 80%
(1) Output Current
70%
(1) Output Current
60%
50% 60%
45C
40% 50% 45C
50C
30% 40% 50C
55C
20% 30% 55C
10% 20%
0% 10%
0 2 4 6 8 10 12 14 16 0%
(2) Switching Frequency [kHz] 0 2 4 6 8 10 12 14 16
(2) Switching Frequency [kHz]
(1) Output current
(2) Switching frequency [kHz] (1) Output current
(2) Switching frequency [kHz]
Illustration 7.8 K1T2 Derating Curve
100%
90%
80%
70%
(1) Output Current
60%
50% 45C
40% 50C
30% 55C
20%
10%
0%
0 2 4 6 8 10 12 14 16
(2) Switching Frequency [kHz]
130BF107.10
100%
90%
80%
70%
(1) Output Current
60%
50% 45C
40% 50C
30% 55C
20%
10%
0%
0 2 4 6 8 10 12 14 16
(2) Switching Frequency [kHz]
7 7 Dimensions
[mm (in)] Height A 338.5 (13.3)
FC 280 with IP21/UL/Type 1 kit
395 (15.6)
395
425 (16.7) 520 (20.5)
(15.6)
Width B 100 (3.9) 115 (4.5) 130 (5.1) 153 (6.0) 170 (6.7)
Depth C 183 (7.2) 183 (7.2) 183 (7.2) 260 (10.2) 260 (10.2)
FC 280 with bottom cable entry cover (w/o top cover)
357
Height A 294 (11.6) 356 (14) 391 (15.4) 486 (19.1)
(14.1)
Width B 75 (3.0) 90 (3.5) 115 (4.5) 133 (5.2) 150 (5.9)
Depth C 168 (6.6) 168 (6.6) 168 (6.6) 245 (9.6) 245 (9.6)
4.6
IP20 2.5 (5.5) 3.6 (7.9) 8.2 (18.1) 11.5 (25.4)
Weight (10.1)
[kg (lb)] 6.5
IP21 4.0 (8.8) 5.5 (12.1) 10.5 (23.1) 14.0 (30.9)
(14.3)
260 297.5
a 198 (7.8) 260 (10.2) 390 (15.4)
(10.2) (11.7)
b 60 (2.4) 70 (2.8) 90 (3.5) 105 (4.1) 120 (4.7)
6.5
Mounting c 5 (0.2) 6.4 (0.25) 8 (0.32) 7.8 (0.31)
(0.26)
holes [mm
d 9 (0.35) 11 (0.43) 11 (0.43) 12.4 (0.49) 12.6 (0.5)
(in)]
5.5
e 4.5 (0.18) 5.5 (0.22) 6.8 (0.27) 7 (0.28)
(0.22)
9.2
f 7.3 (0.29) 8.1 (0.32) 11 (0.43) 11.2 (0.44)
(0.36)
130BE844.11
B C
A1
A2
7 7
130BE846.10
B C
Illustration 7.14 Standard with Bottom Cable Entry Cover (w/o Top Cover)
130BE845.10
B C
A
7 7
b
130BA648.12
B
C e
a
c
A
d
e
a
b
Illustration 7.16 Top and Bottom Mounting Holes
Index DC brake.................................................................................................. 67
Dead band............................................................................................... 25
A Dead band around 0........................................................................... 25
AC input................................................................................................... 15 Derating................................................................................................... 84
Acoustic noise........................................................................................ 91 Directive, EMC.......................................................................................... 8
Additional resources.............................................................................. 5 Directive, Low Voltage........................................................................... 8
AMA.............................................................................................................. 6 Directive, Machinery.............................................................................. 8
AMA with T27 connected.................................................................. 49 Discharge time......................................................................................... 9
Ambient condition............................................................................... 84
Analog feedback................................................................................... 24 E
Analog reference.................................................................................. 24 Efficiency.................................................................................................. 90
Automatic motor adaptation.............................................................. 6 Electronic thermal relay........................................................................ 7
see also ETR
B EMC............................................................................................................ 84
Network connection............................................................................ 53
I NLCP control key................................................................................... 21
IEC 61800-3...................................................................................... 15, 84
IND............................................................................................................. 57 O
Index (IND).............................................................................................. 57 Open loop............................................................................................... 88
Input Ordering
Current................................................................................................. 15 DU/dt.................................................................................................... 77
Power.................................................................................................... 15 Sine-wave filter................................................................................. 76
Terminal............................................................................................... 15 Output current...................................................................................... 87
Inputs Outputs
Analog input................................................................................. 6, 86 Analog output.............................................................................. 6, 87
Digital input................................................................................ 21, 85 Digital output.................................................................................... 87
Pulse input.......................................................................................... 86
Intermediate circuit...................................................................... 46, 91
P
Intermittent duty cycle......................................................................... 7
Parameter number (PNU).................................................................. 57
Internal current control, VVC+ mode............................................ 21
PELV.................................................................................................... 51, 87
PELV, protective extra low voltage................................................. 41
J
Power cycle............................................................................................... 7
Jog......................................................................................................... 5, 67
Preset reference.................................................................................... 24
LCP.................................................................................................... 5, 7, 21 Protection................................................................................................ 41
M Q
Machinery Directive............................................................................... 8 Qualified personnel................................................................................ 9
Mains
AC mains............................................................................................. 15 R
Isolated mains................................................................................... 15 Rated motor current.............................................................................. 5
drop-out.............................................................................................. 46
Supply..................................................................................................... 7 Rated motor speed................................................................................. 6
Supply (L1/N, L2/L, L3)................................................................... 83 RCD............................................................................................................... 7
Supply data........................................................................................ 80
Read coil................................................................................................... 64
Mechanical holding brake................................................................. 42
Read holding registers (03 hex)....................................................... 65
Modbus communication................................................................... 54
Reference limit....................................................................................... 23
Modbus exception code.................................................................... 63
Registers................................................................................................... 64
Modbus RTU........................................................................................... 59
Relay output........................................................................................... 88
Modbus RTU commands................................................................... 64
Reset alarm............................................................................................. 21
Modbus RTU overview....................................................................... 59
RFI filter.................................................................................................... 15
Moment of inertia................................................................................ 46
Rise time.................................................................................................. 91
Motor
RS485
Cable..................................................................................................... 14
RS485............................................................................................. 53, 55
output.................................................................................................. 83
installation and set-up................................................................... 53
phase.................................................................................................... 46
thermal protection................................................................... 46, 69
voltage................................................................................................. 91 S
Motor-generated overvoltage.................................................... 46
Safety precautions.................................................................................. 9
Serial communication
N Serial communication................................................................ 6, 87
Network configuration....................................................................... 59 USB serial communication............................................................ 87
Short circuit............................................................................................ 46
SIL2............................................................................................................... 9
SILCL of SIL2.............................................................................................. 9
Slip compensation.................................................................................. 7
Special conditions................................................................................ 92
Speed PID......................................................................................... 18, 20
Speed PID control................................................................................. 28
Speed reference.................................................................................... 49
Standard and compliance for STO.................................................... 9
Static overload in VVC+ mode......................................................... 46
Status word............................................................................................. 68
Supply voltage....................................................................................... 87
Switching
frequency.............................................................................. 44, 45, 76
Switching on the output.................................................................... 46
Synchronous motor speed.................................................................. 6
T
Telegram length (LGE)......................................................................... 55
Terminal tightening torque.............................................................. 88
Thermistor.......................................................................................... 7, 51
Torque
characteristic..................................................................................... 83
control.................................................................................................. 18
Trip................................................................................................................ 8
V
Voltage level........................................................................................... 85
VVC+..................................................................................................... 8, 20
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MG07B302*