Compulsory Specification for

Circuit-breakers

Published by Government Notice No. R. 967 (Government Gazette 29265)


of 6 October 2006

ICS 29.120.50
VC 8036
Ed. 3
6 No. 29265 GOVERNMENT GAZETTE, 6 OCTOBER 2006

DEPARTMENT OF TRADE AND INDUSTRY

No. R. 967 6 October 2006

STANDARDS ACT, 1993

WITHDRAWAL AND REPLACEMENT OF THE COMPULSORY


SPECIFICATION FOR CIRCUIT BREAKERS

I, Mandisi Mpahlwa, Minister of Trade and Industry, hereby under Section


22(l)(a)(ii) of the Standards Act, 1993 (Act No. 29 of 1993), and on the
recommendation of the Council of the South African Bureau of Standards, withdraw
the compulsory specification for circuit breakers, and replace it with the compulsory
specification, as set out in the schedule, with effect from the date 2 months after the
date of publication of this notice.

M~ ~ q l w a
Minister of Trade and Industry
STAATSKOERANT, 6 OKTOBER 2006 No. 29265 7

SCHEDULE

Compulsory specification for circuit breakers

1 Scope

1.1 This specification covers circuit breakers with moulded cases the main contacts of
which are intended to be connected to circuits with rated voltages not exceeding 1000
V ac or 1500 V dc., rated currents not exceeding 125A and a rated ultimate short
circuit breaking capacity (L,) not exceeding 10 kA.

1.2 This specification does not cover circuit breakers incorporating residual current
protection (earth leakage protection).

2 Definition
For the purpose of this specification the following definition applies:

Circuit breaker: A mechanical switchng device, capable of making, carrying and


breaking currents under normal circuit conditions and also making, carrying for a
specified time, and breaking currents under specified abnormal circuit conditions such
as a short circuit or an earth fault.

3 Requirements

3.1 A circuit breaker shall be safe and shall function safely and correctly during
normal and abnormal circuit conditions.

Compliance with this requirement shall be proven by compliance with the


requirements of either:

3.2 SANS 556-1 Low-voltage switchgear, Part 1- Circuit breakers as published in


Government Notice 39 of 28 January 2005 (Government Gazette 27 179).

Or alternatively, for the period up to 5 years from the date of final publication of this
Compulsory Specification:

3.3 SANS 60947-2 I IEC 60947-2: 1995, Low-voltage switchgear and controlgear -
Part 2: Circuit-breakers, as published by Government Notice No. 41 1 of 27 March
1998, as modified in 3.4 and 3.5

3.3.1 The power-frequency recovery voltage, as given in 8.3.2.2.6 and 8.3.3.4 (table
13) of the said SABS IEC 60947-2:1995, for a circuit-breaker with a
maximum operational voltage of 2201380 V a.c. to 2401415 V a.c. (inclusive),
shall be 2521440 V a.c.
8 No. 29265 GOVERNMENT GAZETTE, 6 OCTOBER 2006

Table 11 - Values of power factors and time constants corresponding to test


currents

1 2 3 4 5 6 7

Time constant
Test current Power factor
I ms

kA
Short- Operadona1 Short- Operational
circuit performance Overload circuit performance Overload
capability capability

1 1 10 0,45 - 0,5 %a 0,45 - 0,5 5 2 2,s