Acmv - Symbols & Legend: For Tender

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

ISSUED:

FOR TENDER
ISSUED DATE:

ACMV - SYMBOLS & LEGEND


EQUIPMENT AIR SIDE
AIR SIDE ABBREVIATIONS

SYSTEM TYPE DESCRIPTION SYMBOL SYSTEM TYPE DESCRIPTION SYMBOL EAD EXHAUST AIR DUCT

FAD FRESH AIR DUCT


INDOOR UNIT CASSETTE TYPE RECTANGULAR AIRDUCT (A WIDE, B DEEP) AxB
SAD SUPPLY AIR DUCT

RAD RETURN AIR DUCT


INDOOR UNIT WALL MOUNTED TYPE AIR DUCT WITH INTERNAL ACOUSTIC LINNING EAG EXHAUST AIR GRILLE

EAL EXHAUST AIR LOUVER

INDOOR UNIT CEILING SUSPENDED TYPE RETURN AIR DUCT RAD FAG FRESH AIR GRILLE

FAL FRESH AIR LOUVER

TAG TRANSFER AIR GRILLE


SMALL CAPACITY OUTDOOR UNIT SUPPLY AIR DUCT SAD
VCD VOLUME CONTROL DAMPER

F.A. FRESH AIR


WALL MOUNTED EXHAUST AIR FAN FRESH AIR DUCT
FAD FD. FIRE DAMPER
NRD. NON-RETURN DAMPER 01 21.12.2015 ISSUED FOR TENDER
MIXED FLOW INLINE DUCT FAN EXHAUST AIR DUCT EAD S.S. STAINLESS STEEL 00 20.10.2015 FIRST ISSUE

E.A. EXHAUST AIR REV DATE DESCRIPTION


Flex.
WM WIRE MESH
CEILING MOUNTED EXHAUST AIR FAN FLEXIBLE DUCT
L/S AIR QUANTITY (LITRES/SECOND)
OWNER:

SU SPLIT TYPE AIR CONDITIONING UNIT


WALL MOUNTED PROPELLER FAN FLEXIBLE CONNECTOR
EAF EXHAUST AIR FAN

FAF FRESH AIR FAN


CEILING FAN, D1600 mm DUCT SET UP UP
KEAF KITCHEN EXHAUST AIR FAN

CF CEILING FAN

AXIAL FAN DUCT SET DOWN DN IDU INDOOR UNIT

ODU OUTDOOR UNIT


APPROVED BY:
VOLUME CONTROL DAMPER (OBD TYPE) GUIDE VANES T/A TO ABOVE
VCD
F/A FROM ABOVE

VOLUME CONTROL DAMPER (BLADE TYPE) SUPPLY DUCT SECTION UP/DOWN T/B TO BELOW
VCD
F/B FROM BELOW ENGINEERING DESIGNER:
FD T/F TO/FROM
RETURN DUCT SECTION UP/DOWN HASKONINGDHV VIETNAM CO., LTD.
FIRE DAMPER
A COMPANY OF
C/W COMPLETE WITH

NRD W/P WEATHERPROOF


NON-RETURN DAMPER EXHAUST DUCT SECTION UP/DOWN
AP ACCESS PANEL

SAD A/C ABOVE CEILING


CONTROL WIRING SUPPLY AIR DIFFUSER (4 WAY) 236/26C Dien Bien Phu Street
FFL FROM FLOOR LEVEL
Ward 17, Binh Thanh District
FGL FROM GROUND FLOOR LEVEL Ho Chi Minh City
Vietnam
RAG
POWER WIRING RETURN AIR GRILLE I.L INVERT LEVEL OF PIPE +84 8 3899 2505 Telephone
+84 8 3899 4469 Fax

EAG GENERAL NOTES: [email protected]


www.royalhaskoningdhv.com
E-mail
Internet
WIRELESS REMOTE CONTROLLER EXHAUST AIR GRILLE

1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.


EAL 2. DO NOT SCALE THE DRAWINGS. GENERAL DIRECTOR:
EXHAUST AIR LOUVER 3. ALL PENETRATIONS THROUGH PARTITION WALLS & FLOORS SHALL BE SEALED WITH MATERIAL OF THE SAME FIRE INTEGRITY.
LARS CROMBACH
WATER SIDE 4. FAN COIL UNIT SELECTIONS SHALL BE BASED ON MEDIUM FAN SPEED.
5. ALL DUCT DIMENSIONS ARE CLEAR INTERNAL DIMENSIONS. PROJECT MANAGER:
6. ALL SUPPLY AND EXHAUST AIR GRILLES SHALL BE COMPLETE WITH VOLUME CONTROL DAMPERS UNLESS OTHERWISE STATED.
ROOM THERMOSTAT T 7. UNLESS OTHERWISE INDICATED ALL DUCTWORK SHALL GENERALLY BE CLASSIFIED
JOOST JAN OOSTERHUIS
SYSTEM TYPE SYMBOL AS MEDIUM VELOCITY/PRESSURE DUCTWORK (FOR CONSTRUCTION AND TESTING PURPOSES). PRINCIPAL MEP:
8. ALL SUPPLY AIR DIFFUSER STATIC PRESSURE DROP SHALL NOT EXCEED 25 Pa. BUI DINH PHU
R 9. ALL EXTERNAL LOUVERS SHALL BE POWDER COATED AND C/W INSECT SCREEN AND SUBJECT TO PROJECT ENGINEERS' APPROVAL.
REFRIGERANT PIPE C/W INSULATION MANHOLE (REFERENCE DRAIN WATER SYSTEM)
10. ALL MV DUCT PASSING THROUGH STRUCTURAL SLAB/FIRE COMPARTMENT WALL SHALL PROVIDE WITH FIRE DAMPERS IN SLAB AND WALL. DESIGNER:
11. PROVIDE ACCESS PANEL DRAWINGS FOR THE SUPPLY AND INSTALLATION BY OTHERS WHERE SERVICES ARE CONCEALED AND WHERE ACCESS IS REQUIRED. TRAN DINH LONG
12. SOUND ISOLATOR FOR ALL VENTILATION FAN SHALL BE INTERNALLY LINED WITH 50mm 60Kg/m3 ROCKWOOL,
D BACKING FABRIC BATTS, WITH 45% OPEN AREA 0.7mm THICK GALVANISED PERFORATED SHEETS, LENGTH ARE 6M FRONT AND 6M BACK OF VENTILATION FAN.
CONDENSATE DRAIN PIPE C/W INSULATION
13. DESIGN DRAWING TO READ IN CONJUNCTION WITH THE DESIGN SPECIFICATION. PROJECT TITLE:

ANIMAL FEED MILL,


MYAUNG DAGAR IZ, MYANMAR
LOCATION: MYAUNG DAGAR INDUSTRIAL ZONE
MYANMAR

ITEM:

00-GENERAL
DRAWING TITLE:

ACMV SYSTEM
SYMBOLS & LEGEND

STAGE:

DETAILED DESIGN
PROJECT No.: DESIGN DISCIPLINE:

2V1836 MEP
SCALE: SHEET SIZE:

NTS [841x594] A1
DRAWING NUMBER: REVISION:

00-ACMV-001 01