This guide is intended to complement the user manual provided by the manufacturer.
It is provided as a basic introduction to the product for Inverter Drive Supermarket customers.
It should not be used as a replacement for the manual issued by the manufacturer.
This product is not a safety device. All safety considerations including but not
limited to Emergency Stop provision should be assessed separately and are
outside the scope of this guide.
Issue 1
20180621
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
Contents
Page 1 Contents
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 1
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
L1 L2 L3 (+) B U V W
Earth
Earth Phase (W)
Live (L1) Phase (V)
Neutral (L2) Phase (U)
Power Motor
Notes: Important:
The illustration above is based on the 0.75kW Use screened or armoured cable between the
230V model. The terminal layout for other Inverter and Motor and ensure it is grounded
ratings is similar. as shown.
The motor must be separately earthed.
The order of the three motor phases The supply must match the Inverter
determines the initial direction the motor turns. specification.
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 2
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
Notes:
Supply Motor
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 3
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
Screen
Earth
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 4
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
4. Parameters - overview
The Inverter contains a number of settings The parameters contain critical information
which can be changed to tailor it for use in a essential to the correct operation of the
wide range of applications. These settings are Inverter. Therefore, they should at least be
known as parameters. checked by the user before the Inverter is
operated for the first time.
Parameters are typically referred to by code or The parameters listed in section 5 are intended
number (eg. C1.07 = Rated Motor Current) to provide a starting point to allow for basic
with a description available in the manual. operation of the EFC 3610 Inverter.
b0.00 Access to additional parameters Default is 0 for Basic Parameters. Set to 2 to enable Advanced Parameters.
E0.08 Maximum output frequency (Hz) Maximum frequency of the Inverter. Default is 50.00; suitable for most applications.
E0.09 Output frequency high limit (Hz) Maximum frequency of speed reference (eg. keypad dial). Default is 50.00; suitable for most
applications. Cannot be higher than E0.08.
E0.10 Output frequency low limit (Hz) Default is 0.00; set to 05.00 for most applications .
E0.26 Acceleration time (s) Default is rating dependent; set to 5 for most applications.
E0.27 Deceleration time (s) Default is rating dependent; set to 5 for most applications.
C2.00 V/F curve mode Default is 0 (linear); set to 1 if the motor is driving a Fan or Centrifugal Pump.
C1.05 Rated motor power (kW) Set to match motor nameplate - eg. 0.8 (for 0.75kW)
C1.06 Rated motor voltage (V) Set to match motor nameplate - eg. 230
C1.07 Rated motor current (A) Set to match motor nameplate - eg. 3.34
C1.08 Rated motor frequency (Hz) Default is 50.00. Change to 60.00 for 60Hz motor only - otherwise set at 50.00
C1.09 Rated motor speed (rpm) Set to match motor nameplate - eg. 1380
C0.05 Carrier frequency (Hz) Default is rating dependent and will suit most applications.
Increasing Carrier frequency may reduce motor noise.
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 5
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 6
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
Press the green button firmly to start the motor. The motor
will accelerate to the speed set in 7.1 (above) in the time
defined by parameter E0.26. The display will increase from
0.00 to the speed reference.
The red button will stop the motor. The display will decrease
from the current speed to 0.00. When stopped, the “Run”
lamp will go out and the display will return to the speed
reference value.
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 7
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
b0.00 Access to additional parameters Default is 0 for Basic Parameters. Set to 2 to enable Advanced Parameters.
E0.00 Frequency Setting Source Default is 0 for keypad dial; set to 2 for terminal (remote) control via AI1.
E1.35 AI1 input mode Default is 2 for 0-10V; default is required for this example.
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 8
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
b0.00 Access to additional parameters Default is 0 for Basic Parameters. Set to 2 to enable Advanced Parameters.
E0.01 First run command source Default is 0 for keypad. Set to 1 for terminal control on the Inverter.
When set to 1, the FWD lamp will go out.
E1.00 X1 input Default is 35 for Forward Run; default is required for this example.
E1.01 X2 input Default is 36 for Reverse Run; default is required for this example.
E1.15 2-wire / 3-wire control mode Default is 0 for 2-wire forward / stop, reverse / stop; default is required for this example.
Switch, 3 Position
Normally Open
“Run Forward / Stop / Run Reverse”
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 9
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
b0.00 Access to additional parameters Default is 0 for Basic Parameters. Set to 2 to enable Advanced Parameters.
E0.01 First run command source Default is 0 for keypad. Set to 1 for terminal control on the Inverter
E1.00 X1 input Default is 35 for Forward Run; default is required for this example.
E1.01 X2 input Default is 36 for Reverse Run; default is required for this example.
E1.15 2-wire / 3-wire control mode Default is 0. Set to 1 for 2-wire forward / reverse, run / stop.
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 10
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
b0.00 Access to additional parameters Default is 0 for Basic Parameters. Set to 2 to enable Advanced Parameters.
E0.01 First run command source Default is 0 for keypad. Set to 1 for terminal control on the Inverter
E1.00 X1 input Default is 35 for Forward Run; default is required for this example.
E1.01 X2 input Default is 36 for Reverse Run; default is required for this example.
E1.02 X3 input Default is 0; set to 25 to select 3 wire control with reverse select
E1.15 2-wire / 3-wire control mode Default is 0. Set to 2 for 3-wire control mode. If the Inverter displays a PrSE error (conflict)
ensure that parameters E1.00 to E1.02 (see above) have been set first.
X1 X2 X3 SC 24V COM
11.2 Connecting the Switches
1 4 2 3 A wiring diagram is shown in the illustration
opposite. The SC and COM terminals must be
linked.
EFC 3610 Link
I/O Terminal cable For “Run” and “Stop”, two suitable
Blocks pushbuttons should be installed. The “Run”
pushbutton should include a Normally Open
contact between terminals X1 and X3 and the
“Stop” a Normally Closed contact between
terminals 24V and X3.
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 11
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
High inertia loads can cause overvoltage trips A Brake Resistor is first installed to absorb
during deceleration and lead to “OE-3" error braking energy and dissipate it as heat. The
messages. In many cases, the solution is to resistor must be correctly sized for both the
increase the deceleration time to compensate. Inverter and application.
However, if the application requires it, dynamic Then, the “brake chopper” within the Inverter is
braking can be enabled to maintain or reduce enabled. This detects excessive braking
deceleration times by absorbing the energy energy and redirects it to the resistor when
generated by such loads. required.
12.1 Relevant parameters for Dynamic Braking
Parameter Description How to set
b0.00 Access to additional parameters Default is 0 for Basic Parameters. Set to 2 to enable Advanced Parameters.
C0.25 Overvoltage prevention mode Default is 3 for Stall overvoltage protection enabled, resistor braking enabled; default is
required for this example.
Heat Resistant
Cable
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 12
Easy Start Guide
Bosch Rexroth EFC 3610 Series Inverter
Press the “Set” button to edit the value of b0.10 and use
the up button to change this from 0 to 1.
13.4 Finished
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright © The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission. Page 13