Air Flow Dynamics and Duct Sizing Reference Guide
Air Flow Dynamics and Duct Sizing Reference Guide
Air Flow Dynamics and Duct Sizing Reference Guide
RE FE R E NCE GUIDE
SUPPLY OR RETURN DUCT SIZE/CAPACITY
PROC E S S (.09 to .10 pressure drop per 100’ EL)
Residential Design Process CFM Round Rectangular (TD)
(No. SL)
Load Calcuation 50 5” 8x6
(Heating & Cooling) ACCA Manual J 75 5” 8x6
100 6” 8x6 3½ x 10 (110)
Air Distribution ACCA Manual T
125 6” 8x6 3½ x 12 (140)
Air Flow, Equipment ACCA Manual S 150 7” 8x6 3½ x 14 (160)
Selection, Components and
Assemblies 175 7” 8x6
200 7” 8x6
Duct Size Calculation ACCA Manual D 250 8” 6 x 10 8x8 6 x 12
300 9” 6 x 10 8x8 6 x 12
Adjust, Test, Balance ACCA Residential Duct 350 9” 6 x 10 8x8 6 x 12
Diagnostic & Repair
400 9” 8 x 10 8x8 6 x 12
EQU I VA L ENT L EN G T H S 500 10” 10 x 10 12 x 8 8 x 12
P L EN U M/ DU C T F I T T IN G S 600 12” 10 x 10 12 x 8 8 x 12
35 -44 .13 .15 .20 .25 .32 .35 .40 .45 .50 .63 .75 .85 .95 1.00 1.25 1.50 1.90 2.54
45- 54 .10 .12 .16 .20 .25 .28 .32 .36 .40 .50 .60 .68 .76 .80 1.00 1.26 1.52 2.02
55 - 64 .08 .10 .13 .17 .21 .23 .27 .30 .33 .42 .50 .57 .63 .67 .83 1.05 1.26 1.68
65 - 74 .07 .09 .11 .14 .18 .20 .23 .26 .29 .36 .43 .49 .54 .57 .72 .90 1.08 1.44
75 - 84 .06 .08 .10 .13 .16 .18 .20 .23 .25 .31 .38 .43 .47 .50 .63 .79 .94 1.26
85 - 94 .06 .07 .09 .11 .14 .16 .18 .20 .22 .28 .33 .38 .42 .45 .56 .70 .84 1.12
95 - 104 .05 .06 .08 .10 .13 .14 .16 .18 .20 .25 .30 .33 .38 .40 .50 .63 .75 1.01
105 - 114 .05 .05 .07 .09 .11 .13 .15 .16 .18 .23 .28 .31 .34 .37 .47 .57 .69 .91
115 - 129 .04 .05 .07 .08 .10 .12 .13 .15 .17 .21 .25 .28 .31 .33 .46 .51 .62 .82
130 - 149 .04 .04 .06 .07 .09 .10 .11 .13 .14 .18 .21 .24 .27 .29 .36 .45 .54 .72
150 - 169 .03 .04 .05 .06 .08 .09 .10 .11 .13 .16 .19 .21 .24 .25 .31 .39 .47 .63
170 - 189 .03 .03 .04 .06 .07 .08 .09 .10 .11 .14 .17 .19 .21 .22 .28 .35 .42 .56
190 - 214 .03 .03 .04 .05 .06 .07 .08 .09 .10 .13 .15 .17 .19 .20 .25 .31 .37 .50
215 - 239 .02 .03 .04 .05 .05 .06 .07 .08 .09 .11 .13 .15 .17 .18 .22 .28 .33 .44
240 - 264 .02 .02 .03 .04 .05 .06 .06 .07 .08 .10 .12 .14 .15 .16 .20 .25 .30 .40
265 - 289 .02 .02 .03 .04 .04 .05 .06 .07 .07 .09 .11 .12 .14 .15 .18 .23 .27 .36
290 - 324 .02 .02 .03 .03 .04 .05 .05 .06 .07 .08 .10 .11 .12 .13 .17 .20 .24 .33
325 - 374 .02 .02 .02 .03 .04 .04 .05 .05 .06 .07 .09 .10 .11 .11 .14 .18 .21 .29
375 - 424 .01 .02 .02 .03 .03. .04 .04 .05 .05 .06 .08 .09 .09 .10 .13 .16 .19 .25
425 - 474 .01 .01 .02 .03 .03 .03 .04 .04 .05 .06 .07 .08 .08 .09 .11 .14 .17 .22
475 - 524 .01 .01 .02 .02 .03 .03 .03 .04 .04 .05 .06 .07 .08 .08 .10 .13 .15 .20
525 - 574 .01 .01 .02 .02 .02 .03 .03 .03 .04 .05 .06 .07 .07 .07 .09 .11 .14 .18
575 - 625 .01 .01 .01 .02 .02 .02 .03 .03 .03 .04 .05 .06 .06 .07 .08 .10 .13 .17
FORM U L A S
Sensible Heat Formula Altitude Correction Friction Rate
Factor (ACF)
0 ft 1.0 5000 ft .826
*used in duct calculators
BTU/Hour = CFM x TD x 1.08 500 ft .981 6000 ft .801
Pressure Drop x 100
1000 ft .962 7000 ft .772 Friction Rate =
BTU/Hour TEL
CFM = 2000 ft .926 8000 ft .749
1.08 x TD x ACF 3000 ft .891 9000 ft .715
Pressure Drop is the available static pressure
4000 ft .858 10000 ft .687
1.08 is a conversion factor (ASP) allocated to the duct work.
TD is the Temperature Difference created by the appliance
ACF is the Altitude Correction Factor (see above table) ASP = Blower Static Pressure - Component
Pressure Drops
Sensible Heat Ratio = Sensible Load
Sensitive Load + Latent Load
TEL is the Total Effective Length of the longest
SHR below .80 = 21º TD High humidity = 350 CFM/ton supply run and the longest return run.
SHR .80 to .85 = 19º TD Ave. humidity = 400 CFM/ton
SHR above .85 = 17º TD Low humidity = 450 CFM/ton CFM Calculations
Southwark Metal Mfg Co. • Philadelphia, PA • Piedmont, SC • Indianapolis, IN • Southaven, MS • Fremont, NE • Caldwell, ID
Corporate Headquarters: 2800 Red Lion Road, Philadelphia PA 19114 • 800-523-1052 • fax 800-722-2076 • www.southwarkmetal.com