General
The DAA2 Series amplifiers are multi-featured amplifiers with
digital audio functionality. Each DAA2 is capable of accessing
and processing one of up to eight audio channels on the DVC
audio loop, amplifying the signal, and distributing it via four
Class B or two Class A outputs. A DAA2-50 or DAA2-75
series amplifier is capable of mounting an optional BDA Digi-
tal amplifier, which can be used to provide one-to-one ampli-
fier backup, or to support two-channel operation, or
increased output wattage to 100W (100W option applies to
DAA2-50 series only, other rules apply).
The DAA2 has two wire digital audio ports to connect to wire
DAL (digital audio loop) segments. Either or both ports may
be converted to fiber using fiber option modules. • Auxiliary input for 1 VRMS, to be used for background
music input, an interface with a telephone paging source,
Up to 32 devices, such as DAA2 amplifiers, can be con- or other compatible audio sources. Audio levels can be
nected to the DAL on one DVC Digital Voice Command unit. adjusted by end user. Optional supervision through pro-
DAA2 amplifiers may be mixed with DAX and DAA series gramming.
amplifiers on the same DAL.
• Isolated alarm bus input, to be used for backup activation
An optional Firefighter telephone riser on the DAA2 supports of alarm messages when normal digital communication is
local and network FFT communications. A DAA2 also sup- lost.
ports use of an RM-1 remote microphone. • Programmable through VeriFire® Tools.
DAA2 amplifiers can store backup alarm and trouble mes- • Up to 106 seconds of backup digital message storage for
sages, and provide an adjustable background music input. use in the event of communication loss (from the Veri-
Fire® Tools message library, or created by the installer).
Features • Battery charger disable provides battery sharing option for
• Listed to UL Standard 864, 9th edition. up to four DAA2s.
• 50 W total output power at 25 VRMS (all DAA2-5025 mod- • Disconnect of deeply-discharged battery (low battery dis-
els) or 70 VRMS (all DAA2-5070 models). connect).
• 75 W total output power at 25 VRMS (all DAA2-7525 mod-
els). Installation
• Supports two Class A high-level audio outputs; or four The DAA2 arrives from the factory already installed on its
Class B outputs. chassis. The DAA2 mounts in one row of any EQ or CAB-4
Series cabinet: The CAB-4 row can be covered using a DP-
• Optional BDA amplifiers support alternative configura-
1B dress panel, ordered separately.
tions.
• Backup amplifier - supports one-to-one backup (all One or two fiber option modules will plug directly onto a
DAA2 models). DAA2 for simple installation. A BDA backup amplifier mounts
directly onto a DAA2.
• Primary amplifier - supports two-channel operation (all
DAA2 models). Batteries for the DAA2 may be installed in any of the following
• Primary amplifier - increase power up to 100W, one- or configurations:
two-channel operation. (DAA2-50 series only, configura- • In a CHS-BH1 optional battery chassis. The CHS-BH1
tion rules apply.) battery chassis will hold two 12.0 AH batteries, and
• Supports one-to-many amplifier backup applications using mounts on the left side of the DAA2 chassis, so that the
the same model DAA2. DAA2 and batteries are contained in a single cabinet tier.
• Firefighter telephone riser supports 7 active firefighter • In the battery row (bottom) of the CAB-4 Series cabinet, or
telephones. System Release 3.0 and higher supports in the bottom row of an EQ Series cabinet.
optional configurations: direct connection for up to 7 fire- • In a cabinet adjacent to the cabinet that holds the DAA2,
fighter telephones, or connection to multiple FTM-1 mod- with connections in conduit. External battery charging is
ules. supported.
• Remote microphone paging option with RM-1.
• Audio output activation via network control-by-event equa-
tions resident within the DVC.
• Two wire digital audio ports that can be converted to fiber
using fiber option modules. Support Style 4 or 7 configura-
tions.

DN-60556:C • 7/19/17 — Page 1 of 4


Specifications ohm 1/2 watt resistor (P/N R-3.9K). Max. wiring resistance
(including individual telephone zone to last handset) permit-
CPS-24 POWER SUPPLY BOARD ted is 50 ohms, 10,000 ft (3048 m) max. wiring distance at 14
AC power (TB1) AWG to last handset.
• Models using 120 VAC, 60 Hz input: Auxiliary Input: Signal strength from low-level analog audio
input (such as background music or telephone paging): 1Vp-p
– DAA2-5025 - 4.68A max.
max. Optional supervision through programming. Recom-
– DAA2-5070 - 4.69A max. mended wiring: 14-18 AWG, twisted-pair. Auxiliary input
– DAA2-7525 - 4.68A max. source must be within 25 ft. (7.6 m) of the DAA2, and within
• “E” version models using 220-240 VAC 60 Hz input: the same room.
– DAA2-5025E - 2.68A max. Speaker circuits: Power-limited outputs (exception: a DAA2-
5070 speaker circuit used with any Canadian Room Isolator
– DAA2-5070E - 2.68A max.
module is non-power limited. Speaker circuit 1 (TB10) can
– DAA2-7525E - 2.68A max. not be used.). Supervision determined by programming.
Recommended wiring: 12 to 14 AWG (1.6 mm O.D.) with DAA2-5025/70, Each circuit rated up to 50 watts*. DAA2-
600 VAC insulation. 7525, each circuit rated up to 75 watts*. Recommended wir-
ing: 12-18 AWG twisted-pair (shielded recommended). Class
Shipping Weight: 13 lb (5.9 kg). B or Class A: Class B requires 20k end-of-line resistors
Secondary Power 5V and 24V AUX Outputs (TB2): (included, P/N ELR-20K). Class A requires 10k end-of-line
24 V AUX: Power-limited, 24V @ 0.5A, utilizes wire sizes 12- resistors (included, P/N R-10K) on the return.
18 AWG (3.31 mm2 - 2.08 mm2. *total wattage may vary per configuration.
5 V: Future Use. Backup: High-level audio input: 25VRMS (DAA2-5025 and
Battery Connections: Supplied cable connections to batter- DAA2-7525). 70 VRMS (DAA2-5070). Recommended wiring:
ies. 14-18 AWG. Not supervised when inactive. Supervised by
backup source when active. Must be in same room or enclo-
Battery Charger: Current-limited sealed lead acid battery sure.
charger which charges two 12 volt batteries in series, up to
200 AH.
Standards and Codes
Charge Charge Charge The DAA2 Series Digital Audio Amplifiers comply with the fol-
7 AH to 26 AH to 50 AH to lowing standards:
26 AH < 50 AH 200 AH
Batteries Batteries Batteries • NFPA 72 2007 National Fire Alarm Code
DAA2-5025 • Underwriter Laboratories Standard UL 864
Yes Yes Yes
DAA2-5070 • Underwriter Laboratories of Canada (ULC) ULC-S527-11
DAA2-7525 Yes Yes No Standard of Control Units for Fire Alarm Systems.
DAA2-5025 or
• Part 15 Class A conducted and radiated emissions as
DAA-5070 w/BDA required by the FCC.
No No No
in Group 2 of • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000
VeriFire® Tools (Seismic).
• CBC 2007 (Seismic)
Table 1: Battery Charging Capabilities
DAA2 BOARDS Listings and Approvals
Digital Audio Ports, wire media, A and B (TB2, TB3): Max- These listings and approvals apply to the basic DAA2 Series
imum distance per segment is 1900 feet (579.12 m) on Digital Audio Amplifiers. In some cases, certain modules may
Belden 5320UJ (18AWG, TP) FPL cable: 18 AWG (0.821 not be listed by certain agencies, or listing may be in process.
mm2) twisted-pair, unshielded, power-limited. For approved Consult factory for latest listing status.
cable types, see wiring documentation, P/N 52916ADD: C
• UL Listed: S635.
Approved Wire Cables for Digital Audio Loops.
• ULC Listed: S635.
Digital Audio Ports, fiber media, fiber option modules:
Digital audio loop connectors support single- and multi-mode • CSFM: 7165-0028:0243 (NFS2-640/NFS-320), 7165-
fiber with the use of fiber option modules. Refer to the Fiber 0028:0224 (NFS2-3030).
Option Module datasheet for fiber specifications. • Fire Dept. of New York: COA#6212 (NFS2-640/NFS-320),
COA#6211 (NFS2-3030).
Alarm Bus: Power-limited, supervised by source. Recom-
mended wiring: 14-18 AWG twisted-pair. Requires 16VDC • FM approved.
minimum @ 20mA across the terminals to activate. Nominal
24VDC. Product Line Information
Remote Microphone Interface: RMI power: +24VDC, 50 WATT DAA2 AMPLIFIERS
power-limited @ 100mA. Supervised. Recommended wiring:
Shipped mounted to the chassis.
14-18 AWG twisted-pair, Max. 14 AWG. Nominal AC signal
strength 2.5VRMS, 3VRMS Max. Maximum distance between DAA2-5025: 120 VAC Digital Audio Amplifier (50 W, 25
remote microphone and DAA2: 100 ft (304.8 m). VRMS).
FFT Riser: Power-limited output, supervised. Class A or DAA2-5070: 120 VAC Digital Audio Amplifier (50 W, 70
Class B operation. Class B 2-wire connections require a 3.9k VRMS).

Page 2 of 4 — DN-60556:C • 7/19/17


DAA2-5025E: 220-240 VAC Digital Audio Amplifier (50 W,
25 VRMS).
DAA2-5070E: 220-240 VAC Digital Audio Amplifier (50 W,
70 VRMS).
75 WATT DAA2 AMPLIFIERS
Shipped mounted to the chassis.
DAA2-7525: 120 VAC Digital Audio Amplifier (75 W, 25
VRMS).
DAA2-7525E: 220-240 VAC Digital Audio Amplifier (75 W,
25 VRMS).
BDA BACKUP DIGITAL AMPLIFIERS
BDA-25V: Backup Digital Amplifier (25 VRMS), switch set-
tings for 75, 50, and 35 W operation. Provides a second
audio channel when programmed as a primary amplifier.
BDA-70V: Backup Digital Amplifier (70 VRMS), switch set-
tings for 50 and 35 W operation. Provides a second audio
channel when programmed as a primary amplifier.
FIBER OPTION MODULES
DS-FM: Fiber option module for multi-mode fiber. Converts a
wire DAP (digital audio port) to a multi-mode fiber port.
DS-SFM: Fiber option module for single-mode fiber. Con-
verts a wire DAP (digital audio port) to a single-mode fiber
port.
DS-RFM: Fiber option module for multi-mode fiber. Used
exclusively for compatibility with multi-mode fiber DVC or
DAA.
ACCESSORIES
CHS-BH1: Battery chassis. Holds two 12.0 AH batteries.
Mounts on the left side of the DAA2 chassis.
DP-1B: Dress panel: covers one tier of CAB-4 Series cabi-
net.
ACT-25, ACT-70: Audio-coupling transformers. Used with
AA-30 or DAA2-series amplifiers to drive thousands of ampli-
fiers in large system applications.
SEISKIT-DAA: Seismic kit for DAA, DAA2, and DAX series
amplifiers. Required when using CHS-BH1 chassis. Includes
battery bracket for two 12AH Power Sonic batteries. See doc-
ument 53851.

DN-60556:C • 7/19/17 — Page 3 of 4


NOTIFIER® and VeriFire® Tools are registered trademarks of Honeywell
International Inc.
©2017 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Country of Origin: USA.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

Page 4 of 4 — DN-60556:C • 7/19/17

You might also like