VRF Catalog 2017-02-08
VRF Catalog 2017-02-08
VRF Catalog 2017-02-08
E-mail: [email protected]
Website: www.ticachina.com
TICA Inverter VRF System
DIRECTORY
%*3&$503:
RICH PRODUCT
PRODUCT LINEUP
LINEUP 5 1
FEATURESUNITS FEATURES 7
OUTDOOR 3
TICA is a hi-tech enterprise specialized in R&D, manufacturing, sales and INTELLIGENT CONTROL 37
services of air-conditioning and refrigeration products. Established in 1991, it has
developed into one of the top four Chinese air-conditioning brands, with factories in CLEANING TECHNOLOGY 43
Nanjing, Tianjin and Guangzhou,and a network of over 70 sales and service filiales
around the world.
TICA has invested up to RMB 600 million in the first phase to build the top
notchcentral air-conditioning R&D and production base,credited as the state Nanjing ࢄϙᕨ䘕ധౝ
Headquarter
enterprise R&D center. Certified by CNAS, it serves as a national R&D public service
platform.
TICA produces over 30 series of products,covering AHUs, VRFs, screw chillers
and centrifugal chillers,diverse enough to meet various requirements with regards to
comfort andmanufacturing processing application.
TICA is a strong competitor in chillers and commercial air conditioning products.
It is the largest producer of AHUs in China for five consecutive years and covers over
40% of the market share as the supplier to such industries as micro-electronics, Tianjin
๖≒ധౝ Base
surgery operation room equipment and biopharmaceuticals.
TICA has established a global strategic joint venture with United Technologies
Corporation (UTC) whose businesses include the world’s most advanced Pratt &
Whitney Aircraft Engines, the largest air-conditioning company Carrier and the
biggest elevator company Otis.
The giant UTC transfers such global cutting-edge core technologies as large
centrifugal chillers, screw chillers, and ORC systems to TICA, thrusting TICA 20 years Guangzhou
Ꭼጋധౝ Base
ahead of its Chinese counterparts in terms of centrifuge technology and 30 years ahead in cryogenic power generation
technology. Meanwhile, TICA and UTC will integrate global resources to create a brand-new international market pattern.
Meanwhile, the company has also provided energy-saving air-conditioning system integration solutions to both domestic
and foreign users like Zhongnanhai, the Great Hall of the People, Beijing Bird’s Nest stadium, the Water Cube, the
Wukesong Indoor Stadium, Petro China, Sinopec, State Grid, Nanjing Panda, Hangzhou Xiaoshan Airport, Hainan Airlines
Group, Shangri-La Hotel, Manila Ocean Park, Abu Dhabi Al Muneera, SM City in Philippines and Unilever, etc.
Product Lineup
TIMS100AX
TIM ●
Four way
Round Flow
TMCF cassette
cassette ● ● ●●●●●●●●●●●●
TIMS120AX
TIM
● TMCS
One way
cassette ● ● ● ● ●
● ● ● ● ●
TIMS140AX
TIM ● TMCD
Two way
cassette ● ● ● ● ●●●●●●● ● ● ●
TIMS160AX
TIM ● TMDN- Slim
Slim duct
Low
AC ESP duct ●●●●●●●●●●●
● ● ● ● ● ● ● ● ● ● ●
TIMS180AX
TIM ● TMDN- Low ESP
AB duct ● ● ● ● ●● ● ● ● ● ● ●● ● ● ● ● ●
TIM
TIMS200AX ●
TIM
TIMS220AX ●
TMDH- High
A ESP duct ●●●●
● ● ● ●
● ● ● ● ● ●●●
Ceiling
Floor &
TIM
TIMS240AX
● ● TMVX Floor
ceiling
● ● ● ● ● ● ● ●
TIMS260AX
● ●
TMVW
Wall-
mounted ● ●●
● ● ● ●●● ● ● ●
● ● ● ● ●●
Big
●●
●●
TMDH- Capacity
Big duct ●
T
TIMS280AX AI duct
T
TIMS300AX ● ● Fresh air
Fresh air
TMDF handling
processor ● ● ● ● ● ● ● ●
● ●
unit
TIMS320AX
T
TIMS340AX
T ● ● AHU Box
T
TIMS360AX ● ● Internal volume of heat
● ●
Model Setting cooling capacity (HP) Indoor unit capacity (kW) reference air
Reference volume (m3/h)
air volume (m3/h) Pictre
Picture
exchanger (dm3)
T
TIMS380AX
8 20~25 3.6855~4.6069 3000
TMDK280
T
TIMS400AX ●●
●● 10
12
25~30
30~36
4.6069~5.5283
5.5283~6.6430
3700
4500
T
TIMS420AX ● ● TMDK450 14
16
36~40
40~45
6.6430~7.3711
7.3711~8.2925
5400
6000
TIMS440AX ●●
●● Basic Modules
TIMS460AX ● ●●
●
TIMS480AX
●●●
●●● TIMS-X
Combination
● ● ●
modules
TIM
TIMS500AX
TIMS520AX
TIM ● ● ● Model TIMS-AX
HP
TIMS080AX
8
TIMS100AX
10
TIMS120AX
12
TIMS140AX
14
TIMS160AX
16
TIMS180AX
18
TIMS200AX
20
TIMS220AX
22
Power type 208-230V 380-415V
●●
● ●
Capacity
KW 28.1 35.2 42.2 49.2 56.3 63.3 70.3 77.4 50Hz/3N / Available
TIMS540AX
TIM
T
Compressor DC DC DC DC DC DC+DC DC+DC DC+DC
● ● ●
60Hz/3N / Available
Fan motor DC DC DC DC DC DC+DC DC+DC DC+DC
TIM
T
TIMS560AX
TIM
T
TIMS580AX
● ●●
●
TIM
T
TIMS600AX
● ●●
●● TIMS-S
Independent
●● ●
●
modules
TIMS620AX
TIM
T
TIM
T
TIMS640AX ● ●●
●● Model
TIMS-
AS
TIM-
S080AS
TIM-
S100AS
TIM-
S120AS
TIM-
S140AS
TIM-
S160AS
TIM-
S180AS
TIM-
S200AS
TIM-
S220AS
TIM-
S260AS
TIM-
S280AS
TIM-
S300AS
TIM-
S320AS Power type 208-230V 380-415V
●●●
●
HP 8 10 12 14 16 18 20 22 26 28 30 32
TIM
T
TIMS660AX Capacity
KW 28.1 35.2 42.2 49.2 56.3 63.3 70.3 77.4 91.4 98.5 105.5 112.5 50Hz/3N / Available
5 6
TIMS-X TIMS-S
High Efficiency
Catering to the global low-carbon trend, TICA launches a new
product - TIMS DC Inverter Multi System central air-conditioning unit.
It comes from multiple energy-saving technologies and is featured in
the advanced energy-saving performance.
ODU units
TIMS-X TIMS-S
1. All DC Inverter Compressors
The TIMS adopts the high-efficiency DC inverter scroll compressor with high-pressure chamber, which adopts asymmetric
scroll design and high-efficiency internal oil separator. By integrating with the enhanced vapor injection technique, the TIMS
can realize the heating under low ambient temperature in winter, and save more energy. The kind of system can run more
stably and reliably.
High Reliability 11
The high-pressure chamber scroll compressor takes advantage of the inherent differential pressure to supply
Convenient Application 16 lubricant, and the lubricant supply is not affected by the rotational speed. Moreover it has long service life and good
stability.
The refrigerant goes into the scroll of the compressor directly, it has less suction gas superheat and high volumetric
Widely Application Range 19 Advantages of efficiency.
high-pressure The high-pressure chamber compressor uses its discharging gas to cool motor, which can not only guarantee the
chamber scroll lubricant temperature when the motor runs at the low temperature, but also provide good control on low temperature.
ODU Specifications 20 compressor When TIMS operates in heating mode, the high compression ratio guarantees the high discharge pressure, improves
supply air temperature and heating efficiency.
The high-pressure chamber compressor has low noise and good noise reduction result.
The new refrigerant cycle design makes the electric motor have the best cooling, lower the operating temperature,
and further improves the motor efficiency.
7 8
2. 180° Sine Wave Control Technology
TIMS-X TIMS-S
Hydrophilic aluminum fin
The outdoor unit adopts the louver-type aluminum Corrosion-resistant coating Fin Hydrophilic coating
Non sensor control technology of permanent magnet synchronous motor makes output current of DC converter sine wave, foil with the hydrophilic coating, which can efficiently
which guarantee stability, reduce vibration prevent from electromagnetic interference to improve running efficiency prevent dirt accumulation, improve defrosting efficiency
and enhance the heat exchange efficiency.
Current The specially designed 2-in-1 refrigerant loop Gaseous refrigerant Liquid refrigerant
Current
can increase the liquid refrigerant volume and
Sine Wave comprehensive heat exchange coefficient, making Gaseous refrigerant
Rectangular
Pressure
Wave Time Pressure Time refrigerant heat exchange more sufficient and system Gaseous refrigerant Liquid refrigerant
ODU units
more optimized.
Traditional Control 180° Sine Wave DC Drive Gaseous refrigerant
TIMS-X TIMS-S
3. All DC Fan Motors
TIMS-X TIMS-S
5. Sub-cooling Design
The new DC inverter fan motor allows to make the five-stage speed regulation and adjust the speed according to the
change in the system operation, and finally guarantees the system runs under the best condition. By matching the air flow
The unique sub-cooling design enhances the cooling capacity, heating capacity, cooling efficiency ratio (EER) and heating
changes and variable refrigerant flow also the heat exchanging demand, the system operates in high efficiency and low
efficiency ratio (COP).
operating noise.
TIMS-X TIMS-S
4. High Efficiency Heat Exchanger
TIMS-X TIMS-S
6. Large Capacity Compressor Design
The outdoor heat exchanger adopts the high-efficiency internal thread copper pipe with the diameter of 7.0 and the new
aluminium fin; its integal molding technology guarantees the larger heat exchange area, improves the air flow distribution,
reduces the airflow resistance, exchanges the heat more efficiently, and reduces the impact of the frosting on the heating Less compressor configuration improves the system stability.
capacity of the system. The heating capacity is more powerful under low temperature,
the exhaust volume and heating capacity are further improved for
Refrigerant circuit of TOD the large capacity compressor configuration under the equivalent
frequency.
The specially designed TOD circuition increase the
liquid refrigerant volume, improves and optimizes the
heat exchange efficiency of the refrigerant.
TIMS-X TIMS-S
7. Stereo Air Inlet Technology of Four Directions
9 10
TIMS-X TIMS-S
2. Ten Major Ultra Quiet Technologies
The TIMS series adopt the omni-directional noise reduction technology and spiral flow fan blade to ensure a smooth suction
High Reliability
structure and reduce the air flow noise. Supplemented with the sound insulation design of compressor, the unit can realize
ultra quiet operation and create a comfortable environment of high quality.
TIMS-X TIMS-S
1. Six-fold Oil Return Control Technology
By virtue of the solid R&D strength, TICA central air conditioning system integrates the advanced VRF technology process
of Japanese expert team, and the full series of VRF units adopt the six-level oil control technology to make operation more The fan motor support employs
stable and reliable. a non-resonant hanger structure Vortex fan blade: The CAE auxiliary
to ensure stable operation design and CFD air flow analysis
Internal Oil Separation Technology of Compressor performance of the motor and technology are used to optimize the fan
Oil Separation Technology of Oil Balancing Pipe
reduce the vibration noise. design, not only lowering the vibration, but
After realizing lubrication in the compressor, only a for Compressor also greatly reducing the pressure loss.
little lubricating oil enters the system together with The oil balancing pipe for compressor is used to provide
the exhausted air. This effectively prevents excessive excessive lubricating oil in the oil pool to the compressor
refrigeration oil from staying in the refrigeration cycle with insufficient oil in the oil pool in the module, ensuring
pipeline, thus ensuring the oil amount required for the lubrication effect of all the compressors.
normal operation of the compressor.
The brushless DC motor is adopted to
The air streamlined fan grille implement stepless speed regulation and more
promotes more smooth discharge stable operation, reducing noises as ensuring
of vortex air flow and reduces the energy conservation and high efficiency.
pressure loss.
Current
The system can control and regulate the oil amount in No oil balancing pipe is needed between ODU modules.
the oil pools of different compressors between ODUs to This reduces pipeline leak points, improves the oil Night Silent Mode
balance oil return between all the modules. return stability and efficiency and makes installation The system adopts the delay judgment mode based on the outdoor Outdoor temperature peak Night mode
convenient. ambient temperature peak. Meanwhile, it will automatically judge
The system automatically determines the proper oil discharge amount according
to the oil amount of compressor, preventing oil leakage of the compressor and whether to start the night silent operation mode according to the ODU
improving reliability. When the oil level reach a fixed height, the refrigeration oil ambient temperature and the current load size.
back to the compressor will be discharged from to the compressor automatically.
Exhaust
Liquid pipe
For the site with a higher silent requirement, the user can select the Night mode started
Air pipe
forced silent operation mode as actually needed to reduce the operation
Return oil rate
When the oil level reach a fixed height, the refrigeration Oil balancing
noise of the unit and create a more quiet and comfortable environment.
oil back to the compressor will be discharged from to the pipe not needed
compressor automatically.
11 12
TIMS-X TIMS-S
Small Room Temperature Fluctuation and High Precision
3. Efficient Heating and Smart Defrosing
The DC inverter control technology is adopted to reach the Temperature
Room temperature ±2°C of household air conditioning system
Room temperature ±3°C of TIMS air conditioning system
TCC (TICA Comfortable Control) defrosting technology (patent No.: CN201320402500.9/ CN201320344961.5) set temperature rapidly when the unit starts, fine regulation Room temperature ±3°C of TIMS air conditioning system
Automatic Addressing
With the partial load, the TIMS system will detect the defrosting time Heat Exchanger Frosting
Heat Exchange amount of Indoor Unit Q All the control boards adopt the SMT surface sealing technology,
according to the heat exchange efficiency of the outdoor unit. Time
and sealing material is added to the control board surface to
improve the anti-clutter interference performance of control board,
prevent the control board from being affected by wind, sand and
Bottom Frosting Prevention Design during Heating humid environment, and prolong the service life.
The system employs the unique bottom frosting prevention design during
heating to ensure that the ice water mixture is completely exhausted
from the unit bottom during heating defrosting in winter, and avoid TIMS-X TIMS-S
decrease of the heating capacity caused by frosting at the unit bottom. 5. Stable Operation Functions
Anti snow capacity In case of an unexpected power failure, the system automatically stores the set memory. When power is restored, the system
can restart automatically (manual startup can also be set), and the setting before the power failure will not be canceled but will
When it snows heavily in winter, the TIMS unit will give priority to start continue to take effect. The program does not need to be reset, so service becomes more intelligent and considerate.
the outdoor fan motor before user starts the outdoor unit; such design Setting before power failure starts automatically after the power supply is connected Memory storage function before power failure
prevents the unit from being covered by the snow. Once the unit works
normally, the fan will run normally. Connect the power Memory storage
supply restarted before the
automatically power supply
TIMS-X TIMS-S
4. Automatic Detection and Regulation Technologies Dual-rotation Operation Function
To ensure operation time balance between compressors and modules, TIMS can implement cyclic operation of all the
Control Technology of Multiple Electronic Expansion Valves
compressors and modules to average the operation time of each compressor and each module effectively, enhance
durability of the entire unit or system, and prolong the service life.
A single ODU module is provided with multiple electronic The first phase The second phase The third phase
expansion valves. Every electronic expansion valve can
implement 480-step refrigerant flow regulation, control the
refrigerant circulation quantity and meet the actual IDU
requirement accurately, thus creating a more comfortable Rotation Rotation
13 14
Three-backup Operation Function
For single-module ODU, If one compressor or motor malfunctions or is being maintained, other compressors and motors
can be urgently put to use. For multi-module ODU, if one module is being maintained, the other modules can also be
urgently put to use, without affecting usability.
Alarm
Convenient
Convenient
Application
Alarm
Operation
TIMS-X TIMS-S
When detecting a pipeline exception (too much or too little refrigerant, etc.)
through real-time monitoring, the system can start pipeline exception protection Compact, Easy to Transport and Handle 360° Outlet Pipe Connection
immediately to avoid further losses.
The modular combination requires less floor space, During construction, the refrigerant pipe can be
Anti-Reverse-Rotation Protection even the largest module occupies only an area of connected to the unit front, left or right freely, reducing
1.07 m2, and seamless assembling between modules the construction cost and construction difficulty and
In case of reverse rotation of ODU fan, the system will stop the fan first upon promotes further space savings. facilitating engineering design and installation.
air conditioner startup, and then make it rotate in the correct direction of
rotation as programmed, preventing the fan blade from being damaged.
Occupied area
1.07 m2
case of any exception such as phase sequence error or over-current protection, compressor anti-liquid hammer systems, maintenance by designated person is
a must.
phase loss, the controller will record the power supply protection, etc.
failure and report an alarm for shutdown. Automated Diagnosis and Self Repair of Faults
Inverter EMI Protection and Temperature
Power High/Low Voltage and Current Protection The unique automatic fault diagnosis function can be
used to get the fault information easily and realize self
Protection Function The system adopts the inverter of upgraded control repair of some faults, enhancing the operation stability A fault occurs
The ODU can identify the power supply signal directly. accuracy, which can suppress harmonic current well and and reliability.
In case of inadequate power supply ( insufficient or features high degree of EMI protection. When the system
too much), the ODU will send an instruction to the detects overheat of the inverter, it can start the inverter
IDU to prohibit startup, thus effectively protecting the temperature protection function to prevent damage to the
system safety. inverter.
15 16
Trial Operation Technology of ODU
During commissioning, the button on the ODU main board can be pressed to implement the forced trial operation
function of the unit, making commissioning easier.
TIMS-X TIMS-S
Design for Main Pipes of TIMS Modular unit Series
Ultra-high External Static Pressure
The system selects the blade with a higher air flow and Exhaust ducts can be installed by layer or in a centralized Total capacity (kW)
the DC fan motor to realize a higher external statistic manner. The higher external statistic pressure realizes Liquid pipe size (mm) Gas pipe size (mm) Branch joint
of downstream IDUs
pressure on the precondition of avoiding noise change. long distance air supply, prevents short circuit of the loop
The maximum external statistic pressure is 80 Pa. effectively, and ensures good ventilation effect. X<16.8 Φ9.52 Φ15.88 TBP4022TA
80Pa
conditioning conditions, the
system fails to TIMS unit
meet the
requirement,
ensures the ODU
installation effect, 33.0≤X<46.0 Φ12.70 Φ25.40 TBP4072TA
short circuit makes heat
easily occurs, exchange more
L0 main pipe
Outdoor branch pipe L0 main pipe
L0 main pipe
LM main
pipeline
TIMS-X TIMS-S
Design of TIMS Independent Main Pipe
17 18
Widely ODU
Application Specifications
Range
ODU units
ODU units
50°C
50°CDB
powerful cooling and heating performance, even operates under -20°C Power supply V/N/Hz 380V/3N/50Hz/60Hz
during cold winter or 50°C in summer. Heating EER kW/kW 4.08 3.95 3.88 3.75 3.56 3.53 3.60 3.68
24 COP kW/kW 4.45 4.49 4.36 4.25 3.99 3.96 4.06 4.14
Cooling kW 6.12 7.09 8.63 10.67 12.64 14.16 15.56 16.71
Rated input
Heating kW 6.07 7.02 8.60 10.58 12.60 14.12 15.52 16.65
Rated Cooling A 12.5 13.4 16.4 19.6 24.1 30.5 35.2 40.0
current Heating A 13.6 13.9 16.7 20.0 24.0 30.1 34.9 35.0
Type R410A
Refrigerant
TIMS-X TIMS-S Charge volume kg 8 10 12 16
3. Overlong Pipe & High Drop Design Brand - Hitachi
m 03 Gross weight kg 245 245 245 310 310 450 450 450
Maximum drop of indoor unit 30 m
Maximum drive IDU NO. unit 14 16 19 22 23 31 33 34
Max. equivalent connection
Maximum permitted length pipe length
m 240 240 240 240 240 240 240 240
40 m
after first branch Working Cooling °C -5-50°C
40
m 0m
9 temp. Heating °C -20-24°C
19 20
TIMS-X TIMS-X
Model TIMS240AX TIMS260AX TIMS280AX T1MS300AX TIMS320AX TIMS340AX TIMS360AX TIMS380AX TIMS400AX TIMS420AX TIMS440AX Model TIMS460AX TIMS480AX TIMS500AX TIMS520AX TIMS540AX TIMS560AX TIMS583AX TIMS60DAX TIMS620AX T1MS640AX TIMS660AX
Combination model 10+14 10+16 14+14 14+16 16+16 14+20 14+22 16+22 20+20 20+22 22+22 Combination model 14+16+16 16+16+16 14+16+20 14+16+22 16+16+22 14+20+22 14+22+22 16+22+22 20+20+22 20+22+22 22+22+22
ODU units
Capacity Cooling kW 68.0 73.0 80.0 85.0 90.0 96.0 101.5 106.5 112.0 117.5 123.0 Capacity Cooling kW 130.0 135.0 141.0 146.5 151.5 157.5 163.0 168.0 173.5 179.0 184.5
Heating kW 76.5 81.5 90.0 95.0 100.0 108.0 114.0 119.0 126.0 132.0 138.0 Heating kW 145.0 150.0 158.0 164.0 169.0 177.0 183.0 183.0 195.0 201.0 207.0
EER kW/kW 3.62 3.56 3.63 3.66 3.61 3.67 3.70 3.65 3.63 3.65 3.68
EER kW/kW 3.83 3.70 3.75 3.65 3.56 3.66 3.71 3.63 3.60 3.64 3.68
COP kW/kW 4.05 3.96 4.08 4.12 4.04 4.14 4.17 3.99 4.09 4.12 4.14
COP kW/kW 4.35 4.15 4.25 4.10 3.97 4.14 4.19 4.07 4.06 4.10 4.14
Cooling kW 35.95 37.92 38.87 40.02 41.99 42.94 44.09 46.06 47.83 48.98 50.13
Rated input
Cooling kW 17.76 19.73 21.34 23.31 25.28 26.23 27.38 29.35 31.12 32.27 33.42 Heating kW 35.78 37.80 38.70 39.83 41.85 42.75 43.88 45.90 47.69 48.82 49.95
Rated input
Heating kW 17.60 19.62 21.16 23.18 25.20 26.10 27.23 29.25 31.04 32.17 33.30 Rated Cooling A 67.80 72.30 78.90 83.70 88.20 94.83 99.60 104.10 110.40 115.20 120.03
current Heating A 68.00 72.00 78.90 79.00 83.00 89.90 90.00 94.03 104.80 104.90 105.03
Cooling A 33.00 37.50 39.20 43.70 48.20 54.80 59.60 31.04 70.40 75.20 80.00
Rated
current Type R410A
Heating A 3350 37.90 40.00 44.00 48.00 54.90 55.00 59.00 69.80 69.90 70.00 Refrigerant
Charge volume kg 12+12+12 12+12+16 12+16+16 16+16+16
Type R410A
Refrigerant Brand - Hitachi
Charge volume kg 8+12 12+12 12+16 16+16
Type - Scroll type
Brand - Hitachi
Compressor
Quantity - 1+1+1 1+1+2 1+2+2 2+2+2
Type - Scroll type
Refrigerant oil charge
Compressor L 1.10+1.10+1.10 1.10+1.10+0.50 1.10+0.50+0.50 0.50+0.50+0 50
Quantity - 1+1 1+2 2+2 volume
Notes:
Notes: 1. Cooling operating temperature range is from -5°C to 50°C, Heating operating temperature range is from -20°C to 24°C.
1. Cooling operating temperature range is from -5°C to 50°C, Heating operating temperature range is from -20°C to 24°C. 2. The cooling condition:indoor side 27°C (80.6°F) DB,19°C (60°F) WB outdoor side 35°C (95°F) DB
2. The cooling condition:indoor side 27°C (80.6°F) DB,19°C (60°F) WB outdoor side 35°C (95°F) DB 3. The heating condition:indoor side 20°C (68°F) DB,15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
3. The heating condition:indoor side 20°C (68°F) DB,15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB 4. Sound level:measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient
4. Sound level:measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions.and lower as a result of ambient conditions when under ultra-silent operation
conditions.and lower as a result of ambient conditions when under ultra-silent operation 5. Choosing fuse or breaker according to MFA and electrical wiring according to MCA.
5. Choosing fuse or breaker according to MFA and electrical wiring according to MCA. 6. The above data may be changed without notice for future improvement on quality and performance.
6. The above data may be changed without notice for future improvement on quality and performance.
21 22
TIMS-S TIMS-S
Single Module: 8/10/12/14/16/18/20/22HP Single Module: 8/10/12/14/16/18/20/22HP
Combination Module: 24HP-66HP, 2-3 modules Combination Module: 24HP-66HP, 2-3 modules
Full DC Inverter Technology Full DC Inverter Technology
Max. 1000m pipe length, Max. 110m height drop Max. 1000m pipe length, Max. 110m height drop
Model TIMS080AS TIMS100AS TIMS120AS TIMS140AS TIMS160AS Model TIMS180AS TIMS200AS TIMS220AS TIMS240AS TIMS260AS TIMS280AS TIMS300AS TIMS320AS
Capacity ranee HP 8 10 12 14 16 Capacity ranee HP 18 20 22 24 26 28 30 32
Capacity Cooling kW 25.0 28.0 33.5 40.0 45.0 Capacity Cooling kW 53.0 56.0 61.5 67.0 73.0 78.5 85.0 90.0
Heating kW 27.0 31.5 37.5 45.0 50.0 Heating kW 58.5 63.0 69.0 75.0 81.5 87.5 95.0 100.0
ODU units
ODU units
EER Kw/kW 4.05 3.93 3.86 3.74 3.54 EER Kw/kW 3.71 3.65 3.68 3.58 3.98 3.78 3.73 3.64
COP Kw/kW 4.41 4.45 4.35 4.23 3.94 COP Kw/kW 4.13 4.13 4.10 3.96 4.46 4.23 4.18 4.06
Cooling kW 6.17 7.13 8.68 10.70 12.71 Cooling kW 14.26 15.34 16.70 18.71 18.34 20.76 22.79 24.73
Rated input Rated input
Heating kW 6.12 7.08 8.62 10.65 12.66 Heating kW 14.18 15.25 16.83 18.93 18.28 20.70 22.71 24.65
Cooling A 12.50 13.40 16.40 19.60 24.10 Cooling A 30.50 35.20 40.00 33.00 37.20 39.20 43.70 48.20
Rated current Rated current
Heating A 13.60 13.90 16.70 20.00 24.00 Heating A 30.10 34.90 35.00 33.90 37.90 40.00 44.00 48.00
Sound pressure level dB (A) 45-57 45-59 Sound pressure level dB (A) 48 ~ 59 48 ~ 60 48 ~ 62
Net weight kg 220 220 220 285 285 Net weight kg 425 425 425 425 425 495 495 495
Gross weight kg 225 225 225 290 290 Gross weight kg 430 430 430 430 430 500 500 500
Maxmum drive IDU NO. unit 14 16 19 22 23 Maxmum drive IDU NO. unit 31 33 34 35 35 36 38 40
Max. equivalent connection pipe lencth m 240 240 240 240 240 Max. equivalent connection
m 240 240 240 240 240 240 240 240
pipe lencth
Cooling °C -5~50°C
Working temp. Cooling °C -5~50°C
Heating °C -20~24°C Working temp.
Heating °C -20~24°C
Notes: Notes:
1. Cooling operating temperature range is from -5°C to 50°C, Heating operating temperature range is from -20°C to 24°C. 1. Cooling operating temperature range is from -5°C to 50°C, Heating operating temperature range is from -20°C to 24°C.
2. The cooling condition:indoor side 27°C (80.6°F) DB,19°C (60°F) WB outdoor side 35°C (95°F) DB 2. The cooling condition:indoor side 27°C (80.6°F) DB,19°C (60°F) WB outdoor side 35°C (95°F) DB
3. The heating condition:indoor side 20°C (68°F) DB,15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB 3. The heating condition:indoor side 20°C (68°F) DB,15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
4. Sound level:measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient 4. Sound level:measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient
conditions.and lower as a result of ambient conditions when under ultra-silent operation conditions.and lower as a result of ambient conditions when under ultra-silent operation
5. Choosing fuse or breaker according to MFA and electrical wiring according to MCA. 5. Choosing fuse or breaker according to MFA and electrical wiring according to MCA.
6. The above data may be changed without notice for future improvement on quality and performance. 6. The above data may be changed without notice for future improvement on quality and performance.
23 24
Round Flow
cassette
Optional
Accessories
Two-way cassette 28 Slim duct 33 Built-in drain pump, drain height can be 1200mm
Built-in with long life drainage pump, Pumping head is Maxmum 120mm
25 26
Two-way
Model TMCF028AB TMCF036AB TMCF045AB TMCF050AB TMCF056AB TMCF063AB TMCF071AB TMCF080AB TMCF090AB TMCF100AB TMCF112AB TMCF125AB TMCF140AB TMCF160AB cassette
Cooling kW 2.8 3.6 4.5 5.0 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0
Capacity
Heating kW 3.2 4.0 5.0 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 18.0
220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/ 220V/
Power supply V/Ph/Hz
1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz 1Ph/50Hz
Air flow volume 750/ 810/ 900/ 900/ 960/ 960/ 1020/ 1200/ 1500/ 1620/ 1700/ 1800/ 1800/ 2100/
m3/h
(H/M/L) 660/540 690/540 720/600 720/600 780/660 780/660 900/690 1080/870 1200/900 1260/1020 1360/1080 1500/1200 1500/1200 1800/1500
490±30/ 490±30/ 580±30/ 580±30/ 580±30/ 580±30/ 670±30/ 670±30/ 590±30/ 590±30/ 630±30/ 630±30/ 630±30/ 630±30/
Speed 400±35/ 400±35/ 490±35/ 490±35/ 490±35/ 490±35/ 600±35/ 600±35/ 500±35/ 500±35/ 590±35/ 590±35/ 590±35/ 590±35/
rpm
(H/M/L/SL) 340±35/ 340±35/ 410±35/ 410±35/ 410±35/ 410±35/ 500±35/ 500±35/ 425±35/ 425±35/ 480±35/ 480±35/ 480±35/ 480±35/
300±40 300±40 360±40 360±40 360±40 360±40 400±40 400±40 350±40 350±40 420±40 420±40 420±40 420±40
Fan motor
Power output W 26 26 30 30 30 30 37 37 50 50 65 65 65 65
Insulation
- B B B B B B B B B B B B B B
class
Optional
Liquid pipe mm φ6.35 φ6.35 φ6.35 φ6.35 φ6.35 φ6.35 φ9.52 φ9.52 φ9.52 φ9.52 φ9.52 φ9.52 φ9.52 φ9.52
Connecting Wireless Wired Wired Centralized
Gas pipe mm φ12.7 φ12.7 φ12.7 φ12.7 φ12.7 φ12.7 φ15.88 φ15.88 φ15.88 φ15.88 φ15.88 φ15.88 φ15.88 φ15.88
pipe
Connection method Flared Flared Flared Flared Flared Flared Flared Flared Flared Flared Flared Flared Flared Flared
External
Drain pipe mm DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25
diameter
Outline dimension (body) mm 840*840*230 840*840*230 840*840*230 840*840*230 840*840*230 840*840*230 840*840*230 840*840*230 840*840*300 840*840*300 840*840*300 840*840*300 840*840*300 840*840*300
Outline dimension (panel) mm 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50 950*950*50
Accessories
Package dimension (body) mm 930*930*300 930*930*300 930*930*300 930*930*300 930*930*300 930*930*300 930*930*300 930*930*300 930*930*370 930*930*370 930*930*370 930*930*370 930*930*370 930*930*370
Package dimension Plenum box Air filter EXV Drain pump AC motor DC Motor
mm 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90 1020*1020*90
(panel)
Body kg 22.5 22.5 24.5 24.5 24.5 24.5 24.5 24.5 29.5 29.5 29.5 29.5 32 32 / Standard Standard(built-in) Standard Standard /
Net weight
Panel kg 6 6 6 6 6 6 6 6 6 6 6 6 6 6
IDU units
Body kg 24.5 24.5 26.5 26.5 26.5 26.5 26.5 26.5 31.5 31.5 31.5 31.5 34 34
Gross
weight
Panel kg 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
Special design for corridor or nallow and long room
Notes:
1. Power supply: 220V/1PH for 50Hz
2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB
3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
Available for room with 3.5m floor height
4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions.
5. The above data may be changed without notice for future improvement on quality and performance.
Model TMCD028A TMCD036A TMCD045A TMCD056A TMCD071A TMCD080A TMCD090A TMCD100A TMCD112A TMCD125A TMCD140A
Cooling kW 2.8 3.6 4.5 5.6 7.1 8.0 9.0 10.0 11.2 12.5 14.0
Capacity
Heating kW 3.2 4.0 5.0 6.3 8.0 9.0 10.0 11.2 12.5 14.0 16.0
Power supply V/Ph/Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz
Power input W 60 62 68 85 94 98 129 135 175 185 268
Air flow volume (H/M/L) m3/h 500/426/376 616/523/462 773/657/580 900/765/657 1165/990/873 1300/1120/980 1450/1310/1160 1600/1450/1280 1725/1550/1280 1980/1680/1500 1980/1680/1500
Sound pressure level (H/M/L) dB(A) 37/31/25 39/36/32 43/37/31 45/41/39 47/43/40 49/45/42 45/42/38 46/43/40 50/48/43 53/50/46 53/50/46
Fan Type - Centrifugal Centrifugalw Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
Power output W 10 12 16 25 30 30 20*2 25*2 30*2 45*2 45*2
Fan motor
Insulation class - B B B B B B B B B B B
Liquid pipe mm φ6.35 φ6.35 φ6.35 φ6.35 φ9.52 φ9.52 φ9.52 φ9.52 φ9.52 φ9.52 φ9.52
Connecting pipe Gas pipe mm φ12.70 φ12.70 φ12.70 φ12.70 φ15.88 φ15.88 φ15.88 φ15.88 φ15.88 φ15.88 φ15.88
Connection method Flared Flared Flared Flared Flared Flared Flared Flared Flared Flared Flared
Drain pipe External diameter mm DN20 DN20 DN20 DN20 DN20 DN20 DN20 DN20 DN20 DN20 DN20
Outline dimension (body) mm 840*520*315 840*520*315 960*520*315 960*520*315 1200*520*315 1200*520*315 1680*520*315 1680*520*315 1680*520*315 1680*520*315 1680*520*315
Outline dimension (panel) mm 1083*630*33 1083*630*33 1203*630*33 1203*630*33 1443*630*33 1443*630*33 1923*630*33 1923*630*33 1923*630*33 1923*630*33 1923*630*33
Package dimension (body) mm 1145*685*395 1145*685*395 1265*685*395 1265*685*395 1505*685*395 1505*685*395 1983*685*395 1983*685*395 1983*685*395 1983*685*395 1983*685*395
Net weight kg 32 32 37 37 40 40 45 45 47 47 47
Gross weight kg 35 35 40 40 43 43 48 48 50 50 50
Notes:
1. Power supply: 220V/1PH for 50Hz
2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB
3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions.
5. The above data may be changed without notice for future improvement on quality and performance.
27 28
One-way
cassette Ceiling & Floor
Optional
Optional
Wireless Wired Wired Centralized
Wireless Wired Wired Centralized
Accessories Accessories
Plenum box Air filter EXV Drain pump AC motor DC Motor Plenum box Air filter EXV Drain pump AC motor DC Motor
Horizonal and vertical air flow Flexible installation,on the floor or on the ceiling
Built-in drain pump,drain height can be 1200mm Automatic horizontal and vertical air flow
Built-in with long life drainage pump, Pumping head is
Air
1200mm, flexible for drainage pipe design. flow
One sided access hole,easy for maintenance
Compact design,unit height only 250mm
Model TMCS028A TMCS036A TMCS045A TMCS056A TMCS071A Model TMVX028A TMVX036A TMVX056A TMVX071A TMVX090A TMVX112A TMVX125A TMVX140A
Gross weight kg 31 31 33 43 43 48 48 48
Notes: Notes:
1. Power supply: 220V/1PH for 50Hz 1. Power supply: 220V/1PH for 50Hz
2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB 2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB
3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB 3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions. 4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions.
5. The above data may be changed without notice for future improvement on quality and performance. 5. The above data may be changed without notice for future improvement on quality and performance.
29 30
Wall mounted Standard duct
Optional Optional
Wireless Wired Wired Centralized Wireless Wired Wired Centralized
/ /
Accessories Accessories
Plenum box Air filter EXV Drain pump AC motor DC Motor Plenum box Air filter EXV Drain pump AC motor DC Motor
Model TMVW028A TMVW036A TMVW040A TMVW056A TMVW063A TMVW071A Model TMDN071AB TMDN080AB TMDN090AB TMDN100AB TMDN112AB TMDN125AB TMDN140AB TMDN160AB
Cooling kW 2.8 3.6 4.0 5.6 6.3 7.1 Cooling kW 8.0 8.0 9.0 10.0 11.2 12.5 14.0 16.0
Capacity Capacity
Heating kW 3.2 4.0 4.5 6.3 7.1 8.0 Heating kW 7.1 9.0 10.0 11.2 12.5 14.0 16.0 18.0
Power supply V/Ph/Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz Power supply V/Ph/Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz 220V/1Ph/50Hz
Air flow volume (H/M/L) m3/h 450/410/380 500/460/425 500/460/425 800/750/710 800/750/710 1000/950/910 Air flow volume (H/M/L) m3/h 1100/1000/900 1300/1150/950 1600/1400/1200 2000/1700/1400
Sound pressure level (H/M/L) dB(A) 38/35/27 38/35/27 40/36/29 45/41/31 45/41/31 48/45/39 ESP Pa 30(15/30/70) 50(15/30/70)
Fan Type - Tubular Tubular Tubular Tubular Tubular Tubular Sound pressure level (H/M/L) dB(A) 40/37/33 42/39/35 44/41/39
Connecting pipe Gas pipe mm φ12.70 φ12.70 φ12.70 φ12.70 φ12.70 φ15.88 Gas pipe mm φ15.88
Connecting
Connection method Flared Flared Flared Flared Flared Flared Liquid pipe mm φ9.52
pipe
Drain pipe External diameter mm φ16 φ16 φ16 φ16 φ16 φ16 Connection method Flared
Outline dimension mm 790*270*185 795*285*215 795*285*215 990*330*230 990*330*230 1090*330*255 Drain pipe External diameter mm DN25
Notes: Notes:
1. Power supply: 220V/1PH for 50Hz 1. Power supply: 220V/1PH for 50Hz
2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB 2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB
3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB 3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions. 4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions.
5. The above data may be changed without notice for future improvement on quality and performance. 5. The above data may be changed without notice for future improvement on quality and performance.
31 32
Slim duct High ESP duct
Optional
Optional
Wireless Wired Wired Centralized
Wireless Wired Wired Centralized
Accessories Accessories
Notes: Notes:
1. Power supply: 220V/1PH for 50Hz 1. Power supply: 220V/1PH for 50Hz
2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB 2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB
3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB 3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions. 4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions.
5. The above data may be changed without notice for future improvement on quality and performance. 5. The above data may be changed without notice for future improvement on quality and performance.
33 34
Big capacity Fresh air
duct Processor
Optional
Optional
Wireless Wired Wired Centralized
Wireless Wired Wired Centralized
Accessories
Accessories
Plenum box Air filter EXV Drain pump AC motor DC Motor
Plenum box Air filter EXV Drain pump AC motor DC Motor / Standard Standard (Extermal) / Standard /
connection
Model TMDH195AI TMDH255AI TMDH410AI TMDH520AI TMDH620AI TMDH790AI TMDF TMDF TMDF TMDF TMDF TMDF TMDF TMDF TMDF TMDF TMDF TMDF
Model
175A-022 210A-020 250A-015 250A-020 250A-030 300A-020 400A-020 400A-030 500A-0200 500A-030 600A-020 600A-030
Cooling kW 19.5 25.5 41.0 52.0 62.0 79.0
Capacity Cooling kW 25.0 28.0 28.0 28.0 28.0 28.0 45.0 45.0 56.0 56.0 56.0 56.0
Heating kW 20.4 28.5 41.5 55.0 68.0 83.0 Capacity
Heating kW 14.0 17.4 17.4 17.4 17.4 17.4 28.0 28.0 35.0 35.0 35.0 35.0
V/Ph/
Power supply 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz
Hz 220V/ 220V/ 380V/ 380V/ 380V/ 380V/ 380V/ 380V/ 380V/ 380V/ 380V/ 380V/
Power supply V/Ph/Hz
1Ph/50Hz 1Ph/50Hz 3N/50Hz 3N/50Hz 3N/50Hz 3N/50Hz 3N/50Hz 3N/50Hz 3N/50Hz 3N/50Hz 3N/50Hz 3N/50Hz
Power input W 1320 1320 2640 2640 4480 4480
Power input W 630 700 480 560 790 750 880 1290 1000 1400 1350 1700
Air flow volume m3/h 4300 4800 7500 9000 11000 13000
Air flow volume m3/h 1750 2100 2500 2500 2500 3000 4000 4000 5000 5000 6000 6000
ESP Pa 200 200 250 250 300 300
ESP Pa 220 200 150 200 300 200 200 300 200 300 200 300
Sound pressure level dB(A) 54 54 55 57 60 60 Sound pressure level dB(A) 49 49 52 55 58 56 59 62 62 65 62 65
Fan Type - Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Fan Type - Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
Fan motor Insulation class - B B B B B B Power input W 630 700 480 560 790 750 880 1290 1000 1400 1350 1700
Fan motor
Insulation class - B B B B B B B B B B B B
Liquid pipe mm φ12.7 φ12.7 φ15.88 φ15.88 φ19.05 φ19.05
Liquid pipe mm φ12.70 φ12.70 φ12.70 φ12.70 φ12.70 φ12.70 φ12.70 φ12.70 φ15.88 φ15.88 φ15.88 φ15.88
Connecting pipe Gas pipe mm φ22.23 φ22.23 φ28.60 φ28.60 φ31.80 φ31.80
Connecting
pipe Gas pipe mm φ22.23 φ22.23 φ22.23 φ22.23 φ22.23 φ22.23 φ28.58 φ28.58 φ28.58 φ28.58 φ28.58 φ28.58
Connection method Welding Welding Welding Welding Welding Welding
Connection method Welding Welding Welding Welding Welding Welding Welding Welding Welding Welding Welding Welding
Drain pipe External diameter mm DN32 DN32 DN32 DN32 DN32 DN32 External
Drain pipe mm DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25
diameter
Outline dimension mm 1451*1204*608 1951*1604*808 2293*1604*1008
Outline dimension mm 1300*820*500 1300*820*500 1300*820*500 1300*820*500 1300*820*500 1300*820*500 1650*850*665 1650*850*665 2000*850*665 2000*850*665 2000*850*665 2000*850*665
Package dimension mm 1451*1204*608 1951*1604*808 2293*1604*1008 Package dimension mm 1360*830*510 1360*830*510 1360*830*510 1360*830*510 1360*830*510 1360*830*510 1767.5*946*848 1767.5*946*848 2117.5*946*848 2117.5*946*848 2117.5*946*848 2117.5*946*848
Net weight kg 150 275 325 335 Net weight kg 75 75 75 75 75 75 140 140 165 165 165 165
Gross weight kg 152 277 327 339 Gross weight kg 80 80 80 80 80 80 160 160 185 185 185 185
Notes: Notes:
1. Power supply: 220V/1PH for 50Hz 1. Power supply: 220V/1PH for 50Hz
2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB 2. The cooling condition: indoor side 27°C (80.6°F) DB, 19°C (60°F) WB outdoor side 35°C (95°F) DB
3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB 3. The heating condition: indoor side 20°C (68°F) DB, 15°C (44.6°F) WB outdoor side 7°C (42.8°F) DB
4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions. 4. Sound level: measured at point 1m in front of the unit at a height of 1.3m. During actural operation, these values are normally somewhat higher as a result of ambient conditions.
5. The above data may be changed without notice for future improvement on quality and performance. 5. The above data may be changed without notice for future improvement on quality and performance.
35 36
Independent Control
Separate control Separate control Separate control Dual controller control Zone control, not exceeding 16 sets
One-way cassette
Two-way cassette
TMCF
TMCS
TMCD
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Implementing Intelligent Control 39 Fresh air handling unit TMDF Optional Optional Optional
37 38
Centralized Control Household-based Charging
Remote management
Data
acquisition
Maximum 64 module
Intelligent Control
RS232-RS485 transfer
module Maximum 64
Password
Remember password
Maximum 64
OK Cancel
Schedule Management
39 40
Building Automation (BMS) System ModBus system
TIMS adopts multiple automatic control systems to access the building automation system easily, and full automatic control
of the system is realized through the computer. The control function is powerful, and operations are simple and clear. Ethernet
LonWorks system
Connecting to a maximum of 1024 IDUs and 16 sets of Shielding function of the user's air conditioner controller
ODUs Free grouping and zone management
Connecting to a maximum of 1024 IDUs and 16 sets of ODUs
Powering on/off the air conditioner, controlling operation, Perfect schedule management function
Powering on/off the air conditioner, controlling operation, and monitoring the operating status
and monitoring the operating status Historical data record
Monitoring the IDU fault code
Monitoring the IDU fault code Schedule control function of week/month/year
Monitoring and setting the IDU temperature Monitoring and setting the IDU temperature Single-unit or centralized operation, shutdown,
Monitoring and switching the operating mode Monitoring and switching the operating mode temperature setting, mode switching, etc.
Setting remote controller permissions Setting remote controller permissions Interlock control (fire alarm, door lock, fault, etc.)
Free grouping and zone management Service monitoring
Perfect schedule management function Automatic unit operation according to settings
Historical data recordn
Schedule control function of week/month/year
Single-unit or centralized operation, shutdown, temperature setting, mode switching, etc.
Interlock control (fire alarm, door lock, fault, etc.)
contro prevention
41 42
TICA VRF Unit Cleaning Technology Fresh Air Ventilator
The joints of cabinet adopt aluminum profiles All the metals in the cabinet are isolated from
with concave and convex grooves, which external metals using polyurethane foam and
form a labyrinth-type patent sealing structure specially designed sealing strips, avoiding the
together with fastening bolts and nuts, thermal insulation strip that must be stuck for
reducing the air leakage rate to 0.029% and ordinary products to prevent condensation,
ensuring lower operation cost. putting to an end to the water dripping
problem of cold bridge, and also reducing the
unit noise.
Characteristics:
The built-in full heat core heat exchanger
achieves higher heat exchange efficiency, the The direct drive fan is adopted and does not
High-grade fashionable appearance design and Wide application scope: The purifiers can be used
maximum temperature efficiency of 70%, and need to be maintained. Only the filter screen
first-class surface process and texture. together with fan coils, VRF units, and commercial the maximum enthalpy efficiency of 60%. needs to be cleaned regularly.
Installation and maintenance are convenient. TICA IDUs.
High efficiency and energy Safe and reliable
provides six types of standard dimensions, meeting Low wind resistance: The minimum resistance of
conservation
your different decoration requirements. air return unit is 8 Pa, and the IDU air return is not
The air flow range is wide, from 340 m 3 /h to affected as clean air is produced.
2400 m3/h, meeting the requirements of different Air volume
ESP (Pa) Cooling (%) Heating (%) Motor input power(kW)
Noise Rated voltage
Model Temperature Enthalpy Temperature Enthalpy
occasions. (m3/h) Air supply Air exhaust recovery recovery recovery recovery Air supply Air exhaust dB(A) (V)
efficiency efficiency efficiency efficiency
Specification of Return Air Purifiers TFD015FC 1500 110 110 59 51 71 59 0.30 0.30 53 220V - 50HZ
Model TRP070BPF TRP090BPF TRP100BPF TRP110BPF TRP160BPF TRP220BPF TFD030FC 3000 100 100 59 51 71 59 0.55 0.55 58 380V 3N - 50Hz
Rated Air Volume 540 900 1000 1100 1300 1700 TFD040FC 4000 110 110 57 50 69 58 1.00 1.00 59 380V 3N - 50Hz
Air Volume Range 340-700 700-900 340-1000 900-1100 950-1700 1300-2400 TFD050FH 5000 100 100 57 50 69 58 1.50 1.50 62 380V 3N - 50Hz
43 44
Note
Fresh Air Ventilators of Small Silent Series
Characteristics:
The air flow range is 150 m3/h~800 m3/h, applicable to sites such as homes, conference rooms, labs, offices, equipment
rooms, restaurants, and gyms. The installation is convenient. The machine is installed in the ceiling, without occupying
the indoor effective space or affecting the interior decoration effect. The machine can also be turned upside down for
installation to improve flexibility. The noise is lower. The international popular structure design, non-metallic material and
the accurate and consistent mold production ensure the perfect silent effect. More complete functions are implemented,
including bidirectional ventilation, air purification, energy recovery, and bypass system.
Characteristics:
The air flow range is 1000 m3/h~6000 m3/h, applicable to sites such as homes, conference rooms, labs, offices, equipment
rooms, restaurants, and gyms. The installation is convenient. The machine is installed in the ceiling, without occupying the
indoor effective space. More complete functions are implemented, including bidirectional ventilation, air purification, and
energy recovery. The sheet metal structure is designed, with thermal insulation cotton stuck inside.
TRD100 850/1000/1000 85/95/120 53/51/51 71/67/67 75/70/70 85/82/82 42/44/45 490/520/550 2.2/2.4/2.7 220 100 1264*1214*388
TRD150 1400/1500/1500 95/110/160 53/51/51 63/62/62 75/70/70 78/77/77 47/50/51 750/860/920 3.5/3.9/4.2 220 143 270*1214*476
TRD200 1400/1700/2000 70/80/105 53/51/51 67/64/61 73/68/68 81/77/75 46/48/52 930/1050/1310 4.5/5.0/6.3 220 175 270*1240*476
TRD250 1600/2000/2500 70/80/100 56/54/51 70/65/62 74/69/69 86/81/80 45/50/53 1000/1410/1630 5.0/6.4/7.6 220 185 270*1240*600
Cleaning Technology
TRD300 1800/2500/3000 70/85/150 68/61/58 79/74/71 76/70/70 88/85/82 45/45/52 1010/1460/1900 4.7/6.8/8.7 220 198 270*1872*660
TRD400 */*/4000 */*/125 */*/51 0/0/65 74/68/68 */*/78 */*/58 */*/1940 */*/5.3 220 290 430*2022*660
TRD500 */*/5000 */*/95 */*/57 */*/71 76/70/70 */*/82 */*/59 */*/2790 */*/7.3 220 360 430*1842*860
TRD600 */*/6000 */*/120 */*/58 */*/70 74/68/68 */*/84 */*/60 */*/3280 */*/7.8 220 390 430*2172*860
45 46
Note Note
47 48