C o n v e n t i o n a l D e t e c t i o n

100 Series™
Low-Profile Plug-in
Smoke Detector

Models Available

2151/2151A* Photoelectronic Detector


*“A” suffix denotes ULC listed product

Product Overview
Sleek, low-profile design System Sensor 100 Series Plug-in Smoke Detectors offer superb performance and
reliability in a profile which is just 1.6˝ (4.2 cm) deep. Model 2151 (photoelectronic
Compatible with 400 Series product
sensor) can be used with a variety of different adapter bases in several wiring config-
Two LEDs blink in standby, providing urations and voltages. Other features include: low current draw, stable performance
360° visibility in high air velocities, built-in tamper resistant base design, remote LED option,
removable cover, and built-in test switch.
Field sensitivity metering of detector to
meet the requirements of NFPA 72
The 100 Series is designed to meet the performance criteria designated by UL.
Broad range of adapter bases available Its sensing chambers are sealed against back pressure air flow, dirt, and insects.
with built-in shorting spring This chamber is protected by a fine mesh screen which can be cleaned or
replaced. Additional key features include a variety of mounting bases and a full
line of accessories.

Photoelectronic
All 100 Series photoelectronic smoke detectors contain a unique optical sensing
chamber designed to sense smoke particles produced by a wide range of com-
bustion sources. A custom integrated circuit incorporates signal processing to
reduce false alarms.

S911 7272-1209:159 (2151) CS308

205-94-E OX5A4.AY 1973


Specifications
Operating Voltage/Alarm Current Construction
See Adapter Base Selection Guide following Flame retardant thermoplastic

Standby Current Temperature


Photo: 85µA Standby 32°F to 120°F (0° to 49°C)

Sensitivity UL Listed Velocity Range


3% ±.7%/ft. Photo Photo: 0 – 3000 fpm (0 – 15.2 m/s)

Shipping Weight Humidity Range


3.6 oz. (102 g) 10% – 93% RH noncondensing

Size Smoke Detector Spacing


1.66″ h. (42 mm) On smooth ceilings (as defined in NFPA 72), spacing of 30 feet (900 sq. ft.)
4.1″/104 mm dia. unflanged base may be used as a guide. Other spacing may be used depending on ceiling
6.1″/155 mm dia. flanged base height, high air movements, and other conditions or response requirements.

Adapter Base Selection Guide


Base Model Number Loop Type Current Limit Resistor Contact Type Nominal Voltage Current Draw on Alarm (mA)
B110LP 2-wire* No — 12/24VDC 10–100**
B110RLP 2-wire* Yes — 24VDC 22–62
B112LP 4-wire Yes Form A&C 24VDC 14–39
B114LP 4-wire Yes Form A&C + A Super visor y 120VAC 75 mA AC Max
B116LP 2-wire* No Form C 24VDC 12–100**
B401† 2-wire* No — 12/24VDC 10–100**
*Functionality contingent on panel compatibility **Must be limited by control panel †Flangeless base
Relay Contact Ratings: Resistive or Inductive (60% power factor) load.
Form A: 2.0A at 30 VAC/DC
Form C: 0.6A at 110VDC, 2.0A at 30VDC
1.0A at 125VAC, 2.0A at 30VAC

Junction Box Selection Guide*


Base Model Number Single Gang 31⁄2″ Octagon 4″ Octagon 4″ Square 50 mm 60 mm 75 mm
B401 NO NO NO NO YES YES NO
B110LP/RLP YES YES YES YES NO NO NO
B112LP/B116LP YES YES YES YES YES YES YES
B114LP NO NO YES YES NO NO NO
*Box depth contingent on base and wire size. Refer to National Electrical Code or local applicable codes for appropriate recommendations.

Ordering Information
Part No. Description
2151 Low-profile photoelectronic detector. Must be mounted to one of the 2151A Low-profile photoelectronic detector, ULC listed.
B100 Series or B400 Series bases listed in Adapter Base
Selection Guide.
Accessories
F110 Retrofit replacement flange for B400 Series flanged bases. EOLR-1 End of line relay for power super vision, 12/24 VDC systems.
RA400Z Remote annunciator for 2 or 4 wire systems, 3-32V. Use with ion M02-04-01 Test magnet.
and photo plug-in detectors. Fits standard single gang electrical M02-09-00 Test magnet with 32″ telescoping handle.
box. XR-2 Detector removal tool. Allows installation and/or removal of
B401BH Sounder base. Requires an external 24 VDC power supply. Mounts 100 Series detector heads from base in high ceiling installations
to 4″ square electrical box (11⁄2″ minimum depth, 21⁄8″ recommend- when used with XP-4.
ed). XP-4 Extension pole for XR-2. Comes in three 5 ft. sections.
MOD400R Detector sensitivity test tool. (See below.) Use with most analog C58-227-01 Replacement dust cover for 100 Series smoke detectors.
or digital multimeters. Satisfies NFPA 72 requirement for sensi- RMK400 Recessed mounting kit for 2151 detector (B401 sold separately).
tivity testing.
SMK400 Sur face mounting kit provides for entr y of sur face wiring con-
duit. For use with B401 or B401R mounting bases only.

The MOD400R Field Sensitivity Test Module


can be used with any standard DC voltmeter
or multimeter to check the sensitivity range
of System Sensor detectors (satisfies NFPA
72 requirement for sensitivity testing).
System Sensor Sales and Service
System Sensor Headquarters System Sensor Canada System Sensor in China System Sensor – Far East System Sensor – India
3825 Ohio Avenue Ph: 905.812.0767 Ph: 86.29.8832.0119 Ph: 85.22.191.9003 Ph: 91.124.237.1770 x.2700
St. Charles, IL 60174 Fx: 905.812.0771 Fx: 86.29.8832.5119 Fx: 85.22.736.6580 Fx: 91.124.237.3118
Ph: 800/SENSOR2 System Sensor Europe System Sensor in Singapore System Sensor – Australia System Sensor – Russia
Fx: 630/377-6495 Ph: 44.1403.891920 Ph: 65.6273.2230 Ph: 613.54.281.142 Ph: 70.95.937.7982
www.systemsensor.com Fx: 44.1403.891921 Fx: 65.6273.2610 Fx: 613.54.281.172 Fx: 70.95.937.7983
­© 2005 System Sensor. The company reserves the right to change product specifications without notice. A05-0182-008•3/05•#1426

You might also like