Transformer Tech Testing
Transformer Tech Testing
Surge Ring
Core
Copper
Conductor
Iron
Kraft
Insulating
Paper
100
180 160 140 120 100 80
Operating Temperature Deg C
Life of winding insulation versus temperature, 65 deg C rise designs
Loading Guides for Oil
Immersed Transformers
Loading guide is voluntary and not a
mandatory standard, and is a conservative
one.
The average annual ambient temperature
does not exceed 20 deg C by more than a
few degrees.
Power transformer do not operate at constant
100% load.
Insulation tensile strength of 50% may not be
the end for the transformer. Remember that
insulation hardly ever dies, it is killed.
Functional Life Testing
Insulation Power Factor ( IPF )
Bushing
Winding
Oil
Over all insulation
Excitation current
Impedance
Short circuit
Watts loss
Functional Life Testing
Dissolve Gas Analyses
Filtration ( vacuum/ heating or purely
cartridge type )
Other tests conducted when short circuit /
overload / transformer fall during transport, a
leakage reactance tesing or sweep frequency
analysis is needed to determine movement of
core, etc.
Transformer Protection
Transformer protection is not just using
breakers, relays, monitors, surge
arresters, cooling, etc., but more of
making sure the transformer operates
well.
Overload and overcurrent is a function
of how transformer is loaded.
Effects of Overload or Over
Heating on Transformers:
Cellulosic Paper;
This insulating material shrinks and
become more brittle. Certain secondary
effects are also important, such as,
production of “gases” and “free water”
during the decomposition of the
pressboard paper and paper. If free water
remains where it is generated, it further
accelerates the degradation process.
Effects of Overload or Over Heating on
Transformers: cont..
Rule to Remember:
Accepted rule for cellulosic paper as the
“8”C rule;
Transformer mineral oil on the “10”C rule
Transformer must be operated with two
critical temperatures: 105 or 110 deg C for
solid insulation; 60 deg C for mineral oil.
Basic Impulse Level or
Impulse Strength
This relates to the ability of the
insulation system to withstand a surge
voltage and retain its original
characteristics within described bounds.
The impulse strength is 2 -2.5 times the
normal electrical stress under operating
voltages.
Basic Insulation Level or
Impulse Strength, cont.
Major Insulation:
This is the heart of the transformer, as
defined by IEEE standards, consists of the
insulation between the HV & LV windings
in the same phase. Between them is Kraft
paper cylinders and layers of sheets; high
density organic sticks bonded with
synthetic resin; pressboard sheets for
phase insulation and colars.
Basic Inpulse Level or Impulse
Strength, cont..
Minor Insulation:
This insulation is between adjacent turns in
a winding and between different sections of
the same winding. This is separated by
pressboard spacers, tape, and synthetic
enamel wire.
Basic Insulation Level or
Impulse Strength, cont..
Phase to Phase Insulation:
This is an insulation between windings of
the same phases. It is separated by heavy
Kraft paper or pressboard
Pictorial Diagram of Three Classes of
Transformer
Minor Ins.
Insulation
Major Ins.
Tank
Core
Oil Windings
8.0
6.0
2.0
1.0
0.8
0.6
Impulse Strength
KV Crest
300
250
200
150
100
100
50
0
Impulse Strength
In Percent
1000
80
60
40
20
0
Percent Power Factor
2 4 6 8 10 12 14 16 18 20
0.1 1.5 2.0 Water Content in Paper Percent
Short Circuit Withstand Causes:
DC Test Voltage
Stop Bad
DC Test Voltage
Stop Bad
Short
DC Test Voltage
Short
DC Test Voltage
Insulating Resistance:
DC winding resistance test is made with a
low resistance ohm meter. It will indicate a
change in dc winding resistance when
there are short circuited turns, poor joints
or bad contacts. This reading should be
compared to factory tests information.
The low resistance is measured by the
potential drop method.
Electrical Tests on Transformers, cont..
Winding Resistance;
The idea is to apply current to the system, the
resistance will be constant, so the potential will
show any voltage drop present. Readings should
be in milliohm range. High readings would
indicate loose or dirty connections.
On 3Ph transformers the measurements are made
on the individual windings (phase to neutral ),
whenever possible.
Electrical Tests on Transformers, cont..
Winding Resistance..
On delta connections, there will always be two
windings ( in series ) which are in parallel with the
winding under test. For this test, three
measurements should be obtain to get close to
accurate results.
Now, since resistance of copper varies with
temperature, all tests readings must be converted
to a common temperature to give good results.
Most factory test data are converted to 75 deg C.
Electrical Tests on Transformers, cont..
Tangent Delta
Capacitance
Inductance
Multiple test