Power System Protection Fundamentals

1) The sub-transient fault current is calculated to be -j4 per unit. 2) The sub-transient current seen by breaker B is also -j4 per unit. 3) The momentary current seen by breaker B is -j4 per unit. 4) After 5 cycles, the current that must be interrupted by breaker B is reduced to zero.

Uploaded by

Malcolm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views

Power System Protection Fundamentals

1) The sub-transient fault current is calculated to be -j4 per unit. 2) The sub-transient current seen by breaker B is also -j4 per unit. 3) The momentary current seen by breaker B is -j4 per unit. 4) After 5 cycles, the current that must be interrupted by breaker B is reduced to zero.

Uploaded by

Malcolm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

FAULT ANALYSIS

Example 9.1

Zone 1 Zone 2 Zone 3


𝑆𝑏𝑎𝑠𝑒3𝜙 = 10 𝑀𝑉𝐴 𝑆𝑏𝑎𝑠𝑒3𝜙 = 10 𝑀𝑉𝐴 𝑆𝑏𝑎𝑠𝑒3𝜙 = 10 𝑀𝑉𝐴
𝑘𝑉𝑏𝑎𝑠𝑒3𝜙 = 11 𝑘𝑉 33 6.6
𝑘𝑉𝑏𝑎𝑠𝑒3𝜙 = ( ) (11) = 33 𝑘𝑉 𝑘𝑉𝑏𝑎𝑠𝑒3𝜙 = ( ) (33) = 6.6 𝑘𝑉
𝒁𝑮𝟏 = 𝒋𝟎. 𝟏𝟓 𝒑𝒖 = 0.15∠900 11 33
𝒁𝑮𝟐 = 𝒋𝟎. 𝟏𝟐𝟓 𝒑𝒖 = 0.125∠900 332 6.62
𝑍𝑏𝑎𝑠𝑒 = = 108.9Ω 𝑍𝑏𝑎𝑠𝑒 = = 4.356Ω
𝑿𝒕𝟏 = 𝒋𝟎. 𝟏𝟎 𝒑𝒖 = 0.1∠900 10 10
𝑆𝑏𝑎𝑠𝑒3𝜙 𝑍𝑡1 (𝑖𝑛 Ω 𝑟𝑒𝑓𝑒𝑟𝑟𝑒𝑑 𝑡𝑜 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦) 𝑍𝑡1 (𝑖𝑛 Ω 𝑟𝑒𝑓𝑒𝑟𝑟𝑒𝑑 𝑡𝑜 𝑡ℎ𝑒 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦)
𝑋𝑡1 = 0.10( 2 ) 33 2 6.6 2
𝑘𝑉𝑏𝑎𝑠𝑒3𝜙 = 1.21 ( ) = 10.89Ω = 17.424 ( ) = 0.69696
112 121 11 33
𝑍𝑏𝑎𝑠𝑒 = = = 12.1Ω 10.89
10 10 𝑍𝑡1 = = 𝑗0.1 𝑝𝑢 0.69696
𝑋𝑡1 (𝑖𝑛 Ω) = 12.1(0.1) = 1.21Ω 108.9
Ω 𝑍𝑡2 (𝑖𝑛 𝑝𝑢) = = 𝑗0.16
10 × 103 𝑍𝑙𝑖𝑛𝑒 (Ω) = 30(0.27 + 𝑗0.36)(𝑘𝑚) ( ) 4.356
𝐼𝑏𝑎𝑠𝑒1 = = 524.86 𝐴 𝑘𝑚 Ω
√3(11) = (8.1 + 𝑗10.8)Ω 𝑍𝑐𝑎𝑏𝑙𝑒 (𝑖𝑛 Ω) = 3(0.135 + 𝑗0.08)(𝑘𝑚) ( )
𝑘𝑚
𝟖. 𝟏 + 𝒋𝟏𝟎. 𝟖 = (0.405 + 𝑗0.24)
𝒁𝒍𝒊𝒏𝒆 (𝒑𝒖) = 𝟎. 𝟒𝟎𝟓 + 𝒋𝟎. 𝟐𝟒
𝟏𝟎𝟖. 𝟗
= 𝟎. 𝟎𝟕𝟒𝟒 + 𝒋𝟎. 𝟎𝟗𝟗𝟐 𝒁𝒄𝒂𝒃𝒍𝒆 (𝒑𝒖) =
𝟒. 𝟑𝟓𝟔
0
= 0.124∠53.130 = 𝟎. 𝟎𝟗𝟐𝟗 + 𝒋𝟎. 𝟎𝟓𝟓𝟏
𝟏𝟎 𝟑𝟑 𝟐 = 0.108∠30.670
𝑿𝒕𝟐 (𝒑𝒖) = (𝟎. 𝟎𝟖) ( ) ( ) = 𝒋𝟎. 𝟏𝟔 𝑆𝑏𝑎𝑠𝑒3𝜙 10 × 103
𝟓 𝟑𝟑 𝐼𝑏𝑎𝑠𝑒3 = = = 874.77 𝐴
= 0.16∠900 𝑘𝑉𝑏𝑎𝑠𝑒3𝜙 √3(6.6)
332
𝑋𝑡2 (𝑖𝑛 Ω) = (0.08) ( ) = 17.424 𝑍𝑡𝑜𝑡𝑎𝑙 (𝑖𝑛 𝑝𝑢) = 𝑍𝐺1 ||𝑍𝐺2 + 𝑋𝑡1 + 𝑍𝑙𝑖𝑛𝑒 + 𝑋𝑡2
5
332 + 𝑍𝑐𝑎𝑏𝑙𝑒
𝑋𝑡2 (𝑖𝑛 Ω) = (0.16) ( ) = 17.424 = (0.0744 + 0.0929)
10
+ 𝑗(0.0682 + 0.1 + 0.0992
10 × 103 + 0.16 + 0.0551)
𝐼𝑏𝑎𝑠𝑒2 = = 174.95 𝐴
33√3 = 0.1673 + 𝑗0.4825 = 0.5107∠70.880
1∠00
𝐼𝑆𝐶 (𝑖𝑛 𝑝𝑢) =
0.5107∠70.80
= 1.9582∠−70.880
𝐼𝑠𝑐 (𝑖𝑛 𝐴) = 1.9582 × 874.77 = 1.958 × 875
= 1,713 𝐴
𝐼𝑚𝑝𝑒𝑑𝑎𝑛𝑐𝑒 𝑏𝑒𝑡𝑤𝑒𝑒𝑛 𝐹 & 11 𝑘𝑉 𝑏𝑢𝑠 =
= (0.0744 + 0.0929) + 𝑗(0.1 + 0.0992
+ 0.16 + 0.0551)
= 0.1673 + 𝑗0.4143 𝑝𝑢
= 0.4468∠680 𝑝𝑢
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑑𝑟𝑜𝑝 (𝑖𝑛 𝑝𝑢)
= 0.4463∠680 × 1.9582∠ − 70.880
= 0.8739∠ − 2.880
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑑𝑟𝑜𝑝 𝑖𝑛 𝑘𝑉 = 0.8729 × 11
= 9.60 𝑘𝑉

Example 9.2

A 25 MVA, 11 kV generator with 𝑋"𝑑 = 20% is connected through a transformer, line and a transformer to a bus that supplies three identical
motors. Each motor has 𝑋"𝑑 = 25% and 𝑋′𝑑 = 30% on a base of 5 𝑀𝑉𝐴, 6.6 𝑘𝑉. The three-phase rating of the step-up transformer is
25 𝑀𝑉𝐴, 11/66 𝑘𝑉 with a leakage reactance of 10% and that of the step-down transformer is 25 𝑀𝑉𝐴, 66/6.6 𝑘𝑉 with leakage reactance of
10%. The bus voltage at the motors is 6.6 kV when a three-phase fault current occurs at the point F. For the specified fault, calculate

(a) the sub-transient current in the fault

(b) the sub-transient current in the breaker B

(c) the momentary current in the breaker B, and

(d) the current to be interrupted by breaker B in five cycles.

Given: Reactance of the transmission line =15% on a base of 25 MVA, 66 kV. Assume that the system is operating on no load when the fault
occurs.
Solution:

Zone 1 (Generator Circuit) Zone 2 (Transmission Line) Zone 3 (Motor Circuit)


𝑆𝑏𝑎𝑠𝑒3𝜙 = 25 𝑀𝑉𝐴 𝑆𝑏𝑎𝑠𝑒3𝜙 = 25 𝑀𝑉𝐴 𝑆𝑏𝑎𝑠𝑒3𝜙 = 25 𝑀𝑉𝐴
𝑘𝑉𝑏𝑎𝑠𝑒(𝐿−𝐿) = 11 𝑘𝑉 66 6.6
𝑘𝑉𝑏𝑎𝑠𝑒(𝐿−𝐿) = ( ) (11) = 66 𝑘𝑉 𝑘𝑉𝑏𝑎𝑠𝑒(𝐿−𝐿) = ( ) (66) = 6.6 𝑘𝑉
𝑋"𝑑 = 20% = 𝑗0.20 𝑝𝑢 11 66
𝑋𝑡1 = 10% = 𝑗0.10 𝑝𝑢 662 6.62
𝑍𝑏𝑎𝑠𝑒 = = 174.24 Ω 𝑍𝑏𝑎𝑠𝑒 = = 1.7424Ω
112 25 25
𝑍𝑏𝑎𝑠𝑒 = = 4.84 Ω (25 × 103 ) 25 × 103
25 𝐼𝑏𝑎𝑠𝑒 = = 218.69 𝐴 𝐼𝑏𝑎𝑠𝑒 = = 2,186.93 𝐴
25 × 103 66√3 6.6√3
𝐼𝑏𝑎𝑠𝑒 = = 1,312 𝐴 𝑋𝑡1 (𝑎𝑐𝑡𝑢𝑎𝑙 𝑟𝑒𝑓. 𝑡𝑜 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦) 25
11√3 𝑋"𝑑 = (0.25) ( ) = 𝑗1.25 𝑝𝑢
𝑋𝑡1 (𝑎𝑐𝑡𝑢𝑎) = (0.1)(4.84) = 𝑗0.484Ω 66 2 5
= ( ) (𝑗0.484) 25
11 𝑋′𝑑 = (0.3) ( ) = 𝑗1.5 𝑝𝑢
= 𝑗17.424 Ω 5
17.424 1∠00
𝑋𝑡1 (𝑝𝑢) = = 𝑗0.1 𝑝𝑢 𝐼"𝑔 = = 1.8182∠ − 900 𝑝𝑢
174.24 0.55∠900
𝑋𝑡2 = 𝑗0.10 𝑝𝑢 1∠00
𝑋𝑙 = 𝑗0.15 𝐼"𝑚 = 3 × = 2.4∠ − 900 𝑝𝑢
1.25∠900
𝐼"𝑆𝐶 = 𝐼"𝑔 + 𝐼"𝑚 = −𝑗1.8182 − 𝑗2.4
= −𝑗4.22 𝑝𝑢
𝐼"𝑆𝐶 (𝑖𝑛 𝑎𝑚𝑝𝑠) = 4.22 × 2,187 = 9,229 𝐴

2
𝐼"𝑆𝐶 = ( ) (−𝑗2.4) − 𝑗1.8182 = −𝑗3.42
3
= 3.42 × 2,187 = 7,479.5 𝐴
𝐼𝐵 (𝑚𝑜𝑚𝑒𝑛𝑡𝑎𝑟𝑦) = 1.6 × 7,479.5
= 11,967 𝐴
𝐼"𝑆𝐶 (𝑡𝑜 𝑏𝑒 𝑖𝑛𝑡𝑒𝑟𝑟𝑢𝑝𝑡𝑒𝑑 𝑏𝑦 𝑡ℎ𝑒 𝑏𝑟𝑒𝑎𝑘𝑒𝑟)
= 1.1 × 2187
1 1
× (2 × + )
𝑗1.5 𝑗0.55
= 7,581 𝐴