Power System Protection Fundamentals
Power System Protection Fundamentals
Example 9.1
Example 9.2
A 25 MVA, 11 kV generator with 𝑋"𝑑 = 20% is connected through a transformer, line and a transformer to a bus that supplies three identical
motors. Each motor has 𝑋"𝑑 = 25% and 𝑋′𝑑 = 30% on a base of 5 𝑀𝑉𝐴, 6.6 𝑘𝑉. The three-phase rating of the step-up transformer is
25 𝑀𝑉𝐴, 11/66 𝑘𝑉 with a leakage reactance of 10% and that of the step-down transformer is 25 𝑀𝑉𝐴, 66/6.6 𝑘𝑉 with leakage reactance of
10%. The bus voltage at the motors is 6.6 kV when a three-phase fault current occurs at the point F. For the specified fault, calculate
Given: Reactance of the transmission line =15% on a base of 25 MVA, 66 kV. Assume that the system is operating on no load when the fault
occurs.
Solution:
2
𝐼"𝑆𝐶 = ( ) (−𝑗2.4) − 𝑗1.8182 = −𝑗3.42
3
= 3.42 × 2,187 = 7,479.5 𝐴
𝐼𝐵 (𝑚𝑜𝑚𝑒𝑛𝑡𝑎𝑟𝑦) = 1.6 × 7,479.5
= 11,967 𝐴
𝐼"𝑆𝐶 (𝑡𝑜 𝑏𝑒 𝑖𝑛𝑡𝑒𝑟𝑟𝑢𝑝𝑡𝑒𝑑 𝑏𝑦 𝑡ℎ𝑒 𝑏𝑟𝑒𝑎𝑘𝑒𝑟)
= 1.1 × 2187
1 1
× (2 × + )
𝑗1.5 𝑗0.55
= 7,581 𝐴