Disjoncteurs e Courant Alternatif A Haute Tension: Ii (Ternati (Lnal Electr (Ltechnical Commissi (LN
Disjoncteurs e Courant Alternatif A Haute Tension: Ii (Ternati (Lnal Electr (Ltechnical Commissi (LN
Disjoncteurs e Courant Alternatif A Haute Tension: Ii (Ternati (Lnal Electr (Ltechnical Commissi (LN
4,
c 0 M M t s s t 0Enl e c T R 0 T E c H N t 0
i l uTEE R N A T t 0 N A L E
(affili6e
d l'0rganisation
Internationale - lS0)
deNormalisation
R E D l l M M A N D A T1I1( E
|LNA CE I
II{TERNATI(lN
ELAE
L C T R ( l T E C H NC
I COAMLM I S S I ( l N
(affiliated
to the International
0rganization - lS0)
for Standardization
IEC REC(lMMEIIDATI(lII
Publication
56-2
6dition-
Troisidme Thirdedition
)
1971
lr
Disjoncteurs
e courant
alternatif
a haute
tension
partie:
0euxiime Caracl6ristiques
n0minales
High-uoltage
alternating-cu
rrentcircuit-breakers
Parl2: Bating
Droits
dereproduction - Copyright
r6serv6s - all rights
reserved
Bureau delaCommission
Central Electrotechnique
lnternationale
1 ,r u ed eV a r e m b 6
0eneve,
Suisse
t.
t
i
rtr
c I
I
j
I
t I
I
t
1 - t l
tu
l
l
=*-*,++:'-'i
-
C. D. U./U.D. C. : 621.310.s7.025.oz7.s| .9.012.4
t .7.001.2.008.8
i
I
C t lM M I S S I ( l E
N TT C T B ( l T E G H
ONUEI I N T ER1 { A T( Il N A T E
(affili6e
i l'0rganisation
lnternationale
deNormalisation - lS0)
R E C ( l M M A N D A Tl 1I (E|LNA CE I
Publication
56-2
6dition-
Troisidme Thirdedition
1971
Disjoncleurs
e couranl
alternatil
a haute
tension
Deuxi0me
partie:Caractdristiques
nominales
High-uoltag
e alternating-cu
rrentcircuil-brea
kers
Parl2: Bating
PERPUSTAKAAN
pustT prtvfuutl^l ilA$ALrHIf il$Tirilr{
No. Ag"nd*
Taaggd
P 5 APR1s??
Bureau
Central
de la Commission
Electrotechnique
lnternationale
l, rue de Varemb6
0endve,
Suisse
?, 48.-
Fiix,'5
3 - t
CONTENTS
Page
FoRewoRo 5
Pnrpncr 5
Clause
l. Rated characteristics. 9
2. Rated voltage . ll
3. Rated insulation level t1
4. Rated frequency l5
5. Rated nolmal current l7
6. Rated short-circuit breaking current l7
7. Rated transient recovery voltage for terminal faults 2l
8. Rated characteristicsfor short-line faults . 29
9. Rated short-circuit making current 35
10. Rated duration of short-circuit 35
I 1. Rated operating sequence 35
12. Rated out-of-phase breaking current . 37
13. Rated line-chargingbreaking current J I
ApprNorx A - Calculation of specified transient recovery voltages for short-line faults from rated
characteristics . 55
.
- 5 -
FOREWORD
r) T h e f o r m a l d e c i s i o n so r a g r e e m e n t so f t h e I E C o n t e c h n i c a l m a t t e i - s ,p r e p a r e d b y T e c h n i c a l C o m m i t t e e s o n w h i c h a l l t h e
N a t i o n a l C o m m i t t e e s h a v i n g a s p e c i a l i n t e r e s t t h e r c i n a r e r e p r e s e n t e d ,e x p r e s s ,a s n e a r l y a s p o s s i b l e , a n i n t e r n a t i o n a l
c o n s e n s u so f o p i n i o n o n t h e s u b j e c t sd e a l t w i t h .
2) T h e y h a v e t h e f o r m o f r e c o m m e n d a t i o n s f o r i n t e r n a t i o n a l r , r s ea n d t h e y a r e a c c e p t e db y t h e N a t i o n a l C o m m i t t e e s i n t h a t
sense.
3) I n o r d e r t o p r o m o t e t h i s i n t e r n a t i o n a l u n i f i c a t i o n , t h e I E C e x p r e s s e st h e w i s h t h a t a l l N a t i o n a l C o m m i t t e e s h a v i n g a s
y e t n o n a t i o n a l r u l e s , w h e n p r e p a r i n g s u c h r u l e s , s h o u l d u s e t h e I E C r e c o n r m e n d a t i o n sa s t h e f u n d a m e n t a l b a s i sf o r t h e s e
rules in so far as national conditions will perntit.
4) T h e d e s i r a b i l i t y i s r e c o g n i z e do f e x t e n d i n g i n t e r n l t i o n a l a g r e e m e n to n t h e s e m a t t e r s t h r o u g h a n e n d e a v o u r t o h a r m o n i z e
n a t i o n a l s t a n d a r d i z a t i o n r u l e s w i t h t h e s e r e c o r n n r e n d a t i o n si n s o f a r : r s n a t i o n a l c o n d i t i o n s w i l l p e r m i t . T h e N a t i o n a l
C o m m i t t e e s p l e d g e t h e i r i n f l r - r e n c teo w a r d s t h a t e n d .
PREFACE
This Recommendation has been prepared by Sub-Committee 17A, High-voltage Switchgear and
Controlgear, of IEC Technical Committee No. 17, Switchgearand Controlgear.
A first draft was discussedat the meeting held in Paris in 1967 and in Arnhem in 1968.As a result of
this latter meeting, a final draft was submitted to the National Committees for approval under the Six
Months' Rule in June 1969.
This Publication forms part of the revision of I E C Publication 56 and constitutesPart 2: Rating.
Australia Italy
Belgium Netherlands
Canada Norway
Czechoslovakia Romania
Denmark South Africa
Finland Sweden
France Switzerland
Germany Turkey
Hungary United States
Iran of America
Israel Yugoslavia
The British National Committee recorded a negative vote becauseit is of the opinion that the values of
power frequency withstand voltages in column 3 of Table I are excessive.The values given are the values of
List 2 in Table I of IEC PublicationTl,Insulation Co-ordination, (fourth edition:1967). IEC Technical
Committee No.28,Insulation Co-ordination, at its meeting in Melbourne in 1969, discusseda revision
of this Table. It agreedthat List 2 should be eliminated and that in the remaining List I the values of 16 kV
and 22 kV applying to rated voltages of 3.6 kV and 7.2kY are to be reduced to 10 kV and 20 kV respectively.
IT
1
t
, 1
i '
- 7 -
Australia Netherlands
Belgium NorwaY
Canada Poland
Denmark Romania
Finland South Africa
France Sweden
Germany Switzerland
Iran TurkeY
Israel United Kingdom
Italy United States
Japan of America
Korea (Democratic People'sRepublic of) Yugoslavia
publication 56 has been divided into the following six parts which are published as separatebooklets:
,
- 9 -
l. Rated characteristics
The characteristicsof a circuit-breaker including its operating devices and auxiliary equipment
that shall be used to determine the rating, are the following:
a) Rated voltage.
b) Rated insulation level.
c) Rated frequency.
d) Rated normal current.
c) Rated short-circuit breaking current.
a) Rated characteristics for short-line faults, for three-pole circuit-breakers designed for direct
connectionto overheadtransmissionlines and rated at 52 kV and above and at more than 12.5kA
rated short-circuit breaking current.
b) Rated duration of short-circuit, for circuit-breakers not fitted with direct over-current release.
c) Rated line-charging breaking current, for three-pole circuit-breakers intended for switching
overheadtransmissionlines and rated at 72.5 kV and above.
f) Rated pressureof compressedgas supply for operation and interruption, where applicable.
'h
- lt
2. Rated voltage
The rated voltage of a circuit-breaker indicates the upper limit of the highest voltage of systems
for which the circuit-breakeris intended (seeIEC Publication 38, IEC Standard Voltages).
The rated voltage of a three-pole circuit-breaker shall be selectedfrom the list of standard values
given below:
S e r i e sI : 3 . 6 ; 7 . 2 ; 1 2 ; 1 7 . 5 ; 2 4 ; 3 6 ; 5 2 ; 7 2 . 5 .
S e r i e sI l : 4 . 7 6 ; 8 . 2 5 ;1 5 . 0 ;1 5 . 5 ; 2 5 . 8 3; 8 ; 4 8 . 3 ; 7 2 . 5 .
SeriesI: 50 Hz and 60 Hz.
SeriesII: 60 Hz based on current practice in the United Statesof America and Canada.
1 00 ; 1 2 3 ; 1 4 5 ;1 7 0 ; 2 4 53; 0 0; 3 6 2 ; 4 2 0 ; 5 2 5 ; 7 6 5 .
The rated insulation level of a circuit-breaker for use on a system exposed to overvoltages of
atmosphericorigin, shall be selectedfiom Tables I, II and III, pages I 3 and 15.
a) For rated voltages up to and including72.5 kV, two tables of rated insulation levels aregiven:
b) For rated voltagesabove 72.5 kY, the rated insulation levelsare given in Table III which contains
alternative values for full and reduced insulation.
Full insulation vaLuesare intended for circuit-breakers for use on systemshaving the neutral isolated,
resonant-earthed or non-effectively earthed.
Reduced insulation values are intended for circuit-breakers for use on systemshaving the neutral
effectively earthed.
Notes /. - Test values for circuit-breakers for use on systen-ls not exposed to overvoltages of atmospheric origin
are under consideration. Examples of such systems are pure cable netrvorks or power station auxiliary
services.
-13_-
3.- The test voltage valuesin Tables I, II and III apply at the standard referenceconditions of temperature,
pressureand humidity specifiedin IEC Publication 60: High-voltage test techniques.
Tru.B I
3.6 45 2l
7.2 60 27
t2 75 35
17.5 95 45
24 125 55
36 170 75
52 250 105
72.5 325 140
Tesrn II
4.76 60 t9
8.2s 75 26
15.0 95 36
t5.5 110 50
2s.8 150 60
38.0 200 80
48.3 2sa r05
72.s 350 160
- 1 5-
Taslr III
Reduced insulation
150
123
t45 230
245 39s
460
175 510
300 570
425 630
550 680
4. Rated frequency
The rated frequency of a circuit-breaker is the power frequency for which the circuit-breaker
designedand to which the other rated characteristicscorrespond.
:--
- 1 7 -
The rated normal current of a circuit-breaker is the r.m.s. value of the current which the circuit-
breaker shall be able to carry continuously without deterioration at its rated frequency with the
temperaturerisesof the various parts not exceedingthe valuesspecifiedin Table IV, page 19.
The values of rated normal currents shall be selectedfrom the following standard values:
4 0 0 ; 6 3 0 ; 8 0 0 ; 1 2 5 0 ; 1 6 0 0 ; 2 0 0 0 ; 2 5 0 0 ;3 1 5 0 ; 4 0 0 0 ; 5 0 0 0 ; 6 3 0 0 A
Note - The above values are selected from the R.l0 series, and, if required, higher values than those shown should
also be selected from this series.
Current transformers shall comply with IEC Publication 185, Current Transformers(Sectiontwo,
Clause 4).
The rated short-circuit breaking current is the highest short-circuit current which the circuit-breaker
shallbe capableof breakingunder the conditions of useand behaviourprescribedin this recommendation
in a circuit having a power frequency recovery voltage corresponding to the rated voltage of the circuit-
breaker, and having a transient recovery voltage equal to the rated value specified in Clause 7.
Where applicable,the provisions of Clause 8 concerningshort-line faults shall be taken into account.
The circuit-breaker shall be capable of breaking any short-circuit breaking current up to its rated
short-circuit breaking current containing any a.c. component up to the rated value and associated
with it any percentaged.c. component up to that specified,under the conditions mentioned above.
i) At voltages below the rated voltage, it will be capable of breaking its rated short-circuit breaking
current.
ii) At voltages above the rated voltage, no breaking current will be guaranteed except to the extent
provided for in Clause 12.
-r
I
l9 -
Tann lV
,C
deg C
I
I . Copper contacts in a l r :
- silver-faced (see Notes l, 2 and 6) r05 65
- not silver-faced 75 35
Copper contacts in o i l :
- silver-faced (see Notes 2 and 6) 90 50
- not silver-faced 80 40
N ot e.s I - When applying the temperature rise of 65 deg C, care should be taken to ensure that no damage is caused
to the surrounding insulating materials.
) - The quality of the silver-facing shall be of such a kind that:
a) alter any of the short-circurt test-duties;
b) after the mechanical test;
there is still a layer of silver at the contact points; otherwise, the contact shall be regarded as " not silver-
faced ".
J.- The values of temperature and temperature rise are valid whether or not the conductor connected to
the terminals is silver-faced.
4.- The temperature must not reach a value where the elasticity of the material is impaired. For pure copper,
this implies a temperature limit of 75 'C.
-2r-
6.1 The r.m.s. value of the a.c. component of the rated short-circuit breaking current shall be selected
from the followins values:
6 . 3 ;8 ; 1 0 ; 12 . 5 ; 1 6 ; 2 0 ; 2 5 ; 3 1 . 5 ; 4 0 ;5 0 ; 6 3 ;8 0 ; 1 0 0k A
a) For a circuit-breaker which can be tripped by the short-circuit current without the aid of any
form of auxiliary power, the percentaged.c. component shall correspond to a time intewal r
equal to the minimum opening time of the circuit-breaker.
b) For a circuit-breaker which is intended to be tripped solely by a form of auxiliary power, the
percentaged.c. component shall correspond to a time interval r equal to the minimum opening
time of the circuit-breaker plus one half cycle of rated frequency.
The minimum opening time mentioned above is the shortest opening time of the circuit-breaker
obtainable under any serviceconditions whether in a breaking operation or a make-break operating
cycle.
The percentagevalue of the d.c. component is dependent on the time interval r and standard values
are given in Figure 2, page 51.
The rated transient recovery voltage (TRV) for terminal faults, relating to the rated short-circuit
breaking current in accordance with Clause 6 is the reference voltage which constitutes the limit of
1 a
/ 1 -
the prospective transient recovery voltage of circuits which the circuit-breaker shall be capable of
breaking in the event of a short-circuit at its terminals.
The waveform of transient recovery voltagesvaries according to the arrangementof actual circuits.
In some cases,particularly in systemswith a voltage greater than 100 kV, and where the short-
circuit currents are relatively heavy in relation to the maximum short-circuit current at the point under
consideration,the transient recoveryvoltage contains an initial period of high rate-of-rise,followed by
a 1ater period of lower rate-of-rise. This type of wave is generally adequately represented by an
*.
envelope consisting of three line segmentsdefined by means of four parameters
The influence of local capacitance on the source side of the circuit-breaker produces a slower rate-
of-rise of the voltage during the first f'ew microseconds of the TRV. This is taken into account
by introducing a time delay.
This representationis also being applied to rated and other specifiedtransient recovery voltages
which are representedby four-parameter or two-parameter reference lines together with delay lines'
The following parameters are used for the representation of rated TRV:
c) Time delay
A circuit-breaker has a rated time delay ra (rrs). The circuit-breaker shall be capable of interrupting
in any circuit in which the TRV wave passesonce through a " delay line " and does not recross it.
- 2 5 -
first section of
The delay line starts on the time axis at the rated time delay /a, runs parallel to the
the referenceline and terminatesat a specified voltageu'(time co-ordinate t').
TnnLE V.q.
KV kv ps KV ps kVipr,s
Tenl,n Vs
Under consideration.
-27-
Tnsrn Vc
Rated First Time I TRV peak Time Time Voltagei Time I Rate
voltage reference co- | value co- delay co- I co- | of rise
voltage ordinate ordinate ordinate I ordinate
KV KV l,rs KV l-r.s ps k V l p r , t l k v / p s
U c : 1 . 4u t ;
u : : I u,; ta : 0.02 tt
TnsLE Vo
For rated voltages above 100 kV, four parametersare used. Values are given in Table Vc for a
first-pole-to-clearfactor of 1.3 and in Table Vp for a first-pole-to-clearfactor of 1.5.
The tables also indicate values of rate-of-rise,taken as u"f t'. and urft, in the two-parameter and
four-parametercasesrespectively,which, together with TRV peak values us, rn&! be used for purposes
of designation.
The values given in the tables are prospectivevalues. They apply to circuit-breakersfor general
transmissionand distribution in a three-phasesystemwith frequenciesof 50 Hz or 60 Hz consisting
of transformers, overhead lines, and short lengths of cable.
c) circuit-breakersadjacent to seriesreactors.
In circuits having large cable networks directly on the source side, it may be more economical to
use circuit-breakershaving a lower rate-of-riseof rated transient recovery voltage, but in this casethe
values shall be subject to agreementbetween manufacturer and user.
The rated transient recovery voltage corresponding to the rated short-circuit breaking-current on
the occurrence of a terminal fault, is used for testing at breaking-currents equal to the rated value.
However, for testing at breaking-currentslessthan 100%of the rated value, other values of transient
recovery voltage are specified(see Sub-clause 7.5 of I E C Publication 56-4); further additional require-
ments apply to circuit-breakers rated at 52 kV and above and having rated short-circuit breaking
currents exceeding12.5kA, which may be called upon to operate in short-line fault conditions (see
Clause 8).
Rated characteristics for short-line faults are required for three-pole circuit-breakers designed for
direct connection to overheadtransmissionlines and having a rated voltage of 52 kV and above and
a rated short-circuit breaking current exceeding 12.5 kA. These characteristicsrelate to the break-
ing of a single-phaseline-to-earth fault in a system with effectivelyearthed neutral.
Note. - For the purpose of this Recommendation,a single-phasetest at the voltage to neutral is deemed to cover
all types of short-linefault.
In this context it is consideredimmaterial that in isolatedneutral systemssingle-phaseline-to-earthfaults do
not subiecta circuit-breakerto short-linefault conditions'
- 3l
The short-line fault circuit is taken as composed of a supply circuit on the sourceside of the
circuit-breakerand a short line on its load side (see Figure 5, page 53) with the following rated
c har ac t er is t ic s :
Short-circuit current, in case of terminal fault, equal to the rated short-circuit breaking-current
of the circuit-breaker.
prospective transient recovery voltage, in case of terminal fault, given by the standard values in
Tables VIn, VIs (under consideration)and Table VIc.
Note. The standard values in Tables VII and VIc are derived fron-r Tables Va and Vo by dividing
voltages by the first-pole-to-clear factor of 1.5, the time co-ordinates remaining unchanged. See
also the Note of Sub-clause7.3.
Standard values of rated surge impedanceZ and rated peak factor k are given in Table VII, page
33, related to the number of conductors per phase.The correlation betweenthis number, the rated
voltage and the rated short-circuit current is also given.
TesI-E VIA.
TasLE Vls
T.tBrB VIc
KV KV ps KV ps ps k v l r r t l k V / P s
T.q.sI,nVII
U I Z
kv KA o
5 2 - = < U< 2 4 5
t.7 | 0.214
12.5<I<44
=40
375** 1.6 | 0.166
* Subject to special agreementbetween manufacturer and user, the parameters given for 3 or 4 conductors may be
uppii"d if the rated short-circuit current is equal or higher than 40 kA.
** The valuesof surgeimpedancefot 2,3 and4 conductors may be revisedin future in order to take account of conduc-
tor attraction with heavy short-circuit currents.
*** For the RRRV factor s, seeAppendix A, page 55.
- 3 5 -
The rated short-circuit making current, see Figure l. page 50, of a circuit-breakeris that which
correspondsto the rated voltage,and shall be 2.5 times the r.m.s. value of the a.c. component of its
rated short-circuitbreakins current (seeClause6).
The rated duration of short-circuitof a circuit-breakeris that period of time for which it can earry,
when closed,a current equal to its rated short-circuitbreaking current.
A rated duration of short-circuit need not be assignedto a circuit-breaker fitted with a direct
over-currentreleaseprovided that, when connectedin a circuit the prospectivebreaking current of
which is equal to its rated short-circuit breaking current, the circuit-breaker shall be capable of
carrying the resulting current for the break-time required by the circuit-breakerwith the over-current
releasesetfor the maximum time lag, when operatingin accordancewith its rated operatingsequence.
q) O-1-CO-I'-CO
t' : 3 min.
b) CO-r"-CO
wit h:
7" : 15 s, for circuit-breakersnot intendedfor rapid auto-reclosing
wher e:
O representsan opening operation,
CO representsa closing operation followed immediately (that is, without any intentional time-
delay) by an opening operation,
t, t' and /" : time-intervalsbetweensuccessiveoperations.
/ and r' should always be expressedin minutes (symbol min) or in seconds(symbol s).
/" should always be expressedin seconds(symbol s).
SeeIEC Publication 267: Guide to the Testing of Circuit-Breakers with respect to Out-of-phase
Switching.
The rated line-charging breaking current is the maximum line-charging breaking current that the
circuit-breaker shall be capable of breaking at its rated voltage and under the conditions of use and
behaviour prescribedin this specificationand without exceedingthe appropriate maximum permissible
switching overvoltages(under consideration).
Tlsrn VIII
Rated line-charging
breaking current
72.5 t0
100 20
r23 31.5
r45 50
170 63
24s 125
300 200
362 315
420 400
525 500
Note. - For singleconductor overheadlines operating at 50 Hz, the breaking currents indicated in Table VlIl imply
a length in kilometres approximatelyequal to 1.2 times the rated voltage of the circuit-breakerin kilovolts.
The rated cable-charging breaking current is the maximum cable-charging current that the circuit-
breaker shall be capable of breaking at its rated voltage and under the conditions of use and behaviour
prescribed in this specification and without excaedingthe appropriate maximum permissible switching
overvoltages (under consideration).
-39-
TesI.r IX
3.6 t0
7.2 l0
t2 25
17.5 31.5
24 31.5
36 50
52 80
72.5 12s
100 125
123 r40
145 160
174 r60
245 250
300 315
362 355
420 400
525 500
Note. - The values of Table lX correspond to the normal maximum requirements of the majority of power systenrs.
Cable-charging currents in excessof these values should be the subject of special agreement between manu-
facturer and user.
The rated capacitor breaking current is the maximum capacitor breaking current that the circuit-
breaker shall be capable of breaking at its rated voltage and under the conditions of use and behaviour
prescribed in this specification and without exceedingthe appropriate maximum permissible switching
overvoltages(under consideration).
This breaking current refers to the switching of a single (isolated) shunt capacitor bank. The
assignment of a rated capacitor breaking current to a circuit-breaker is not mandatory but is made
on request.
Note. - Standard values of rated capacitor breaking currents are under consideration and, until these have been
agreed internationally, values based on the R.10 series should be assigned to particular circuit-breakers,
either through national standards, or by agreement between manufacturer and user.
Under consideration.
I
4t-
The rated supply voltage of closing or opening devices is the voltage which determines their
conditions of operation and of heating, as well as the insulation of the control circuits.
The supply voltage of thesedevicesshall be understood to mean the voltage measuredat the circuit
terminals on the apparatus itself during its operation, including, if necessary,the auxiliary resistor
or accessoriessupplied or required by the manufacturer to be installed in series with it, but not
including the conductors for the connection to the electricity supply.
The rated supply voltage for auxiliaries shall preferably have one of the appropriate standard
values in Tables X. XI and XII.
Tenr.e X
Direct current
24
48
I l0 or 125
220 or 250
TesI-n XI
Single-phasea.c.
SeriesI SeriesII
100 120
220 t201240
240
Note. - Where two values are indicated, they refer to three-wire systemsand the lower value is the voltage between
phasesand neutral, the higher value being the voltage betweenphases.
Where only one value is indicated,it refers to two-wire systems.
Tlsrr XII
Three-phasea.c.
Series I SeriesII
1271220 1201208
2201380 240l4rs
2771480
Note. - The two values indicated refer to four-wire systems and the lower value is the voltage between phases and
neutral, the higher value being the voltage between phases.
'I
43-
Rated supply voltages of auxiliary circuits shall preferably be selectedfrom the standard values in
Tables X, XI and XII, page 41.
19. Rated supply frequency of closing and opening devicesand of auxiliary circuits
The rated supply frequency of closing and opening devicesand of auxiliary circuits is the frequencl'
at which the conditions of operation and heating of these devices and circuits are determined.
The rated pressureof a compressedgas supply for operating a pneumatic control device or a gas-
blast circuit-breaker is the pressureat which the conditions for operation of the control device or
for arc extinction are determined.
For circuit-breakersprovided with individual reservoirs, the pressure of the gas supply shall be
understood to mean the pressuremeasuredin the reservoir immediately before the operation of the
circuit-breaker.
For specific operating requirements, it is also necessaryto know the maximum and minimum
operating pressures.
No standard values of rated pressureare given, these being specifiedby the manufacturer.
The co-ordination tables are not mandatory and are intended as a guide for preferred values.
-45-
Tesr,B XIII
3.6 l0 400
16 630 250
25 250 I 600 2 500
4A 2s0 1 600 2 500 4 000
7.2 8 400
12.5 400 630 250
l6 630 250 600
25 630 254 600 2 500
40 250 600 2 500 4 000
l2 8 400
12.5 400 630 250
l6 630 250 600
25 630 2s0 600 2 500
40 254 600 2 500 4 000
50 250 600 2 500 4 000
I
40 I 600 2 500 4 000
8 630
12.5 630 250
t6 630 2s0 600
I
25 250 600 2 500 I
52 8 800
12.5 | 2s0
20 | 250 I 600 2 000
Note. - The co-ordination table is not mandatory and is intended to be used as a guide for preferred values.There-
fore a circuit-breakerwith another combination of the rated values is not outside the I E C Recommendation
for circuit-breakers.
The valuesof the rated voltage are those given in Sub-clause2.1 for SeriesI. The valuesof the rated short-
circuit breakingcurrent and rated normal current are selectedfrom thosegivenin Clause 5 and Sub-Clause6.1.
47-
Tnnr,EXIV
(Under consideration)
The values given in the present table show for inforrnation the present practice
in U.S.A. and Canada
I{ote. - The co-ordination table is not mandatory and is intended to be used as a guide for preferred values. There-
fore a circuit-breaker with another combination of the rated values is not outside the I E C Recommendation
for circuit-breakers.
The values of the maximum rated voltage are those given in Sub-clause 2.1 for Series Il. The values of rated
normal current are selected from those given in Clause 5. See Note in Clause 6r,) regarding interpolation of
short-circuit breakine currents for intermediate voltages.
I
_49_
Tnsr,B XV
362 20 2 000
31.5 2 000
40 1 600 2 000 3 150
40 I z o o oI 3 r 5 o I
Note. - The co-ordination table is not mandatory and is intended to be used as a guide for preferred values. There-
fore a circuit-breaker with another combination of the rated values is not outside the I E C Recommendation
for circuit-breakers.
The values of rated voltage are those given in Sub-clauses2.2, omitting 100 kV. The values of rated short-
circuit breaking current and rated normal current are selectedfrom those given in Clause5 and Sub-clause6.1.
-50-
ligne de z6ro
BX
normal zero line
valeur efficace de la composante p6riodique du courant d chaque instant, mesur6e d partir de CC'
DD'
r.m.s. value of the a.c. component of current at any instant, measured from CC'
Courant 6tabli
lrvtc
making current
i
t
- 5l -
P o u r c e n t a g ed e l a c o n r p o s a n t ea p 6 r i o d i q u e
P e r c e n t a g ed . c , c o m p o n e n t
100
90
BO
70
60
50
40
30
20
10
10 2A 30 40 50 OU 70
T e m p s A p a r t i rd u d 6 b u t d u c o u r a n t d e c o u r t - c i r c u i t
T i m e f r o m i n i t i a t i o no f s h o r t - c i r c u i t r (ms)
- --_
-\)-
L '1 L2 Temps
Time
Frc. 3. - Repr6sentation d'une TTR sp6cifi6e par un trac6 de r6f6rence ir quatre paramdtres
et par un segment de droite d6finissant un retard.
Representation of a specified TRV by a four-parameter reference line and a delay line.
T e ns i o n
Voltage
rd L Lg
Temps
Time
Flc. 4. - Reprdsentation d'une TTR spdcifide par un tracl de rdf6rence d deux paramdtres
et par un segment de droite d6finissant un retard.
Representationof a specifiedTRV by a two-parameterreferenceline and a delay line.
T
53-
X I ,
4
source de puissance
G
source of power
disjoncteur
CB
circuit-breaker
imp6danced'onde de la ligne
z surge impedance of line
-55-
APPENDIX A
l. Basic approach
For rating and testing purposes,it has been decided to consider only a short-line fault occurring
from one phase to earth in a system having the neutral effectively earthed, the severity of this being
suffi.cientto cover other cases,except in special circumstanceswhere the system parameters may be
more severethan the standard values.
(Jp: UI 13 (1)
This voltage drives the current 1" through the circuit consisting of reactancesX, and X, in series.
The r.m.s. value of the voltage drop on the source side will be:
When the current is broken the instantaneousvoltase to earth of the line terminal of the circuit-
breaker will be:
This voltage will return to zero by a series of travelling waves reflected back and forth along the
line between the circuit-breaker and the fault, producing a transient voltage on the line side in the
form of a damped saw-tooth oscillation * as shownby u" in Figure 6,page 62.The voltage to earth
on the source side terminal of the circuit-breaker will also be uo at the instant of breaking. It will
rise to a peak value z- depending upon the transient recovery voltage characteristics on the source
side as shown by u" in Figure 6, the crest value U- of the power frequency voltage to earth on the
source side (after the ending of transient phenomena)becoming:
The resulting specified transient recovery voltage for short-line faults appearing across the circuit-
breaker is the differencebetween the source and the line side voltages as shown by u, - uL in Figure 6.
* Note. - In practice the saw-tooth shapeis in some degreemodified by an initial time delay due to lumped capaci-
tances present at the terminals of the circuit-breaker (capacitancesof voltage transformers, current trans-
formers, etc.); also the top of the oscillation is slightly rounded. However, there is insufficientinformation
available at this time to specify values.
*\--,
l*
'----*-'--
- 5 7 -
The ratio betweenthe voltage uo at the instant of breaking and the crest value U^ of the driving
voltage is dependent only on the reduction in current due to the reactanceof the line, and is inde-
pendent of rated voltage, rated short-circuit breaking current and the line constants. hence:
This relation is shown in Table XVI for the standard ratios of short-line fault currents: for other
ratios it can be taken from Figure 7, page 63.
Tnsrn XVI
The line-side characteristicshave been standardized as shown in Table VII, page 33.
The excursion a"* of the line-sidevoltage urfrom the initial value ao is obtained by multiplying the
value uoby the appropriate peak factor k:
uL* =: kuo Q)
The time /" to the first voltage peak a"* is obtained from the rate-of-riseof voltage of the line-side
transient, as follows:
The rate-of-rise dutldt of the line-side voltage on breaking the current I : f"^f Tsin(2rcf t)
at current zero is:
where:
-59-
Valuesof s correspondingto the surgeimpedancesin Table Vll, page 33, forf : 50 Hz and 60Hz
are given in Table XVII below.
Tanr-r XVII
Rate-of-rise
factorsfor line-sidetransientvoltages
0.2t4
0 . 16 6
0.146
uL*
tL : (e)
s Ir,
After time /, the voltage will fall to zero by a damped saw-toothoscillation;the exact shapeof this
dependingupon the characteristicsof the actual line. This is shown as an exampleonly by the dotted
lines in Figure 6, page 62, as the preciseform of these oscillations is not specified.
Note. - The approximate length of line corresponding to a given short-line fault can be obtained by the formula:
r-j (10)
The course of the source-sidetransient voltage from the initial value uoto the peak value u^canbe
derived from Tables VI, pages 31 and 33. The times tr, tr, /B and /u given there canbeuseddirectly.
The voltaEa ut in Table VIc equalling the power-frequencycrest voltage U*, is not affected,but the
TRV peak value a" must be scaleddown to the value a_ such that
In service,the source-sidevoltage will commenceto rise as a curve having as a boundary the delay
line. The most important part of the short-line fault transient recovery voltage is up to the time t,
of the first voltage peak on the line side. For the calculation of the source-sidecontribution z,* at
6t-
the time /L, negligible error is introduced by ignoring the curvature, the voltage being deemed
to
follow the straight delay line running parallel to the referenceline with time delay /6, compare
Figures 3
and 4, page 52.
5. Example of calculation
Circuit-breaker ratinss :
U:245kVi I:3t.5kAi f :50H2
Short-line fault current considered:
Ir-: 0 . 7 5I = : 2 3 . 6 k A
Power-frequencycrest voltage [from equation (5) or u, in Table VIc, page 33]:
uo : 0.25 x 200 =: 50 kV
First excursionof line-sidevoltage[from equation(7) and TableVII, page33]:
u L *- 1 . 7x 5 0 : 85kV
Time /t to first peakof line-sidevoltage[from equation(9) and TableXVII of this Appendix]:
85 85
tL : ;:;; ^- -: :--:-: : 16.8
1 6 ' 8P
rrss
o2L4\ 23s: 5.05
LengthL of line to fault [from equation(10)]:
o'3x16'8:2.52km
L-
2
From the above data,the initial line-sidetransientcan be constructed(seeFigure 6, page
62),
The times tr, t, and lo for the source-sidevoltage can be obtained from Table VIc:
t r : 3 0 0l r s i t,:900psi ta:6ps
Source-siderate of rise:
200- s0
: 0.5 kV/pts
300
Source-side
voltagecontributionat time /r:
u"* : (t" - /J 0.5 : (16.8 -
6) 0.5 =: 5.4 kV
(if t" I tu the source-sidecontribution is deemed to be zero).
Peak voltage Ltmon the sourceside [from equation (12) or Table XVI of this Appendix]:
I
I
)
_62_
ut
1-"1"--'---
---.-/-
irrr A
U :u,
m l
200 kv /l\i /A-
t
/
U s^ - U Lt l
/
. t v
\iJ
I
J''il
uo
16.8
fL
'l
'[
1r
I
i
i
r
I
I
u ^ lun
-
u^ u^
-1
uo l L
m
Frcune 7