On-load tap-changer OILTAP® R
Technical Data TD 115
2 TD 115/02 115/02/01/0
Table of Contents
Table of Contents
1 General .................................................................................................................................................................................................................. 4
1.1 Summary of the technical data ....................................................................................................................................................... 4
1.2 Survey ....................................................................................................................................................................................................... 6
NOTE
These technical data are intended for the calculator and designer of the transformer. These type-specific data are only
valid in connection with the information contained in the general section (TD 61) since this section contains important
information on such subjects as potential connection, leakage inductance, current division, and so on.
Dimensional drawings and connection diagrams are subject to change without prior notice.
Drawings submitted during bidding and ordering are always binding.
Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformer
manufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirements
of the transformer are met.
115/02/01/0
TD 115/02 3
1 General
1 General
Max. rated step voltage Uim 4000 4000 4000 4000 3000
(in V)1)
Operating positions Without change-over selector: max. of 18 With change-over selector: max. of 35
Oil compartment Pressure-proof up to 0.3 bar continuous difference pressure (test pressure 0.6 bar),
head and cover of the on-load tap-changer are vacuum-proof.
Temperature range The on-load tap-changer OILTAP® R can be operated in the rated load range with oil
temperatures of -25 °C to +105 °C.
Table 1 a
4 TD 115/02 115/02/01/0
1 General
with change- 595 (7704)) 410 (5004)) 505 (6404)) 505 (6404)) 595 (7804))
over selector
Displacement 72.5 kV 289 (3674)) 274 (3534)) 280 (3604)) 280 (3604)) 286 (3674))
volume 123 kV 314 (3924)) 299 (3764)) 305 (3844)) 305 (3844)) 311 (3924))
(in dm3)
ca. 170 kV 334 (4124)) 319 (3964)) 325 (4044)) 325 (4044)) 331 (4124))
245 kV 354 (4324)) 339 (4164)) 345 (4244)) 345 (4244)) 351 (4324))
Table 1 b
115/02/01/0
TD 115/02 5
1 General
1.2 Survey
8997470E_01
Fig. 1a Survey of the on-load tap-changer designs (no. of poles, change-over selector, and installation lengths)
6 TD 115/02 115/02/01/0
1 General
8997470E_02
Fig. 1b Survey of the on-load tap-changer designs (no. of poles, change-over selector, and installation lengths)
115/02/01/0
TD 115/02 7
1 General
Survey of the basic connection diagrams (figures 2a, 2b, 2c) with designation of the tap selector contact terminals in accord-
ance with MR standards. This contact terminal designation corresponds to the specifications in the on-load tap-changer
dimensional drawings.
Fig. 2a
8 TD 115/02 115/02/01/0
1 General
Fig. 2b
8906164D_2
115/02/01/0
TD 115/02 9
1 General
Fig. 2c
8906164D_3
10 TD 115/02 115/02/01/0
1 General
115/02/01/0
TD 115/02 11
1 General
Fig. 4 Example: On-load tap-changer R III 1200 Y–E, basic connection diagram 14 27 1 G
12 TD 115/02 115/02/01/0
1 General
115/02/01/0
TD 115/02 13
1 General
14 TD 115/02 115/02/01/0
2 Technical Data
2 Technical Data
2.1 Rated through-current (Iu), rated step voltage (Ui) and step capacity (PStN)
R I 2003
On-load- R III 1200 Y R I 1201 R I 2002 (Special R I 24021) R I 3003
tap-changer design)
Iu (A) 700 1200 700 1200 1070 2000 1300 2000 1400 2400 2000 3000
Ui (V) 4000 2500 4000 2500 4000 2200 4000 3000 4000 2500 3000 2000
PStN (kVA) 2800 3000 2800 3000 4280 4400 5200 6000 5600 6000 6000 6000
Table 2 Rated through-currents (Iu), related rated step voltages (Ui) and step capacities (PStN),
at highest and lowest rated step voltage of the step capacity curve (see fig. 7 and fig. 8)
1)
Note: R I 2402 with forced current division by two parallel winding branches
Fig. 7
Step capacities (rated step voltages Ui, rated through-
currents Iu) for on-load tap-changer R III 1200 Y,
R I 1201, R I 1202
CAUTION:
Only applies to network service. When used for
8997510E
industrial transformers, please contact us.
115/02/01/0
TD 115/02 15
2 Technical Data
8997510E
Fig. 8
Step capacities (rated step voltages Ui, rated through-currents Iu) for on-load tap-changer R I 2002,
R I 2003 (= special design), R I 2402, R I 3003.
Note: 1) R I 2402 with forced current division by two parallel winding branches.
CAUTION: Only applies to network service. When used for industrial transformers, please contact us.
16 TD 115/02 115/02/01/0
2 Technical Data
KHW 579-4
Fig. 9 Expected mean contact life under average load
n – Number of operations
Iu – Rated through-current
Ium – Max. rated through-current
115/02/01/0
TD 115/02 17
2 Technical Data
With coarse tap selector in (+) - position With coarse tap selector in (-) - position
CAUTION
Adhere to the maximum rated
8997560M lightning impulse withstand
voltage stress on a0 in mid-position.
18 TD 115/02 115/02/01/0
2 Technical Data
Insulation Tap selector size C Tap selector size D1) Tap selector size E
distances kV 1.2I50 kV, 50 Hz, 1 min kV 1.2I50 kV, 50 Hz, 1 min kV 1.2I50 kV, 50 Hz, 1 min
a0 Ub £ 72.5 kV: 140 kV 1.2I50; 30 kV, 50 Hz, 1 min / Ub >72.5 kV: 80 kV 1.2I50; 3 x USt
Table 3 Rated withstand voltages (in kV) of the internal insulation of the tap selector
1)
Note: Tap selectors in accordance with basic connection diagrams 10 09 1 W, 12 11 1 W, 14 13 1 W are designed as
18 09 1 W, 18 11 1 W, 18 13 1 W.
Tap selectors in accordance with basic connection diagrams 16 15 1 W and 18 17 1 W are not possible.
2)
Higher values up to 550 kV on request
3)
Omitted for on-load tap-changers R I 1201, R I 2002/2402, R I 3003
The tap selector size (ID letters C, D, E) characterizes the internal insulation of the tap selector whose rated withstand
voltages must be adjusted to the requirements of the transformer winding.
The permissible maximum service voltage along the individual tap selector paths is half the AC withstand voltages listed in
table 3.
115/02/01/0
TD 115/02 19
3 Appendix
3 Appendix
Dimensional drawings
On-load tap-changer OILTAP® R III 1200 Y, tap selector size C/D, E ...................................................................................... 896722, 897867
On-load tap-changer OILTAP® R I 1201, tap selector size C/D, E ........................................................................................... 899753, 899401
On-load tap-changer OILTAP® R I 2002, tap selector size C/D, E ........................................................................................... 896721, 897866
On-load tap-changer OILTAP® R I 2402, tap selector size C/D, E ........................................................................................... 897490, 897864
On-load tap-changer OILTAP® R I 3003, tap selector size C/D, E ........................................................................................... 896720, 897865
Tap selector and change-over selector terminal contacts, tap selector size E ...................................................................................... 897868
Installation drawings
Tap selector size C/D ................................................................................................................................................................................................ 896705
Tap selector size E ..................................................................................................................................................................................................... 897873
Additional drawings
On-load tap-changer head .................................................................................................................................................................................... 893899
On-load tap-changer cover with mounting flange for pressure relief valve ........................................................................................ 895168
Versions of the on-load tap-changer head, swiveling range of gear unit ............................................................................................. 896703
Special design for installation in bell-type tanks ........................................................................................................................................... 896762
Horizontal drive shaft, tap selector size C/D, E .............................................................................................................................. 896708, 897872
Jumpers for parallel connection of tap selector terminal contacts for on-load tap-changer OILTAP® R I 2002,
R I 3003, selector size C/D, E ................................................................................................................................................................ 896706, 898713
Tap selector bottom, shielding, tap selector size C/D .................................................................................................................................... 896702
Tap selector bottom, tap selector size E ............................................................................................................................................................ 897869
Tie-in resistors, tap selector size C/D .............................................................................................................................. 896707, 898124 - 898135
Potential switch, tap selector size C/D, E ......................................................................................................................................... 898136, 898614
Additional drawings for on-load tap-changer ................................................................................................................................................ 898826
20 TD 115/02 115/02/01/0
8967227E
On-load tap-changer OILTAP® R
R III 1200 - C/D, dimension drawing
115/02/01/0
TD 115/02 21
8978677E
On-load tap-changer OILTAP® R
R III 1200 - E, dimension drawing
22 TD 115/02 115/02/01/0
8997530E
On-load tap-changer OILTAP® R
R I 1201 - C/D, dimension drawing
115/02/01/0
TD 115/02 23
8994011E
On-load tap-changer OILTAP® R
R I 1201 - E, dimension drawing
24 TD 115/02 115/02/01/0
8967218E
On-load tap-changer OILTAP® R
R I 2002 - C/D, dimension drawing
115/02/01/0
TD 115/02 25
8978666E
On-load tap-changer OILTAP® R
R I 2002 - E, dimension drawing
26 TD 115/02 115/02/01/0
8974905E
On-load tap-changer OILTAP® R
R I 2402 - C/D, with forced current division with two parallel
winding branches, dimension drawing
115/02/01/0
TD 115/02 27
8978646E
On-load tap-changer OILTAP® R
R I 2402 - E, with forced current division with two parallel
winding branches, dimension drawing
28 TD 115/02 115/02/01/0
8967208E
On-load tap-changer OILTAP® R
R I 3003 - C/D, dimension drawing
115/02/01/0
TD 115/02 29
8978657E
On-load tap-changer OILTAP® R
R I 3003 - E, dimension drawing
30 TD 115/02 115/02/01/0
8978683E
On-load tap-changer OILTAP® R
Tap selector size E,
tap selector and change-over selector terminal contacts
115/02/01/0
TD 115/02 31
8967056E
On-load tap-changer OILTAP® R
Tap selector size C/D, installation drawing
32 TD 115/02 115/02/01/0
8978733E
On-load tap-changer OILTAP® R
Tap selector size E, installation drawing
115/02/01/0
TD 115/02 33
893899AE
On-load tap-changer OILTAP® MS, M, R, RM
On-load tap-changer head, centric drive
34 TD 115/02 115/02/01/0
8951685E
On-load tap-changer OILTAP® MS, M, R, RM
With flange for pressure relief valve
115/02/01/0
TD 115/02 35
8967034E
On-load tap-changer OILTAP® R
Versions of the on-load tap-changer head, swiveling range and
drive direction of the gear unit
36 TD 115/02 115/02/01/0
8967627E
On-load tap-changer OILTAP® MS, M, R, RM
Special design for installation in bell-type tank
Lifting device
O-Ring 44.2 - 5,7
Suction pipe
Transformer cover
O-Ring
Level traverse
Supporting flange
Level traverse
Z = Guiding pin
115/02/01/0
TD 115/02 37
8967087E
On-load tap-changer OILTAP® MS, M, R, RM
Horizontal drive shaft (limit dimensions)
Tap selector size C/D, centric drive
38 TD 115/02 115/02/01/0
8978723E
On-load tap-changer OILTAP® R
Horizontal drive shaft (limit dimensions)
Tap selector size E, centric drive
115/02/01/0
TD 115/02 39
8967066E
On-load tap-changer OILTAP® R
R I 2002, R I 3003, tap selector size C/D
Jumpers for parallel connection of tap selector terminal contacts
40 TD 115/02 115/02/01/0
8987131E
On-load tap-changer OILTAP® R
R I 2002, R I 3003, tap selector size E
Jumpers for parallel connection of tap selector terminal contacts
115/02/01/0
TD 115/02 41
8967028E
On-load tap-changerOILTAP® R
Tap selector size C/D, tap selector bottom shown with the lowest parts connected to
the voltage, standard design without grading ring, special design with grading ring
42 TD 115/02 115/02/01/0
8978695E
On-load tap-changer OILTAP® R
Tap selector size E, tap selector bottom shows lowest parts
connected to voltage
115/02/01/0
TD 115/02 43
8967078E
On-load tap-changer OILTAP® R
Tap selector size C/D, principal arrangement of potential switch and
tie-in resistors
44 TD 115/02 115/02/01/0
8981242M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WP, tap selector size C/D,
Um = 72.5 kV to 300 kV, 2 x 14 to 2 x 18 resistors
115/02/01/0
TD 115/02 45
8981252M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WP, tap selector size C/D,
Um = 72.5 kV to 300 kV, 2 x 3, 2 x 5, to 2 x 13 resistors
46 TD 115/02 115/02/01/0
8981262M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WP, tap selector size C/D,
Um = 72.5 kV to 300 kV, 2 x 4, 2 x 6 to 2 x 12 resistors
115/02/01/0
TD 115/02 47
8981272M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WP, tap selector size C/D,
Um = 72.5 kV to 300 kV, 3 to 26 resistors
48 TD 115/02 115/02/01/0
8981282M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WR, tap selector size C/D,
Um = 72.5 kV to 300 kV, 2 x 14 to 2 x 18 resistors
115/02/01/0
TD 115/02 49
8981292M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WR, tap selector size C/D,
Um = 72.5 kV to 300 kV, 2 x 3, 2 x 5, to 2 x 13 resistors
50 TD 115/02 115/02/01/0
8981302M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WR, tap selector size C/D,
Um = 72.5 kV to 300 kV, 2 x 4, 2 x 6, to 2 x 12 resistors
115/02/01/0
TD 115/02 51
8981312M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R I to WR, tap selector size C/D,
Um = 72.5 kV to 300 kV, 3 to 26 resistors
52 TD 115/02 115/02/01/0
8981322M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R III 1200 WP, tap selector size C/D,
Um = 72.5 kV to 245 kV, 3 x 2 to 3 x 7 resistors
115/02/01/0
TD 115/02 53
8981332M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R III 1200 WP, tap selector size C/D,
Um = 72.5 kV to 245 kV, 3 x 8 to 3 x 10 resistors
54 TD 115/02 115/02/01/0
8981342M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R III 1200 WR, tap selector size C/D,
Um = 72.5 kV to 245 kV, 3 x 2 to 3 x 8 resistors
115/02/01/0
TD 115/02 55
8981352M
On-load tap-changer OILTAP® R
Tie-in resistor cylinder R III 1200 WR, tap selector size C/D,
Um = 72.5 kV to 245 kV, 3 x 9 to 3 x 11 resistors
56 TD 115/02 115/02/01/0
8981362M
On-load tap-changer OILTAP® R
Potential switch R III 1200 WS, R I to WS, tap selector size C/D,
Um = 72.5 kV to 300 kV
115/02/01/0
TD 115/02 57
8986142M On-load tap-changer OILTAP® R
Potential switch R III 1200 WS, R I to WS, tap selector size E,
Um = 72.5 kV to 300 kV
58 TD 115/02 115/02/01/0
8988261E On-load tap-changer OILTAP® R
Additional drawings for on-load tap-changer
115/02/01/0
TD 115/02 59
© Maschinenfabrik Reinhausen GmbH Phone +49 941 40 90-0
www.reinhausen.com Falkensteinstrasse 8 Fax +49 941 40 90-111
93059 Regensburg, Germany E-Mail [email protected]
Please note: The data in our publications may differ from the data of the devices delivered.
We reserve the right to make changes without notice.
TD 115/02 en • 0903/1000 • 115/02/01/0 • F0019601 • Printed in Germany