IPM Troubleshooting

This Tech Tip is to be used if The Inverter Power Module (IPM) is


you are getting an IPM error or located where the compressor leads
attach to the printed circuit
the compressor does not start.
board(PCB).They are marked U,V and W
on the PCB and where the Yellow and
1.Turn power off to outdoor unit and Blue wires attach P and N
wait 3 minutes for DC voltage to
discharge.
2.Check that IPM is wired Test 2
correctly.(According to Schematic) Place meter in (Diode mode)
3.Check the following resistance values
on the IPM. (Before taking resistance
readings remove all wires connected to the
IPM.On certain models the red and black wires
to the ACTPM and white and black wires to
CN200 on control board should also be
removed.)
4. All readings on test 1 should be
within +/- 20 ohms of each other and
test 2 should be within values shown.

Test 1
Place meter in (Mega Ohms)

5.If the readings on Tests 1 or 2 are


incorrect and the wiring is correct
replace the board that contains the IPM
and depending on model the ACTPM
board if it has one.
6.When your IPM is bad you will also
need to ohm out compressor and test
outdoor fan motor according to Tech Tip
#008 and confirm both are good before
replacing the IPM or any other boards.
Tech Tip #014
Rev. Date 11/20/13