Test Report For Motor Protection Relay-Sel 710: DATE: 21.06.2018
Test Report For Motor Protection Relay-Sel 710: DATE: 21.06.2018
Test Report For Motor Protection Relay-Sel 710: DATE: 21.06.2018
Serial No : 3140060039
1. Phase Over Current TOC – [ 51P] Non Directional Current (I) – 4XFLA A : TD- 0s ,FLA:0.905
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 3.62 3.62 0 0.034
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 5 5 0 0.015
Y-N 5 5 0 0.020
B-N 5 5 0 0.019
JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 1.81 1.81 5 4.93
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 0.814 0.814 5 5.04
Phase Sett Voltage (v) Inj. Voltage(v) Actual Tripping Trip Time(s)
Time (s)
R-N 45 45 2 2.02
Y-N 45 45 2 2.00
B-N 45 45 2 2.02
JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018
Check List:
JAYAMKONDAN V MR.JEYAKUMAR