Stability Test Diagram For Typical Substation

1. The document contains diagrams for testing the stability of SOLKOR switchgear under different fault conditions. 2. The diagrams show the test setup connections between a minimum 250kVA generator, switchgear panels and transformers. 3. Notes explain that for each test the circuit breaker under test should be closed while other breakers are open, and faults are applied both inside and outside the protected zone.

Uploaded by

ajeez86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
1K views3 pages

Stability Test Diagram For Typical Substation

1. The document contains diagrams for testing the stability of SOLKOR switchgear under different fault conditions. 2. The diagrams show the test setup connections between a minimum 250kVA generator, switchgear panels and transformers. 3. Notes explain that for each test the circuit breaker under test should be closed while other breakers are open, and faults are applied both inside and outside the protected zone.

Uploaded by

ajeez86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

SOLKOR Stability Test Diagram

11kV SWBD at BS-160S/S


Panel-7 : INCOMER-1 Feeder
Panel-9 : INCOMER-2 Feeder

(Note 1)

630/1A 87F
CT
HV Test Plug

1R x 3C x 150
(900m)

630/1A CT 87F
11kV Isolation SWBD At B-1 Generator
S/S
G Min. 250kVA
Panel-4 : O/G Feeder
Panel-9 : O/G Feeder
TEMPORARY
CABLE

11 KV B-1
SS

(Note 2)
11/3.3kV
2000kVA

3.3 KV B-1
SS

Note
1. VCB shall be in rack-out position.
2. Disconnect the permanent cable and connect Test Generator cable to outgoing
feeder terminal.
TR Diff. Stability Test Diagram

Generator
G Min. 250kVA

574-SWBD-
1004A/B
11kV Isolation (Note 1)
SWBD
at Unit S/S

574-TR-
09/10
11/0.457kV
2000kVA

(Note 4)

87T

(Note 1)
574-SWBD/MCC-1006, 440V SWBD/MCC at Unit
S/S

(Note 2)

(Note 3)

Note
1. Particular VCB/ACB under test shall be in service position and closed.
2. The other CB’s shall be in isolated position.
3. Fault point outside protected zone. (3-phase short circuit)
4. Fault point inside protected zone. (3-phase short circuit)
TR REF Stability Test Diagram

Generator
G Min. 250kVA

574-SWBD-
1004A/B (Note 1)
11kV Isolation
SWBD
at Unit S/S

574-TR-
09/10
11/0.457kV
2000kVA

(Note 4)

64R

(Note 1)
574-SWBD/MCC-1006, 440V SWBD/MCC at Unit
S/S

(Note 2)

(Note 3)

Note
1. Particular VCB/ACB under test shall be in service position and closed.
2. The other CB’s shall be in isolated position.
3. Fault point outside protected zone. (1-phase to earth fault)
4. Fault point inside protected zone. (1-phase to earth fault)