Report
Report
Report
1) INTRODUCTION
3) RELAYS
4.1 Introduction
4.2 Main circuits in transformers
4.2.1 Magnetic Circuit
4.2.2 Electric Circuit
4.2.3 Dielectric Circuit
4.2.4 Thermal Circuit
4.2.5 Structural Circuits
4.3 Instrument transformer
4.3.1 Current transformer
4.3.2 Potential transformer
4.4 Metering and indicating instruments
4.5 Power line carrier communication system
5) STRUCTURAL STRUCTURES
5.1 Conservator
5.2 Breather
5.3 Pressure relief device/expansion vent
5.4 Temperature indicators
5.5 Buchol’z relay
5.6 Bushings
5.7 Tap Changer
5.7.1 Off-Circuit tap changer
5.7.2 On Load Tap Changer
2
Page
LIST OF ABBERVIATIONS
1. ac Alternating current
2. dc Direct current
3. kV Kilo Volts
4. PT Potential transformer
5. CT Current transformer
6. HT High terminal
7. MOCB Minimum Oil Circuit Breaker
8. IDMTL Inverse Minimum Time Over
Current Relay
3
Page
Page
4
INTRODUCTION
In the beginning of the electrical age, electricity was generated,
transmitted and distributed in the form of direct current and voltages
were low. With the development of transfer, ac system has become
predominant. The present day large power systems have been possible
only due to adoption of ac system.
Introduction:-
ii) The grid station has double bus-bar system, one main bus-bar and the
other reserve bus-bar. The incoming lines can be connected to either
bus-bar with the help of an arrangement of ckt. Breaker & isolators. The
advantage of a double bus-bar system is that if t repair is to be carried on
one bus-bar or isolators, clamps or insulators of one bas bar, the supply
need not to be interrupted as the entire load can be transferred to the other
bus.
1x15MVA = 15MVA
Page
v) The instrumental transformers (P.T.) and (C.T.) are used for metering &
protections of the system. The secondary’s of the C.T and P.T are
connected to the energy meter and relays through cables via cable trench.
of relay ckt. The P.T is connected right on the point where the line is
terminated. The CTs are connected at the terminals of each ckt. Breakers.
vi) The lighting arresters are connected near the transformers terminals (on
H.T. side) to protect them from lighting strokes.
vii) Again there is provision for further step down 132 kv supply to 33kv by
two transformers-2x50MVA-100MVA
viii) There are other is auxiliary in the grid station such as wave trapper,
capacitor bank for power factor improvement, earth connections, local
supply connections, dc supply connections.
1.3 SUBSTATIONS
8
Page
Substations serve as a source of energy supply for the local areas of
distribution in which these are located. Their main functions are to receive energy
transmitted at high voltage from the generating stations, reduce the voltage to a
value appropriate for local distribution and provide facilities for switching. Some
substations are simply switching stations where different connections between
various transmission lines are made; others are converting substations which
convert AC into DC or vice versa or convert frequency from higher to lower or
vice versa. Substations have some additional functions. They provide points where
safety devices may be installed to disconnect equipment or circuit in the event of
fault. Voltage on the outgoing feeder can be regulated at a substation. A substation
is convenient place for purpose of improving power factor and make measurement
to check the operations of the various parts of the power system.
The substations may be defined as the assembly of apparatus, which transforms the
characteristics of electrical energy from one form to another: e.g- from AC to DC
or the voltage in operation from 66kv, 110kv or 220kv. However, 500kv will be
used for the national grid system in the near future. The consumer do not use such
high voltage and so they must be transformed to low voltage levels by means of
substations, thus a substation may be called as link between the generating stations
and the consumer.
The advantage of outdoor type is that do not need any buildings. In case of indoor
type the cost of transformers and switch gear equipments are less than that of
outdoor type. Also the conditions for inspections and maintenance are better in
indoor type than in outdoor types.
insulators.
Page
This arrangement has been quite frequently adopted where the load and continuity
of supply justify additional cost. This type of bus bar is used in Gladni(Bus 1 and
Bus 2).
2.3 INSULATORS
The line conductors supported on the towers in such a way that currents from
conductors do not flow to earth through supports. This is achieved by securing the
conductors to support with the help of insulators. The insulators provide necessary
insulation between the conductor and supports, thus prevent any leakage current
from conductors to earth.
The insulators serve two purposes. They support the conductors; confine the
current to the conductors. The most common material for manufacture of the
insulators is porcelain. Toughened glass is also sometimes used for insulators but
its use is limited to about 33 KV. The design of the insulators is such that the stress
due to contraction and expansion porcelain to come in direct contact with hard
metal screw thread. Normally cement is used between metal and porcelain.
TYPES OF INSULATORS:-
There are several types of insulators and there use in the substation will depend on
the service requirements:-
Pin Type
Suspension Type
Post Insulator Type
14
Page
2.3.1 PIN TYPE INSULATOR :-
As the name suggests, the pin type insulator is secured to the cross-arm to
the pole. There is a groove on the upper end of the insulator for housing the
conductor. The conductor passes through this groove and is bound by the annealed
wire of the same material as of conductor.
The pin type insulators are normally used up to 33KV .It is not desirable to
use them beyond 50 KV as a cost of such insulators then increase much faster than
the voltage.
For high voltage greater than 33kv these insulators are used they
consist of number of porcelain discs connected in series by metal links in form of a
string. The conductor is suspended at the bottom and the end of this string while
the other end of the string secured to the cross-arm of the tower. Each disc is
design for 11KV. The number of discs in series would depend upon the working
voltage.
Post insulator is used for bus bars. A post insulator consists of porcelain body, cast
iron cap and flanged cast iron base. The hole in the cap is threaded so that the bus
can directly bolt to the cap.
15
Page
2.4 ISOLATING SWITCHES :
One of the important developments in the design of oil circuit breaker has
been to reduce the amount of oil needed. The other advantages are reduction in
tank size, reduction in total weight and reduction in cost. It used minimum amount
of oil and is only used for arc extinguishing. The current conducting parts are
insulated by porcelain or organic insulated material. Low oil circuit breaker
employs solid materials for insulations purpose and uses smallqtty.of oil which is
just sufficient for arc extinguishing .By using suitable arc control devices, the arc
extinguishing can be further facilitated in low circuit breaker. There are two
different design of the arching chamber in terms of the venting provided; - Axial
venting; radial venting.
Axial venting generates high gas pressure and high dielectric strength; it
17
is used mainly for the interruption of low current at high voltages. The radial
Page
venting is used for interruption of relatively heavy current at low voltages as a gas
pressure developed is low and also the dielectric strength is low.
The negative ion formed are relatively heavier as compared to free electrons and
therefore under a given electric field the ions do not attain sufficient energy to lead
cumulative ionization in the gas.
In such breakers (degree of vacuum being from 10-7 to 10-5tore) is used as arc
quenching medium. Since vacuum offers the high insulating strength, it has
superior quenching properties than any other medium e.g. when contacts of the
breaker are opened in vacuum , the interruption occurred at first current zero with
dielectric strength between the contacts building at a rate of 1000 th of times higher
than that obtained with other circuit breaker . Thus a vacuum arc is different from
the general class of low & high pressure arc. In the vacuum arc the neutral atoms,
ions and electrons do not come from the medium in which the arc is drawn but
they are obtained from the electrodes themselves by evaporating its surface
material, because of the large mean free path for the electrons, the dielectric
strength of the vacuum is a 1000 times more than when the gas is used as the
interrupting medium. In this range of vacuum the break down strength is
independent of the gas density and depends only on the gap length and upon the
20
2.5.2 APPLICATIONS :
For a country like India where distance are quite large & accessibility
to remote areas difficult the insulation of such outdoor ,maintenance free circuit
breaker should prove a definite advantage . Vacuum circuit breaker are being
employed for outdoor application ranging from 22KV to 66KV with limiting of
say 62 to 100 MVA ; they are suitable for a majority of applications in rural
areas.
21
Page
2.6 LIGHTENING ARRESTERS :
It is protective device which conducts the high voltage surges on the power
systems to the ground.
Surge voltages are abnormal voltage that may cause break down of insulation of
electrical equipment. These voltages may result from switching disturbance in the
electrical installation circuit or from lightning stroke.
In Gladni grid station valve type arrester is used. It consists of two assemblies:
Series spark gaps and non-linear resistor discs. These both are connected in
series under normal conditions; the normal system voltage is insufficient to
cause the breakdown of air gap assembly. On the occurrence over voltage, the
breakdown of series spark gap take place and the surge current is conducted to
earth via the non-linear resistor. They provide effective protection.
22
Page
4.3 INSTRUMENT TRANSFORMERS :
The lines I substation operate at high voltage and carry current of
1000 of amperes. The measuring instruments and protective devices are
designed for low voltages (for generally 110 volts) and currents (about 5 A).
Therefore, they don’t work satisfactory if mounted directly on the lines this
difficulty is overcomes by installing instrument transformers on the power
lines. The function of these instrument transformers is to transfer voltage or
current in the power lines to values which are convenient for the operation of
measuring instrument and relays. There are two types of instrument
transformers viz
Current Transformer
4.3.2 POTENTIAL TRANSFORMER:
Potential Transformer
24
Page
4.4 METERING & INDICATING INSTRUMENTS :
A WAVE TRAP
3) PROTECTIVE RELAY AND EARTHING
It is a device that detects the faults and initiates the operation of the
ckt breaker to isolate the defective element from the rest of the system .The
relay ensures the safety of the ckt equipment from any damage which might
be otherwise caused by the fault.
Buchol’z relay is a gas actuated relay used for protecting oil immersed
transformer against all types of internal fault and makes use of the fact that fault
decompose oil thus generating gases. The device relies on the fact that an electrical
fault inside the transformer tank is accompanied by generation of gas, and if the
fault current is high enough by a surge of oil from the tank to the conservator.
27
Page
3.3 EARTHING:-
(1 ) SYSTEM EARTHING :-
It is required to provide low fault impedance to the ground fault currents for proper
operation of the protective relays and for meeting the system requirement by
effectively earthed system.
( II ) SAFETY EARTHING :-
It is required to provide protection to the operating staff working in the yard and
substation from any injury during fault condition by keeping the voltage gradient
with in safe limits. The above two parts have common earth mat from which flat
iron risers are taken out to connect all the non-current carrying metal parts of the
equipment. At the same time the earth mat conductor rise to voltage, which is
equal to the resistance of the earth mat multiplied by ground fault current. This
difference of potential results in voltage gradients.
28
Page
3.3.1 NEUTRAL GROUNDING:-
A) Fuses
B) Carrier-current Equipment
C) Substation AuxiliarySupplies.
29
Page
FUSES :
4.1 INTRODUCTION:-
Cold rolled grain oriented silicon (CRGOS) Steel (with lower specific
losses to the flow of magnetic flux along the direction of grain
orientations is universally utilized.
With the advent of computer controlled machines for cutting the
laminations precisely, step lap lamination joints are economically used to
achieve low no- load losses.
31
Page
4.2.1 ELECTRIC CIRCUIT:-
It consists of primary and secondary winding which are costliest and which have to
meet stringent requirement of Dielectric, thermal and mechanical stresses expected
during testing as well as service conditions. ANNEALED rectangular shaped
copper conductors most commonly used and for Distribution transformer and high
voltage testing transformers and conductor are also used. In order to minimize the
stray losses in the winding, continuously transposed conductor (CTC) are used
type of winding normally include Helical, continuous Disc, Multilayer and inter
leaved Disc winding.
It comprises of insulation:
- Minor insulation between lure to lure on within the layers of same winding.
- Oil serves as an insulation as well as coolant paper oil combination has been
This is essential to house the transformer oil, flitting and accessories such as
terminal arrangements, conservator, Breather, safety device etc. The structural
32
5.1 CONSERVATOR:
surface.
Page
5.2 BRAETHER:-
Both transformer oil and celluloses’ paper are highly hygroscopic .Paper being
more hygroscopic than mineral oil .The moisture, if not excluded from oil surface
in conservator, this will find its way finally into paper insulation and causes
allowed to breath only through silica gel column, which absorb the moisture in air
Transformers tank is a pressure vessel as the inside pressure can group steeply
whenever there is a fault in the windings and the surrounding oil is suddenly
vaporized. TANKS as such are tested for a pressure with stand capacity of 0.35 kg
/cm. To prevent bursting of the tank, these tanks are in addition providing with
expansion vents with a thin diaphragm made of Bakelite /Copper / glass at the end.
In present day transformer, pressure relief device are replacing expansion vents.
These are similar to safety valves on boilers.
Most of transformer (Small transformers have only OTI) are providing with
indicators that display oil temperature and winding temperature .There are
thermometers.
35
Page
5.5 BUCHOL’Z RELAY:-
Buchol’z relay is a gas actuated relay used for protecting oil immersed
transformer against all types of internal fault and makes use of the fact that fault
decompose oil thus generating gases. The device relies on the fact that an electrical
fault inside the transformer tank is accompanied by generation of gas, and if the
fault current is high enough by a surge of oil from the tank to the conservator.
5.6 BUSHINGS:
Transformer are connected to HV lines and therefore care is to taken to prevent flash-over from
high voltage connections to earthed tank .Connections from cables are made in cable boxes , but
overhead connections are to be brought through bushing specially designed for different classes
of voltages.
36
Page
BUSHINGS
It is very essential to maintain system voltage within prescribed limits for better
health of electrical equipments voltage of system can be varied by changing the
true ratio of transformer .The device tap changer is used for adding a cutting out
turns of primary or secondary winding of transformer .It is of basically two types :
The cheapest method of changing turn ratio of transformer is use of off-circuit tap
On-load tap changers are employed to change the turn ratio of the transformer to
regulate system voltage while transformer is delivering normal load. With the
considerably improved.
38
Page
133.3 MVA TRANSFORMER (SINGLE PHASE)
39
Page
160 MVA POWER Transformer (3 Phase)
LV(A)
Page
50MVA EMCO Transformer
LV
41
LV 699.8 874.7
50 MVA CGL Transformer
TYPE OF COOLING ONAN ONAF
No load voltage HV(KV) 132.8
LV 33
Current HV 218.7
42
Page
43