Engineering Specification
CABLE CLEATS AND INTERMEDIATE RESTRAINTS
4. Short circuit Rating
a. The maximum mechanical force between conductors during exposure to a short circuit
(equation recognized by EN-50368:2003) is stated as:
Ft = (0.17 x IPEAK2) / S
Where:
Ft = Maximum Force on Conductor (N/m)
IPEAK = 1st Cycle Peak Asymmetrical Short Circuit Current (kA)
S = Spacing between conductor centers (meters)
b. The manufacturer will deliver short circuit mechanical force calculations in accordance
with EN 50368:2003 for the following:
i. The specified project application using the manufacturer recommended cleat
spacing
ii. The application listed in the independent third-party test certificate
iii. The calculations will clearly indicate the following:
1. Ft = Maximum Force on Conductor (N/m)
2. IPEAK = 1st Cycle Peak Asymmetrical Short Circuit Current (kA)
3. S = Spacing between conductor centers (meters)
4. Cable outer diameter used in calculation (meters)
c. The calculated mechanical force between conductors for the specified project
application must be less than or equal to the forces resulting from the certified test
report for the same EN 50368:2003 short circuit protection category (i.e. Category 1 or
Category 2).
d. Short circuit tolerance shall be documented by an independent third-party test certificate
from a nationally or internationally certified testing laboratory. Manufacturer self-
certification will not be accepted.
e. If only RMS short circuit values are known for the specified project application, the
manufacturer shall apply the following formula to calculate the maximum mechanical
force on the conductors:
ii. Where:
1. ISC-RMS = RMS Short Circuit Current (kA)
2. IPEAK = ISC-RMS x 2.2
f. Test certificates shall document the final physical condition of the cables, Cable Cleats
and intermediate restraints after the short circuit test(s).
i. The Cable Cleats and intermediate restraints shall be intact with no missing
metallic parts (including mounting, fastening and closure hardware and devices).
ii. The Cable Cleats and intermediate restraints shall be reusable, and capable of
removal and reinstallation.
iii. There shall be no cuts or damage to the outer sheath of the cable caused by
Cable Cleats or intermediate restraints as a result of excessive cable movement
during the test.
iv. Cables shall successfully pass the specified voltage withstand test if Category 2
short circuit test has been carried out.
Sheet 2 of 3
Engineering Specification
CABLE CLEATS AND INTERMEDIATE RESTRAINTS
v. Any missing parts or damage as stated above will cause the Cable Cleats and
intermediate restraints to be deemed unacceptable for the specified project
application.
g. Test certificates shall clearly state whether the subject Cable Cleats and intermediate
restraints are certified to either EN 50368:2003 Category 1 or Category 2 resistance to
electromechanical force.
5. Product Features
a. The use of integral liners is recommended for Cable Cleats and intermediate restraints
in order to:
i. Cushion cables from the magnetic forces arising during fault currents
ii. Protect cables from chafing against the Cable Cleat frames, intermediate
restraint frames and mounting system in areas subject to recurring vibration
iii. Protect cables from chafing against the mounting system between two modules
subject to the differential movement (common on offshore structures and marine
vessels)
iv. Protect the cables from the extreme movement found in high-shock installations
(e.g. military and seismic applications)
v. Restrain cables from axial movement during periods of thermal elongation
b. For applications requiring the use of mounting surface adapters (e.g. mounting the cleat
around a non-perforated ladder tray rung), the adapters shall ideally be integral to the
cleat frame.
c. Cable Cleats shall have ‘range-take’ capability to accommodate the manufacturing
tolerances common to electrical cable manufacturing.
6. Materials of Construction
a. Metallic or composite cleats shall be aluminum or non-magnetic 316L marine grade
stainless steel (including brackets, mounting adapters and any permanently mounted
manufacturer supplied installation and fastening means).
b. Liners shall be low-smoke, low-fume, zero halogen, polymeric material with UV
stabilization for use in high salt, marine outdoor (e.g. exposed to sunlight) locations.
c. Certain applications (e.g. chemical laden environments) may require the use of
specialized finishes or coatings. The manufacturer shall propose alternate finishes or
coatings as required.
7. Documentation
a. The following documentation shall accompany every proposal:
i. A copy of the relevant independent third-party short circuit test certificate
ii. The manufacturer’s short circuit mechanical force calculations in accordance with
EN 50368:2003 for the following:
1. The specified project application using the manufacturer recommended
cleat and restraint spacing
2. The Cable Cleat application documented in the third-party test certificate
iii. Data sheets for the recommended Cable Cleats and intermediate restraints
iv. Installation guides for the recommended Cable Cleats and intermediate restraints
v. Technical drawings of the Cable Cleats and intermediate restraints.
Sheet 3 of 3