Load Characteristics and Power Factor Correction: 6 Lecture's Outline
Load Characteristics and Power Factor Correction: 6 Lecture's Outline
Lecture 6th
Load Characteristics
and Power Factor Correction
Course Teacher:
Dr. Muhammad Mohsin Aman
Course Code:
EE-524
Course Title:
Electrical Power Distribution System Engineering -1
Venue:
Department of Electrical Engineering , NED University Karachi.
1
Utilization Factor
✓Utilization Factor (FU): It is the ratio of the maximum demand of a system
to the rated capacity of the system. Therefore FU is:
maximum demand
FU
rated system capacity
✓The utilization factor can also be found for a part of the system.
✓Another factor is defined to indicate the actual use that is made of plant and
is called plant use factor.
38,750
Plant Capacity Factor 0.46 46%
3,500 24
Therefore,
38,750 kWh
Plant Use Factor 0.994 99.4%
39,000kWh
Remarks
• In the above example, the load curve variation and the exact size of
plant to fit the load curve are chosen as ideal, the plant use factor being
practically 100%. This would rarely be achieved in practice. It would be
difficult to choose units of such capacity that when in use they could run
continuously on full load.
• In practice the plant use factor would be much smaller than 100%. It
is however higher than the plant capacity factor when some reserve plant
is necessary.
• A number of staring and loading operations can be easily handled in
hydro and diesel electric stations but are time consuming in steam stations.
Problem
Load factor, plant capacity factor
and the use factor
Problem
• The annual load duration curve a
power system is shown in Fig. 2.3. The
maximum demand is 20MW. The load is
supplied by two power plant, one having
a capacity of 12.5MW and the other a
capacity of 10MW.
• Plant no. 1 (12.5MW) is used
throughout the year and plant No. 2 is
used whenever the load exceeds the
capacity of plant no. 1.
Problem
• The area aqprefa under the load
duration curve represents the energy
produced by plant No. 1 during the year.
This is found to be 98x105 kWh
(given).
• The area abqa under the load
duration curve represents the energy
produced by plant No. 2. The area abqa
represents 9,900,000 kWh (given).
• Find out the load factor, annual load
factor, plant capacity factor and the plant
use factor of each plant.
Solution
• Plant No. 1 (12.5MW) is run to supply as
much of the load as it can for 100% of the
year. This is therefore shown on the lower
portion of the load duration curve and when a
plant is used in this way it is known as base
load plant.
• The remaining load, above this line is
supplied by plant No. 2. A plant used is this
way is known as a peak load plant, as it
supplies the load on top portion of the curve.
Solution
Plant No. 1
• The line aq is the line of
demarcation of load, as the maximum
load is supplied by this plant is 12.5MW.
• Plant No. 1 is run for all the time,
namely 100% of the year and the
maximum load that it can supply is
12.MW. It has no reserve capacity.
• Therefore load factor of plant No. 1,
acting as a base load plant
Energy consumed during year
Load factor
Maximum Demand x 8760hrs
98,000 ,000
0.895 89 .5%
12,500 8760
Solution (load factor, plant capacity factor and the use factor )
• There is no reserve at plant No. 1 so that its capacity factor is the same as its
load factor, i.e. 89.5%.
98,000,000
Plant Capacity factor 89.5%
12,500 8760
• All the plant has been running for the whole year i.e. 8760 hours
continuously. The plant use factor therefore is same as the plant capacity or load
factor.
98,000,000
Annual Load Factor 89.5%
12,500 8760
98,000,000
Plant Use Factor 89.5%
12,500 8760
Solution
• Plant No. 2 supplies the remaining load;
the maximum demand on it is 7.5MW and it
is run for 40% of the year; its capacity is
10MW.
• The load factor of plant No. 2 is the
area under the abqa and the no. of hrs during
which the plant is run.
9,900,000
Load factor 37.6%
7,500 0.4 8760
Solution (load factor, plant capacity factor and the use factor )
• Similarly
9,900,000
Annual Plant Capacity Factor 11.3%
10,000 8760
9,900,000
Plant Use Factor 28.2%
10,000 0.4 8760
Problem
• Find out the annual load factor of the whole system for the
previous problem.
Solution
• The annual load factor of the whole system can also be found
from the data.
• Total energy generated =
98,000,000+9,900,000=107,900,000kWh
107 ,900,000
AnnualLoad factor of a system 0.615 61.5%
20,000 8760
Solution
• The annual load duration curve thus helps in choosing the plants for
base load and peak load operation for the required length of time.
• The load factor, plant capacity factors and plant use factors can be
calculated from the load duration curve.
• From this information, it is possible to study the financial aspects of
supplying the system load.
• The cost of generation per kWh for the base-load plant and for the
peak load plant can be worked out.
• The capacity required in the base load plant and peak load plant,
economical load sharing between the two plants and the minimum
combined cost per kWh generated by the whole system can be determined.
Solution
• The load factor the peak load plant is much less than that of the base
load plant.
• It is cheaper to generate power at the higher load factor. The cost of
energy to supply base load is therefore less than the cost of energy to
supply peak load.
Items KU
Motors Typical 0.75
Lighting Circuits 0.1
Socket Outlets 0.1 to 0.2
✓where kVA is the actual maximum 3-phase apparent-power value shown on the
diagram for the circuit concerned, and U is the phase to- phase voltage (in volts).
Power Factor
✓In alternating current circuits, the current absorbed by the user can be represented
by two components:
1. The active component IR, in phase with the supply voltage.
2. The reactive component IQ, in quadrature to the voltage.
✓ In the most common case, in the presence of ohmic-inductive type loads, the
total current (I) lags in comparison with the active component IR.
✓ In an electrical installation, it is necessary to generate and transmit active power
P and a certain reactive power Q, which is essential for the conversion of
electrical energy, but not available to the user.
✓ The complex of the power generated and transmitted constitutes the apparent
power S.
Power Factor
✓The necessary formulae are as follows:
P VI R VIcos
Q VI Q VIsin
S P jQ P 2 Q 2
Power Factor
✓Power factor (cosϕ) is defined as the ratio between the active component IR and
the total value of the current l; ϕ is the phase shifting between the voltage U and the
current I. It results:
I R P VIcos
Power Factor cos
I S VI
✓The reactive demand factor (tanϕ) is the relationship between the reactive power
and the active power:
Q
tan
P
Q Ptan
Power Factor
✓Table 1 shows some typical power factors:
Where
▪ P is the active power
▪ Q1 and ϕ1 are the reactive power and the phase shift before power factor
correction
▪ Q2 and ϕ2 are the reactive power and the phase shift after power factor
correction
▪ QC is the reactive power supplied from capacitor bank
Kc Factor
Table 2 shows the value of
the relationship
QC
KC ( tan1 tan 2 )
P