Earthing Calculation, Rev-5, (As BUILT)
Earthing Calculation, Rev-5, (As BUILT)
Earthing Calculation, Rev-5, (As BUILT)
IP1475-8378-61-0982 05
PROJECTS & DEVELOPMENT INDIA LTD IPL DOCUMENT NO REV
SHEET 1 OF 6
FORM NO: 02-0000-0021F2 REV1Z:\8378 Backup consultancy LPG Mounded bullet IOCL Haldia\electrical\jpkhorwal\8378 AS BUILT DATED
21.05.09\EARTHING CALCULATION REV.04\EARTHING CALCULATION REV-5 (AS BUILT).doc All rights reserved
33 CLIENT : IOCL HALDIA IP1475-8378-61-0982 05
PLANT : OHCU HALDIA REFINERY IPL DOCUMENT REV
PROJECT : 8378 SHEET 3 OF 6
1. SCOPE.
This documents details the Earthing system calculation for the Backup Consultancy
LPG Mounded Bullets at IOCL Haldia
2. SITE CONDITION
4. EARTHING CALCULATION
4.1 Calculation Method
4.1.1 Calculation of Earthing Conductor Size:
The earthing conductor size is calculated by the following equation taken from
Code of practice for Earthing, IS-3043-1987 section 12.2.2.1
S = (Ixªt) / k (mm2)
Where
FORM NO: 02-0000-0021F2 REV1Z:\8378 Backup consultancy LPG Mounded bullet IOCL Haldia\electrical\jpkhorwal\8378 AS BUILT DATED
21.05.09\EARTHING CALCULATION REV.04\EARTHING CALCULATION REV-5 (AS BUILT).doc All rights reserved
44 CLIENT : IOCL HALDIA IP1475-8378-61-0982 05
PLANT : OHCU HALDIA REFINERY IPL DOCUMENT REV
PROJECT : 8378 SHEET 4 OF 6
4.1.3 STRIP ELECTRODES
The Strip Electrode resistance (RS) is calculated by following formula taken from
Code of practice for earthing IS 3043 section 9.2.3
Where
RS= (100!) x log; (2xI ²/wt) / (2xxI) (ohms)
RS : Resistance of Strip Electrode
! : Soil resistivity (Ohm-m)
I : Length of the strip (cm)
w : Depth of burial of the electrode (cm)
t : Width of the Strip (cm)
ANNEXURE
S = (Ixªt ) / k
Minimum Earth Conductor size required to meet the short circuit requirement is
calculated as below
I :50KA
t :1Sec
K :56
S = (Ixªt) / k
=50000 xª1 / 56
= 892.85
Since 75X12 mm = 900 Sq. mm
B) The maximum fault current at down stream load terminal in process area will be
very less ie 7.557 KA for calculation refer Annexure –1 ( 1 sheet ). Considering the
fault current 7.557KA for 1 Sec with corrosion factor the earth strip size will be =
202 Sq. mm
Accordingly the 50x6 Sq.mm earth Conductor size shall be adequate.
Since the earthing system are designed for 50KA for 1 sec , hence the earth
Strip size selected as 75x12 Sq.mm
Formula Used
! : 6.10 Ohm-m (Refer Soil Investigation report)
I : 300cm (As per doc No. LI-OEE-STD-0177)
d : 10 cm (As per doc No. LI-OEE-STD-0177)
FORM NO: 02-0000-0021F2 REV1Z:\8378 Backup consultancy LPG Mounded bullet IOCL Haldia\electrical\jpkhorwal\8378 AS BUILT DATED
21.05.09\EARTHING CALCULATION REV.04\EARTHING CALCULATION REV-5 (AS BUILT).doc All rights reserved
66 CLIENT : IOCL HALDIA IP1475-8378-61-0982 05
PLANT : OHCU HALDIA REFINERY IPL DOCUMENT REV
PROJECT : 8378 SHEET 6 OF 6
n = 2 Nos
RE =Re / n
= 1.549/ 2
= 0.7745
RT=RE II RS
RS= 0.0492
RE= 0.7745
RT=
RT = RS x RE / RS + RE
= 0.0492 x 0.7745/ 0.0492 + 0.7745
= 0.0381/ 0.8237
= 0.0462 ohms
= < 1 ohms
5) CONCLUSION
6) NOTES
1. Earth Electrodes shall be connected to each other by GI strip of size 75x12 Sq.mm
(1Run)
2. New earthing shall be connected to existing earthing system at the nearest point by
GI Strip of size 75 x 12 Sq.mm
FORM NO: 02-0000-0021F2 REV1Z:\8378 Backup consultancy LPG Mounded bullet IOCL Haldia\electrical\jpkhorwal\8378 AS BUILT DATED
21.05.09\EARTHING CALCULATION REV.04\EARTHING CALCULATION REV-5 (AS BUILT).doc All rights reserved
Annexure –1
Fault level calculation for plant area
Motor rating = 75 Kw
Zc = (0.02884 + j 0.011928)
I/Zm Pu = - j 0.0104
= 5.4326 MVA
Due to cable impedance the Maximum fault current at down stream load terminal in process area will
be very less ie 7.557KA
Earth strip size based on fault current = 7.557KA is
I = 7.557 KA
t = 1 Sec.
K = 56
S = I x ªt / K = 7.557x ª1 / 56 = 135 Sq.mm
Corrosion factor = 150 %
= 135 Sq mm X 1.5 = 202.5
Since = 50 x 6 mm = 300 Sq. mm
1) Calculation of earth strip size considering fault current at down stream load terminal in
process area is only for information.
2) Earthing system are designed for 50 KA for 1 Sec. Hence the earth strip size selected as
75x12 Sq.mm
Z:\8378 Backup consultancy LPG Mounded bullet IOCL Haldia\electrical\jpkhorwal\8378 AS BUILT DATED 21.05.09\EARTHING CALCULATION
REV.04\Annexure-1, REV 05 doc(AS BUILT).DOC