National Contracting Co. LTD.: Project
National Contracting Co. LTD.: Project
National Contracting Co. LTD.: Project
CUSTOMER:
UGANDA ELECTRICITY TRANSMISSION CO. LTD (UETCL)
10 HANNINGTON ROAD, FIFTH FLOOR
KAMPALA, REPUBLIC OF UGANDA
CONSULTANT:
GOPA-INTERNATIONAL ENERGY CONSULTANTS GMBH
JUSTUS-VON-LIEBIG-STR. 1,
61352 BAD HOMBURG V.D.H., GERMANY
SUBSTATION NAME: DOCUMENT NUMBER :
BUJ/S/7300/BUJ/DD/ESO
EXTENSION OF 220/132kV BUJAGALI SUBSTATION
/0007
-
SHORT CIRCUIT FORCE CALCULATION
DATE NAME SIGN
PRPD 06.06.18 RSL SCALE SIZE PAGES: REV
CHECK. 06.06.18 BSR
-- A4 0
APPRD. 06.06.18 BSR
NATIONAL CONTRACTING CO. LTD.,
T & D Division
Kingdom of Saudi Arabia
DOC. NO: BUJ/S/7300/BUJ/DD/ESO
PROJECT 220kV BUJAGALI SUBSTATION EXTENSION
/0007
e. Duration of Short Circuit current flow = 3 s (As per Spec. Cl: S2.1.1)
(ii) Number of sub-conductor per phase = 2 Nos. As per 220kV Switchyard plan
(iii) Mass per unit length of one subconductor = 2.566 kg/m As per Conductor details (Attached)
(iv) Cross-section of one sub-conductor = 766.55 mm2 As per Conductor details (Attached)
(viii) Minimum Creepage distance per kV = 6125 / 245 = 25 mm/kV (As per Spec. Cl: S2.1.1)
(ix) Creepage distance of a disc insulator = 432 mm/kV As per typical vendor drawing (Attached)
(x) Distance between centres of disc units = 145 mm As per typical vendor drawing (Attached)
(xi) Material Constant Cth = 2.7E-19 m4/A2s As per IEC - 865 (Pg No: 45) cl:2.3.2.4
attached annexure-II
F' = ¿
¿ IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:19
μ0
×0.75׿ annexure-II Aattched
2π
where
¿
= 40000 A
= 4.5 m
= 30.50 m
lc = Cord length of the main conductor in the span
= 30.5 - ( 2 x (2.175+0.75)
= 24.65 m
μ0 = Permeability of free space, 4 π x 10-7
Hence
= 43.104
b. Ratio of electromagnetic force under short-circuit conditions to the gravitational force on a conductor
r = F' IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:20
annexure-II Aattched
n×m sc '×g n
where
= 2 Nos.
m's = Mass per unit length of one sub-conductor
= 2.566 kg/m
gn = Conventional value of acceleration of gravity
= 9.81 m/s2
Hence
= 0.856
c. Direction of resulting force exerted on the conductor
δ1 = arctan (r)
IEC - 865 (Pg No:39) cl:2.3.2.1
Eq:21annexure-II Aattched
= ATAN(0.856) rad
= 0.70807 rad
= 0.70807 × 180/π °
= 40.569 °
= 19620 N
Hence
bc = 2 x 2.566 x 9.81 x 30.5^2/(8 x 19620) m
= 0.298 m
=
2π 0.8
√ bc
gn
2 x π x √(0.8 x 0.298/9.81) s
IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:23
annexure-II Aattched
= 0.980 s
[ [ ]]
2 annexure-II Aattched
4 π2 δ1
√ 1+r 2 1−
64 900
= 0.98011/[(1 + 0.85617^2)^(1/4) x {1 – π^2/64 x (40.569/90)^2}] s
= 0.882 s
E
(
F st
nA s σ fin
×900
)] For
For
nA s
F st
≤σ fin IEC - 865 (Pg No:41) cl:2.3.2.1 Eq:26 ,
27 annexure-II Aattched
>σ fin
where nA s
δfin = Lowest value of δ when Young's modulus becomes constant
= 5E+07 N/m²
Fst/(n As) = 19620.000/(2 x 0.000766550) where As is cross-section of one sub-conductor
= 1.28E+07 N/m2
≤ δfin
Hence
Es = 7.8E+10 [0.3 + 0.7 SIN{19620.000/(2 x 0.000766550 x 5.0E+07) x 90°}] N/m²
= 4.49.E+10 N/m²
Hence
= 3.42.E-07 1/N
= 0.038
2 δ1
(
Tk1
T res
×3600
)] For 0 ≤ Tk1/Tres ≤ 0.5
where
Tk1 = Duration of first short-circuit current flow
= 0.4T (Minimum(0.4T,1))
= 0.392 s
Tk1/Tres = 0.392/0.882
= 0.445 ≤ 0.5
Hence
δk = 40.569{1 – COS(360° x 0.392/0.882)} °
= 78.702 °
= 0.160
l. Maximum swing-out angle
δm = 1.25 arccosχ For 0.766 ≤ χ ≤ 1 (i) IEC - 865 (Pg No:43) cl:2.3.2.1 Eq:31
annexure-II Aattched
Hence
δm = 90.769 °
3.2 Tensile force during short-circuit caused by swing out (short-circuit tensile force)
a. Load parameter φ
T res
φ = 3 ( √ 1+r 2 −1 ) For T k 1≥ IEC - 865 (Pg No:43) Cl:2.3.2.2 Eq:32
annexure-II Aattched
4
T res
3(rsinδk + cosδk – 1) For T k1<
4
Tk1/Tres = 0.392/0.882
= 0.44 ³ 0.25
Hence
φ = 3{√(1 + 0.85617^2) – 1}
= 0.949
b. Load parameter Ψ
The factor Ψ is a function of ζ and φ – it can be calculated as a real solution of the equation:
ϕ2Ψ3 + ϕ(2 + ζ)Ψ2 + (1 + 2ζ)Ψ – ζ(2 + ϕ) = 0 IEC - 865 (Pg No:43) Cl:2.3.2.2 Eq:33
annexure-II Aattched
= 0.949^2×0.089^3+0.949(2+0.038)×0.089^2+(1+2×0.038)×0.089–0.038×(2+0.949)
= 0.000
c. Tensile force Ft during short circuit caused by swing out (short-circuit tensile force)
Ft = Fst(1 + φΨ) For n = 1, single conductor IEC - 865 (Pg No:43)Cl:2.3.2.2 Eq:34
annexure-II Aattched
2385.880 kg
3.3 Tensile force Ff after short circuit caused by drop (drop force)
This is significant for r > 0.6 if δm ≥ 70°
r = 0.85617
δm = 90.77 °
Ff
Ff
=
=
√
1. 2 F st 1+8 ζ
180
δm
Ff = 25283.943 N
= 2577.364 kg
3.4 Maximum Horizontal span displacement (bh) and minimum air clearance(amin)
= 1.30E-03
k3} } } over { ital nA rSub { size 8{s} } } } right ] rSup { size 8{2} } T rSub { size 8{k1} } } {
¿ for Tk1 ≥ Tres/4
I¿
¿
¿
cth ¿
¿
= 0.27E-18*(40000/(2*0.0007666))²*0.88/4
εth = 4.05E-05
√
= 2
[ ]
3 l IEC - 865 (Pg No:45)Cl:2.3.2.4 Eq:38
1+ ( ε els + ε th ) annexure-II Aattched
8 bc
= √(1+3/8*(30.5/0.30)²*(1.30E-03+4.05E-05))
CD = 2.50
= 0.97+ 0.1*0.8562
CF = 1.056
e. Maximum Horizontal span displacement ( bh)
For slack conductors bh = CF CD bc for δm > 90o IEC - 865 (Pg No:47) Cl:2.3.2.4
CF CD bc sin δm for δm < 90o Eq:40,41 annexure-II Aattched
= 1.06*2.50*0.2984(sin(40.57))
bh = 0.51 m
= 4.5- 2*0.51
amin = 3.48 m
= 0.250 m
ls = Distance between two adjacent spacers
= 2.400 m
ds = Diameter of flexible conductor
= 0.036 m
Hence
as/ds = 0.250/0.036
= 6.944
ls/as = 2.400/0.250
= 9.600
So, sub-conductors shall not clash effectively during short-circuit and Tensile Force caused by pinch effect shall be
calculated following the below steps:
K = 1. 02+0 . 98 exp
−3 ( Rx ) Refer IEC-60909-0 Page 101 Cl:4.3.1.1 annexure-II Attached
Ta = X 1
Refer IEEE-605-1998 Page 17 Cl:10.2 annexure-II Attached
Where
R
2 πf
Ta = 0.06 s Refer IEC -62271-100 Page 71 annexure-II Aattched
R 1
=
X Ta× 2 πf
= 1 / (0.06 x 2 π x 50)
= 0.053
K = 1.86
[ − 2π
f
3
× ln
( k −1. 02 )
( 0 . 98 ) { }] IEC - 865 (Pg No:109) Cl:A.6 Fig:8 annexure-II
Aattched
= 0.060 s
d. Factor γ
γ = tan-1(2πft) IEC - 865 (Pg No:109) Cl:A.6 Fig:8 annexure-II
Aattched
= ARCTAN(2 x π x 50 x 0.06000)
= 1.518
e. Factor v1 I k 3 } over {n} } right ) rSup { size 8{2} } { {n - 1} over {a rSub { size 8{s} } } } } } } } { IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:46
¿
¿ annexure-II Aattched
μ0
¿
v1 =
2π
( a s −d s ) msc '
¿
¿
1
f √¿
180 0
sin
n
¿
= 2.071
g. Factor v2
= 2.200
As per IEC - 865, From Fig 8, k=1.86,(Pg No:87)
v3 =
d s / as √ ( a s / d s )−1
180 0 tan −1 √ ( as / d s )−1
sin ( ) n
= (0.036/0.25)/SIN(180°/2) x √(0.25/0.036–1)/ATAN{√(0.25/0.036–1)}
= 0.297
= 5686.237 N
= 1.267
Fv l N
εpi = 0 3
0 . 375 n
s3
( as − d s )
3
sin (180
n ) IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:48
annexure-II Aattched
= 2.060
k. Parameter determining the bundle conductor configuration during short-circuit current flow, j
√
j = ε pi
IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:49
1+ ε st annexure-II Aattched
= √{2.05964/(1 + 1.26736)}
= 0.953
j ≥ 1 : The sub-conductors clash.
for j = 0.953
& εst = 1.267 ≈ 2^0
ve 2
m. Fpi
where
=
(
F st 1+
ε st
η
) IEC - 865 (Pg No:51) Cl:2.3.3.3 Eq:54
annexure-II Aattched
ve = 1/2 + √ (A1 A2 A3) - 1/4 IEC - 865 (Pg No:51) Cl:2.3.3.2 Eq:52
annexure-II Aattched
I k 3 } over {n} } right ) rSup { size 8{2} } N} {
A1 =
¿
¿
9 μ
n ( n−1 ) 0 ¿
8 2π
¿
= 6.1629121474E-05 4
1800
ls 4 ( sin )
A2 = v2
( a s −d s ) η4
n
= 268539.1146
−1
A3 = 1−
tan √ v4
v4
= 0.222
v4 = a s −d s
η
as −η ( as − d s )
= 1.056
Hence
ve = 2.352
CONCLUSION
Design load for structures, insulators and connectors
The maximum value of Ft or Ff of flexible conductor spans shall be applied to the structure, the insulators and the
connectors as as static load.
Maximum of Ft , Ff , Fpi (if applicable):
= 3.336 Tonne
5 Critical Spacer span
From the below tabular column, it is clear that the subconductor clashes after a spacer distance of 2.4m. Hence a spacer
span of 2.4m is selected. Subconductor clashes after
this span
Short Circuit force (Tonne) 3.26 3.26 3.26 3.26 4.01 3.46 3.14
5.00
SCF in tonnes
4.50
4.00
3.50
3.00
2.50
2.00
1 1.5 2 2.5 3 3.5 4 4.5 5
Spacer span in mtrs
Step - 1: Input
Mink Wolf
= 8.25E+10 8.02E+10
#REF!
Step - 2: Check/revise formula of lc according to conductor SLACK/STRINGED
Strained
Step - 3: Check condition for c.
0.9012 y3
1.9347 y2
1.0760 y
- 0.1121 Constant
est epi
1000 1500 2000 2500 3000 4000 5000 6000
0.02 0.1 0.27 0.37 0.55 0.57 0.57 0.47
A1 6.163E-05
V4 5.944
A3 0.515
A2 659.7879
Ve Err:502
Fpi Err:502
Err:502
Err:502
Panther Zebra Moose
21 28.62 31.77 mm
F388: ed027:
CHECK FOR "0"
F584: vsh:
From graph with V1 & k
F631: Note:
Check the value of j to decide further steps either as per §2.3.3.2 or §2.3.3.3 of IEC 865-1
N97: vtn:
0.27*10-18 m4/A2s for Aluminium alloy & Cross section area of Aluminium/Steel > 6
0.17*10-18 m4/A2s for Cross section area of Aluminium/Steel < 6
0.088*10-18 m4/A2s for Cross section area of Copper
N103: Note:
For string bus insulator string length shall be entered.
For equipment connection, this shall be zero.
X647: est
Z647: epi
NATIONAL CONTRACTING CO. LTD.,
T & D Division
Kingdom of Saudi Arabia
DOC. NO: BUJ/S/7300/BUJ/DD/ESO
PROJECT 220kV BUJAGALI SUBSTATION EXTENSION
/0007
e. Duration of Short Circuit current flow = 3 s (As per Spec. Cl: S2.1.1)
(ii) Number of sub-conductor per phase = 2 Nos. As per 220kV Switchyard plan
(iii) Mass per unit length of one subconductor = 2.566 kg/m As per Conductor details (Attached) Mass pe
(iv) Cross-section of one sub-conductor = 766.55 mm2 As per Conductor details (Attached) Cross-s
(v) Young's Modulus = 7.99E+05 Kg./Cm2 As per Conductor details (Attached) Young's
(viii) Minimum Creepage distance per kV = 6125 / 245 = 25 mm/kV (As per Spec. Cl: S2.1.1)
(ix) Creepage distance of a disc insulator = 432 mm/kV As per typical vendor drawing (Attached)
(x) Distance between centres of disc units = 145 mm As per typical vendor drawing (Attached)
(xi) Material Constant Cth = 2.7E-19 m4/A2s As per IEC - 865 (Pg No: 45) cl:2.3.2.4
attached annexure-II
F' = ¿
¿ IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:19
μ0
×0.75׿ annexure-II Aattched
2π
where
¿
= 40000 A
= 4.5 m
= 6.00 m
lc = Cord length of the main conductor in the span
= 6 - ( 2 x (0+0)
= 6.00 m
μ0 = Permeability of free space, 4 π x 10-7
Hence
= 53.333
b. Ratio of electromagnetic force under short-circuit conditions to the gravitational force on a conductor
r = F' IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:20
annexure-II Aattched
n×m sc '×g n
where
= 2 Nos.
m's = Mass per unit length of one sub-conductor
= 2.566 kg/m
gn = Conventional value of acceleration of gravity
= 9.81 m/s2
Hence
= 1.059
c. Direction of resulting force exerted on the conductor
δ1 = arctan (r)
IEC - 865 (Pg No:39) cl:2.3.2.1
Eq:21annexure-II Aattched
= ATAN(1.059) rad
= 0.81421 rad
= 0.81421 × 180/π °
= 46.651 °
= 1962 N
Hence
bc = 2 x 2.566 x 9.81 x 6^2/(8 x 1962) m
= 0.115 m
=
2π 0.8
√ bc
gn
2 x π x √(0.8 x 0.115/9.81) s
IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:23
annexure-II Aattched
= 0.610 s
[ [ ]]
2 annexure-II Aattched
4 2 π2 δ1
√ 1+r 1−
64 900
= 0.60971/[(1 + 1.05936^2)^(1/4) x {1 – π^2/64 x (46.651/90)^2}] s
= 0.527 s
E
(
F st
nA s σ fin
×900
)] For
For
nA s
F st
≤σ fin IEC - 865 (Pg No:41) cl:2.3.2.1 Eq:26 ,27
annexure-II Aattched
>σ fin
where nA s
δfin = Lowest value of δ when Young's modulus becomes constant
= 5E+07 N/m²
Fst/(n As) = 1962.000/(2 x 0.000766550) where As is cross-section of one sub-conductor
= 1.28E+06 N/m2
≤ δfin
Hence
Es = 7.8E+10 [0.3 + 0.7 SIN{1962.000/(2 x 0.000766550 x 5.0E+07) x 90°}] N/m²
= 2.57.E+10 N/m²
Hence
= 1.69.E-06 1/N
= 0.298
2 δ1
(
Tk1
T res
×3600
)] For 0 ≤ Tk1/Tres ≤ 0.5
where
Tk1 = Duration of first short-circuit current flow
= 0.4T (Minimum(0.4T,1))
= 0.244 s
Tk1/Tres = 0.244/0.527
= 0.463 ≤ 0.5
Hence
δk = 46.651{1 – COS(360° x 0.244/0.527)} °
= 92.033 °
= -0.059
l. Maximum swing-out angle
δm = 1.25 arccosχ For 0.766 ≤ χ ≤ 1 (i) IEC - 865 (Pg No:43) cl:2.3.2.1 Eq:31
annexure-II Aattched
10° + arccosχ For – 0.985 ≤ χ ≤ 0.766 (ii)
Hence
δm = 103.403 ° Step - 4: Ch
3.2 Tensile force during short-circuit caused by swing out (short-circuit tensile force)
a. Load parameter φ
T res
φ = 3 ( √ 1+r 2 −1 ) For T k 1≥ IEC - 865 (Pg No:43) Cl:2.3.2.2 Eq:32
annexure-II Aattched
4
T res
3(rsinδk + cosδk – 1) For T k1<
4
Tk1/Tres = 0.244/0.527
= 0.46 ³ 0.25
Hence
φ = 3{√(1 + 1.05936^2) – 1}
= 1.370
b. Load parameter Ψ
The factor Ψ is a function of ζ and φ – it can be calculated as a real solution of the equation:
ϕ2Ψ3 + ϕ(2 + ζ)Ψ2 + (1 + 2ζ)Ψ – ζ(2 + ϕ) = 0 IEC - 865 (Pg No:43) Cl:2.3.2.2 Eq:33 1.8779
annexure-II Aattched
= 1.370^2×0.345^3+1.370(2+0.298)×0.345^2+(1+2×0.298)×0.345–0.298×(2+1.370)
= 0.000 Step - 5: Do
c. Tensile force Ft during short circuit caused by swing out (short-circuit tensile force)
Ft = Fst(1 + φΨ) For n = 1, single conductor IEC - 865 (Pg No:43)Cl:2.3.2.2 Eq:34
annexure-II Aattched
324.072 kg
3.3 Tensile force Ff after short circuit caused by drop (drop force)
This is significant for r > 0.6 if δm ≥ 70°
r = 1.05936
δm = 103.40 °
Ff
Ff
=
=
√
1. 2 F st 1+8 ζ
δm
1800
1.2 × 1962.000 x √(1 + 8 × 0.298 x 103.40/180°)
IEC - 865 (Pg No:45)Cl:2.3.2.3 Eq:35
annexure-II Aattched
Ff = 3622.435 N (1b)
= 369.259 kg
7.3 3.4 Maximum Horizontal span displacement (b h) and minimum air clearance(amin)
= 2.06E-03
εth = 2.42E-05
√
= 2
[ ]
3 l IEC - 865 (Pg No:45)Cl:2.3.2.4 Eq:38
1+ ( ε els + ε th ) annexure-II Aattched
8 bc
= √(1+3/8*(6/0.12)²*(2.06E-03+2.42E-05))
CD = 1.76
= 0.97+ 0.1*1.0594
CF = 1.076
e. Maximum Horizontal span displacement ( bh)
For slack conductors bh = CF CD bc for δm > 90o IEC - 865 (Pg No:47) Cl:2.3.2.4 Eq:40,41
CF CD bc sin δm for δm < 90o annexure-II Aattched
= 1.08*1.76*0.1155(sin(46.65))
bh = 0.16 m
= 4.5- 2*0.16
amin = 4.18 m
= 0.250 m
ls = Distance between two adjacent spacers
= 0.900 m
ds = Diameter of flexible conductor
= 0.036 m
Hence
as/ds = 0.250/0.036
= 6.944
ls/as = 0.900/0.250
= 3.600
So, sub-conductors shall not clash effectively during short-circuit and Tensile Force caused by pinch effect shall be calculated
following the below steps:
K =
1. 02+0 . 98 exp
−3 ( Rx ) Refer IEC-60909-0 Page 101 Cl:4.3.1.1 annexure-II Attached
Ta = X 1
Refer IEEE-605-1998 Page 17 Cl:10.2 annexure-II Attached
Where
R
2 πf
Ta = 0.06 s Refer IEC -62271-100 Page 71 annexure-II Aattched
R 1
=
X Ta× 2 πf
= 1 / (0.06 x 2 π x 50)
= 0.053
K = 1.86
[ − 2π
f
3
× ln
( k −1. 02 )
( 0 . 98 ) { }] IEC - 865 (Pg No:109) Cl:A.6 Fig:8 annexure-II
Aattched
= 0.060 s
d. Factor γ
γ = tan-1(2πft) IEC - 865 (Pg No:109) Cl:A.6 Fig:8 annexure-II
Aattched
= ARCTAN(2 x π x 50 x 0.06000)
= 1.518
e. Factor v1 I k 3 } over {n} } right ) rSup { size 8{2} } { {n - 1} over {a rSub { size 8{s} } } } } } } } { IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:46
¿
¿ annexure-II Aattched
μ0
¿
v1 =
2π
( a s −d s ) msc '
¿
¿
1
f √¿
180 0
sin
n
¿
= 2.071
g. Factor v2
v3 =
d s / as √ ( a s / d s )−1
0
tan −1 √ ( as / d s )−1
sin (180n )
= (0.036/0.25)/SIN(180°/2) x √(0.25/0.036–1)/ATAN{√(0.25/0.036–1)}
= 0.297
= 2083.877 N
= 0.088
Fv l N
εpi = 0 3
0 . 375 n s3
( as − d s ) 3
sin (180
n ) IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:48
annexure-II Aattched
= 0.197
k. Parameter determining the bundle conductor configuration during short-circuit current flow, j
√
j = ε pi
IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:49
1+ ε st annexure-II Aattched
= √{0.19671/(1 + 0.08808)}
= 0.425
j ≥ 1 : The sub-conductors clash.
for j = 0.425
& εst = 0.088 ≈ 2^-2
ve 2
m. Fpi
where
= F st 1+
( ε st
η
) IEC - 865 (Pg No:51) Cl:2.3.3.3 Eq:54
annexure-II Aattched
ve = 1/2 + √ (A1 A2 A3) - 1/4 IEC - 865 (Pg No:51) Cl:2.3.3.2 Eq:52
annexure-II Aattched
I k 3 } over {n} } right ) rSup { size 8{2} } N} {
A1 = ¿
¿
9 μ
n ( n−1 ) 0 ¿
8 2π
= 0.0003045697 ¿
0 4
ls 4 ( sin
180
)
A2 =
=
v2
(
287119.494683
a s −d s ) η4
n
−1
A3 = 1−
tan √ v4
v4
= 0.068
v4 = a s −d s
η
as −η ( as − d s )
= 0.232
Hence
ve = 2.888
CONCLUSION
Design load for structures, insulators and connectors
The maximum value of Ft or Ff of flexible conductor spans shall be applied to the structure, the insulators and the connectors as
static load.
Maximum of Ft , Ff , Fpi (if applicable):
= 0.517 Tonne
Step - 1: Input
Mass per unit length of one subconductor = 0.255 0.727 0.976 1.623 2 kg/m
#REF!
Step - 2: Check/revise formula of lc according to conductor SLACK/STRINGED
Strained
Step - 3: Check condition for c.
1.8779
3.1484
1.5950
1.0027
A1 0.0003
V4 5.944
A3 0.515
A2 32.2634
Ve Err:502
Fpi Err:502
Err:502
Err:502
F388: ed027:
CHECK FOR "0"
F635: Note:
Check the value of j to decide further steps either as per §2.3.3.2 or §2.3.3.3 of IEC 865-1
N97: vtn:
0.27*10-18 m4/A2s for Aluminium alloy & Cross section area of Aluminium/Steel > 6
0.17*10-18 m4/A2s for Cross section area of Aluminium/Steel < 6
0.088*10-18 m4/A2s for Cross section area of Copper
N103: Note:
For string bus insulator string length shall be entered.
For equipment connection, this shall be zero.
X651: est
Z651: epi
NATIONAL CONTRACTING CO. LTD.,
T & D Division
Kingdom of Saudi Arabia
DOC. NO: BUJ/S/7300/BUJ/DD/ESO
PROJECT 220kV BUJAGALI SUBSTATION EXTENSION
/0007
e. Duration of Short Circuit current flow = 3 s (As per Spec. Cl: S2.1.1)
(ii) Number of sub-conductor per phase = 2 Nos. As per 220kV Switchyard plan
(iii) Mass per unit length of one subconductor = 2.566 kg/m As per Conductor details (Attached) Mass pe
(iv) Cross-section of one sub-conductor = 766.55 mm 2 As per Conductor details (Attached) Cross-se
(v) Young's Modulus = 7.99E+05 Kg./Cm2 As per Conductor details (Attached) Young's
(viii) Minimum Creepage distance per kV = 6125 / 245 = 25 mm/kV (As per Spec. Cl: S2.1.1)
(ix) Creepage distance of a disc insulator = 432 mm/kV As per typical vendor drawing (Attached)
(x) Distance between centres of disc units = 145 mm As per typical vendor drawing (Attached)
(xi) Material Constant Cth = 2.7E-19 m4/A2s As per IEC - 865 (Pg No: 45) cl:2.3.2.4
attached annexure-II
F' = ¿
¿ IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:19
μ0
×0.75׿ annexure-II Aattched
2π
where
¿
= 40000 A
= 4.5 m
= 4.00 m
lc = Cord length of the main conductor in the span
= l – (2 × ( length of one insulator chain + half of the girder width)) Step - 2: Che
= 4 - ( 2 x (0+0)
= 4.00 m
μ0 = Permeability of free space, 4 π x 10-7
Hence
= 53.333
b. Ratio of electromagnetic force under short-circuit conditions to the gravitational force on a conductor
r = F' IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:20
annexure-II Aattched
n×m sc '×g n
where
= 2 Nos.
m's = Mass per unit length of one sub-conductor
= 2.566 kg/m
gn = Conventional value of acceleration of gravity
= 9.81 m/s2
Hence
= 1.059
c. Direction of resulting force exerted on the conductor
δ1 = arctan (r)
IEC - 865 (Pg No:39) cl:2.3.2.1
Eq:21annexure-II Aattched
= ATAN(1.059) rad
= 0.81421 rad
= 0.81421 × 180/π °
= 46.651 °
= 1962 N
Hence
bc = 2 x 2.566 x 9.81 x 4^2/(8 x 1962) m
= 0.051 m
=
2π 0.8
√ bc
gn
2 x π x √(0.8 x 0.051/9.81) s
IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:23
annexure-II Aattched
= 0.406 s
[ [ ]]
2 annexure-II Aattched
4 π2 δ1
√ 1+r 2 1−
64 900
= 0.40647/[(1 + 1.05936^2)^(1/4) x {1 – π^2/64 x (46.651/90)^2}] s
= 0.351 s
E
(
F st
nA s σ fin
×900
)] For
For
nA s
F st
≤σ fin IEC - 865 (Pg No:41) cl:2.3.2.1 Eq:26 ,
27 annexure-II Aattched
>σ fin
where nA s
δfin = Lowest value of δ when Young's modulus becomes constant
= 5E+07 N/m²
Fst/(n As) = 1962.000/(2 x 0.000766550) where As is cross-section of one sub-conductor
= 1.28E+06 N/m2
≤ δfin
Hence
Es = 7.9E+10 [0.3 + 0.7 SIN{1962.000/(2 x 0.000766550 x 5.0E+07) x 90°}] N/m²
= 2.59.E+10 N/m²
Hence
= 2.53.E-06 1/N
= 0.089
2 δ1
Tk1
T res
×3600
)] For 0 ≤ Tk1/Tres ≤ 0.5
where
Tk1 = Duration of first short-circuit current flow
= 0.4T (Minimum(0.4T,1))
= 0.163 s
Tk1/Tres = 0.163/0.351
= 0.463 ≤ 0.5
Hence
δk = 46.651{1 – COS(360° x 0.163/0.351)} °
= 92.033 °
= -0.059
l. Maximum swing-out angle
δm = 1.25 arccosχ For 0.766 ≤ χ ≤ 1 (i) IEC - 865 (Pg No:43) cl:2.3.2.1 Eq:31
annexure-II Aattched
10° + arccosχ For – 0.985 ≤ χ ≤ 0.766 (ii)
Hence
δm = 103.403 ° Step - 4: Che
3.2 Tensile force during short-circuit caused by swing out (short-circuit tensile force)
a. Load parameter φ
T res
φ = 3 ( √ 1+r 2 −1 ) For T k 1≥ IEC - 865 (Pg No:43) Cl:2.3.2.2 Eq:32
annexure-II Aattched
4
T res
3(rsinδk + cosδk – 1) For T k1<
4
Tk1/Tres = 0.163/0.351
= 0.46 ³ 0.25
Hence
φ = 3{√(1 + 1.05936^2) – 1}
= 1.370
b. Load parameter Ψ
The factor Ψ is a function of ζ and φ – it can be calculated as a real solution of the equation:
ϕ2Ψ3 + ϕ(2 + ζ)Ψ2 + (1 + 2ζ)Ψ – ζ(2 + ϕ) = 0 IEC - 865 (Pg No:43) Cl:2.3.2.2 Eq:33 1.8779
annexure-II Aattched
= 1.370^2×0.173^3+1.370(2+0.089)×0.173^2+(1+2×0.089)×0.173–0.089×(2+1.370)
= 0.000 Step - 5: Do
c. Tensile force Ft during short circuit caused by swing out (short-circuit tensile force)
Ft = Fst(1 + φΨ) For n = 1, single conductor IEC - 865 (Pg No:43)Cl:2.3.2.2 Eq:34
annexure-II Aattched
272.099 kg
3.3 Tensile force Ff after short circuit caused by drop (drop force)
This is significant for r > 0.6 if δm ≥ 70°
r = 1.05936
δm = 103.40 °
Ff
Ff
=
=
√
1. 2 F st 1+8 ζ
δm
1800
1.2 × 1962.000 x √(1 + 8 × 0.089 x 103.40/180°)
IEC - 865 (Pg No:45)Cl:2.3.2.3 Eq:35
annexure-II Aattched
Ff = 2792.891 N (1b)
= 284.698 kg
7.3 3.4 Maximum Horizontal span displacement (b h) and minimum air clearance(amin)
= 1.79E-03
εth = 1.61E-05
√
= 2
[ ]
3 l IEC - 865 (Pg No:45)Cl:2.3.2.4 Eq:38
1+ ( ε els + ε th ) annexure-II Aattched
8 bc
= √(1+3/8*(4/0.05)²*(1.79E-03+1.61E-05))
CD = 2.26
= 0.97+ 0.1*1.0594
CF = 1.076
e. Maximum Horizontal span displacement ( bh)
For slack conductors bh = CF CD bc for δm > 90o IEC - 865 (Pg No:47) Cl:2.3.2.4
CF CD bc sin δm for δm < 90o Eq:40,41 annexure-II Aattched
= 1.08*2.26*0.0513(sin(46.65))
bh = 0.09 m
= 4.5- 2*0.09
amin = 4.32 m
= 0.250 m
ls = Distance between two adjacent spacers
= 0.900 m
ds = Diameter of flexible conductor
= 0.036 m
Hence
as/ds = 0.250/0.036
= 6.944
ls/as = 0.900/0.250
= 3.600
So, sub-conductors shall not clash effectively during short-circuit and Tensile Force caused by pinch effect shall be calculated
following the below steps:
K =
1. 02+0 . 98 exp
−3 ( Rx ) Refer IEC-60909-0 Page 101 Cl:4.3.1.1 annexure-II Attached
Ta = X 1
Refer IEEE-605-1998 Page 17 Cl:10.2 annexure-II Attached
Where
R
2 πf
Ta = 0.06 s Refer IEC -62271-100 Page 71 annexure-II Aattched
R 1
=
X Ta× 2 πf
= 1 / (0.06 x 2 π x 50)
= 0.053
K = 1.86
[ − 2π
f
3
× ln
( k −1. 02 )
( 0 . 98 ) { }] IEC - 865 (Pg No:109) Cl:A.6 Fig:8 annexure-II
Aattched
= 0.060 s
d. Factor γ
γ = tan-1(2πft) IEC - 865 (Pg No:109) Cl:A.6 Fig:8 annexure-II
Aattched
= ARCTAN(2 x π x 50 x 0.06000)
= 1.518
e. Factor v1 I k 3 } over {n} } right ) rSup { size 8{2} } { {n - 1} over {a rSub { size 8{s} } } } } } } } { IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:46
¿
¿ annexure-II Aattched
μ0
¿
v1 =
2π
(a s −d s ) msc '
¿
¿
1
f √¿
180 0
sin
n
¿
= 2.071
g. Factor v2
= 2.100 As per IEC - 865, From Fig 8, k=1.86, (Pg No:87)
v3 =
d s / as √ ( a s /d s ) −1
180 0 tan −1 √ ( as / d s )−1
sin ( ) n
= (0.036/0.25)/SIN(180°/2) x √(0.25/0.036–1)/ATAN{√(0.25/0.036–1)}
= 0.297
= 2035.415 N
= 0.131
Fv l N 0 3
εpi = 0 . 375 n
s3
( as − d s )
3
sin (180
n ) IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:48
annexure-II Aattched
= 0.287
k. Parameter determining the bundle conductor configuration during short-circuit current flow, j
√
j = ε pi
IEC - 865 (Pg No:49) Cl:2.3.3.1 Eq:49
1+ ε st annexure-II Aattched
= √{0.28674/(1 + 0.13144)}
= 0.503
j ≥ 1 : The sub-conductors clash.
for j = 0.503
& εst = 0.131 ≈ 2^-1
ve 2
m. Fpi
where
= F st 1+
( ε st
η
) IEC - 865 (Pg No:51) Cl:2.3.3.3 Eq:54
annexure-II Aattched
ve = 1/2 + √ (A1 A2 A3) - 1/4 IEC - 865 (Pg No:51) Cl:2.3.3.2 Eq:52
annexure-II Aattched
I k 3 } over {n} } right ) rSup { size 8{2} } N} {
A1 = ¿
¿
9 μ
n ( n−1 ) 0 ¿
8 2π
¿
= 0.0004545349 0 4
ls 4 ( sin
180
)
A2 =
=
v2
(
71135.67613
a s −d s ) η4
n
A3 =
tan−1 √ v 4
1−
v4
= 0.100
v4 = a s −d s
η
as −η ( as − d s )
= 0.361
Hence
ve = 2.223
CONCLUSION
Design load for structures, insulators and connectors
The maximum value of Ft or Ff of flexible conductor spans shall be applied to the structure, the insulators and the connectors as
as static load.
Maximum of Ft , Ff , Fpi (if applicable):
= 0.525 Tonne
NEAR MAIN BUS (TRANSFORMER BAY)
Step - 1: Input
Mass per unit length of one subconductor = 0.255 0.727 0.976 1.623 2 kg/m
#REF!
Step - 2: Check/revise formula of lc according to conductor SLACK/STRINGED
Strained
Step - 3: Check condition for c.
1.8779
2.8622
1.1772
0.2986
A1 0.00045
V4 5.944
A3 0.515
A2 31.5131
Ve Err:502
Fpi Err:502
Err:502
Err:502
F605: Note:
Check the value of j to decide further steps either as per §2.3.3.2 or §2.3.3.3 of IEC 865-1
N97: vtn:
0.27*10-18 m4/A2s for Aluminium alloy & Cross section area of Aluminium/Steel > 6
0.17*10-18 m4/A2s for Cross section area of Aluminium/Steel < 6
0.088*10-18 m4/A2s for Cross section area of Copper
N103: Note:
For string bus insulator string length shall be entered.
For equipment connection, this shall be zero.
X621: est
Z621: epi
NATIONAL CONTRACTING CO. LTD.,
T & D Division
Kingdom of Saudi Arabia
Input Data
Three Phase initial symmetrical Short circuit Current I"k3 = 40.0 kA (As per Spec.)
Length of Jumper (Maximum length considered) LT = 10.0 m As per 220kV Switchyard plan
Center line distance between conductors at one end a1 = 4.5 m As per 220kV Switchyard plan
Center line distance between conductors at another end a2 = 4.5 m As per 220kV Switchyard plan
Conductor Data
= 4.5 m
Electromagnetic Force / per metre length Fm3 = μ0 x 0.75 x (I"K3)2 x L Where, L=1m - Assumed for
2π x a typical calculation
IEC - 865 (Pg No:39) cl:2.3.2.1 Eq:19 annexure-II Aattched
= 53 N/m
= 533 N
= 0.533 KN
= 54.4 kg
SINGHAL ENTERPRISES PVT. LTD
NATIONAL CONTRACTING CO. LTD.,
T & D Division
Kingdom of Saudi Arabia
DOC. NO: BUJ/S/7300/BUJ/DD/ESO
PROJECT: 220kV BUJAGALI SUBSTATION EXTENSION
/0007
Span in m 30.5
No. of sub-conductor 2
SCF - SUMMARY OF THE LOADING EQUIPMENTS IN "T" ACSR CONDUCTOR - LINE FEEDER
1 LA 0.0 4.00 0.0 0.00 5.15 0.00 2.58 0.00 2.58 262.55
2 CT 4.0 3.00 0.0 5.15 5.15 0.00 5.15 0.00 5.15 525.09
Disconnecting switch
3 4.0 4.00 0.0 5.15 5.15 0.00 5.15 0.00 5.15 525.09
(with ES)
Disconnecting switch
4 6.0 3.00 7.5 5.08 5.15 0.40 5.11 0.40 5.51 562.04
(with ES) busbar side
Disconnecting switch
5 without ES (busbar 3.0 6.00 7.5 5.15 5.08 0.40 5.11 0.40 5.51 562.04
side)
6 CB 3.0 0.0 10.0 5.15 0.00 0.53 2.58 0.53 3.11 316.91
7 CVT 3.0 4.0 0.0 5.15 5.15 0.00 5.15 0.00 5.15 525.09
8 BPI 0.0 6.0 10.0 5.15 0.00 0.53 2.58 0.53 3.11 316.91