Binder1 PDF
Binder1 PDF
Binder1 PDF
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the generator system.
• Prime mover and alternator size: Take into account connected loads including ancillaries,
harmonics and transient operation.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature. Include:
- General arrangement drawings.
- Control diagrams.
- Prime mover and alternator data.
- Power output curves.
- Generator system efficiency at 50%, 75% and 100% full load.
- Start up temperature (minimum).
- Fuel and lubricating oil characteristics and consumption, as outlined in BS ISO 3046-1.
- Minimum run time without fuel and lubricating oil tank replenishment.
- Calculations for performance of acoustic enclosures and silencers.
- Maintenance access dimensions.
- Details of plinths and anti-vibration mountings.
The Generator system shall be provided with a full complete fully operational G59
synchronisation system for operation in parallel with the utility mains (NIE). All necessary
equipment components cabling interconnections etc as necessary to form a full and
complete system shall be provided and installed.
Additionally the contractor shall ensure inclusion of a sum in the amount of £2000.00 for
the necessary application to NIE relating to the G59 parallelling
290A PROTECTION
The following shall be incorporated within the distribution switchgear associated with the
generator system.
- Overcurrent/Short Circuit
- Restricted Earth fault/nvd
- Neutral earthing contactors
- Reverse power
Reverse kVAr (mainly for parallel operation mode)
PRODUCTS
340 INTERNAL COMBUSTION ENGINES Two generator sets will be installed to the Generic
Ward Block Building. Each set will be capable of supporting the full building load therefore
the generator system shall be considered as N+1 .
• Standards: To BS ISO 8528-2 and BS 5514-6.
• Type: Compression engine.
• Manufacturer: FG WIlson or Catapillar or Equal or Approved
- Product reference: P2250P1/P2500E1.
• Number of cylinders: 16.
- Total displacement: 61L.
• Rated speed: 1500 rpm.
• Overspeed protection: To BS 5514-6.
• Air/ fuel intake: Turbo-charged.
• Air filters: Replaceable dry element type.
• Fuel filters:
- Type: Replaceable paper type preceded by fuel polishing system - refer to section S40
of this specification.
- Filtration: To remove contaminants larger than 10 µm.
• Oil filters: Replaceable full flow type.
• Crankcase oil heater: Thermostatically controlled.
• Oil reservoir tank: To maintain the required oil level in the sump.
- Reservoir capacity: 5 L.
- Oil level monitor: Required.
- Drain valve: Locate to provide gravity oil removal and easy maintenance.
- Used oil container: Provide.
• Cooling system: Air.
- Coolant heater: Required.
- Radiator: Engine mounted.
Protective guard: Required .
- Drain valve: Locate to provide easy maintenance.
- Fan: Engine driven and mounted .
• Engine starting method: Electric starter motor, 2 starter circuits per set .
- Starter lockout: Whilst engine is running .
• Accessories: Air intake manifold heaters and Glow-plugs .
350 GOVERNOR
• Standard: To BS 5514-4.
• Type: Electronic.
• Manufacturer: System manufacturer.
- Product reference: Submit proposals.
• Mode of operation: To enable engine to operate continuously at rated speed from no-load
to the rated full electrical load.
• Adjustments:
- Acceleration rate;
- Load gain;
- Maximum speed;
- Speed droop; and
- Stability.
380A SYNCHRONISATION
The Generator system shall be provided with a full complete fully operational G59
synchronisation system for operation in parallel with the utility mains (NIE). All necessary
equipment components cabling interconnections etc as necessary to form a full and
complete system shall be provided and installed.
Additionally the contractor shall ensure inclusion of a sum in the amount of £2000.00 for
the necessary application to NIE relating to the G59 parallelling
450 CONTROL PANEL Each generator will be provided with its own control panel and output
circuit breaker to be located within the generator room.
• Standard: To BS ISO 8528-4.
• Manufacturer: System manufacturer.
- Product reference: Submit proposals.
• Configuration: Group controls, alarms and indicators in common control panel.
• Controls:
- Alarm reset;
- Automatic/ manual switch;
- Emergency stop;
- Frequency adjust;
- Key operated start/ stop switch;
- Lamp test;
- Load bank test;
- Mains failure simulation;
- Maintenance bypass;
- Mute alarm;
- Return to mains operation; and
- Voltage adjust ±5%.
• Indicators:
- Electrical:
- Ammeter with phase selector switch;
- Battery voltage;
- Frequency meter;
- Generator synchronised;
- kW·h meter;
- Power factor meter with phase selector switch; and
- Voltmeter with phase selector switch.
- Prime mover:
- Coolant temperature gauge;
- Fuel gauge;
- Oil pressure gauge; and
- Tachometer.
- Status:
- Coolant heater on;
- Emergency stop activated;
- Generator in use;
- Generator ready;
- Generator off-load indication ;
- Generator on-load indication ;
- Hours run meter;
- Mains available indicator;
- Mains failure indicator; and
- Oil heater on.
• Alarms:
- Visual:
- Battery charge failure;
- Battery low voltage;
- Cooling fan failure;
- Engine overspeed;
- Engine start failure;
- Engine underspeed;
- High oil temperature;
- Low fuel; and
- Low oil pressure
- High Exhaust Temperature
490 LOAD BANKS Load bank connections will be incorporated into the main generator
switchboard, refer to main electrical LV schematic 1005885-BSXX(61)0002
• Type: Permanent resistive load.
• Manufacturer: Submit proposals.
• Product reference: Contractor's choice.
• Rating: 100% rated output of generator system.
• Enclosure:
- Ingress protection to BS EN 60529: IP44.
- Anti-condensation heater: Thermostatically controlled..
• Arrangement: Switch in equal load steps controlled from the generator system control
panel.
- Number of load steps: 5.
• Forced air cooling with run on timer: Required.
• Selective load control and load indicator: Required.
- Load step size: 10%.
FABRICATION
EXECUTION
COMPLETION
960 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
980 LABELLING
• Rating plate: To BS ISO 8528-5.
990 MAINTENANCE
• Servicing and maintenance: Undertake.
- Consumables: Provide.
• Duration: Until 12 months after Practical Completion.
- Maintenance interval: 3 months.
The Contractor will joint and connect HV cabling to HV cable loops as identified in the Acute
Services Block Enabling Works as built drawings.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the high voltage distribution system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
EXECUTION
COMPLETION
940 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
950 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
PRODUCTS
320 HIGH VOLTAGE SWITCHBOARDS Initially switchgear will operate on a 6.6 kV medium
voltage private network and switchgear ratings will reflect the current carrying capacity
required to operate on a 6.6kV network. After an indeterminate period of time it is
intended that the network voltage will be increased to 11kV and all installed equipment and
distribution infrastructure must be capable of accepting the changed network voltage
without alteration, including CT's.
Incoming cables will be connected to Ring Main Units installed within the Acute Services Block
in a location identified on Drawing 1005885-BSXX(60)4003. Ring Main units (RMU's) will be
provided by two different manufacturers and will be rated at 600A to allow for the 6,600 Voltage
range initially used on the private medium voltage network.
The Acute Services Block Medium Voltage 6.6kV / 11kV switchboard shall be installed
within a dedicated switchroom on the West side of the building at Level 1 Mezzanine plant area.
All installed switches shall be capable of operation from a remote switching panel located
outside the room. The remote switching panel will be provided by the same manufacturer
as the 11kV switchgear, when not in use leaving the HV switches in 'local' mode will
prevent unauthorised use of the remote switching panel. The remote panel shall be locked
with the same type, style and designation of padlock used throughout the HV system within
the Hospital HV network.
Once energised and works or operations involving HV switching will require switching
programs, permits to work, limitations of access and valid approved risk assessment to be
presented to Health Estates prior to approval of works.
The remote switching panel will be clearly labelled for all connected 11kV switches and
will include status indicators for all 11kV switches. A mimic panel which details the local
status settings of the switchgear shall be provided within the main control room
• Type: Cubicle .
• Manufacturer: Refer to schedule of preferred manufacturers and Suppliers.
- Product reference: Submit proposals.
• Access: Front.
• Switchgear arrangement: Submit proposals.
• Voltage rating: 6.6-11 kV.
• Prospective rated short circuit current (1 s): 250MVA
• Terminals: Suitable for the dry connection of copper and aluminium conductors.
• Enclosure: Manufacturer's standard.
- Accessories: Padlock and key cabinets.
• Service conditions: Normal indoor.
• Functional units: High voltage circuit breakers.
• High voltage busbars: Required.
• Transportation or installation restrictions: None.
• Accessories: Manufacturer's standard.
330 RING MAIN UNITS A ring main unit shall be provided adjacent to the building HV
switchgear which will connect the building to the external HV ring. It should be noted that
the HV ring currently operates on a medium voltage of 6600V. This will be upgraded to
11,000 Volts (11kV) therefore all switchgear provided must be capable of operating on dual
voltage
• Manufacturer: Each Ring main unit shall compromise switchgear provided by more than
one manufacturer. The Client has approved ABB, Lucy and Group Schneider .
- Product reference: Submit proposals .
• Ring switches: High voltage switch-disconnectors.
• Outgoing feeder device: High voltage circuit breakers
- Protection relay: Required
• Transportation or installation restrictions: None.
423 WATTMETERS
• Standard: To BS 89-3.
• Manufacturer: As Switchgear Manufacturer.
- Product reference: Submit proposals.
FABRICATION
515 PROPOSALS
• Content: Include the following:
- Overall dimensions.
- Degree of ingress protection.
- Mounting and fixing details.
- Builders work requirements including details of cast in rails.
- Fault level and rated short circuit characteristics.
- Functional unit details.
- Details of paint systems and colour finishes.
- Door swings.
- Access panel details.
- Schedule of labels.
- Dimensioned general arrangement drawings, plans elevations and sections.
- Shipping sections.
- Cable gland plate details.
- Routing of cables within assembly.
- Arrangement of busbars, connections and supports.
- Internal controls, instrument and meter diagrams.
• Proposals: Submit before fabrication.
EXECUTION
640 CONNECTIONS
• Incoming high voltage cables: Connect to switchgear.
COMPLETION
915 LABELLING
• Name plates in accordance with BS EN 60694: Provide.
• Equipment identification labels: circuit references
• Anti-condensation heaters: Provide caution notices advising against accidental switching
off.
• Standby power: Provide danger warning notices stating that assemblies may be energized
from more than one source.
• Indicator lamps: Label each lamp describing its function.
• Fuses, terminal blocks and other assembly components: Label describing their purpose.
• Spare fuses: Label, describe their rating.
• Cabinets for padlocks and spare keys: Label.
PRODUCTS
410 MANHOLES
• Access chambers: As section P30.
• Inspection chambers: As section P30.
EXECUTION
620 EXCAVATIONS
• Excavations next to existing underground services: In accordance with HS(G) 47.
- Method statement: Submit.
• Existing underground services: Expose and identify.
COMPLETION
920 DOCUMENTATION
• Record drawings: Submit. Show route, depth, cable types and sizes, ducts lengths and
sizes, joint locations, joint and service phasing.
GENERAL
SYSTEM PERFORMANCE
210 DESIGN
• Standard: To BS 7671.
• Design: Complete the design of the low voltage distribution system.
• Spare capacity throughout the low voltage distribution system: 20% of current carrying
capacity.
• Scope: Provide electrical supplies to equipment requiring power.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
• Switchgear drawings: To BS EN 61082-1.
EXECUTION
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
- Number of copies: 3 + electronic.
930 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
PRODUCTS
420 BUSBARS
• Standard: To BS EN 13601.
• Manufacturer: Refer to Schedule of Manufacturers and Suppliers.
- Product reference: Submit proposals.
• Approval: ASTA certified.
• Material: Hard drawn high conductivity copper.
• Cross section: Rectangular with radiused edges.
• Enclosure:
- Ingress protection to BS EN 60529: IP42.
- Material: Sheet steel.
- Finish: Powder coated
- Colour: Submit proposals.
465A SAFETY MATTING Provide along full lengths of accessible elevations of switchboards.
Ensure no overlapping (trip hazards)
• Standard: To BS 921.
• Manufacturer: Submit proposals.
- Product reference: Submit proposals.
• Thickness (minimum): 6.5 mm.
• Width (minimum): 900 mm.
• Length (minimum): Match low voltage switchgear assembly.
FABRICATION
515 PROPOSALS
• Content: Include the following:
- Overall dimensions.
- Degree of ingress protection.
- Protection against electric shock.
- Form of internal separation and details of busbar and terminal shrouding.
- Mounting and fixing details.
- Builder's work requirements and plinth details.
- Fault level and rated short circuit characteristics.
- Functional unit details.
- Details of internal and external paint systems and colour finishes.
- Door swings.
- Access panel details.
- Schedule of labels.
- Dimensioned general arrangement drawings, plans, elevations and sections.
- Shipping sections.
- Gland plate details.
- Routing of cabling within assembly.
- Busbar arrangements, links and supports.
- Internal controls, instrument and meter wiring diagrams.
540 LAYOUT
• Phase sequence: Set-out phase sequence for phases L1, L2, and L3, from left-to-right, top
-to-bottom, and back-to-front when viewed from the front of the assembly.
• Fuseholders: Mount such that fuses can be withdrawn towards the operator and away from
live parts.
• Heights of components (from finished floor level to underside of component):
- Equipment requiring operation or maintenance: 500-1600 mm.
- Instruments: 1200-2000 mm.
- Emergency switching devices: 800-1600 mm.
• Busbars and connections:
- Supports: Insulated.
- Identification: Provide 25 mm wide colour bands to busbars at 500 mm intervals with a
minimum of one band in each compartment.
- Future extensions: Pre-drill busbars for future extensions and extend busbar droppers
into spare functional unit locations.
EXECUTION
COMPLETION
970 LABELLING
• Switchgear terminals: To BS EN 60445.
• Anti-condensation heaters: Provide caution notices advising against accidental switching
off.
• Standby power: Provide danger warning notices stating that assemblies may be energized
from more than one source.
• Indicator lamps: Label each lamp describing its function.
• Fuses, terminal blocks and other assembly components: Label describing their purpose.
• Spare fuses: Label, describe their rating and associated outgoing ways.
• Cabinets for padlocks and spare keys: Label.
PRODUCTS
EXECUTION
PRODUCTS
310 LIGHTING BUSBAR TRUNKING Not included in the Cundall design but where proposed
by the contractor;
• Standard: To BS EN 60439-2.
• Manufacturer: E&I or Electrak or Equal & Approved.
- Product reference: Submit proposals.
• Assembly: Fully type-tested.
• Current rating: 40 A.
• Configuration: 5 pole.
• Place of installation: Indoor.
• Protection against electric shock: Submit proposals.
• Prospective rated short circuit current (1 s): 25 kA.
• Casing:
- Standard: To BS EN 62208.
- Material: Aluminium.
- Finish: Hot dipped galvanized.
- Colour: Galvanised.
- Ingress protection to BS EN 60529: IP40.
• Mechanical design:
- Mechanical loads: Normal.
- Additional loads: General lighting system.
• Conductors: Copper .
• Supports:
- Ceiling bracket;
- Clamp for channel;
- Suspension clamp; and
- Suspension ring.
• Accessories:
- Elbows;
- End covers;
- Flexible connections;
- Joint covers; and
- Plug outlet covers.
320 POWER BUSBAR TRUNKING Power Busbar trunking will be provided in electrical risers
located near stair cores 1,2 and 3. Power Busbar will provide power to all ward levels
within the Acute Services Block. Tap offs to all local distribution boards indicated in the
drawings will be provided as part of the contract, plus an additional 15% of the total number of
tap off boxes will be provided as spares. Spares will be provided complete with all necessary
items to allow the tap off to operate once a cable is installed to the tap off.
• Standard: To BS EN 60439-2.
• Type: Low voltage.
• Manufacturer: E&I or Schneider .
- Product reference: PowerBar or Canalis or Equal & Approved.
• Assembly: Fully type-tested.
• Current rating: 630 A.
• Configuration: Clean earth and 100% earth.
• Additional circuits: Submit proposals.
• Place of installation: Indoor within Electrical Risers.
• Attitude: Vertical.
• Protection against electric shock: Submit proposals.
• Prospective rated short circuit current (1 s): 50 kA.
• Casing:
- Standard: To BS EN 62208.
- Material: Aluminium.
- Finish: Self finished.
- Colour: manufacturers standard.
- Ingress protection to BS EN 60529: IP55.
• Mechanical design:
- Mechanical loads: Normal.
- Additional loads: Ladder supports.
• Conductors: Copper .
• Supports: Wall brackets.
• Accessories:
- Flexible connections;
- Joint covers; and
- Thrust units.
320A POWER BUSBAR TRUNKING Power Busbar trunking will be provided between the generators
and the main Generator switchboard with the busbar then continuing to feed the main LV
Switchboard. The main switchboard will also be served directly from the two main transformers
via busbar also.
• Standard: To BS EN 60439-2.
• Type: Low voltage.
• Manufacturer: E&I or Schneider .
- Product reference: PowerBar or Canalis or Equal & Approved.
• Assembly: Fully type-tested.
• Current rating: 4000 A.
• Configuration: Clean earth and 100% earth.
• Additional circuits: Submit proposals.
• Place of installation: Indoor within Electrical Risers.
• Attitude: Vertical.
• Protection against electric shock: Submit proposals.
• Prospective rated short circuit current (1 s): 75 kA.
• Casing:
- Standard: To BS EN 62208.
- Material: Aluminium.
- Finish: Self finished.
- Colour: manufacturers standard.
- Ingress protection to BS EN 60529: IP55.
340 TAP-OFF UNITS Tap offs to all local distribution boards indicated in the drawings will be
provided as part of the contract, plus an additional 15% of the total number of tap-off boxes
will be provided as spares. Spares will be provided complete with all necessary items to
allow the tap-off to operate once a cable is installed to the tap-off.
• Standard: To BS EN 60439-2.
• Type: Plug-in.
• Manufacturer: E&I or Schneider to match power busbar or Equal & Approved..
- Product reference: Power Bar or Canalis.
• Rating: As schematics, drawings and circuit charts.
• Phase: Three.
• Assembly: Partially type-tested.
• Circuits: To match busbar trunking.
• Accessories: Circuit-breaker.
350 FEED UNITS End feed units shall include an isolator fully rated to the system requirements
• Standard: To BS EN 60439-2.
• Type: End feed.
• Manufacturer: E&I or Schneider or Equal & Approved.
- Product reference: PowerBar or Canalis.
• Circuits: To match busbar trunking.
• Accessories: Submit proposals.
EXECUTION
620 INSTALLING POWER BUSBAR TRUNKING Power busbar will be installed vertically
within electrical risers with the end feed unit mounted at the lowest practical point to
maximise space for tap-offs within the risers.
• Generally: In accordance with BS 7671.
• Location: Within electrical risers.
• Expansion joint interval: 30m .
• Supports and fixings:
- Supports: Purpose made brackets.
- Finish and colour: Match trunking.
- Locations where moisture may occur: Corrosion resistant, selected to prevent
deterioration by electrolytic action.
630 INSTALLING TAP OFF UNITS Tap-offs will be installed within riser cupboards and connect
distribution boards to the 400V electrical network..
• Generally: In accordance with BS 7671.
• Location: Within electrical risers - on the same floor level as the connected equipment.
• Tap-off point intervals: 600 mm.
640 INSTALLING FEED UNITS Each busbar will have a dedicated end feed unit, main rising
busbars shall be connected by LSA/SWA/xple cable to the main switchboard.
• Generally: In accordance with BS 7671.
• Location: Within electrical risers at lowest available floor.
650 INSTALLING FIRE BARRIER UNITS Where busbar trunking penetrate walls and
compartments.
• Generally: In accordance with BS 7671.
• Location: At all fire walls.
COMPLETION
910 CLEANING
• Trunking: Clean immediately before handover.
950 LABELLING
• Busbar terminals: To BS EN 60445.
960 DOCUMENTATION
• Drawings: Submit, showing the busbar trunking and tap-off units.
PRODUCTS
EXECUTION
COMPLETION
PRODUCTS Harmonic Filtering equipment will be installed on the main switchboard. The
contractor will allow for carrying out a survey once the building has been operation for 6
months. The contractor will also allow for installing the required filtration when required
following the survey.
EXECUTION
620 SURVEY
• Objectives: To determine harmonic content and development within the operational
Electrical infrastructure.
• Scope of survey: Main and sub-main distribution switchgear, major rotating plant loads, IT
power distribution switchgear .
COMPLETION
COMPLETION The particular testing and inspection requirements shall be fully addressed
in accordance with applicable statutory recommendations and guidance. Systems in this
respect shall include but not limited to
1) HV
2) LV
3) MEiGAN
920 GENERAL
• Standards: To BS 7671 and in accordance with IEE Guidance note 3.
• Notice before commencing tests (minimum): 7 d.
• Installed equipment standards: Verify and confirm compliance with the relevant equipment
standards.
• Electronic devices: Isolate to prevent damage during testing.
• Continuity of protective conductors:
- Parallel earth paths: Isolate before testing.
- Equipment: Continuity tester with short circuit current of at least 200 mA, and a no load
d.c. or a.c. voltage between 4 V and 24 V.
• Insulation resistance (minimum):
- SELV and PELV circuits: 1 megohm.
- Other circuits less than or equal to 500 V: 2 megohm.
- Circuits less than or equal to 500 V: 2 megohm.
• External earth fault loop impedance: Direct measurement.
• Connection of test equipment to existing switchgear: Submit proposals.
- Timing: 14 days notice on LV, 28 days notice on HV.
• Earth fault loop impedance:
- Method: Direct measurement.
• Measurement locations: Origin, switchgear, fixed equipment and outlets, circuit extremities.
• Prospective fault current:
- Method: Direct measurement.
- Location: Origin, and at points where protective devices are required to operate under
fault conditions.
• Phase sequence: Verify.
• Cable containment: Measure electrical continuity and insulating properties of containment.
Submit results.
920A GENERAL
• Standards: To BS 7671 and in accordance with IEE Guidance note 3. Engineering
Recommendations, MEiGAN
• Notice before commencing tests (minimum): 7 d.
• Installed equipment standards: Verify and confirm compliance with the relevant equipment
standards.
• Electronic devices: Isolate to prevent damage during testing.
• Continuity of protective conductors:
- Parallel earth paths: Isolate before testing.
- Equipment: Continuity tester with short circuit current of at least 200 mA, and a no load
d.c. or a.c. voltage between 4 V and 24 V.
• Insulation resistance (minimum):
- SELV and PELV circuits: 1 megohm.
- Other circuits less than or equal to 500 V: 2 megohm.
- Circuits less than or equal to 500 V: 2 megohm.
• External earth fault loop impedance: Direct measurement.
• Connection of test equipment to existing switchgear: Submit proposals.
- Timing: 14 days notice on LV, 28 days notice on HV.
• Earth fault loop impedance:
- Method: Direct measurement.
• Measurement locations: Origin, switchgear, fixed equipment and outlets, circuit extremities.
• Prospective fault current:
- Method: Direct measurement.
- Location: Origin, and at points where protective devices are required to operate under
fault conditions.
• Phase sequence: Verify.
• Cable containment: Measure electrical continuity and insulating properties of containment.
Submit results.
GENERAL The requirements for this project include but not limited to compliance with BS
7671 , associated Guidance notes and in certain defined areas MEIGAN. The physical
arrangements and provisions of the electrical infrastructure in such defined areas shall
primarily be fully in accordance with MEIGAN stipulations. The installations in this regard
shall have the necessary earthing installations inclusive of increased earth conductor sizes.
The Cath labs installation shall require termination of the main equipment supplies at the
associated UPS. Electrical services earthing provisions shall terminate at the ERB within
the UPS plant room Contractor shall ensure positioning of the Distribution switchgear
which serves the Cath labs areas shall be suitably positioned with respect to the ERB, and
testing and certification regimes of the electrical services to the space.
SYSTEM PERFORMANCE
210 DESIGN
• Provision of small power: Fixed and portable equipment requiring power.
• Design: Complete the design of the small power systems.
• Diversity: In accordance with IEE Guidance note 1 .
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
PRODUCTS
EXECUTION
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
930 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
PRODUCTS
GENERAL
Provide full and complete systems. Ensure inclusion and provision of all necessary
interconnection cabling between all items of plant equipment and components.
310B UNINTERRUPTIBLE POWER SUPPLY FOR CATH LAB EQUIPMENTN+1 UPS systems
will be provided in separate distinct modes of operation which include;
• Static Online UPS for data systems / IT protection within the Server Room
Static Online UPS for Cath Lab main plant protection (Provided and installed as part of
Cath labs installation. Electrical contractor to provide and install power supplies terminating
at Cath lab UPS system.
• IPS / UPS combined supply's to medical and theatre equipment
• Cabinet mounted UPS systems to Krone Frames installed to Hub Rooms
UPS systems for Cath lab protection
This system shall be provided and installed as part of the Cath labs equipment specialists
works. The electrical contractor shall arrange the non Cath equipment electrical services
arrangements to suit the Cath lab UPS/MEiGAN infrastructure requirements (including
Testing and inspection).
• Standard: To BS EN 62040-3.
• Type: On-line Double Conversion.
• Manufacturer: Supplied as part of Cath Labs Installation. Electrical Contractor shall liaise
fully with systems specialist to ensure all necessary attendant electrical services provisions
are include to, from and about this system .
350 BATTERIES
• Type: Lead-acid valve regulated (VRLA) to BS 6290-4, BS EN 60896-21 and BS EN 61056
-1
• Voltage: Submit proposals
• Battery autonomy (stored energy time at rated power): Various autonomies applicable (all
at full power) to specific systems/applications as detailed elsewhere.
• Fused parallel battery strings: Multiple strings. Must have fused transition box..
- Automatic disconnection of a faulty string: Fusing Required
• Impact resistant plastic shields to intercell terminal and output terminals: Required.
• Battery supply d.c. circuit breaker with overload and short circuit protection: Required.
• Ripple free battery charger with automatic temperature and float voltage compensation:
Required.
• Battery recharge time: Submit proposals
EXECUTION
COMPLETION
915 LABELLING
• Identification label: All UPS systems to be labelled with distribution system name, where
incoming cables are fed from and details of switching and bypass arrangements .
940 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
950 MAINTENANCE
• Servicing and maintenance: Undertake.
- Consumables: Provide.
- Duration: Until 12 months after Practical Completion.
GENERAL
SYSTEM PERFORMANCE
210 DESIGN
• Standard: In accordance with CIBSE Code for lighting LG2.
• Design: Complete the design of the general lighting systems.
• Average power density energy consumption (maximum): 8 W/m².
• Initial circuit luminous efficacy (minimum): 60 lm/W.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
220 PERFORMANCE
• Lighting performance: Lighting to be RA90 with 4000 Kelvin Lamps.
PRODUCTS
345 LIGHTING EXTENDER LEADS All cables to be fully supported throughout length in
accordance with BS7671 and associated Guidance notes. No cables to be loose laid in
ceiling void. Ensure sufficient length and additional extender leads as necessary to clip and
dress cabling to soffit slab following neat horizontal building lines between lighting
distribution modules and between luminaires. Where extender leads serve light fittings they
are to be clipped to point on slab directly above light fitting..
• Manufacturer: Refer to Schedule of Preferred Manufacturers and Suppliers.
- Product reference: Submit proposals.
• Cable type: Prefabricated LSZH insulated singles in flexible conduit.
- Number of cores: 5.
- Size: 2.5 mm².
• Length: 10 m.
• Connectors:
- Arrangement: One fully shrouded male connector and one fully shrouded female
connector.
- Poles: 6.
350 LUMINAIRE CONNECTION CABLES Ensure that the final connection cable is not more
than depth of ceiling void +300mm at any location. Review ceiling void depth accordingly
and ensure details issued to luminaire suppliers for integration.
• Manufacturer: Refer to Schedule of Preferred Manufacturers and Suppliers.
- Product reference: Submit proposals.
• Cable type: Prefabricated LSZH insulated and sheathed multi-core.
- Number of cores: 3 and 4.
- Size: refer to distribution board schedule
• Length: Not more than depth of ceiling void +300mm at any location.
• Connectors:
- Arrangement: One fully shrouded male connector and one fully shrouded female
connector and One fully shrouded male connector and one free cable end.
- Poles: 6.
375 T CONNECTORS .
• Standard: To BS EN 60320-1.
• Manufacturer: Refer to Schedule of Preferred Manufacturers and Suppliers.
- Product reference: Submit proposals.
• Type: Fixed to luminaire and Flying lead.
• Cable type: Prefabricated LSZH insulated singles in flexible conduit.
- Number of cores: 5.
- Size: 2.5 mm².
• Length: Where used as fixing to luminaire ensure that the final connection cable is not
more than depth of ceiling void +300mm at any location. Review ceiling void depth
accordingly and ensure details issued to luminaire suppliers for integration. Where used as
flying lead principle as per lighting extender lead (clause 345 of this specification section.
• Connectors:
- 'T'arrangement: One fully shrouded male connector and one fully shrouded female
connector.
- Connection to luminaire: Fully shrouded male connector.
EXECUTION
COMPLETION
930 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
- Number of copies: 3 + electronic.
940 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after completion.
GENERAL
PRODUCTS
EXECUTION
COMPLETION
915 LABELLING
• Equipment and sensor identification labels: Provide.
• Central controller: Label describing its purpose.
- Output circuits: Label.
GENERAL
110 CENTRAL BATTERY EMERGENCY LIGHTING AND SIGNAGE SYSTEM A full complete
fully operational certified system will be provided and installed. The emergency lighting
systems will be a distributed central system whereby control and battery enclosures will
be installed throughout the building and not at one central location.
The system will be addressable type with DALI control and distribution system to serve
system power, control and monitoring requirements
SYSTEM PERFORMANCE
210 DESIGN
• Standards: To BS EN 1838, BS EN 50171, BS EN 50172 and in accordance with BS 5266-
1.
• Design: Complete the design of the emergency lighting and signage systems.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
• Mode of operation: 0,1, 6.
- Facilities: B, C, D .
- Full load duration under rated load conditions (minimum): 180 minutes.
PRODUCTS
320 BATTERIES
• Manufacturer: Refer to Schedule of preferred suppliers and Manufacturers.
- Product reference: Submit proposals.
• Type: Sealed nickel-cadmium prismatic cells.
• Labelling: Indelibly mark with year of manufacture and installation.
FABRICATION
EXECUTION
620 SAMPLES
• Samples to be submitted: all emergency lighting luminaires and signage to be submitted to
the Client via the Architect.
• Submittals: Include manufacturer's technical information with each sample.
• Identification: Label samples with the project luminaire references.
COMPLETION
940 SPARES
• Quantity of manual test keys (minimum): 10
960 DOCUMENTATION
• Documentation: In accordance with BS 5266-1.
• Certificate of testing: Submit.
- Certficate: In accordance with BS 5266-1, Annex B.
- Number of copies: 3+ electronic.
• System log book: Required.
970 MAINTENANCE
• Service and maintenance: In accordance with BS 5266-1.
- Duration: Undertake until 12 months after completion.
PRODUCTS Internal artificial lighting shall be provided by low energy lamp sources, in
particular light emitting diode (LED) light sources. All selected luminaires must be compliant
to the requirements of BREEAM 2008 Healthcare. For specific clauses relating to BREEAM
please refer to the requirements listed in Section B06
of this document.
Fluorescent lighting shall be provided by linear or circular 'T5' lamps. '2D' (TCDD) Lamps
will not be accepted on this project.
395 ENCLOSURES FOR CONTROLGEAR where non integral control gear is used internally
• Manufacturer: System manufacturer.
- Product reference: Submit proposals.
• Material: Submit proposals.
- Finish: Match luminaire.
- Colour: As Luminaire schedule.
• Degree of ingress protection to BS EN 60529: IP31.
• Hardware: Cylinder lock and handle. Standardize key type.
• Labelling: Describe controlgear purpose.
402 CONTROL GEAR Unless otherwise stated control gear shall be integral to the luminaire.
• Position: Integral within luminaire.
405 LUMINAIRES .
• Manufacturer: As per approved list of manufacturers. The contractor may choose the
fitting listed as the design fitting for each luminaire, or offer one of the approved
alternatives as a replacement for the design fitting. The contractor does not have to buy all
the fittings for the project from a single manufacturer, but must utilise the approved
alternatives provided. The contractor can take a commercial decision as to which fittings
will be supplied from any particular manufacturer from the approved manufacturer and
fitting schedule.
It should be noted that the approved luminaire schedule has been carefully assessed for
the equality of light fittings and the quality of light output. If the contractor offers any other
alternatives the contractor must provide full details of comparative quality of materials
including diffuser technologies and lamps. The Contractor will also be expected to provide
comparative light output with fully detailed lighting plots in relux or dialux format as part of
the submission. No non-approved alternatives will be accepted without full documentation
proving the quality of light and materials and justification of what advantages other
alternatives can offer to the project.
The design team is not bound to accept any changes in specification or quality of light
output from the lighting installation and deviations from the approved schedule shall have
to be approved collectively in writing by the Engineer, The Architect and the Client before
implementation of any changes thereto. .
- Product reference: As per manufacturers and luminaires schedules..
• Description: As per schedules and drawings.
FABRICATION
EXECUTION
610 SAMPLES
• Samples: Before ordering, supply samples of the following luminaires: A sample of each
type of luminaire is to be provided to the Client via the Architect. All samples to be
provided for comment at least two calendar months before any orders for fittings are
placed with suppliers. Electrical Contractor is to allow appropriate timescales to achieve
client comments within the programme of works.
• Submittals: Include manufacturer's technical information with each sample.
• Identification: Label samples with the luminaire references.
COMPLETION
910 CLEANING
• Luminaires and lamps: Clean when building works are complete.
GENERAL
120A FEATURE LIGHTING SYSTEMS Feature lighting will be installed to landscaping and
courtyards in line with Landscape Architect and Electrical drawings and specifications.
• System manufacturer: As per lighting schedules.
- Product reference: As per lighting schedules.
• Electrical supply: Low voltage connection, as section V11.
• Low voltage switchgear: Cable distribution cabinet, as section V31 or fed direct from plant
room (dependant on location).
• Luminaire supports: As per lighting schedules.
- Painting: Not required.
• Concrete bases to columns/pedestals: Not required.
• Luminaires: As Luminaire schedule.
- Operating voltage to BS 7671: Low voltage.
• Controls:
- Types: Photoelectric control units, as section V51 and Time switches , as section V51,
PIR's and sequencing (DMX).
- Configuration: Group.
- Accessories: As per lighting schedules.
• System accessories: Electrical cut outs.
120B SECURITY LIGHTING SYSTEMS External areas surrounding the Acute Services Block
shall be designed and installed to Secured by Design Criteria
• System manufacturer: As per Lighting Schedules.
- Product reference: As per Lighting Schedules.
• Electrical supply: Low voltage connection, as section V11.
• Low voltage switchgear: Cable distribution cabinet, as section V31.
• Luminaire supports:
- Steel lighting columns;
- Steel lighting pedestals;
- Steel column luminaire brackets; and
- Steel luminaire brackets.
- Painting: Anti-graffiti textured finish.
• Concrete bases to columns/pedestals: Required.
• Luminaires: As section V59.
- Operating voltage to BS 7671: Low voltage.
• Controls:
- Types: Photoelectric control units, as section V51 and Time switches , as section V51,
PIR sensor and master over-ride control .
- Configuration: Group.
- Accessories: Enclosures for control gear .
• System accessories: Electrical cut outs.
SYSTEM PERFORMANCE
PRODUCTS
EXECUTION
• Locating components: Accurately position, plumb and provide secure temporary support.
Prevent disturbance for at least 48 hours after placing concrete.
• Cable ducts: Connect to column cable entry slot and protect against collapse during
backfilling.
• Compaction: Fully compact as filling proceeds.
COMPLETION
910 CLEANING
• Electrical equipment: Clean immediately before handover.
930 COMMISSIONING
• Setting for control devices: Submit proposals and commission.
• Operation of control devices: Verify.
• Orientation of adjustable luminaires: Adjust to give optimum performance.
950 DOCUMENTATION
• Timing: Submit at completion.
• Contents:
- Full technical description of each system installed.
- Manufacturers' operating and maintenance instructions for fittings and apparatus
including relamping instructions for luminaire types. Identify hazardous lamps that
require specialist disposal.
- Recommended frequency of testing and inspection, both for electrical safety, and for
matters such as the corrosion and security of lighting columns and luminaire fixings.
- Manufacturers' guarantees and warranties.
- Record drawings showing circuits and their ratings and locations of fittings and
apparatus.
- List of normal consumable items and their sources.
980 KEYS
• Padlock keys:
- Number for each padlock: 2
• Lighting column access door keys:
- Number for each group of columns: 3
• Timing: At completion.
990 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
PRODUCTS
FABRICATION
520 DIAGRAMS
• Material: Paper print, encapsulated.
• Format: Single line engineering drawings to BS EN 61082-1.
• Information to be included:
- Supply characteristics.
- Maximum demand.
- Cable types and sizes.
- Switchgear ratings.
- Protective device types, ratings and function.
- Prospective fault current values: At each item of switchgear.
- Earth fault loop impedance values: At each item of switchgear.
- Circuits containing equipment vulnerable to testing: Label.
• Mounting: Wall.
EXECUTION
620 SAMPLES
• Labels: Submit samples showing material, style, colour, lettering, and fixing method for
each label type.
630 ARRANGEMENT
• Location: Submit proposals.
• Fixing: Secure, plumb and level.
- Type: Round head bolt, washer and lock nut.
GENERAL
GENERAL Earthing will generally be provided and installed fully in accordance with the
requirements as indicated in BS7671 and associated Guidance notes BS7430 and BS EN
62305. There are specific areas however where it is necessary to incorporate fully the
requirements of MEiGAN. In such instances it shall be necessary to increase the size of
CPCs and earth conductors , consolidate LV distribution infrastructure of such areas to
UPS rooms at different floor levels and generally amend earthing infrastructure physically
to suit Notwithstanding this the earthing arrangements shall remain compliant with BS7671
110 EARTHING AND BONDING SYSTEMS Generally works shall be carried out in full and
complete strict accordance with BS7671. There are instances in the installation where the
MEiGAN requirements shall take precedence. In these defined areas the MEiGAN
stipulations shall take precedence. Where the medical device manufacturer stipulates an
electromagnetic interference (EMI) screen for mains supply cables, the SWA shall be
terminated with a zoned earthing and neutral (ZEN) gland. The SWA shall be earthed only
at the distribution board unless that would conflict with the equipment manufacturer's
instructions for earthing arrangements for electromagnetic compatibility (EMC).
The steel wire armour (SWA) shall provide mechanical and electro-magnetic compatibility
protection; it shall not be used as the main earth conductor. Connection to earth shall be
achieved by means of a copper conductor, having a cross sectional area (CSA) greater
than or equal to that of the phase conductors. Where the medical device
supplier specifies a greater cross sectional area, the supplier's instructions shall be
followed. The copper earth conductor shall be connected to the source of the supply
unless it can be shown that a more local distribution panel can provide a copper conductor
of adequate CSA from the earth reference bar (ERB) to the earth distribution bar of the sub
-station (verify by inspection).
SYSTEM PERFORMANCE
210A DESIGN
• Standards: To BS 7671 and in accordance with BS 7430 and MEiGAN.
• Design: Complete the design of the earthing and bonding systems.
• Proposals: Submit drawings, technical information, calculations and manufacturer's
literature.
280 DESIGN FOR THE SAFE USE AND HANDLING OF FLAMMABLE LIQUIDS
• Design: In accordance with HS(G) 140.
PRODUCTS
EXECUTION
COMPLETION
940 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
GENERAL Induction loops will generally be required at fixed points of contact between
staff and visitors . These are generally identified as (but not limited to) interim main
entrance, sub-reception areas, staff bases training rooms, meeting rooms, interview rooms
rest areas. Systems will be stand-alone with dedicated loops, control amplifiers,
speakers, microphones and all necessary cabling and components etc to effect full
complete fully operational systems with optimal interference free clarity of
signal/communication.
SYSTEM PERFORMANCE
210 DESIGN
• Design and planning: In accordance with BS 7594.
- Variations: None.
• Design: Complete the design of the induction-loop system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
• Qualifications of designer: Member of the Institute of Sound and Communication Engineers
or Member of the Professional Lighting and Sound Association.
Loop cable type and size: Submit proposals.
- Design loop current: Submit proposals.
• Equipment: Provide electrical supplies to equipment requiring power.
PRODUCTS
350 TRANSFORMERS
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Type: Matching.
450 SIGNAGE
• Requirements in accordance with BS 7594:
- Equipment identification: Figure 2.
- Areas where an induction-loop system is installed: Figure 2.
- Areas where reception of the induction-loop system does not meet the system
performance: Figure 3.
• Material: PVC.
• Dimensions: 300 mm x 300 mm.
EXECUTION
COMPLETION
960 SPARES
• Spare fuses:
- Quantity (minimum): 5% of each type and rating used.
970 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit
980 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
High Definition signals shall be transmitted to all the Televisions installed in the Acute Services
Block. Each of the bedrooms will be separately connected to the TV network and
shall be capable of delivering 'Freeview HD' TV and radio services. The system will be
integrated with the Nurse call system to enable full control of the end use television
apparatus by means of a handset interfaced with the nurse call system within bedrooms,
elsewhere standard infra-red controllers will be employed. Within bedrooms the television
system will use a dedicated controls wiring installation as the mechanism for switching
control functionality and interconnection from the individual plug-in handsets to the local
television system/apparatus.
The IPTV system will be capable of accepting inputs to and from a central computer
terminal for hospital wide text and graphical displays e.g daily meal menu information and
any other hospital wide notifications required. To allow two way communication each TV
will be addressable to room location thereby allowing the selection of meal menu choices
by the patient. Provision will be made for internal 'on demand' services from a local
server held within the IT room for the building.
IPTV's will comply with and be certified to Energy Saving Trust Recommended Criteria;
Digital televisions must meet the following Energy Saving Trust Recommended product
certification criteria:
Compliance with 642:2009 (e.g. on passive standby and auto power down)
Compliance with the RoHs & WEEE Directives can be demonstrated by manufacturers self
declaration
On mode power consumption of =50W
The Home Mode must be set at a brightness level not less than 65% of the maximum
Certification proof
To prove that the individual product has met the Energy Saving Trust Recommended
criteria we require the following documentation:
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the television distribution system.
- Standards: To BS EN 60728-11, the requirements of the Digital Television Group
guide, The CAI Code of practice for television aerials and TV systems, and BS 7671.
• Proposals: Submit drawings, technical information, calculations and manufacturers
literature.
• System designer: Specialist Supplier as per Schedule of Preferred suppliers.
- Qualifications of designer:
- Member of the Society of Cable and Television Engineers (SCTE);
- Member of the Confederation of Aerial Industries (CAI); or
- Member of the Independent Digital Standards Commission (IDSC).
220 PERFORMANCE
• ITU impairment grade: 5.
PRODUCTS
320 FM ANTENNAE
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Approval: CAI Benchmark
• Forward gain dB(i): Submit proposals.
• Front/ back ratio dB(i): Submit proposals.
360 EQUALIZERS
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Type: Band pass and Cluster levellers.
• Transmitter source: Submit Proposals.
• Signal loss: Submit proposals.
380 MULTISWITCHES
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Frequency:
- Satellite bandwidth: 950-2150 MHz.
- Terrestrial bandwidth: 47-862 MHz.
• Inputs:
- IF: Submit Proposals.
- Wideband UHF-VHF: Submit Proposals.
• Outputs Submit Proposals.
• Satellite signal loss Submit Proposals.
• Terrestrial signal loss Submit Proposals.
• Switching: 13 V, 18 V, 13 V/ 22 kHz, 18 V/ 22 kHz.
390 DIPLEXERS
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Type:
- Diplexed (radio and TV);
- Double F satellite master outlet (radio, TV and satellite 1 and 2);
- Single F satellite;
- Single IEC radio or TV out; and
- Triplexed (radio, TV and satellite).
• Signal loss: Submit proposals.
EXECUTION
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
- Number of copies 3 + electronic.
940 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
GENERAL
110 TELECOMMUNICATIONS SYSTEM The requirements are for a full complete fully
operational telecommunications system to serve the complete telecommunication
requirements of the project. The contractor will engage the services of a system specialist
from the schedule of preferred suppliers and manufacturers to carry out the installation.
The telecommunications shall be installed as Voice over Internet Protocol (VOIP) and shall
be installed as part of the data distribution network as section W31.
Pass through technology shall be used to allow voice communications and computers to
connect to the same Cat 6 cabling installation. The Trust shall also install a Vocera mobile
communications system which will operate over the wireless and hard wired data networks
described in Section W31. The Contractor will not install the Vocera system which will be
independently procured by the Trust. The system will be utilised to transmit and
distribute a wide variety of data from discrete systems, such as, Security/access control
Vocera, BMS Nurse call, patient recording, Endoscope processing etc
Emergency phone lines use in lifts and for redcare notifications will not be connected into
the data network; The Contractor will wire these as separate analogue phone lines
directly connected to the Security Office.
The Contractor will install analogue phone lines within the Main reception for 2 off
payphones and 1 off taxi phone which will only connect to approved local taxi companies
(numbers to be provided by the Trust )
• System manufacturer: Cabling will be a mixture of fibre and copper as per Section W31.
Telephone handsets will not be provided by this contract.
• Type of system: Voice Over IP.
• Method of operation: Digital.
• UPS: As section V44.
• Connection to public telephone network: Required.
• Distribution panels: Required.
• Cables: As per W31.
• Cabling topology:
- Backbone cabling: As section W31.
- Horizontal cabling: As section W31.
• Telecommunications outlets: RJ45 Data outlets.
• Terminal devices: Required.
• Payphones: Not required.
• Operator consoles: Not required.
• Lightning protection: As section W60.
• Transient over-voltage surge suppression devices: As section Y67.
• Accessories: Call information logging equipment.
120 CONTAINMENT The voice communications shall use the data containment network
cabling and containment.
• Containment: Cable basket, as section Y63.
• Rewireable installation: Required.
• Concealed installation: Required.
• Draw wires: Provide in conduit drops.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the telecommunications system.
- Standards: To BS 6701 and BS EN 50174-1.
- Proposals: Submit drawings, technical information, calculations and manufacturers'
literature. Include:
- Cabinet general arrangements.
- Cabling topology schematics.
- Distribution point layouts.
- Equipment room layouts.
- Interconnection diagrams.
- Work area layouts.
250 RESILIENCE
• Resilience: Submit design and cost proposals.
• Fall back facility: Submit design and cost proposals.
• Spare capacity: Submit design and cost proposals.
PRODUCTS
365 PAYPHONES Install two payphones to the Ward Block Main Reception area
• Standard: To BS 7983.
• Manufacturer: Submit proposals.
- Product reference: Submit proposals.
• Types:
- Coin operated;
- Credit card operated; and
- Phonecard operated.
• Handsets fitted with inductive couplers: Required.
• Facilities: Fast dial key type and Outgoing calls only.
EXECUTION
COMPLETION
920 DOCUMENTATION
• Standard: To BS EN 50174-1.
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
925 LABELLING
• Standard: to BS EN 50174-3.
• Cabling topology schematics:
- Location: Main telephone exchange.
- Format: A1 paper print.
- Installation: In glazed frame, wall mounted with cup and screw fixings.
• Equipment: Label with unique identifier.
- Type: Face engraved rigid plastic laminate.
• Cable schedules:
- Location: Building telephone exchange.
- Format: Card within a reusable clear plastics envelope.
- Size: A5.
- Contents: Outgoing cable designation and destination
• Cable labels: Wrap-around machine-printed label with cable identifier.
- Location: Within 100 mm of each termination.
• Outlet labels: Machine printed adhesive label with extension identifier.
- Format: Submit proposals.
940 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
- Level of maintenance: system infrastructure Hardware and software excluding terminal
devices.
• All incoming ductwork and containment for BT and Virgin Media cabling to connect to the
Level 1 Server Room. BT will be installed from two locations (East side Level 2 and West
side at high Level under the Link bridge connecting to Level 1. Virgin Media will be
installed form the East side of the Building at Level 2.
• All outgoing containment and ductwork to connect a fibre network to other buildings within
the Ulster Hospital Estate
• All containment systems for backbone cabling including blown fibre containment with 50%
spare capacity to each hub room
• All backbone cabling OM3 & OS2 (fibre)
• All reserve/back up backbone cabling (CAT 6 copper)
• All distributed Cat 6 Cabling and final termination face plates
• All cabinets to server room, generally 42U and quantities as per server room layouts.
• All Krone APF frames to hub rooms (two per hub room)
• All high integrity earthing to Server and hub rooms. *Note all small power used will have
high integrity earthing
• Patch panels
• Patch leads of the same standard and data rate as the Cat 6 cabling (quantities to be
confirmed by Trust IT)
Backbone fibres between the Acute Services Block server room and other buildings Server
Rooms will be run on diverse routes in separate ducts via separate risers. The minimum
separation between ducts is to be 30 m. Within each building the separation between the
routes to the two central server rooms will be maintained as far as possible and use
separate risers. There is no minimum separation within the hub / patch rooms.
The main runs between buildings will be a loose-tube, gel-free, armoured cable that is
rated for external and internal use in ducts and risers without the need for a transition
splice. This allows the fibre to be brought into the server rooms for direct termination.
The sub-distribution within a building will be a similar loose-tube, riser-rated cable with a
toughened jacket but does not need to be armoured.
Administration or Nurse workstations VoIP systems may share a single data socket by
pass through technology for both the phone and the PC, however in line with Trust IT
policy four RJ45 data outlets and three twin switched socket outlets (tsso) are required per
person / workstation
At each bed-head three CAT-6 sockets will be provided (two for medical use and one for
future patient entertainment).
Wi-Fi
A pair of CAT-6 cables connecting to twin Wi-Fi outlets are required for each wireless access
point. The wireless access points do not require 230 Vac as they can be powered over the
CAT-6 cable from the network switch as a Power over Ethernet (PoE) system. Wireless
access points will be Trapeze (Juniper). At every internal Wi-Fi point 5 meters spare of data
cable shall be left prior to the termination to allow for adjustments to the Wi-Fi coverage
during final surveying of the Wi-Fi network distribution.
Wi-Fi coverage will be provided as full coverage to the entire building including all plant
spaces, stairwells, public areas and service support areas. Within areas with radiation
shielding a Wi-Fi point will be located in each room of that particular radiation shielded area.
External Wi-Fi
The contractor shall install an external Wi-Fi network to provide full coverage for Vocera
voice communications (Vocera by others). The external Wi-Fi network shall provide
coverage to the following areas;
It should be noted that an external duct network has been installed as part of the enabling
works which connect to the North Loop road, however all other containment and routes will
be installed by the electrical contractor as part of this contract. External drawings will detail the
routes.
• Cabling hierarchy:
- Campus distributors (CD): Cabinets.
- Campus backbone cabling: Optical fibre cabling.
- Building distributors (BD): Krone Frames within hub rooms.
- Building backbone cabling: Optical fibre cabling.
- Floor distributors (FD): Balanced twisted-pair cabling patch panels.
- Horizontal cabling: Balanced twisted-pair cabling.
- Consolidation points (CP): Balanced twisted-pair cabling patch panels.
- Consolidation point cabling: Balanced twisted-pair cabling.
- Telecommunications outlets (TO): Balanced twisted-pair cable outlets.
- Work area cabling: Patch cords.
• Cabling topology:
- Campus backbone: Ring.
- Building backbone cabling: Submit design and cost proposals.
- Horizontal cabling: Star.
• Accessories: Transient over-voltage surge suppression, as section Y67.
120 CONTAINMENT Incoming duct points must be met by main containment with blown fibre
provision to take the incoming cables to the server room to ensure the cable(s) are not
unsupported at any point. Incoming routes from the East and West sides of the building
must be diverse and as far as reasonably practical must be installed to separate fire
compartments (a common point of termination within a single fire compartment is
acknowledged)
The electrical contractor shall install cable containment routes; generally main routes will
be provided with galvanised cable baskets with final conduit down drops concealed in walls
terminating to single or double gang steel back boxes. The data cabling specialist shall
procure, install, test and commission all data wiring. Conduits above non accessible
bedroom ceilings which terminate to recessed back boxes within walls or bedhead trunking
must have a pull-in points with draw tapes located above the accessible ceiling panels to
allow future cable changes or additions without the need to disrupt or break into ceiling
finishes.
For horizontal final distribution all containment bending radii and back box depths will
allow for the required performance criteria for Cat6 cabling.
SYSTEM PERFORMANCE
210 DESIGN
• Standards:
- To BS EN 50173-1;
- To BS EN 50173-2;
- To BS EN 50173-3;
- To BS EN 50173-4;
- To BS EN 50173-5;
- To BS EN 50174-1; and
- To ISO/IEC 11801.
• Design: Complete the design of the data distribution system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
- Drawings. Include:
Cabinet general arrangement drawings.
Cabling topology schematics.
Distribution point layout drawings.
Equipment room layout drawings.
Interconnection diagrams.
Work area layout drawings.
250 RESILIENCE
• Spare capacity: 50% spare backbone cabling and blown fibre capacity. One spare
horizontal final data cable to each room with more than 5 data connections.
Provisions shall enable two way data transmission between systems. All infrastructure
shall be provided and installed to meet the requirements.
PRODUCTS
330A SINGLE MODE OPTICAL FIBRE CABLES to be used where cable lengths exceed 300m
• Standard:
- Singlemode: To BS EN 60793-2-50.
• Manufacturer: SE Trust approved supplier.
- Product reference: Submit proposals.
• Physical characteristics: Singlemode.
• Category: OS2
• Optical fibre strands: 24.
• Environment: Outdoors / indoors without petroleum fill (LSOH).
• Accessories: Pulling eye.
400 CABINET
• Type: 19 inch racking with front and rear adjustable rails.
• Manufacturer: Refer to schedule of preferred suppliers and Manufacturers.
- Product reference: Submit proposals.
• Size:
- Width: 600 mm.
- Depth: Network 1000mm/Server 1200mm.
- Height: 42 U.
• Enclosure:
- Mounting: Free standing.
- Material: Steel.
- Finish: Black powder coating.
- Front door: Ventilated with lock.
- Rear door: Split Rear Door Ventilated with lock.
- Side panels: Removable.
- Handles: Recessed side mounted.
- Base: Height adjustable supports.
• Cabinet locks: Common key.
• Ventilation: Front to back.
• Power: Integral.
• Vertical power modules with outlets mounted at rear and master power switch at front: Req
uired.
- Arrangement: 2 per side.
- Outlets to BS 1363-2: rated at 32Amp 20no. IEC 60320 C13 10A with retaining clip.
• Lighting: Not required.
• Space for active equipment: 42U.
• Cable entry with grommets: Bottom/Top.
• Horizontal cable supports: 1 U for each 48 port patch panel with 1 U spare.
- Covers: Required.
• Vertical cable supports: Left and right hand sides.
- Support spacing: 8 U.
• Spare U sections: Provide individual blanking plates.
400A FRAMES To maximise the use of available space each Hub Room will be fitted with data
frames as an alternative to data cabinets. 42U Data Frame accommodating up to 42 1U
panels and 1000+ patch cords
• Type: 19 inch racking with front and rear adjustable rails.
• Manufacturer: Krone.
- Product reference: APF.
• Size:
- Width: 985mm .
- Depth: 501mm .
- Height: 2232mm .
• Enclosure:
- Mounting: Free standing.
- Material: Steel.
- Finish: Manufacturers Standard.
- Front door: N/A.
- Rear door: N/A.
- Side panels: N/A.
- Handles: Not required.
- Base: Height adjustable supports.
• Ventilation: N/A Open Rack.
• Power: Integral.
• 1 U horizontal mounted power modules with outlets mounted at rear and master power
switch at front: Required.
- Arrangement: 1 at top of cabinet.
- Outlets to BS 1363-2: 6.
• Vertical power modules with outlets mounted at rear and master power switch at front: Required.
- Arrangement: 1 per side rated at 16amp.
- Outlets to BS 1363-2: 6.
• Lighting N/A
• Space for active equipment: 42U.
• Cable entry with grommets: Bottom and Top.
• Horizontal cable supports: 1 U for each 48 port patch panel with 1 U spare.
- Covers: Not required.
• Vertical cable supports: Left and right hand sides.
- Support spacing: 8 U.
• Spare U sections: Provide individual blanking plates.
• Accessories: Vented equipment shelf.
EXECUTION
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
940 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
950 LABELLING
• Cabling topology schematics:
- Location: Main server room.
- Format: Glazed A1 size paper print.
- Installation: Wall mounted with cup and screw fixings.
• Equipment: Label with unique identifier.
- Type: Face engraved rigid plastic laminate.
• Cable schedules:
- Location: At each cabinet.
- Format: Clear encapsulated card.
- Size: A4.
- Contents: Outgoing cable designation, purpose and destination
• Patch panels: Machine printed label with patch panel identifier
- Outlet ports: Machine printed label with circuit description.
• Cables: Wrap around machine printed label with cable identifier.
- Location: Within 100 mm of each termination and Every 5 m throughout the cable
length.
• Outlets: Machine printed label with circuit description.
- Format: unique identity label to each individual cable. The identity should always refer
the reader back to the source point of the cable..
GENERAL
110 ACCESS CONTROL SYSTEM Access Control will be installed to control and define public
access areas and staff access areas. The Access Control system shall operate via a stand
alone data network.
Two or four door controllers shall be employed to reduce the number of door control units
and associated spur points required on the project.
The Trust has introduced a single user card policy for all building operations that require an
identity card. Access Control system, controllers and readers shall be capable of
operating, integrating with and utilising HID cards as the single card system used on site.
The cards shall be 'Iso-thin' HID cards
Access control to main ward entrances (1 main entrance per ward) shall be capable of
being switched off at visiting times to allow access to individual wards as deemed
appropriate. Access control to the secondary (staff) entrance to wards from the building
'hotlink' shall remain operational at all times except during a fire alert in the fire
compartment or adjacent fire compartment. Note; only door access doors which are on
designated escape route shal de-activate during a fire alarm event.
The Nurse shall be capable of assessing the person activating the video intercom with
voice and visual indication on the tablet pc. The nurse will be capable of sending a door
unlock signal via the wifi system to allow access to the ward if appropriate. Unless stated
otherwise, it is expected that talet pc's will operate on the current Microsoft Windows
operating system or its successor at the time of installation.
Individual door release button's for both ward exit / entrance doors will be provided at all
three Nurse Stations in each ward.
Certain doors shall be capable of limited time hold open to allow patient beds or patient
wheel chairs to be pushed through the door without staff having to hold the door. Where
this functionality is required the access control system shall be provided with the
appropriate integral time delay mechanism to effect requirements.
Within the A&E department there will be access control installed on all doors that lead to
medical assessment areas. There will also be a requirement to install a lock down of the
department should rioting ensue within the A&E department.
The Stair Core 2 lift shall auto park at Level 3 during a blue route event with the lift doors in
the open position. The lift will be fitted with an HID proximity control access card which will
allow the lift to be sent to a floor by the occupants provided the occupants have the Crash
Team group stetting on their proximity cards. After delivering the crash team members to
the floor called on the lift car control panel the lift should return to Level 3 with its door open
incase of further Crash Team member movements towards the activation point. This
process will continue until the Blue Route activation has been reset.
The blue route is controlled by the Nursecall system and will unlock door access doors
which are designated as being on the blue route during a blue route cardiac event. After
the event / when the blue route activation has been reset all door access doors will return
to normal operation. Any auto doors on the blue route should open until the blue route
system is reset.
The Contractor will provide a door access system and autodoor system cause and effects
and develop the cause and effects as the detail design is carried out post contract.
Auto doors
In addition to door access controls that hold doors closed, the contractor shall install a
number of auto doors which open on approach to allow staff through unhindered. Auto
doors on the hotlink shall cater for beds and laundry trolleys being pushed through the
doors
• Standards: To BS EN 50133-1 and in accordance with BS EN 50133-7.
• Manufacturer: Inner Range.
- Registration: A member of BSIA or A Gold member of NSI.
• Operation in the event of mains failure: Access points remain secure except on escape
routes..
• Tokens: HID iCLASS 13.56 MHz read/write contactless smart card .
• Readers: Proximity readers.
• Standby battery supply: 24 h.
• Locking mechanisms: Magnetic locks and strike plates.
• Controls:
- Access control system controller;
- Door controllers; and
- Personal computer.
• Accessories:
- Access control point status monitoring devices;
- Card printer;
- Digital camera;
- Emergency break glass units; and
- Request to exit buttons.
130 A VIDEO INTERCOM SYSTEM Separate video intercom systems shall be provided
to each ward. Video intercom's shall be provided at each Ward entrance and to the main
entrance of the A&E department. On arrival at
the Ward Visitors will connect to the staff bases by one-way video link to allow staff to
assess the visitor prior to the door being operated. The video system system shall
incorporate facility to also integrate with additional systems particularly the Nurse call
system which shall be deemed a means of control monitoring of access to the ward(s) .
The video intercom shall be capable of streaming vive H.264 video signal's to tablet
computers carried by staff within the individual wards allowing Staff to deal with visitors
to the Wards without having to be at the Staff Bases. This will be an intercom over IP
system and should be capable of supporting Android, Windows or Apple OSX -
dependant on what tablets are used.
• Entrance panel: Required.
- Remote handsets: Desktop handsets at staff bases (3 per ward) .
• Manufacturer: Refer to Schedule of Preferred Suppliers and Manufacturers. The contractor
shall engage the services of a system specialist to design provide install test commission
integrate and interface the system with the access controls and nurse call system to effect
requirements..
• Product reference: Submit design and cost proposals.
• Audio communication: Two way.
• Video communication: One way.
• Video image: Colour.
• Remote door opening via handset: By door access system operated from one of three staff
bases in each ward..
• Calling method: Push button.
140 CABLING AND CONTAINMENT Cabling at all points in the network shall be concealed
and protected from unauthorised access. The Access control system shall operate on a
standalone data network which shall comprise of the following;
Video door entry panel / handset- Cat 6e cable
field devices - Belden 8 core alarm cable (proximity readers, push exits, mag locks etc)
Automatic door operators - Belden 8 core alarm cable
LAN - Belden 8723 LAN cable
• Cable type: Access control cables.
• Containment: Cable basket and conduit as section Y63.
• Rewireable installation: Required.
• Concealed installation: Required.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the access control system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
220 ACCESS CONTROL POINTS All access control points and door controllers shall be
installed to the same recognition classes
• Recognition classification to BS EN 50133-1: Class 3.
• Access classification to BS EN 50133-1: Class B.
• Environmental classification to BS EN 50133-1: Class I and Class II locations to be
installed.
• Number of transactions (minimum): 2500 per 24 h.
Operation in the event of a Blue Route signal: The routing of 'Blue Route' will be
dependant on the activation point of a cardiac alarm in the Nursecall system (dependant on
Ward) Where a Blue route activation affects any individual door the particular door will
receive an unlock signal from the local door controller. The door will remain unlocked until
the Blue Route activation has been cancelled The blue route shall be defined. t from the
The deactivation o the door shall be permitted via the sequential addressing
interconnection between the originating call point, the primary blue route to that point from
the serving lift core, and the intermediate access controlled door sets between those
points.
PRODUCTS
EXECUTION
630 INSTALLING CABLING The data network cabling shall be installed to the main 'Security'
containment installation provided to all floors of the building. The electrical contractor shall
install final containment to door positions to allow the security specialist to install final
cables to the door controller positions. As part of a 'door set installation' the electrical
contractor shall install the final containment to card reader positions, break glass positions
and to magnetic lock positions..
• Standard: To BS 7671.
• Route: Refer to 1005885 (65)Series drawings for main containment routes. Secondary
containment routes shall be designed and installed by the contractor.
• Timing: Do not start internal cabling until building enclosure provides permanently dry
conditions.
• Cables: Install in one length.
• Cable pulling: Submit proposals. Do not overstress. Prevent kinks and twisting of the cable.
• Cables passing through walls: Sleeve with conduit or pipeduct. Bush at both ends.
• Jointing: At equipment and terminal fittings only.
COMPLETION
950 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
970 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
GENERAL The requirements are for the provision and installation of a full complete fully
operational intruder detection and alarm system with appropriate interfaces input outputs
etc to ancillary supporting, complementary and supported systems and infrastructure. The
system shall use a variety of detection methods to protect the building and nominated
spaces from intrusion. The contractor shall engage the services of an intruder detection
and alarm system specialist as indicated in the schedule of preferred suppliers and
manufacturers to complete the design, provide, supply, install, test, commission, set to
work, and certify the system provided.
110 INTRUDER DETECTION AND ALARM SYSTEM An intruder detection and alarm system
shall be installed to the main kitchen and servery area on Level 1.
An intruder detection and alarm system shall be installed to the internal automatic glass
doors located at Level 1&2 for use out of working hours.
An intruder detection and alarm system shall be installed to the Café for use out
with working hours.
An intruder detection and alarm system will be installed to Level 1 and level 7 plant areas.
An intruder detection and alarm system will be provided to serve the ward floors and
specialised process rooms (operating suites)
• Standard: To BS EN 50131-1.
• System manufacturer: Submit proposals.
- Registration: A member of BSIA or A Gold member of NSI.
• Grade: Grade 3 for Reception and the Café, Plant areas and specialised process
rooms (operating Suites)
• Power supply: Type A.
• Environmental classification: Class I to Reception and the Café.
• Areas to be protected: Café & Servery
• Perimeter protection: All external doors and windows.
• Detectors:
- Acoustic detectors ;
- Combined passive infra-red and microwave detectors ;
- Combined passive infra-red and ultrasonic detectors ;
- Passive infrared detectors ;
- Protective switches ; and
- Ultrasonic movement detectors .
• Equipment interconnectivity: Wired.
• Cabling and containment:
- Cable type: Multi-core intruder alarm cable.
- Containment: Rigid conduit, as section Y60.
- Rewireable installation: Required.
- Concealed installation: Required.
• Warning devices:
- Internal: Electronic sounders and Xenon beacons.
- External:
- Sounders;
- To alarm receiving centre (ARC); and
- Main Security Office.
- Signalling method: Dual Signalling.
• Control and indicating equipment (CIE): Main control panel with integral keypad and
Remote keypad.
• Accessories: None.
• Completion: Submit design and cost proposals.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the intruder detection and alarm system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
Isolate protected doors from monitoring regime where such doors fail open as part of fire
strategy. Maintain monitoring to protected doors which do not form part of monitoring
regime or are fail secure..
PRODUCTS
EXECUTION
COMPLETION
935 DOCUMENTATION
• Standard: To BS EN 50131-1.
• Operation and maintenance manual: Submit.
• Record drawings: Submit.
949 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
GENERAL
The requirements are for design, provision installation testing commissioning setting to
work and certification of a full complete fully operational CCTV installation inclusive of but
not limited to:
- Cameras (PTZ, Fixed)
- Bracketry
- Covers,
- Housings,
- Columns,
- Cabling
- Containment
- Internal heaters/wipers,
- Power supplies,
- Monitors
- Switching controls,
- Digital recording facilities,
- Motion sensors,
- Transmission facility
- Distribution racks
The Contractor shall engage the services of a CCTV system specialist to validate and
verify the proposals as indicated on the drawings and within this specification.
The CCTV system will be generally located as indicated on the drawings subject to final
system proposals submitted.
110 CCTV SYSTEMCCTV will be an Internet Protocol system with Power over Ethernet (PoE)
cameras connected to a dedicated data network.
CCTV monitors and control will be provided to the Security suite to display the images
being recorded both internally and externally to the Acute Services Block. The CCTV system
will integrate with the existing site security data network.
All cameras within this system are to be network cameras using H.264 compression and
POE. Power outlets should not be provided to cameras unless internal heaters are
required. The Contractor will appoint a specialist sub-contractor to carry out the design,
installation and commissioning of the CCTV
• System: In accordance with BS EN 50132-7 and Home Office Scientific Development
Branch CCTV operational requirements manual.
• Manufacturer: Refer to Schedule of Preferred Manufacturers and Suppliers.
- Registration:
- A member of BSIA;
- A Gold member of NSI; or
- A member of SSAIB.
• Format: Consultative Committee for International Radio (CCIR) PAL colour, 625 scan
lines/frame, 25 frames/second.
• Purpose: Site security safety and monitoring.
• Type: Internet protocol (IP).
• Surveillance equipment: Visible cameras only, no covert equipment .
• Controller: Control matrix.
• Telemetry transmitter and receivers: Required.
• Number of monitors: Camera: monitor ratio (maximum)10:1.
• Data collection: Digital video recorders.
• Accessories:
- CCTV signage;
- Infrared illuminator's; and
- Camera masts.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the CCTV system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
PRODUCTS
310A CAMERAS CCTV will be an Internet Protocol system with Power over Ethernet (PoE)
cameras connected to a dedicated data network.
CCTV monitors and control will be provided to the Security suite to display the images
being recorded both internally and externally to the Generic Ward Block. The CTV system
will integrate with the existing site security data network.
• Manufacturer: System manufacturer.
- Product reference: System manufacturer.
• CCD sensor format: 0.25 inch.
• Resolution (minimum): 5 megapixel.
• Power supply: Power over Ethernet (PoE).
• Camera synchronising: Genlock and Line lock with phase adjust
• Signal to noise ratio (minimum): 48dB.
• Image strength with 75 ohm terminations: 1 V peak to peak.
• Automatic gain control: Required.
• White balance control: Automatic and Presets for daylight, fluorescent and tungsten
halogen lighting.
• Backlight compensation: Required.
• Present gamma settings: 1 and 0.45.
• Iris: Automatic.
• Shutter speed adjustment: Automatic.
• Infrared sensitive: Required.
• Colour to monochrome switching: Automatic at pre-determined threshold (25 lx)
• Lens mounts: CS type.
• Lens:
- Type: Variable focal length.
- Filter: Polarising.
• Mounting points: Bottom and Top.
• Accessories:
- Anti-tamper devices;
- Camera brackets;
- External camera housings;
- Internal camera housings;
- Lens hood;
- Power supply units; and
- Wire guards.
380A DIGITAL VIDEO RECORDERS Provide infrastructure and recorders to serve the quantity
of cameras as per layouts together with sufficient spare capacity for additional 20%
additional cameras per recorder
• Manufacturer: System manufacturer.
- Product reference: System manufacturer.
• Resolution:
- Horizontal: 720 pixels.
- Vertical: 576 pixels.
• Storage media: Hard disk.
- Capacity: 31 recording days.
• Inputs: Submit proposals.
• Recording speed: 0.1-50 frames/s.
• Event recording mode: Required.
- Pre-event buffer: 20 s.
• Camera inputs: 16.
• Monitor outputs: 4.
• IEEE 1394 connections:
- Input: Required.
- Output: Required.
• Integral CD recorder: Windows-based removable hard drive.
• Video motion detection: Required.
400G CAMERA BRACKETS For wall mounting externally Corner surface mounted.
• Manufacturer: System manufacturer.
- Product reference: System manufacturer.
• Type: Surface Corner Mounted.
• Material: Aluminium.
- Finish: White.
• Camera mount adjustment: Single bolt release.
- Pan: ±360°.
- Tilt: ±70°.
450A CAMERA MOUNTING COLUMNS Generally. Final quantity and locations to be surveyed
reviewed and agreed.
• Manufacturer: System manufacturer.
- Product reference: System manufacturer.
• Type: Circular tubular section and Submit proposals.
Base: Concrete Flange fixing bracket and concrete foundation and fixings as required to
suit
• Height above ground level: 6 m.
• Tilt over facility: Required.
• Anti climb guards: Required.
• Finish: Galvanized.
EXECUTION
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
940 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 24 months after Practical Completion.
GENERAL
GENERAL The requirements are for the provision of a full complete and fully operational
fire alarm system to serve the compete fire detection and alarm requirements of the
project. It is essential to recognise the building is a hospital Ward Block where patients are
generally within allocated individual rooms and are potentially non ambulant. The system
shall be provided and installed to suit the environment and comply with the appropriate HTM
guidance BS 5839 and statutory requirements.
The contractor shall engage the services of a system specialist from the schedule of
preferred suppliers and Manufacturers to design, procure, provide, install, test,
commission, set to work and certify the system
110 FIRE DETECTION AND ALARM SYSTEM The fire detection and alarm system shall be
capable of interfacing and working with the site wide installed fire alarm data control
network.
The existing installed fire panels are Morley Analogue Addressable with Apollo fire
detection sensor equipment.
130 ASPIRATING DETECTION SYSTEMS Aspirating fire detection is to be installed to the top
of the lift shafts to allow lift shafts to be monitored for fire events whilst allowing the
maintainable items of the system to be located out with the lift shafts. The aspirating control
equipment shall be wall mounted and located at the same level as the top of the lift shaft
e.g. Level 7 as required. The control equipment is to be protected from the
elements if installed at level 7. Control equipment will not be accessible to members of
the public, clinical staff or patients must be safely and easily accessible to
maintenance staff and contractors employed to maintain or repair the equipment.
• System manufacturer: Submit proposals, to match other fire equipment and to operate on
the same network..
• System type: Localised sampling to monitor within lift shafts to BS 6266.
• Equipment interconnectivity: Enhanced fire resisting cabling .
• Cable containment:
- Cable basket, as section Y63;
- Cable ladder, as section Y63;
- Cable tray, as section Y63;
- Rigid conduit, as section Y60; and
- Trunking or ducting, as section Y60.
• Rewireable installation: Required.
• Concealed installation: Required.
SYSTEM PERFORMANCE
Details of critical alarms shall be supplied from the Trust as a schedule separate from this
specification.
• Type: Systems interfaces.
PRODUCTS
435 SOUNDERS
• Standard: To BS EN 54-3.
• Manufacturer: Apollo.
- Product reference: Submit proposals.
• Type: Match existing.
• Sounder cut off time (maximum): 30 minutes.
• Ingress protection standard: Type A for Indoors & Type B for outdoors.
• Colour: Red.
• Directional output at 1 m (minimum): Variable dependant on application e.g bedhead or
courtyards - to comply with HTM Firecode..
• Integral beacon: Where appropriate.
• Mounting: Surface.
• Power supply: From loop.
EXECUTION
COMPLETION
960 CERTIFICATION
• Format: In accordance with BS 5839-1 Annex G.
• Number of copies: 3+ electronic.
• Design certificate: Submit.
• Installation certificate: Submit.
• Commissioning certificate: Submit.
• Verification certificate: Submit.
965 DOCUMENTATION
• Operation and maintenance manual: Submit.
• Record drawings: Submit.
• Fire evacuation plan: Submit.
- Format: Electronic colour CAD layout.
995 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 24 months after completion.
GENERAL Requirements are for the provision of full complete fully operational assistance
call systems to those public access areas fitted with Disabled accessible fixtures and
fittings. The system shall be of the same manufacturer as that provided for the Nurse call
system though they shall be considered completely separate systems for the purposes of
this project. The Assistance call systems shall be of discrete nature with alarms raised and
reset locally to the space served. This shall generally be the disabled WCs within direct
public accessible areas. Such provisions shall not be considered those patient disabled
accessible rooms/areas. The contractor engage the services of the system specialist to
design, procure provide instal test commission certify and set to work these discrete
systems.
120 CABLING AND CONTAINMENT A dedicated full compete fully operational Containment
system shall be provided to serve the complete system requirements
• Cable type: LSZH singles as section V32.
• Containment: Cable conduit, trunking basket tray as Sections Y60 and Y63.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the assistance call system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
PRODUCTS
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
• Test certificate for disabled refuge call system in accordance with BS 5839-9: Not
applicable.
GENERAL
110 NURSE CALL SYSTEM The Nursecall system shall be an Internet Protocols (IP) based
system providing full Ethernet connection providing up to 10Mbps of data at every bedhead
from an segregated structured IT cabling network.
The IP Nursecall system shall provide as a minium multicast streaming, including video
and IPTV with Layer 2 specification with IGMP v2 and IGMP
snooping. The system shall be capable of connecting with the Juniper wireless Ethernet
installed throughout the hospital wards to allow the connection of handheld tablet pc's as
part of the nursecall system for mobile nursing staff integration. Redundancy shall be built
into the system to allow auto configuration/reconfiguration capability to enable replacement
parts to be installed without system reprogramming.
The system shall operate as a full nurse call system providing the following features for
nurse call;
• Two way voice communication between patient handset and staff bases
• nursecall from patient handset
• nursecall from patient pull cords
• cardiac alert from bedhead
• over door indicator for nursecall
• over door indicator for cardiac alert
• out of bed indication alert (connected to wall mounted PIR's which also operate wall
mounted low level lighting during the hours of darkness
Visual and audible alarms;
All visual indications shall comply with Part M of th Building Regulations and BS8300.
Colours for alarm call, indication and reassurance lights are as follows;
Amber - Patient call and call indicator
Light grey Patient call reset switch and indication
Green - Staff presence indicator & switch
Amber - over door indicator (covers all calls)
Red - Emergency nurse call switch
Blue - Cardiac alarm switch
Black - Intruder attack / alarm switch
Red - Controlled drugs cupboard indicator
Yellow - Door entry call & indicator
Brown - Equipment fault indicator
The following services shall also be incorporated into the nursecall system as functionality
over and above nursecall requirements;
• Media services - IPTV (Freeview) TV and radio control (On / Off and channel selection)
and TV volume control
• Lighting Control - provide scene setting lighting control which the patient can control from
the bed. Lighting control should allow for the following modes of lighting; TV lighting where
lighting is set to allow the patient to watch TV comfortably. Reading lighting where the
lighting is set to allow the patient to read comfortably. Visitor Lighting where the patient
has visitors in the room. Lighting off. Where the patient switches the lights off. It should
be noted the nurse will have separate lighting controls which will over ride patient controls
to allow for medical lighting and observation lighting. Overide controls will be used to
provide full compliance to LG2.
• Blind control. The patient shall be able to control up and down as well as tilt controls for
the main external window blinds from the bed.
Voice over IP
Connectivity to 3rd Party Proprietary I/O Devices including, but not limited to; Fire Alarms,
Video intercomms at each ward entrance door , Security Systems including door access,
staff attack and CCTV
- Activation of Blue Route protocols. This shall incorporate but not limited to :
Activation of dedicated Blue Route Illumination from that point at which the
call has been made to the emergency response (crash) team.
Inhibiting/deactivation of access control of each controlled access door
from the source of call to the crash team positions
Prioritising lifts so as to send a lift car to the floor level at which the crash
team shall access vertical transportation to floor(s) at which the call was made. Doors shall
open on arrival.
• System manufacturer: Wandsworth IPiN or equal approved .
• Call initiation devices:
- Patient handsets: At each bed .
- Patient pull cords: At visitor / table space within each bedroom and within the en-
suites .
- Nurse emergency pull-switches: At each bed and In treatment rooms .
• Visual signals:
- Ward entrance indicators: Required.
- Direction indicators: Required.
- Reassurance indicators: Integral within patient handsets .
• Operating voltage to BS 7671: Extra low voltage.
• Equipment interconnection: Wired, Internet Protocol system .
• Power supply units: Required.
• Call indicator panels: Required.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the nurse call system in accordance with HTM 2015.
• Spare capacity: 10% of installed call initiation devices.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
• Equipment electrical power: Provide electrical supplies to equipment requiring power.
PRODUCTS
350A AUDIO/TELEVISUAL CALL SYSTEM Provide and install two way televisual system
interconnecting all nominated areas. System to form integral part of nurse call system.
Ensure integration of call, answer, push to reset and indication of availability of service
• Manufacturer: System manufacturer.
- Product reference: Submit proposals.
• Lamp: Twin LED.
- Colour: Red.
- Labelling: Unique call device identification code.
• Mounting plate material: Zinc plated steel.
- Finish: Match electrical accessories.
• Mounting type: Wall/theatres control panel.
• Accessories: Integral sounder (inhibited on call answered).
EXECUTION
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
940 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
GENERAL The requirements are for the provision of a full complete fully operational
lightning protection system to serve the complete requirements of the building. System
shall be of the Faraday cage type and fully in accordance with BS EN 62305. Engage the
services of a lightning protection systems specialist to develop the design and provide a
certificated system as per BS EN 62305
SYSTEM PERFORMANCE
210 DESIGN
• Standards: To BS EN 62305-2, BS EN 62305-3 and BS EN 62305-4.
• Design: Complete the design of the lightning protection system.
• Class of LPS to BS EN 62305-2: I.
• Coverage of LPS: External and Internal.
• Internal equipment to be protected: Electrical, IT, Communications, Controls, signalling,
processing systems, equipment, cabling and infrastructure.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
PRODUCTS
340 COPPER TAPE Provide and install tape grid to roof level to meet system requirements for
compliance with BSEN 62305 and including the building characteristics and function as
primary design constraints.
• Standards: To BS EN 13601 and BS EN 50164-2.
• Manufacturer: System manufacturer .
- Product reference: Submit proposals.
• Size: 25 x 6 mm.
• Cover: Tinned.
- Colour: Not applicable.
350 COPPER SOLID CIRCULAR CONDUCTORS Copper circular conductors may be used
where appropriate for connections to rebar within insitu concrete.
• Standards: To BS EN 13601 and BS EN 50164-2.
• Manufacturer: System manufacturer .
- Product reference: Submit proposals.
• Size: Submit proposals.
• Cover: Bare.
- Colour: Not applicable.
400 ANTI-VANDAL GUARDS For protection of test points and system joints as required
• Manufacturer: System manufacturer .
- Product reference: Submit proposals.
• Material: Galvanized steel.
EXECUTION
715 BONDING
• Standards: To BS EN 62305-3 and BS EN 62305-4.
• Bond the following to the lightning protection system:
- Base of a down conductor to the main switchgear earthing terminal;
- Base of down conductor to base of vertical steelwork in lift shaft;
- Metal fire escape;
- Metal flue pipe;
- Shields of incoming services; and
- Vertical steelwork in lift shaft to structural steelwork of building at eaves and ground
levels.
• Bonding conductor sizes: To BS EN 62305-4.
• Locations of bonds: Submit proposals.
COMPLETION
940 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
950 MAINTENANCE
• Maintenance: In accordance with BS EN 62305-3 and BS EN 62305-4..
• Duration: Undertake until 12 months after completion.
GENERAL
GENERAL Requirements are for the design provision coordination installation of full
complete fully operational accessible containment distribution systems to serve the
complete requirements of the project inclusive of specialist systems distribution
infrastructure. The contractor shall develop the primary secondary and final containment
systems to meet the setting out requirements of all electrical services and systems
(including specialist) as indicated on the layouts drawings and specifications. conduit and
Trunking systems shall be fully electrically and mechanically continuous throughout their
lengths and include proprietary earth continuity straps to maintain continuity across
separate sections.
PRODUCTS
330 PLIABLE CONDUIT For use only as part of induction loops systems
• Standard: To BS EN 50086-2-2 or BS EN 61386-22.
• Manufacturer: Submit proposals.
- Product reference: Submit proposals.
• Material: Non-metallic.
• Mechanical properties:
- Resistance to compression: Light.
- Resistance to impact: Light.
- Resistance to bending: Pliable.
- Tensile strength: Light.
- Suspended load capacity: Light.
• Temperature range:
- Lower temperature: -15°C.
- Upper temperature: 120°C.
• Electrical properties: With electrical continuity properties.
• Ingress protection to BS EN 60529: IP54.
• Resistance against corrosion: Submit proposals.
• Resistance against flame propagation: Required.
• Sizes (OD): 16 mm.
• Special features: Containment for induction loop cabling.
340 FLEXIBLE CONDUIT Proprietary associated with lighting and emergency lighting systems
• Standard: To BS EN 50086-2-3 or BS EN 61386-23.
• Manufacturer: Lighting and Emergency lighting controls systems specialists.
- Product reference: Submit proposals.
• Material: Metallic.
• Mechanical properties:
- Resistance to compression: Medium.
- Resistance to impact: Medium.
- Resistance to bending: Flexible.
- Tensile strength: Light and Medium.
- Suspended load capacity: Light.
• Temperature range:
- Lower temperature: -25°C.
- Upper temperature: 120°C.
• Electrical properties: With electrical continuity properties.
• Ingress protection to BS EN 60529: IP44.
• Resistance against corrosion: To BS EN 61386-1, Class 4.
• Resistance against flame propagation: Required.
• Sizes (OD):
- 16 mm;
- 25 mm; and
- 32 mm.
• Special features: Distribution of final circuitry electrical power and controls wiring to lighting
and emergency lighting. .
440A SERVICE OUTLET POLES To match existing within Endoscope reprocessing in Main
ACU block (which forms part of this project). Survey required to ensure inclusion of type
fixing arrangements and distribution method.
• Type: Floor to ceiling.
• Manufacturer: To match existing.
- Product reference: To match existing.
• Material: To match existing.
• Profile: Square.
• Colour: To match existing.
• Outlet boxes: as identified on layouts.
- Arrangement: Double sided.
• Cover: Flush fitting.
- Lockable: Not required.
• Segregation of cabling: Maintain using bridges and dividers.
EXECUTION
COMPLETION
910 CLEANING
• Electrical equipment: Clean immediately before handover.
930 DOCUMENTATION
• Drawings: Submit, showing the location of conduit, trunking and service outlets.
- Dimensions: Include sufficient to locate components accurately.
PRODUCTS
320A CABLE BASKETS FOR FIRE DETECTION AND ALARM SYSTEM WIRING.
• Manufacturer: Swift (Legrand) or equal approved.
- Product reference: Submit proposals.
• Material: Steel wire.
- Diameter: 4 mm.
• Coating material: Hot dip galvanized.
• Sizes:
- Width: 100 / 150 mm.
• Side height: 30 mm.
• Features:
- Segregation: Cable dividers.
- Protective cover: Not required.
330 CABLE LADDERS for Sub mains and equipment directly fed from main switchboard
• Standard: To BS EN 61537.
• Manufacturer: Swift (Legrand) or equal approved.
- Product reference: Submit proposals.
• Material: Metal.
• Resistance against flame propagation: Non flame propagating.
• Electrical properties:
- Continuity characteristics: With electrical continuity.
• Conductivity characteristics: With electrical conductive system component.
• Coating material: Hot dip galvanized.
• Temperature properties for transport, storage, installation and application:
• Minimum: 5°C.
• Maximum: +40°C.
• Mechanical properties:
- Cable ladder free base area: Class Y.
- Resistance to impact: Up to 50 J.
• Width: various.
• Features:
- Segregation: Not required.
- Protective cover: Not required.
EXECUTION
COMPLETION
PRODUCTS
360A FUSED CONNECTION UNITS for public accessible areas and operational areas
• Standard: To BS 1363-4.
• Manufacturer: MK.
- Product reference: Logic +.
• Ingress protection to BS EN 60529: IP 2X.
• Mounting: Flush.
• Control: Switched.
• Indicator lamp: Not required.
• Fuse carrier access: Pull out.
• Poles: Double pole.
• Flex outlet: Base or front entry dependant on application.
400 INDUSTRIAL SOCKET OUTLETS For use in Server and Hub Rooms
• Standards: To BS EN 60309-1 and BS EN 60309-2.
• Manufacturer: MK.
- Product reference: Commando.
• Ingress protection to BS EN 60529: IP 44.
• Material: Polycarbonate.
• Voltage rating: 200-250 V a.c..
• Current rating: 16A / 32 A.
• Frequency rating: 50 60 Hz.
• Pin configuration: 3 pole.
• Mounting: Panel mount.
• Controls: None.
400A INDUSTRIAL SOCKET OUTLETS for use in plant areas / roof mounted for Building
Maintenance Unit
• Standards: To BS EN 60309-1 and BS EN 60309-2.
• Manufacturer: MK.
- Product reference: Commando.
• Ingress protection to BS EN 60529: IP 67.
• Material: Polycarbonate.
• Voltage rating: 100-130V a.c., 200-250 V a.c., 380 - 415V a.c. .
• Current rating: 16A / 32 A / 63A.
• Frequency rating: 50 60 Hz.
• Pin configuration: 3 pole for 110V and 230V Installations, 3 pole neutral and earth for 400V
installations.
• Mounting: Surface angle mount.
• Controls: Integral switch with interlock for 400V outlets.
405 INDUSTRIAL PLUGS for use in plant areas / roof mounted for Building Maintenance Unit
• Standards: To BS EN 60309-1 and BS EN 60309-2.
• Manufacturer: MK.
- Product reference: Commando.
• Ingress protection to BS EN 60529: IP 67.
• Material: Polycarbonate.
• Voltage rating: 100-130V a.c., 200-250 V a.c., 380 - 415V a.c..
• Current rating: 16A / 32 A / 63A.
• Frequency rating: 50 60 Hz.
• Pin configuration: 3 pole for 110V and 230V Installations, 3 pole neutral and earth for 400V
installations.
• Number to be supplied: 1 for every industrial socket outlet installed + 10 spares.
430 ROUND PIN SOCKET OUTLETS For specific non standard restrictive use
• Standard: To BS 546.
• Manufacturer: As electrical accessories manufacturer.
- Product reference: Submit proposals.
• Ingress protection to BS EN 60529: IP 2X.
• Mounting: Flush.
• Rating: 15 A.
EXECUTION
620A ARRANGEMENT
• Locations: as per room data sheets and to the requirements of Part M (refer to Cundall
drawing.
- Coordinate with other wall or ceiling mounted equipment. Submit proposals.
• Positioning: Accurate and square to vertical and horizontal axes.
• Alignment: Align adjacent accessories on the same vertical or horizontal axis.
• Fixing: Secure, plumb and level.
• Mounting heights (finished floor level to underside of accessory in compliance with Part M):
- Light switches: 900 -1100 mm.
- switches requiring precise movements: 750 -1200 mm
- switches requiring precise movements: 750 -1200 mm
- controls requiring close vision: 1200 -1400 mm
- Single voltage shaver outlets: 1200 mm.
- Shaver supply units: 1200 mm.
- Socket outlets: 400 - 1000 mm.
- Emergency pull cord coloured red, located as close to the wall as possible with 2 red
50mm bangles one set at 100mm and the other between 800-1000mm
- Fan isolators: Adjacent fan.
- Cooker control units: 200 mm above worktop.
- Cooker connection units: 600 mm.
• Separation distance between adjacent accessories: (minimum): 30 mm.
COMPLETION
920 SPARES
• Plugs: Supply 5% for each socket outlet type.
PRODUCTS
340 ENCLOSURES.GENERALLY
• Manufacturer: Refer to Schedule of Preferred Suppliers and Manufacturers of distribution
switchgear.
- Product reference: Submit proposals.
• Ingress protection to BS EN 60529: To BS EN 60529, IP66.
• Material: Manufacturer's standard.
- Finish: Manufacturer's standard.
- Colour: Submit proposals.
EXECUTION
COMPLETION
915 LABELLING
• Electrical equipment: Label indicating its purpose.
• Safety signs: Install where voltages above ELV exist.
• Voltage warning notices: Label equipment when the voltage exceeds 230 V.
• Format: To BS 5499-5. Include warnings of the voltage present.
Electrical Specification
Doc No: -
Latest Revision: -
Initials
Signature
V Electrical systems 52
GENERAL
The purpose of these Employers Requirements is to provide a specification for:
- Electrical services associated with the build and fit out of a 31,000m² (approx.)
Acute Services Block at the Ulster Hospital, Dundonald, Belfast.
The Mechanical and Electrical Contractors will allow for coordination of services with the
mechanical and electrical specifications, as well as controls, vertical transportation systems
and public health specifications, drawings and schedules. The contractor will also allow
for Installation and specialist sub contract design and work within the constraints of the
Mechanical and Electrical Preliminaries and the Main Contract Preliminaries.
The Contractor is to provide the electrical services installation to the Acute Services Block
including office accommodation, staff rest areas, plant space, Clinical areas, Consulting
rooms, Accident & Emergency, CT Scanning Facilities, MRI Scanning, Fluoroscopy, X-Ray,
Ultrasound, Resus, Main Kitchen & Servery, reception, IT hubrooms, communal areas,
processing area external services and ambulance parking facilities.
All services will be designed for 24 hours, 7 days per week continuous operation. The
works undertaken in this set of Employers Requirements covers the design of electrical
and specialist services and systems, manufacture, works testing, supply and delivery to
site, erection, connection, site testing, commissioning adjusting and setting to work to form a
complete functioning package as defined by the drawings, this specification, preliminaries
documents and instructions from the Contract Administrator.
The works will comprise the whole of the labour, plant, and unless otherwise indicated, all
of the materials necessary to form the "complete, fully operational installation" including all
necessary, manufacture, works testing and such commissioning and testing as are
prescribed in subsequent sections of this document and as may otherwise be required to
give an effective working installation.
The Electrical Contractor will also be responsible for engaging all Utilities Providers and
all connections to the building for Electricity, Telecoms, Virgin Media and any other Utilities
deemed necessary to complete the project.
This specification includes but is not limited to the following services and systems;
- incoming medium voltage supply,
- electrical LV distribution,
- all metering,
- installing to BREEAM Excellent standards,
- vertical and horizontal distribution of electrical services,
wiring systems,
- wiring accessories,
- supply provision installation and connection of emergency generators,
- Canteens and Kitchen power design,
- lighting,
- lighting energy control,
- lighting scene setting for patient and staff use,
- external lighting,
- Emergency lighting
- connection of medical equipment, (the contractor will allow for all final connections)
- IT cabling, termination and containment,
- electrical and specialist systems containment,
- fire detection,
- fire alarm,
- alarm monitoring via the fire alert system,
- UPS systems,
- IPS/UPS systems,
- Assistance call
- nurse call,
- Induction hearing loops,
- electrical connections to the plant and BMS system,
- electrical supplies & fire alarm system interfaces to Automatic Smoke Damper
systems
- electrical supplies & fire alarm system interfaces to Automatic Smoke Transfer
Grille systems
- trace heating,
- access control,
- building security,
- renewable energy systems,
- earthing and bonding including 'clean' and 'reference' earthing.
- MEiGAN
- lightning protection
- alterations to existing
- coordination with all members of the design team.
- Oil transfer system
The Electrical Contractors will be required to coordinate with the Mechanical Contractors to
provide power to mechanical plant and ensure all mechanical and electrical equipment is
installed in an organised, coordinated and effective manner to all spaces. Where clauses
are listed or noted that are not included within this specification refer to the appropriate
section of the Mechanical specification.
The requirements are the provision of fully complete fully operational systems. Include for all
necessary equipment, components, plant, accessories, cabling, containment, hardware,
software as appropriate to effect the requirements. Engage with the suppliers of the
equipment to verify the proposed systems and include for procurement of all system
components accordingly.
The systems proposed under these works will require integration with specialist services
and systems (including medical). The contractor will liaise and coordinate fully with
respect to provision and coordination of services to meet the defined requirements of these
specialist services and systems.
This specification will be read in conjunction with the Conditions of Tendering, Conditions
of Contract, all the Contract Drawings issued with it, and all architectural and structural
drawings associated with the project.
The Mechanical and Electrical Contractors will take cognisance of and design to the
ceiling access allowances provided by the Project Architects and adopted by the Project
Electrical and Mechanical Engineers. The Contractor will therefore ensure that all
installation works are coordinated with ceiling access locations and all contractor designed
work packages comply with the access strategy demonstrated in the detailed design
drawings issued as both 'Tender' and 'Contract' status issue by the Acute Services Block
Design Team.
Electrical and Mechanical Sub Contractor elements that require design & installation to be
termed as specialist shall include but not be limited to;
The installation will be completed in compliance with the HTM documentation as detailed
below, MEiGAN, the 17th Edition IEE Wiring Regulations (BS 7671:2008) and associated
guidance notes together with the Regulations laid down by the Supply Authority (NIE). The
Electrical Contractor will be required to execute all work under the Sub-Contract in strict
compliance the HTM documentation as detailed below, MEiGAN, the 17th Edition IEE
Wiring Regulations (BS 7671:2008) and associated guidance notes and any additional
requirements of the NIE.
Applicable HTMS to the project are inclusive of but not limited to:
- Health Technical Memorandum 04-01: The control of Legionella, hygiene, _safe_ hot
water, cold water and drinking water systems
- Health Technical Memorandum 05: Firecode – fire safety in the NHS
- Health Technical Memorandum 05-01: Managing healthcare fire safety
- Health Technical Memorandum 05-02: Guidance to support functional provisions
for healthcare premises
- Health Technical Memorandum 05-03: Operational provisions
- Health Technical Memorandum 06: Electrical services
- Health Technical Memorandum 06-01: Electrical services supply and distribution
- Health Technical Memorandum 06-02: Electrical safety guidance for low voltage
systems
- Health Technical Memorandum 06-03: Electrical safety guidance for high voltage
systems
- Health Technical Memorandum 07: Environment and sustainability
- Health Technical Memorandum 07-01: Safe management of healthcare waste
- Health Technical Memorandum 07-02: EnCO2de – making energy work in
healthcare
- Health Technical Memorandum 07-03: Transport management and car parking:
best practise guidance
- Health Technical Memorandum 08: Specialist services
- Health Technical Memorandum 08-01: Acoustics
The Contract includes for the supply, delivery, installation, testing, commissioning and
certification/ documentation of the complete Electrical Services associated with the
construction in accordance with the true intent of this specification and accompanying
drawings and to the satisfaction of the Employer and the Contract Administrator.
The electrical contractor, during tender period, will liaise with Main Contract tenderers to
ensure that all items of equipment and plant (requiring electrical services supplies,
infrastructure, containment, wiring etc.) identified in Architectural and Structural drawings,
details, and documents are included. This requirement shall include those items over and
above those indicated on the electrical services tender drawings and documents requiring
electrical services wiring, containment systems, testing, commissioning, setting to work,
demonstration, client training & instruction, maintenance , emergency call-out etc. It is a
requirement that these and all such items are identified by the electrical contractor and
allowed for in his tender submission as no additional costs will be subsequently entertained
for variations for any such items not included by the electrical contractor following award of
tender.
The contractor will include for amendment to existing services and systems as required to
ensure maintenance of services to areas which may partially (at outset) serve project and
non-project areas. Where such instances occur the contractor will alter the systems to
segregate project from non project areas and reinstate operational those sections serving
non-project areas. This will include lighting and small power services.
The existing site services have been altered under a separate contract (Enabling Works) to
facilitate:
The incoming electrical supplies will be derived from allocated connection points to the
site infrastructure. The proposed works will require the provision and installation of the
connections to the necessary networks involved (HV Electricity, Voice/Data Com's, Fire
alarm, BMS, Telecommunications etc. together with any alterations of switchgear settings
as determined by the grading studies existing and that grading study to be carried out as
part of this project by the contractor. The contractor will note that the source services will be
derived from utility infrastructures which are distributed through the site.
It is a requirement in any event that the contractor undertake an underground services
survey to ensure that the existence of all underground and buried services are accounted
for and recorded to facilitate the construction and services works. . .
• Systems: Underground services survey, as section C12 and Building services survey, as
section C14 .
The electrical contractor will include for liaison with the Main contractor for the
purposes of integration and incorporation of all electrical services system distribution
infrastructure plant and equipment/outlets within the building and associated construction
elements as detailed below. The electrical contractor will include for detailing of all of his
requirements for builders works attendances to the main contractor. Building works: The
contractor will note requirements for detailing to the main contractor builders attendances
requirements for incorporation of electrical services in the following elements:
- Plinth systems
- Bund systems
- Trenching
- Ducting
- Formation of chases
All such details will be provided to the main contractor by the electrical contractor in the
form of Builders' work drawings for every interaction with the building fabric, elsewhere
showing fully dimensioned, all foundations, bases, holes, or any other builder's work
requirement. The electrical contractor will include for liaison with the Main contractor for
the purposes of integration and incorporation of all electrical services system distribution
infrastructure plant and equipment/outlets within the building and associated construction
elements as detailed below. The electrical contractor will include for detailing of all of his
requirements for builders works attendances to the main contractor.
Out with the bedhead services the electrical contractor will provide install, test,
commission full and complete small power installations as required to medical gas supply
equipment and controllers provided and installed by others. Coordinate the installation fully
and ensure all power supplies terminate to present outlets suitably at medical gas system
terminal outlets. Provide and install primary containment to distribute power and
controls/BMS cabling to medical gas outlets. Include for integration to BMS system to
ensure all critical alarms are individually reported and that all secondary alarms are
indicated via common alarm. Audible /visual alarms shall be installed
.
• Systems:
- Medical oxygen supply system, as section S20;
- Medical nitrous oxide supply system, as section S21;
- Medical compressed air supply system, as section S22;
- Medical vacuum system, as section S23; and
- Medical anaesthetic gas scavenging system, as section S25.
Bedhead Services will consist of two vertical column flush mounted bedhead panels
which will be a pre-fabricated Bedhead Services Enclosure Panel System fitted with
services as described in the Room Data Sheets, Room Loaded drawings and services
drawings including but not limited to; (54) Series Medical Gases, (60) Series Schematics
(62) Series Small Power and Data layouts and (64) Series Nurse Call Systems.
Product reference: Bedhead Panel System fitted with clip-fit laminate mdf decorative front
panels (spec TBA) of overall thickness 18mm, integrated light, equipment rail and
protectors.
Fixing: extruded anodised aluminium base frame of sections 50 x 35mm fixed to wall as
per Architect's room elevation & loaded plans.
Other requirements: Internal segregation and screening to allow the fitment, cabling,
maintenance and certification of a compliant system to ISO 11197:2009. Services trunking
modules to M&E specification, powder coated (colour TBA by Architect) with all exposed
anodised silver framework in AA25.
Supplied to site fully factory assembled, gas terminal unit assemblies and pipework as
Medical Gas specification, complete with the components as per RDS and Architect's
room/panel elevation drawings, with services feds from above via ceiling voids.
Visible bedhead services will be finished in a RAL colour confirmed by the Project
Architect. All surfaces will be smooth, easy wipe and without visible fixing screws and
comply with HFN30 infection control requirements. Services outlet plates shall have a
modular design ethos that allows for simple reconfiguration of services or the addition of
extra services to the bedhead as well as being quickly accessible for maintenance and
servicing.
All bedhead services shall be compliant with, but not limited to the following;
ES ISO 11197
HTM 08-03 Bedhead Services
HTM 06-01 Electrical Services
HTM 02-01 Medical gas pipeline systems
MEIGaN Regulators (where required - refer to room data sheets)
HFN 30 Infection Control in the built environment
HBN 57 (facilities for treatment to be allowed from both sides of the
bedhead)
BS EN 61000-4-2 Air discharge electrostatic discharge tests (+/- 4KV contact
discharge and +/- air discharge tests)
BS EN ISO 11197 EMC Requirements
The same manufacturer of bedhead services will be used throughout the entire Acute Services
Block installation providing the same standard of finish from the same range of equipment
throughout. The bedhead manufacturer and the Nurse call manufacturer are not required
to be supplied by the same provider, however the contractor will coordinate the two
suppliers for both systems to create an integrated bedhead system.
Assuming the bedhead services trunking is delivered to site with pre-installed gas
pipework, the Electrical Contractor will allow for all pipework jointing and testing within the
medical services trunking to join the pre-fabricated sections together, the Electrical
Contractor would then allow for access and coordination by the specialist medical gas
contractor to connect the medical trunking medical gas pipework to main medical gas
routes and or distribution manifolds.
If medical services trunkings are delivered to site without factory medical pipework
installations the Electrical Contractor shall install the trunking system and allow access and
coordination with the specialist medical gas installer to install medical gas pipework to the
containment system.
Provision will be made to prevent the bed or bed attachments damaging the bedhead
services equipment while the bed is being moved, raised or lowered (for example to
provide some means of buffering fixed to wall, bed or floor).
For a full description of colour codes refer to the Nurse call section of this specification;
standard colours for use on bedheads include;
Orange - patient to nurse calls (two way speech)
Red - emergency staff to staff calls
Blue - Cardiac calls
Small power
All bedhead small power will be clearly labelled with the sockets being engraved with the
relevant circuit reference. All circuits in the same room should be from the same phase although
note from the same power supply to improve redundancy in the system (refer to electrical circuit
charts and (62) series drawings). Socket-outlets and switches should not be installed within a
200 mm radius from the centre of a medical gas terminal unit. Where socket-outlets are
panel-mounted, they should allow for full plug insertion as required by BS 1363-2.
Structured Data wiring In addition to the comprehensive Wi-Fi network points connecting
every patient bedroom to the hospital network fixed data points shall be terminated to the
bedhead service connecting to the hospital IT network. Data points will be capable of
connecting to Electronic Patient Records (EPR) systems when appropriate equipment is
terminated to the RJ45 outlet(s). The data outlets will be capable of voice over IP
termination when appropriate equipment is connected to the bedhead data outlets .
• .
All HV switching equipment installed as part of this project will include remote lockable
switching panels located outside the HV Switchroom which include illuminated status indicators
to demonstrate the status of each HV switching device (switching devices include Incoming
switches, Outgoing outgoing switches and bus couplers etc)
Procure, provide, supply, and install all new full complete fully operational power, control
and signalling wiring and associated containment systems to the HV distribution systems of
the Project. Test commission and certify systems provided .
• Systems: Incoming electricity supply, as section V10 and High voltage distribution system,
as section V20.
The LV distribution systems will terminate as required to various items of plant and
equipment inclusive of but not limited to:
- Lighting & controls, Fire alarm & detection systems, security systems, nurse call
systems, hearing aid systems, general power provisions, data & IT systems,
- BMS and mechanical plant including air handling, pumping, heating & cooling,
humidification, vacuum systems, pneumatic systems
The contractor shall provide and install full and complete fully operational low voltage
services systems and installations to meet the complete requirements of the
project. Installations will include but not limited to protective devices, wiring (power,
control, signalling, communication) outlets, cabling, earthing, bonding, accessories,
containment etc. separately and independently serve the discrete systems of the project as
detailed elsewhere including specialist systems. Generally primary distribution to
specialists services and equipment are required though where a service or system is
procured by the electrical contractor then the electrical infrastructure for that service or
system will be provided by the electrical contractor.
Should there be a loss of the primary supply to the building the two generators will take up the
load of the building to ensure all electrical systems are fully operational. The generator
sequencing will allow both generators to run up to speed with the primary generator taking the
full load of the building with the other generator running on to cool and then switch off. The
generator supply within the ASB will also provide a tertiary supply to the CCC building to ensure
that the electrical supplies are backed-up, this will be changed over manually within the CCC
building by the use of castell keys.
• Systems:
- Proprietary generator system, as section V12;
- Low voltage distribution system, as section V30;
- Low voltage small power system, as section V40; and - Earthing and bonding
system, as section V81 .
The Electrical services to the fit-out space allocated for the Imaging equipment will
be entirely derived from the existing LV distribution infrastructure designed for this purpose and
will be located within dedicated spaces adjacent to this equipment.
- Medical Pendants,
- Medical Operating lamps,
- Operating theatre control panels
- Operating suites MEiGAN systems installation requirements.
- Cath labs planar equipment,
- UPS infrastructure/switchgear
- Endoscope processing washers, drying cabinets, data transfer systems
- CD automated handling/distribution equipment
- Bed head services modules
- patient bedroom hoists
- Motorised blinds
The contractor will note that all imaging equipment will be provided and installed by
the specialist systems supplier including all wiring and services between components from
the system service cabinets. The Electrical contractor will include for isolating switch
supply termination up to and onto these system cabinets from the main switchboard. The
specialist will extend from those points to the actual cabinets themselves and beyond. It
will be necessary to provide and install separate CPCs to the sub-main supplies of not
less than CSA matching those of the individual phase conductors. The electrical contractor
will install full and complete isolated sub-main supply circuitry, integration of systems with
MEiGAN earthing and test facilities as applicable to various areas of the project,
supplementary and complementary electrical services (i.e. lighting, small power, fire alarm
etc) The electrical contractor will liaise fully with the system specialist to ensure services
provisions meet the required electrical safety & functional earthing considerations and suit
final coordinated room layouts.
The contractor will provide and install full and complete fully operational low voltage
services systems and installations to meet the complete requirements of the
project. Installations will include but not limited to protective devices, wiring (power,
control, signalling, communication) outlets, cabling, earthing, bonding, accessories,
containment etc. separately and independently serve the discrete systems of the project as
detailed elsewhere including specialist systems. Generally primary distribution to
specialists services and equipment are required though where a service or system is
procured by the electrical contractor then the electrical infrastructure for that service or
system will be provided by the electrical contractor.
The contractor will allow for all 'reference earths' deemed necessary by the medical
equipment suppliers to each room / zone that medical equipment is installed. Should there be a
loss of the primary supply to the building the two generators will take up the load of the building
to ensure all electrical systems are fully operational. The generator sequencing will allow both
generators to run up to speed with the primary generator taking the full load of the building with
the other generator running on to cool and then switch off. The generator supply within the
ASB will also provide a tertiary supply to the CCC building to ensure that the electrical supplies
Ulster Hospital Redevelopment Acute Services Block
B06 Engineering services general description
are backed-up, this will be changed over manually within the CCC building by the use of castell
keys.
• Systems:
Proprietary generator system, as section V12;
- Low voltage distribution system, as section V30;
- Low voltage small power system, as section V40; and
- Earthing and bonding
system, as section V81 .
Each cold store will be provided with quantities of small power and data in compliance with
the Architect's specification and internal lighting to each cold store will provide 200lux at
finished floor level. All internal fixtures and fittings for each cold store will be part of the
cold store specialists design package. The electrical contractor will provide for BMS
connections and door access control to each cold store with emergency door release from
inside each cold store to be provided. Door safety controls will be capable of operating
without failure at a minimum of 30° C below the set point of the cold store close control
temperature set point .
Systems:
- Low voltage distribution system, as section V30;
- Low voltage small power system, as section V40; and
- Earthing and bonding system, as section V81.
The luminaires within the Imaging areas will utilise luminaires which will provide adequate
lighting levels whilst ensuring that infection control is not jeopardised.
The general lighting will be served by a DALI lighting control system allowing for full control
of individual/groups of general luminaires from a variety of switching control points
including photocells presence detectors, nurse call hand-sets, 2 way and intermediate switching
dimming control etc.
The system will interface with fire alarm systems to ensure suitable levels are reinstated
(i.e. full output in the event of fire alerts being raised via the automatic fire detection and
alarm system(s)) For this purpose the lighting control system will be configured to suit the
compartmentation layout and function in accordance with the fire alarm cause and effect.
In the event of a fire alert in a ward the lighting throughout the particular ward where the
confirmed fire alert is initiated shall activate to full output irrespective of initial status at time
of alert (i.e. on/off/dimmed). Other wards abutting will be configured in these fire alert
conditions to raise their light levels only in main access routes on floor/through Ward.
Lighting in patient rooms will remain in their status current prior to fire alert (i.e.
on/off/dimmed). In the event of automatic/manual declaration of complete evacuation than
the lighting in all areas shall be switched on raised throughout to full output to facilitate
evacuation.
Throughout the building(s) emergency lighting systems to BS5266 will be provided and
installed as indicated on the drawings, schedules and within the specification
documentation. The emergency lighting system will comprise of decentralised central batteries
located throughout each level and utilise an inverter to ensure 240V to each of the emergency
luminaires located within the building. The system is fully addressable with monitoring loops
which monitor the phases of the electrical supply at the required distribution point. The system
uses LED luminaires to provide the emergency lighting requirements.
.
• Systems:
- General lighting system, as section V50;
- Automatic Lighting Controls as section, as section v51
- Central battery emergency lighting and signage system, as section V56
- Luminaires and Lamps, as section V59; and
- External lighting systems, as section V60.
The contractor will confirm within submission of luminaire selection for approvals and
before placement of orders that the fittings selected will meet the BREEAM stipulation of
HEA4 On completion.
Light fittings will be installed to provide maintained illuminance (lux) levels in accordance
with the CIBSE Code for Lighting 2006 in all internal areas of the building as well as
meeting the requirements of CIBSE Lighting Guide LG2: Hospitals and health care
buildings.
For areas where computer display screens are regularly used, the lighting scheme will be
designed and installed in accordance with the recommendations of CIBSE Lighting Guide
7 Sections 3.3, 4.6, 4.7, 4.8 and 4.9.
The external lighting will be designed and installed to achieve illuminance levels in
accordance with CIBSE Lighting Guide 6, 'The outdoor environment' for all external areas
within the construction zone (the site being developed for the Acute Services Block and the
external site areas that fall within the scope of the new works).
On completion, the contractor will provide a formal written declaration confirming that light
fittings have been installed in compliance with the relevant standards and that no changes
have occurred in the lighting specification used to demonstrate design stage compliance.
Where changes have occurred, a further declaration will be provided confirming that the
revised lighting specification is in compliance with the BREEAM criteria.
The lighting scheme will be zoned to allow separate occupant control of the following
areas:
a. Wards / bedded areas: zoned lighting control for individual bed spaces and control for
staff over groups of bed spaces.
b. Treatment areas, dayrooms, waiting areas: zoning of seating and activity areas and
circulation space with controls accessible to staff
c. Office and circulation spaces
d. In office areas and consulting rooms, zones of no more than four workplaces
e. Workstations adjacent to windows or atria and other building areas separately zoned
and controlled
f. Seminar and lecture rooms: zoned for presentation and audience rooms
g. Library spaces: separate zoning of stacks, reading and counter areas
h. Dining, restaurant, café areas: separate zoning of servery and seating / dining areas
Light switches or controls for a particular zone of the building will be located accessibly to
individuals occupying that zone to enable them to operate the lighting in the space they
occupy. The controls shall be located within, or within the vicinity of, the zone they control.
Within the ward areas of the hospital the lighting control will be automatically controlled and will
dim down at the required times to be advised by the client, the nurses will have control of the
lighting via a dimming switch located at the staff base area of the ward should they require to
adjust the lighting.
Within the ward rooms the lighting design has been designed to provide 300lux at the bed to
allow general examination this will be achieved by all lighting within the room being turned on.
Should there be a requirement to examine the patient in more detail then the use of a portable
examination lamp will be required. The patient will also have the ability to control the lighting
within the space by scrolling through a number of pre-programmed scenes by pushing the
relevant buttons on the patient handset.
On completion, the contractor will provide as-built drawings or specification to verify and
confirming that the lighting zones and the location and scope of the user-controls for the
lighting strategy are in compliance with the BREEAM requirements.
All external light fittings for the building, access ways and pathways will have a luminous
efficacy of at least 50 lamp lumen/circuit Watt when the lamp has a colour rendering index
(Ra) greater than or equal to 60 OR at least 60 lamp Lumen / circuit Watt when the lamp
has a colour rendering index (Ra) less than 60.
All external light fittings to car parking areas, associated roads and floodlighting will have
a luminous efficacy of at least 70 lamp lumen/circuit Watt when the lamp has a colour
rendering index (Ra) greater than or equal to 60 OR at least 80 lamp Lumen's / circuit
Watts when the lamp has a colour rendering index (Ra) less than 60.
All external light fittings for signs and uplighting will have a luminous efficacy of at least
60 lamp lumen's/circuit Watt when the lamp wattage is greater than or equal to 25W OR at
least 50 lamp lumen's/circuit Watt when the lamp wattage is less than 25W.
All external light fittings and roof plant light fittings will be controlled through a time switch
and / or daylight sensor, to prevent operation during daylight hours. Daylight sensor
override on a manually switched lighting circuit will be considered acceptable.
Any decorative lighting and floodlighting provided will be installed in accordance with the
compliance requirements outlined above.
On completion, the contractor will provide as-built site plans and elevations confirming the
location and purpose of all external lighting fittings. The contractor will also provide as-
built lighting specification or lighting designer's calculations confirming lamp lumen's/circuit
watt for each type of fitting as well as the colour rendering index Ra and the external
lighting control strategy. In addition, the contractor shall provide manufacturers' literature
confirming th technical specification for the installed external light fittings.
External lighting will be designed and installed to comply with the requirements of
'Secured by Design' and light levels will allow for facial recognition with the external
CCTV system.
The external lighting for the cycling storage facilities shall be provided in accordance with
BS5489 Part 1 - Lighting of roads and amenity areas. External lighting to the cycling
facilities will be designed and installed to comply with the requirements of 'Secured by
Design' and light levels will allow for facial recognition with the external CCTV system.
The external lighting strategy will be designed and installed in compliance with Table 1
(and its accompanying notes) of the ILE Guidance notes for the reduction of obtrusive light,
2005.
All external lighting (except for safety and security lighting) will be automatically switched
off between 2300hrs and 0700hrs. This shall be achieved by providing a timer for all
external lighting set to the appropriate hours.
Where safety and security lighting will be provided and will be used between 2300hrs and
0700hrs, this part of the lighting system will comply with the lower levels of lighting
recommended during these hours in Table 1 of the ILE's Guidance notes, for example by
using an automatic switch to reduce the lighting levels at 2300 or earlier.
Where specified, any illuminated advertisements will be designed in compliance with ILE
Technical Report 5 – The Brightness of Illuminated Advertisements.
On completion, the contractor will provide a marked-up copy of the as-built site plan
showing the areas of the building and site that will be externally lit and any nearby
properties. The contractor will provide a copy of the as-built external lighting design or
specification confirming the external lighting design in compliance with Table 1 of the ILE
Guidance notes, the controls for all external lighting and illuminated advertisements
designed in compliance with ILE Technical Report 5 (if relevant). In addition, the contractor
will provide indicative examples of where and how the strategy complies
with the requirements
If the bathrooms are built as 'pods' before being sent to site the pods will come with all
electrical circuits complete and installed to a roof mounted junction box ready for supply
230V cabling to be installed on-site by the contractor. If the bathrooms are supplied
partially built or 'flat packed' the electrical circuit wiring should be coiled up on the rear of
the bathroom walls ready for connecting to a high level junction box .
The contractor will include for procurement, provision, supply, delivery, installation,
testing, commissioning and setting to work of suitably rated full complete fully operational
power supply systems to meet the installation detail of the bathrooms whether fully built,
partially built/flatpacked or constructed completely on site. The contractor will fully
coordinate the installation connections of the electrical distribution infrastructure to suit the
bathroom termination points whether connection points are required for fully built or
partially built/flatpack options.
If the bathrooms are built on site the electrical contractor will provide all lighting, if the
bathrooms are factory built the lighting shall either be free issued by the main contractor to
the manufacturer or sourced by the manufacturer to specification compliant standards.
.
• Systems: General lighting system, as section V50 and Central battery emergency lighting
and signage system, as section V56.
The contractor will engage the services of an induction loop specialist to carry out system
configuration assessment to ensure the functional operation of the system to be installed to
the room construction and any constraints involved.
The specialist will be retained to test and commission and adjust the system during the
installation phase and at completion to ensure any necessary adjustments are addressed
and made during installation to eliminate any necessity for alterations at completion stage
to meet specified operational performance characteristics.
All systems configurations will be coordinated with building constructional details of the
area served including architectural structural etc. .
• Systems: Induction-loop system, as section W16.
The contractor will install an Internet Protocol (IP) distributed television system to the
Acute Services Block. The contractor will engage the services of a specialist designer
installer to design procure provide install test commission set to work and certify the
system. The contractor will ensure that the full range of equipment and accessories
necessary to provide a high quality signal reception at all outlet points from the television
distribution network is provided. The system will be provided with cabling with appropriate
levels of shielding to eliminate interference and transient surges from other installations
from corrupting the signal/data transmissions from the system. the electrical contractor
will provide and install full complete electrical services installations to facilitate the
television system. including but not limited to power supplies, cabling and containment
system routed within risers ceiling voids etc. to serve the specialists installation. The
contractor will liaise with and coordinate with the IT systems specialist installers to ensure
the integration of the IPTV system to the Data network space allocated. The televisions will be
procured by the client and issued to the contractor to install.
The electrical contractor will engage the services of a voice and data systems installation
contractor to provide and install a full complete fully operational system to effect the
complete requirements of the project to Clients requirements. The electrical contractor
will provide and install a full complete fully operational power supply, containment, outlet
and cabling installation to meet the requirements of the system throughout the project and
to interconnect to the site wide installation. The contractor will distribute the installation to
the points as indicated on the layouts. The contractor will note restriction on length of run
of final telecommunications/data cable connection of 90m with the patch panels being
strategically placed throughout the building in cleaners cupboards or within the electrical risers,
they will not be placed within the dedicated hub rooms as these are for the medical IT services
only.
.
• Systems:
- Television distribution system, as section W20;
- Telecommunication systems, as section W30; and
- Data distribution system, as section W31.
• Access Control
Access control will operate with HID proximity cards, electromagnetic door locks, push to
release buttons, emergency release units, door controllers control panels. Access control
shall release doors on the 'Blue route' during a cardiac alert activation.
The Blue route will operate in the following way; When a Cardiac alert push button is
activated at a bedhead the nurse call system will create a cardiac alert response.
Appropriate alert lights will be activated within the ward indicating the bedroom where the
cardiac alert activation has been initiated. The Nurse call system will alert the Cardiac
Response of 'Crash' team of the event and the crash team presence will also be backed
up by staff controlled voice communications.
The Nursecall system will activate a series of blue lights external to the Ward where the
cardiac alert has been raised. These blue lights will indicate the 'blue route' and will
guide the Crash Team from their source point to the bedroom where the cardiac alert has
been initiated.
The crash team originate from Level 3 Cardiology. The crash team will use the staff lift at
Stair core 2 (North) to access all levels. All access doors on the blue route between the
Level 3 Crash team location in Cardiology and the bedroom where the activation has taken
place will unlock to allow the Crash Team easy access to the route. The staff lift will auto
-park at Level 3 and remain there until the Crash Team operate the lift. Any auto-doors on
the blue route shall open to allow easy access for the Crash Team.
The access controlled doors and auto doors will remain in the open state until the blue
Route alarm is reset. This will be a manual operation by a member of the Ward staff as
part of the Crash Team Cardiac procedure. As part of the Blue route map throughout the
Generic Ward Block & the Acute Services Block. The blue route is controlled by the Nurse-call
system and will unlock door access doors which are designated as being on the blue route
during a blue route cardiac event.
After the event / when rest door access doors will return to normal operation. Any auto
doors on the blue route should open until the blue route system is reset. The stair core two
staff lift will auto-park at Level 3 after every use whilst the blue route alert is active.
• Intruder detection
Intruder detection will utilise PIR sensors for the purposes of detection of movement, door
and window contacts to detect forced entry.
• CCTV
CCTV cameras to enable observation and recording of public and strategic areas/locations
around the site utilising IP topology ensuring all images are able to be viewed within the security
room this will require a fibre cable to connect to these areas.
The electrical contractor will provide and install full complete fully operational cabling
containment and distributions systems and infrastructure to deliver access control
provisions to points required by the specialist installers. Systems components provided for
this purpose will be suitable for application and subject to specialists recommendations.
The electrical contractor will liaise fully with the specialist to ensure suitability of
containment systems components
• Systems:
- Access control system, as section W40;
- Intruder detection and alarm systems, as section W41
- Closed Circuit Television Systems, as section W44
- Conduit and Trunking as section Y60
- Cable supports as section Y63.
All systems and building features will be installed in accordance with the
recommendations of the Architectural Liaison Officer (ALO) or Crime Prevention Design
Advisor's (CPDA) recommendations. The final building and site design will embody the
recommendations of the ALO / CPDA and will be built to conform to the principles of
Secured by Design . The contractor will engage with these bodies to develop and ensure
incorporation of their recommendations.
On completion of the project, the contractor will provide correspondence from the ALO /
CPDA confirming that the as-built development or design complies with their
recommendations and a copy of the development's 'Secured by Design' certificate.
The electrical contractor will provide and install full and complete fully operational power
supply, cabling and containment systems to serve the full and complete requirements of
the fire alarm system.
Critical alarms will be alerted to the site main 24hour switchboard via the fire alarm
system. Critical alarms include but are not limited to ;
Cold Stores Temperature
Cold Stores power supply
Medical gas alarms
Fire suppression systems activation
Staff panic alarms
An assistance call system will be installed primarily for assistance calls from accessible
facilities located in public areas . The electrical contractor will engage the services of a
systems specialist to undertake the installation works including testing commissioning and
certification. The electrical contractor will provide and install all necessary power supply,
cabling and containment to meet the requirements of the systems specialist
The functional requirements of the system will include but not be limited to:
The electrical contractor will provide and install a full complete IP based system to effect
these requirements. The contractor will provide and install a full complete fully
operational power supply, cabling and containment system to effect the systems'
services requirements.
.
• Systems:
- Fire detection and alarm system, as section W50;
- Assistance call system, as section W53;
- Nurse call system, as section W55; and
- Water leak detection and alarm system, as section W58 .
ASDs and associated control panels shall be provided and installed as part of the
mechanical services contract.
They shall be located where ductwork passes through fire compartment walls and/or where
indicated on the drawings.
The ASD systems will comprise a number of smoke damper control panels allocated to
serve control and operational requirements of local groups of ASDs. Each of the ASD
Control Panels will be provided with direct wired power supplies through the electrical
contract. Each of the ASDs will also be provided with direct wired power supplies through
the electrical contract. The Control Panel of each ASD system will be provided with a fire
alarm interface. This interface will initiate a signal to the control panel which will in turn
signal the group of ASDs served to operate in accordance with the cause and effect
schedule. The mechanical contractor is responsible for providing the complete control
wiring and associated installation between the ASD control panels and the ASDs.
Local power supplies to the controls panels and dampers will be provided under the
electrical contract. The mechanical contractor is responsible for the final connection of the
panels and smoke dampers to these power supplies. All such works in this regard will be
in accordance with BS7671 17th Edition IEE regulations and associated Guidance Notes.
The installation details and methods to be adopted for this element of the works will
match that of the electrical services circuitry infrastructure .
Fire alarm interfaces shall be the primary controller of the ASDs under fire conditions. In
the event of a confirmed fire alert the fire alarm interfaces will be configured to close the
ASDs. Final connections between the ASDS, associated control panels and the power
supplies & fire alarm interfaces shall be carried out as part of the mechanical services
contract works.
The provision and installation, testing commissioning and certification of the final wiring
connections and associated containment installations to the ASDs shall be the
responsibility of and carried out by the mechanical services contractor.
The electrical services contractor will liaise with the fire alarm system specialist and the
mechanical contractor to ensure that the mutual commissioning requirements are fully
coordinated and integrated into the fire alarm cause and effect.
.
ASTGs will be provided and installed as part of the mechanical services contract.
They shall be located where ductwork passes through fire compartment walls and/or where
indicated on the drawings.
The ASTGs controllers will be provided with dedicated individual direct wired power
supplies through the electrical contract. Each of these ASTG controllers will also be
provided with a dedicated fire alarm system interface through the electrical contract. The
power supplies and fire alarm interfaces of each individual ASTG will be coordinated with
the associated controller. Where an ASTG is installed within a door, the mechanical
contractor will be responsible for the control wiring installation and associated containment
between the ASTG and its controller. In the event of a confirmed fire alert locally the fire
alarm interfaces will be configured to close the ASTGs
Local power supplies to the ASTGs and associated controllers will be provided under the
electrical contract. The mechanical contractor is responsible for the final connection of the
ASTGS and controllers to these power supplies. All such works in this regard will be in
accordance with BS7671 17th Edition IEE regulations and associated Guidance Notes.
The installation details and methods to be adopted for this element of the works will
match that of the electrical services circuitry infrastructure .
Fire alarm interfaces will be the primary controller of the ASTGs under fire conditions. In
the event of a confirmed fire alert the fire alarm interfaces will be configured to close the
ASTGs. Final connections between the ASTGs, associated controllers and the power
supplies & fire alarm interfaces will be carried out as part of the mechanical services
contract works.
The provision and installation, testing commissioning and certification of the final wiring
connections and associated containment installations to the ASTGs will be the
responsibility of and carried out by the mechanical services contractor.
The electrical services contractor will liaise with the fire alarm system specialist and the
mechanical contractor to ensure that the mutual commissioning requirements are fully
coordinated and integrated into the fire alarm cause and effect.
.
Smoke Vent systems will be provided and installed as part of the main building contract.
They will be located within stairwells and/or where indicated on the drawings.
The Smoke Vent Systems Control panels shall be provided with dedicated individual direct
wired power supplies through the electrical contract. Each of these control panels will
also be provided with a dedicated fire alarm system interface through the electrical
contract. The power supplies and fire alarm interfaces of each individual Smoke vent
control panel will be coordinated with system installer. The Smoke Vent system
contractor will be responsible for the control wiring installation and associated containment
between the Smoke vent system control panel and its field equipment and components. In
the event of a confirmed fire alert locally the fire alarm interfaces will be configured to
initiate action of the Smoke Vent system in accordance with the cause and effect schedule.
The Smoke Vent system contractor is responsible for the final connection of the smoke
vent systems control panels to these power supplies and fire alarm system interfaces. All
such works in this regard will be in accordance with BS7671 17th Edition IEE regulations
and associated Guidance Notes. The installation details and methods to be adopted for
this element of the works will match that of the electrical services circuitry infrastructure .
Fire alarm interfaces will be the secondary controller of the Smoke Vent Systems under
fire conditions. In the event of a confirmed fire alert the Smoke vent control panels will be
configured to operate in accordance with the fire strategy cause and effect schedule. Final
connections between the Smoke Vent Systems and the power supplies & fire alarm
interfaces will be carried out by means of fire resistant cabling to match the electrical
infrastructure wiring specification as part of the Smoke Vent System contract works.
The provision and installation, testing commissioning and certification of the final wiring
connections and associated containment installations to the Smoke Vent Systems will be
the responsibility of and carried out by the Smoke Vent System specialist.
The electrical services contractor will liaise with the fire alarm system specialist and the
Smoke Vent system installer to ensure that the mutual commissioning requirements are
fully coordinated and integrated into the fire alarm cause and effect.
.
Natural Vent systems will be provided and installed as part of the main building contract.
They will be located within hot-links, walkways and/or where indicated on the drawings.
The Natural Vent Systems Control panels will be provided with dedicated individual
direct wired power supplies through the electrical contract. The power supplies of each
individual Natural Vent control panel will be coordinated with system installer. The Natural
Vent system contractor will be responsible for the control wiring installation and associated
containment between the Natural Vent system control panel and its field equipment and
components.
The Natural Vent system contractor is responsible for the final connection of the Natural
Vent systems control panels to these power supplies. All such works in this regard will be
in accordance with BS7671 17th Edition IEE regulations and associated Guidance Notes.
The installation details and methods to be adopted for this element of the works shall
match that of the electrical services circuitry infrastructure .
Final connections between the Natural Vent Systems and the power supplies will be
carried out by means of cabling to match the electrical infrastructure wiring specification as
part of the Natural Vent System contract works.
The provision and installation, testing commissioning and certification of the final wiring
connections and associated containment installations to the Natural Vent Systems will be
the responsibility of and carried out by the Natural Vent System specialist.
The electrical services contractor will liaise with the mechanical services contractor and
the Natural Vent system specialist to ensure that the mutual commissioning requirements
are fully coordinated and integrated into the building and systems commissioning
programme.
.
• Systems: .
The electrical contractor will provide and install a full and complete fully operational
lightning protection system in accordance with BSEN62305. The contractor will engage
the services of a lightning protection systems specialist to verify and validate the proposed
layouts, design procure provide install test commission and certify the full and complete
fully operational system. The systems specialist will provide and install systems surge
arrester to meet impulse transmission through the services installations as detailed on the
layouts. The lightning protection systems specialist will review all services and systems
layouts to ensure all necessary requirement in this regard are met. The system will be
based on the Faraday Cage principle. The specialist will review all geographical
constraints in the determination of the system requirements.
The electrical contractor will provide all necessary attendances on the systems specialist
to effect a full and complete fully operational system. The system specialist will review the
building plans, sections and constructional details to ensure all elements are suitably
integrated and protected. All roof top plant, infrastructure and extraneous metal work are
bonded to system
.
• Systems Lightning protection system, as section W60.
The electrical contractor will provide and install a full and complete fully operational
earthing and bonding installation in accordance with BS 7671 and associated Guidance
notes, BS7430, BSEN62305 and MEiGAN. The contractor will engage the services of a
MEiGAN systems specialist to verify and validate the proposed layouts, design procure
provide install test commission and certify the full and complete fully operational system.
The systems specialist will provide and install systems surge arrester to meet impulse
transmission through the services installations as detailed on the layouts. The earthing and
bonding systems specialist will review all services and systems layouts to ensure all
necessary requirements in this regard are met.
The electrical contractor will provide all necessary attendances on the systems specialist
to effect a full and complete fully operational system. The system specialist will review the
building plans, sections and constructional details to ensure all elements are suitably
integrated and protected. All roof top plant, infrastructure and extraneous metal work are
bonded to system.
The Contractor will install earth mats for LV network, MV network and LV Generators as
part of this project.
LV
Low voltage earthing will connect to the start point of each of the two dedicated building
transformers. A earth mat for LV earth shall be located below the Level 1 floor slab, this
earth will be sized to suit the potential fault current from the Low Voltage network and will
be installed and commissioned before the Level 1 slab is poured. The contractor will
record all test results and inform the Electrical Engineer of the impedance values to allow
the checking of electrical calculations. The Contractor will be responsible for carrying out
all protection studies based on the selected equipment to allow disconnection times and
discrimination levels to be set by the commissioning Engineer.
HV Earthing
The HV earthing system will be interconnected to the existing site wide HV earthing
arrangement. a dedicated HV earth mat will be provided and installed local to the HV
switchroom (refer to drawings). Interconnections will be made to the LV earth mat and the
utility/REC HV earth to ensure continuity under fault conditions. interconnections will be
made such as to enable isolation for testing and verification etc..
Generator earthing
A separate generator earthing mat will be provided and installed. The generator earthing
system will incorporate neutral earthing contactors to enable isolation of the generator
systems from the LV/HV earthing infrastructure.
.
• Systems Lightning protection system, as section W60
Earthing and Bonding as section V81
MEiGAN.
Separate accessible energy sub-meters, labelled with the end energy consuming use, will
be provided for the following systems (where installed):
- Space heating
- Domestic Hot Water
- Humidification (each individual humidifier)
- Environmental Cooling
- Process cooling
- Fans (major)
- Lighting
- Small power (lighting and small power can be on the same sub-meter where supplies
are taken at each floor / department)
- Other major energy consuming items where present (kitchen plant, cold storage plant,
laboratory plant, transportation systems (e.g. lifts)).
- Separate metering shall be provided for plant of the following sizes:
(i) Any boiler installation comprising one or more boilers or CHP plant feeding a
common distribution circuit with a rated output of 50kW or more.
(ii) Chiller installations comprising one or more chillers units feeding a common
distribution circuit.
(iii) Any electric humidifiers with a rated output of 10kW or more
(iv) Motor control centres providing power to fans and pumps with a rated rated
output of 10kW or more.
(v) Any final electrical distribution boards with a rated output of 50kW or more.
The energy meters will be located on the main LV Switchgear which will allow for easy access
to facilitate regular monitoring and readings by the building staff and facilities manager.
suitable location are the plant room, main distribution room or control room.
All energy sub-meters will have a pulsed output to enable connection to the Building
Management System (BMS) for the monitoring of energy consumption.
The electrical contractor will include for provision and installation of electrical energy
metering facilities as indicated on the schematic layouts. The contractor will include for
modbus collation of energy meter readings within the associated switchboard. The
contractor will liaise with the BMS systems specialist to ensure integration of the
Modbus outputs to the BMS system. The contractor will confirm to the BMS specialist
the services of each and every individual metered supply.
A power point and and network access point will be provided to facilitate the installation
and connection of an electronic 'real-time' public transport information system to enable
staff and building visitors to access up-to-date public transport information and plan their
journey. The system will be provided to the main entrance area with adequate signage
at its point of use and throughout appropriate areas of the development indicating its
purpose and location / existence.
On completion, the contractor will provide as-built drawings or specification confirming the
installation of a BREEAM compliant travel information point.
An occupant control shading system (blinds) will be provided on all windows, glazed
doors and rooflights in areas fitted with beds, desks or workstations. The blinds in each
space will be operated by means of individual handheld electronic controllers provided for
each space.
GENERAL The diesel supply system for the generator installation is defined in this section
of the specification. The provision, installation, testing, commissioning, certification, and
setting to work of the diesel supply system shall be undertaken by the generator system
specialist as part of the Electrical Contractors works.
120 DIESEL SUPPLY SYSTEM The requirements are for the provision and installation of a
complete fully operational effective diesel supply system to serve the individual generator
sets of the project. The diesel supply system will include fuel polishing equipment to
remove water, fungi and microbiotic organisms from the stored diesel delivery system.
Fuel polishing must be located at point of use for both generators to deal with the main
underground storage tanks and the day tanks which will be installed adjacent to the
generator sets. System shall include all necessary levels monitoring, shut-off controls,
BMS and fire alarm interfaces as necessary .
• Manufacturer: Generator systems specialist.
• Supply: Pumped.
• Service tanks: twin walled Carbon steel.
- Accessories:
- Contents gauges;
- Fill points;
- Sight glasses; and
- Overfill alarms and overfill prevention devices.
• Storage tanks: twin walled underground carbon steel.
- Accessories: Fill points and Overfill alarms and overfill prevention devices.
• Location of tank: Underground.
• Diesel heating methods: Trace heating.
• Pipelines: As section Y10.
- Accessories:
- De-aeration devices;
- Filters;
- Fuel meters; and
- Remote-acting fire safety valves.
• Diesel pump: Transfer pump, as section Y20.
• Outlets: Generator systems, as section V12.
• Controls: As section Y40.
• Completion:
- Plant and equipment identification: As section Y32
SYSTEM PERFORMANCE
210A DESIGN
• Design: Complete the design of the generators' diesel supply system.
• Proposals: Submit drawings, technical information, design, calculations and manufacturers'
literature.
PRODUCTS
310 SERVICE TANKS, CARBON STEELA day tank will be installed for each generator within
the generator room at Level 1 of the Generic Ward Block. The tanks shall be suitably
mounted and supported to afford gravity feed to the associated generator set. Layout shall
be provided to suit generator systems arrangements.
• Standard: To BS EN 12285-1, BS EN 12285-2 or BS EN 14015.
• Type: Double skin.
• Manufacturer: Generator supplier.
- Product reference: Submit proposals.
• Mounting: Horizontal.
• Tank class to BS EN 12285: .
• Tank capacity: Day tank must allow for a minimum of 8 hours continuous running at full load.
The day tank will be capable of being refilled from the main storage tank without the
generator shutting down. .
- External diameter of tank: Submit proposals..
- Overall length of tank: Submit proposals.
• Manhole diameter: 1000 mm.
• External coating: Epoxy or polyurethane.
• Fittings:
- Fill pipe;
- Vent pipe;
- Isolating valves; and
- Drain valve
330 STORAGE TANKS, CARBON STEEL The storage tanks shall afford 120 hours run-time
capacity (excluding day tank capacity) for the generators. The physical size of the tanks
proposed shall incorporate within the dimensions proposed the fuel consumption rates of
the proposed generator sets. The tanks shall be underground type
• Standard: To BS EN 12285-1, BS EN 12285-2 or BS EN 14015.
• Type: Double skin.
• Manufacturer: Generator Specialist.
- Product reference: Submit proposals.
• Mounting: Horizontal.
• Tank class to BS EN 12285: .
• Tank capacity: Capacity must allow for 120 hours continuous running at full load .
- External diameter of tank: Submit proposals.
- Overall length of tank: Submit proposals.
• Manhole diameter: 1000 mm.
• External coating: Polyurethane.
• Fittings:
- Fill pipe;
- Vent pipe;
- Isolating valves; and
- Drain valve
- Leak detection.
370 TRACE HEATING TO PIPELINES Provide and install a full complete fully operational and
effective installation including necessary services and associated connections
• Standards: To BS 799-5 and in accordance with BS 5410-2.
• Type: Electric cables.
• Manufacturer: Raychem or equal.
Product reference: Submit proposals.
380 ANTI-SYPHON VALVES Provide and install a full complete fully operational and effective
installation including necessary services and associated connections
• Manufacturer: System Manufacturer.
Product reference: Submit proposals.
390 FILTERS Provide and install a full complete fully operational and effective installation
• Standard: To OFS E104.
• Manufacturer: System Manufacturer .
- Product reference: Submit proposals.
400 REMOTE-ACTING FIRE SAFETY VALVES Provide and install a full complete fully
operational and effective installation including necessary services and associated
connections
• Standard: To BS 799-5.
• Type: Electrical.
• Manufacturer: System Manufacturer .
- Product reference: Submit proposals.
410 CONTENTS GAUGES Provide and install a full complete fully operational and effective
installation including necessary services and associated connections
• Standards: To BS 799-5 and OFS E103.
• Type: Electronic.
• Manufacturer: System Manufacturer .
- Product reference: Submit proposals.
420 FILL POINTS Provide and install a full complete fully operational and effective installation
including necessary monitoring, communications, controls, services and associated
connections
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Accessories: Cabinet and Cap and chain.
430 SIGHT GLASSES Provide and install a full complete fully operational and effective
installation
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Diameter: 25 mm.
• Connections: Flanged.
440 OVERFILL ALARMS AND OVERFILL PREVENTION DEVICES Provide and install a full
complete fully operational and effective installation including necessary monitoring,
communications, controls services and associated connections
• Standard: To OFS E105.
• Manufacturer: System Manufacturer .
- Product reference: Submit proposals.
460A FUEL METERS Provide and install a full complete fully operational and effective
installation including necessary services and associated connections
• Manufacturer: System Manufacturer.
- Product reference: Submit proposals.
• Type of fuel: Diesel.
• Flow rate: To 4 x fuel consumption rates of generator sets (both together at full rated
Output).
• Size: Submit proposals.
• Connections: Flanged.
• Output: R232.
470 DE-AERATION DEVICES Provide and install a full complete fully operational and effective
installation including necessary services and associated connections.
• Manufacturer: System Manufacturer .
- Product reference: Submit proposals.
EXECUTION
COMPLETION
910 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
920 COMMISSIONING
• Commissioning: In accordance with OFTEC Technical Books 2 and 5.
930 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion .
GENERAL
109B GENERAL
The requirements are to provide three off; complete fully operational and effective gaseous
fire-extinguishing/suppressant systems. The fire suppressant system to be utilised within
the Acute Services Block LV Switchroom and transformer rooms is Heptafluoropropane
HFC227ea or equal approved. The sub contract design and installation for the
suppression systems will be considered as part of the electrical installation contract.
The Electrical contractor will liaise with the mechanical contractor to coordinate an
exhaust ventilation system for the LV Switchroom and transformer rooms that will be capable of
ten air changes per hour. The electrical contractor will coordinate with the building contractor
to install pressure relief grillage to the free area (m²) defined by the specialist sub contract
designer. The Main Contractor will be responsible for providing the wall penetrations to
the sizes and locations stated by the specialist system designer
The suppressant systems will be connected to the building fire alarm system for status
monitoring but will not be controlled by the building fire alarm systems. Each suppressant
system will require its own control panel and fire detection activation which is separate,
distinct and not influenced by the building fire detection and alert system.
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the gaseous fire-extinguishing system.
• Proposals: Submit drawings, technical information, calculations and manufacturers'
literature.
PRODUCTS
326 HIGH AND LOW PRESSURE SELECTOR VALVES AND THEIR ACTUATORS
• Standard: To BS EN 12094-5.
• Manufacturer: Submit System Manufacturer.
- Product reference: Submit proposals.
EXECUTION
COMPLETION
910A TESTING
• Notice (minimum): 14 days.
• Static pressure test:
- Open ended pipelines: Pneumatically test in a closed circuit for 10 minutes at 3 bar
(300 kPa). The pressure drop must not exceed 20% of the test pressure.
- Closed sections of pipelines: Hydrostatically test to 190 bar (19000 kPa) for high
pressure systems and 36 bar (3600 kPa) for low pressure systems, for a period of 2
minutes. After this period check that there is no leakage.
• Purging: On completion of testing, purge the systems. Remove moisture.
Purge system using:-
Nitrogen.
Or C.O.2.
This is to prove continuity of pipework and that the nozzles are clear.
Flimsy paper bags are to be attached to all nozzles during the purge
and removed upon completion of the purge.]
• Performance testing:
Application. Gas Suppression.
All performance testing will be witnessed by the Mechanical
Services Engineer and will consist of the following:
1. Localised smoke puff tests on selected detectors in all zones to
ensure all aspects of the electrical installation, plunger actuation
and fire damper operation react as required.
2. Localised smoke puff tests to ensure that the AHSSD operates
to the specified criteria.
Note. The gas bottles will be disconnected during all performance testing.
930 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
950 MAINTENANCE
• Servicing and maintenance: Undertake.
- Duration: Until 12 months after Practical Completion.
GENERAL
SYSTEM PERFORMANCE
210 DESIGN
• Design: Complete the design of the high voltage connection in accordance with the
Electricity Distributor's guidelines.
• Proposals: Submit drawings showing equipment positions and routes, technical information
and calculations.
• Evidence of agreement with Electricity Distributor: Submit.
EXECUTION
630 MANAGEMENT
• Establishing the supply: Manage and liaise with the Electricity Distributor and Electricity
Supplier to establish the incoming electricity supply.
• Evidence of liaison: Submit.
640 LOCATION
• Incoming point of supply: Coordinate the location and establish the spatial requirements for
the Electricity Distributor's equipment and metering.
- Proposals: Submit.
• Location and colour coding of equipment: In accordance with NJUG 'Guidelines on the
positioning and colour coding of utilities' apparatus'.
COMPLETION
920 DOCUMENTATION
• Operation and maintenance instructions: Submit.
• Record drawings: Submit.
GENERAL The generator system shall comprise 2 no. generator sets integrated to LV
distribution infrastructure as detailed on the layouts and schematics.
Engage the services of a generator systems specialist to design provide install test
commission and certify a full complete operational and effective dual operation
(standby/prime mover) installation including all necessary direct and ancillary services and
associated connections. The specialist shall also provide that associated diesel supply
system as per requirements detailed under section S40
115 PROPRIETARY GENERATOR SYSTEM Provide and install a full complete fully
operational and effective installation including necessary services and associated
connections.
• System manufacturer: Refer to schedule of preferred manufacturers and suppliers.
• Components: Manufacturer's standard.
• Prime mover: Internal combustion engines.
• Fuel: Diesel supply systems, as section S40.
- Storage tanks:
- Day tank;
- Storage tank, as section S40; and
- Submit design and cost proposals.
• Governor: Required.
• Alternator: Required.
• Automatic voltage regulators: Required
• Exhaust and silencer: Custom to provide attenuation to 65dBA at 1000mm installed (not
free field) when systems are operating at 100% load..
• Control panel: Required
• Gas detection and alarm systems: As section W57
• Generator enclosure: Required to provide attenuation to 65dBA at 1000mm installed (not
free field) when systems are operating at 100% load..
• Louvres: As section L15.
• Earthing: As section V81.
• Signs and notices: As section N15.
• Ventilation: Mechanical supply ventilation system, as section U10 and Mechanical extract
ventilation system, as section U10.
• Vibration isolation mountings: Heavy duty Vibration isolation mountings, as section Y31.
• Accessories:
- Day tank;
- Drip tray;
- Emergency stop buttons;
- Load bank; and
- Safety guards and stone guards.