Automatic Transfer Switch

ATI Range
Automatic Transfer Switch
250 – 3200A

Image shown may not reflect actual configuration.

The panels use a mechanically held motorised Features


switch to transfer the load between the mains and
the genset and vice versa. In the event of mains Controls
failure, the control logic will automatically start • Automatic and manual operation for increased
the genset and transfer the load. The connection reliability
between the control panel and the ATI panel • Manual operation possible without opening the
incorporates a two wire control system. panel
The motorised switch can also be manually • 4-pole changeover switch including electronics
operated in the event of failure of any other part of control to meet IEC 60947-6-1 standard
the system. A further benefit of the switch is that it • Simple network configurations
will remain mechanically held in position despite • T
 est operations and sequences are accessible
any fluctuations in supply. In addition, should
from front panel or remotely
maintenance be required on the control system,
the switch will stay in position and can be operated
manually. Two Wire
Control
The electronic control module is situated on the Generator
set
front of the unit. The module will operate with
any three phase voltage from 190-480 volts (50 Load fed
or 60 Hz), with easy conversion to single phase from genset
operation. Load

Load fed
All models have been designed with customer
from mains
accessibility in mind, boasting features such as
a removable front cover, entry gland plate, cable Load Transfer
Panel
access plate and a removable control module and/
or motor.
Mains

LEHE0886-00 Page 1 of 3
Automatic Transfer Switch

Features Optional Features


Motorised Mechanically Held Facia Top Cable Entry (TICT)**
Switch Symbolic icons to allow for multiple
Facility for manual changeover languages Lightning Protection (TLPRB)
Ensuring the safety of system
Status Indication Controls during lightning storms
• Utility power available • Under/over frequency failure
• Utility power on load • Under/over frequency Water Ingress Protection (TIP5)*
• Generator available/ restoration IP54 and NEMA 3 protection for
generator on load • Manual/auto re-transfer the control module
• Utility power and generator off • Mode select pushbutton
load • Under/over volts failure Communicatons Module
• Manual mode/automatic mode • Under/over volts restoration (TCOM)
• Test on load/test off load • Delay on start timer Plug in module that uses Jbus/
• Manual re-transfer enabled/ • Delay on transfer modbus protocol to allow remote
required • Delay on re-transfer communication of the changeover
• Power/error indication (LED) • Dead band timer system
• Run on timer
Liquid Crystal Display (LCD) Solid Neutral Link (TLNK)**
• Auto/manual control keyswitch
• Utility power L12, L13, L23 • Lamp test pushbutton
voltage Volt-Free Contacts (TIO2)
• Padlock facility For utility power available and
• Utility power L1N, L2N, L3N
voltage Auxilary Contacts (TAUXS) generator available
• Generator L13 voltage For switch position, padlocking Power Metering (TMET)**
• Utility power frequency/ and auto/manual To measure load current, kW,
generator frequency
Standards kVAr, kVA, power factor
• Number of commutation
(service counter) • Complete enclosure meets *Standard with ATI2000, ATI2500,
• Timer settings standard IEC 60947-6-1 ATI3200.
• Switch meets standard AC31-B **Available with ATI250 – 1600 but
D.T.O. only for ATI2000 – 3200.

LEHE0886-00
Page 2 of 3
Automatic Transfer Switch

Dimensions and Weights


Rating A B C Weight
Model (Amps) mm (in) mm (in) mm (in) kg (lb)
ATI 250 250 500 (19.7) 600 (23.6) 300 (11.8) 33 (77)
ATI 400 400 600 (23.6) 600 (23.6) 375 (14.7) 40 (88)
ATI 630* 630 900 (35.4) 600 (23.6) 475 (18.7) 65 (143)
ATI 800* 800 1100 (43.3) 775 (30.5) 650 (25.6) 120 (265)
ATI 1000* 1000 1100 (43.3) 775 (30.5) 650 (25.6) 145 (320)
ATI 1250* 1250 1400 (55.1) 1005 (39.6) 650 (25.6) 200 (441)
ATI 1600* 1600 1600 (63.0) 1005 (39.6) 800 (31.5) 330 (728)
ATI 2000* 2000 1899 (74.8) 1005 (39.6) 1007 (39.6) 550 (1213)
ATI 2500* 2500 1899 (74.8) 1005 (39.6) 1007 (39.6) 600 (1323)
ATI 3200* 3200 1899 (74.8) 1005 (39.6) 1007 (39.6) 600 (1323)
*Floor mounted, (height includes 100 mm pedestal)

ATI floor mounted ATI wall mounted

www.Cat-ElectricPower.com
©2015 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” trade dress as well as corporate and product identity used
LEHE0886-00
(07/15) herein, are trademarks of Caterpillar and may not be used without permission.