Cepex Electric Butterfly Valve Extreme
Cepex Electric Butterfly Valve Extreme
Cepex Electric Butterfly Valve Extreme
EXTREME
11
N DESCRIPTION MATERIAL DN50- DN250- 4
DN200 DN300
BUTTERFLY VALVES
12
1 Body PP-GR 1 1
13
2 Sealing gasket EPDM / FPM 1 1
Electric actuator
10
3 Disc PVC-U/PPH/CPVC/PVDF/ABS 1 1
8
4 Upper Bearing POM 2 2
5 Auxiliary bearing POM 1 1 1
DANGER. Risk of electrocution. Failure to follow the advice set out here may result in electrocution. For more technical information about the actuators, please refer to the instruction manuals attached 70
DANGER. Failure to follow the advice set out here may result in personal harm or damage to the apparatus. to the valve documentation. 60
% Kv
50
WARNING. Failure to follow the advice set out here may result in damage to the automatic valve or apparatus.
3.2 GUARANTEE 40
This equipment has been extensively tested in the factory, thus guaranteeing it is in perfect working 30
GENERAL SAFETY ADVICE condition. This guarantee will be applicable assuming the device has been properly installed and 20
The valves described in this manual are especially designed to ensure a correct flow circulation in all working phases. not used in an incorrectly. For this reason, this equipment must be installed by a suitably qualified 10
Apparatus should be installed in accordance with the specific instructions for each installation. All existing safety legislation person. 0
should be respected at all times in order to avoid accidents. 0 10 20 30 40 50 60 70 80 90 100
% valve opening / % apertura
Any modification to the electric actuator requires the prior authorisation of the manufacturer. Spare parts and accessories 3.3 TECHNICAL CHARACTERISTICS
authorised by the manufacturer are a guarantee of greater safety. The manufacturer of this actuated valve is exempt from all DN65 DN80 DN100
responsibility for damage arising from unauthorised spare parts and accessories. Pressure / Temperature Chart. (G 3.1-3.2) DN125 DN150 DN250
During operation, the electrical parts of this apparatus will have electrical current running through them. All work on the psi bar
automatic valve and other related equipment should only be carried out having first disconnected the start up mechanism. psi bar
The user should ensure that all assembly and maintenance work is carried out by suitably authorised, qualified personnel, and PVC-U
PVC-C PVDF
that these have previously read the installation and service instructions set out in this manual. PP-H ABS
Safe usage of this actuated valve can only be guaranteed by closely following the installation and service instructions laid out DN63-DN200
DN63-DN200
here.
Voltage limits should not be exceeded under any circumstances.
In case of malfunction or breakdown, contact the nearest factory representative or technical assistance service department. DN250-DN315 DN250-DN315
Avoid shocks during transport, since they may damage the body and mechanism of the valve.
Store the valve in the original packaging, protected against humidity and direct sunlight.
ºC -30
ELECTRIC BUTTERFLY VALVE WARNINGS ºC 0 10 20 30 40 50 60 70 80 90 100 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120
ºF 32 50 68 86 104 122 140 158 176 194 212 ºF -22 -4 14 32 50 68 86 104 122 140 158 176 194 212 230 248
The maximum service life of the valve is specified in EN ISO 16136. It is verified on the production plant by aging tests specified
Pressure loss table (T3.1) Pressure loss chart (G 3.3) Kv / % opening (G 3.4)
in the standard.
Correct installation and handling of the valve, as well as adherence to the maximum pressure and temperature conditions 1 Flow / valve opening
D DN Kv (l/min) Cv (GPM) Caudal / Apertura
specified in this manual are essential for preserving the service life of the valve. 100
The driven liquid must be compatible with the valve materials. Consult chemical resistance charts published by Cepex or 63-75 (2 1/2”) DN65 1568 110 90
consult the technical department. 90 (3”) DN80 4980 349 Pérdida de carga (bar) 80
0,1
Using tools for opening or closing the manual valve control is not recommended. Pressure loss (bar) 70
110 (4”) DN100 7212 505
Before carrying out any maintenance operations on the pipe or valve, ensure that the system is depressurised by releasing the 60
% Kv
50
pressure and emptying the pipes, following the specific safety regulations of each product. 125-140 (5”) DN125 12320 863 40
Before installation, check that the valve is undamaged and that it contains all the parts required for installation. 160 (6”) DN150 25447 1134 0,01
30
After long periods of inactivity, check the grease on the gasket and follow the maintenance instructions set out in this manual. 20
The grease must be compatible with the valve materials. 200-225 (8”) DN200 35778 2505 10
It is important to avoid rapid closure of valves to eliminate the possibility of water hammer causing damage to the pipeline. 250 (10”) DN250 65222 4567
0
0 10 20 30 40 50 60 70 80 90 100
When using the valve as the final element of a installation, take into account the risks of the liquid and control the pressure and % valve opening / % apertura
temperature, according to the standards of safety of each product. 315 (12”) DN300 94660 6629 0,001
10 100 1000 10000 100000
DN65 DN80
Caudal (l/min)
Flow (l/min) DN100 DN125
Make all connections following the instruction referring to electrical supply as set out in this manual. Ensure that all cables are DN150 DN200, DN250, DN300
Valve operating torque
correctly connected.
Should you need to open the box at the end of the run, on closing again, check that it is correctly positioned to avoid any water Operating torque values at rated pressure (PN) and 20 °C in as new direct from the factory condition. Installation (flange tightening)
contact. Also check that connectors are correctly situated. and operating (pressure and temperature) conditions will affect these values.
At all times, avoid contact, albeit accidental, with the actuated valve’s moving parts during operation and/or before it has come The actuator that is required for an automatic operation must be calculated according to some safety factors that were determined
to a complete stop. in life tests carried out in the factory.
Before beginning any electrical, ensure that the start-up mechanisms are blocked. It is advisable to follow the following steps Operating torque table (N·m) (T3.2)
before any alteration to the actuated valve:
1.- Disconnect the electrovalve from the main supply. DN65 DN80 DN100 DN125 DN150 DN200 DN250 DN300
2.- Block the system’s start-up mechanisms.
N·m 25 28 35 85 110 110 180 250
3.- Make certain that their is no voltage running through the circuits, including the auxiliary circuits and supplementary services.
All the above should be taken as indicative and not directly tied to safety procedure as specific safety norms may be in place in lbf·inch 221 248 310 752 974 974 1593 2213
some cases. T 4.1 (mm)
IMPORTANT: As a result of the complexity of the subject, the installation, usage and maintenance instructions to be found in this 4. DIMENSIONS. Fig. 3
manual are not designed to cover all imaginable service and maintenance scenarios. Should you require further instructions or DN A B E F H K HOLES
encounter specific problems, please do not hesitate to contact the distributor or valve manufacturer. 65 201 156 120 18 48 125-145 4
Butterfly valve for isolating the flow in liquid handling systems. The liquid can flow in both directions. 100 255 212 148 19 59 180-192 8
Design based on the EN ISO 16136 Standard in accordance with the 97/23/EC Directive.
125 284 238 164 22 66 190-215 8
The valve is available with PVC-U, CPVC, PP-H, PVDF and ABS discs and EPDM and FPM sealing gaskets. The choice of material for the
disc and gasket depends on the type of liquid to be carried and on the working temperature of the liquid, in accordance with the che- 150 314 265 180 24 72 240 8
mical resistance tables available on our website and the pressure/temperature chart in this Manual.
200 378 320 217 23 73 270-298 8
The electric actuator controls the positions of the valve (closed / opened).
250 450 453 310 29 114 329-355 12
2. COMPONENTS 300 545 477 310 29 114 384-427 12
2.1 GENERAL ASSEMBLY
See the actuator manual to check the dimensions
Fig. 1 N DESCRIPTION MATERIAL Q M, N and L.
7 125 F07 17 / 22
8 150 F07 17 / 22
200 F07/F10 17 / 22
1
250 F07/F10/F12 22 / 27
300 F07/F10/F12 22 / 27
Valve design Flanged dimensions Valve connections Other connections Actuator coupling
ISO 16136: 2005 EN 558-1,ANSI B16.5 Class 150,JIS B2220, BS/E EN 1090-1 ISO15494, ISO15493, ISO10931 EN/ISO 5211
ENGLISH EXTREME ELECTRIC BUTTERFLY VALVE ENGLISH EXTREME ELECTRIC BUTTERFLY VALVE
Fig. 5 Fig. 6 Screws and screw tightening torque T 5.1 DN300 30674 30679 35912
63 50 - 4xM16x120 25 221
6. OPERATION OF THE ACTUATOR The valve is not fully watertight at Misalignment between sockets and valve. Disassemble the valve and reassemble with concentric
the sockets. alignment (observe the correct tightening sequence and
The motorised valve consists of an electronic actuator mounted on a conventional valve. torque).
OPERATION. When an electric signal is received, the motor turns to either “OPEN” or “CLOSE” depending on the switching signal until the
Flange screws not tight enough. Tighten flanges as indicated in table T5.1.
internal cam connects to the microswitch, bringing the motor to a stop. When it receives an electric signal again, the motor will turn in the
opposite direction. The valve is not completely Inadequate chemicals. Check compliance with the specifications in this
- Reversible monophase motor with visual position indicator and exit signal. watertight at the sealing gasket . Temperature out of range. document.
- Applications: In 90° turns (or 180° in the case of the three-way ball valve). Excess pressure.
- Both AC and DC power supply. Both positions possible with the same actuator. Always follow the connection diagram on the actuator label. Conduction of abrasive elements.
- Emergency manual operation. The motor will be automatically disconnected by putting the lever in the M (Manual) position. Damaged sealing gasket. Replace the gasket.
- Additional auxiliary contacts for transmission position signal.
- WARNING. Do not connect low voltage actuators to higher voltage sources. Similarly do not connect high-voltage actuators The valve does not open or close. Lack of current. Check current supply to the actuator
to lower voltage sources. Actuators do not have fuses and incorrect voltages can cause irreparable damage to the device.
The valve does not close completely. The actuator stroke is not properly adjusted to the Check adjustment limits according to the actuator manual.
valve.
J+J Characteristics
- Thermostat controlled temperature: Incorporation of a thermostat-controlled 4W heating system, working temperature between 20°C and The torque of the valve has increased above the Check the valve: obstructions in the disc or malfunction
30°C (68°F to 86°F). In order for the system to work correctly it is important to keep the voltage running through the actuator. calculated value. of the valve.
- Safety: The actuator features an automatic electronic cut-off system in case the maximum torque is exceeded. Should this happen, the
device may be manually operated using the handle on the actuator.
- A permanently lit internal LED indicates that the actuator is working correctly. If it starts flashing, this means something is wrong and the
power supply to the actuator will automatically switch off.
Optional accessories:
- Digital positioning System
- Safety block. Independent terminal providing power supply to the actuator in the event of power failure
To mount a new actuator or a new valve, proceed in opposite sense of the previous description.