Design For DCM Columns

This document summarizes the confining design of a reinforced concrete column. It provides details of the column dimensions, material properties, reinforcement details, and design checks. The key points are: - The column has dimensions of 500mm x 700mm with 3100mm clear length and C28/35 concrete. - 32 longitudinal bars of 22mm diameter and transverse bars of 10mm diameter at 150mm spacing are provided. - Checks are performed to ensure the confinement effectiveness, confinement index, and normalized axial load meet Eurocode 8 requirements. - The design is found to not satisfy the confinement condition for normalized axial load. Modifications are needed to strengthen the column confinement.

Uploaded by

Truong Phuoc Tri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
308 views2 pages

Design For DCM Columns

This document summarizes the confining design of a reinforced concrete column. It provides details of the column dimensions, material properties, reinforcement details, and design checks. The key points are: - The column has dimensions of 500mm x 700mm with 3100mm clear length and C28/35 concrete. - 32 longitudinal bars of 22mm diameter and transverse bars of 10mm diameter at 150mm spacing are provided. - Checks are performed to ensure the confinement effectiveness, confinement index, and normalized axial load meet Eurocode 8 requirements. - The design is found to not satisfy the confinement condition for normalized axial load. Modifications are needed to strengthen the column confinement.

Uploaded by

Truong Phuoc Tri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Confining Design for RC Column

Grade of concrete C28/35 (M450) Design code Eurocode 8


Rebar As C-III Calc. column C2-01
Rebar Asw C-II ULS case Tie detailing
Property and coefficients Design values Note
Column general DCM
Fundamental period of the building : T1(s) 3 in horizontal direction interest
Constant acceleration region of the elastic spectrum : Tc(s) 0.8
Behavior factor - q0 4 Follow EC8 5.2.2.2 Table 5.1
Design concrete compressive strength - fcd (MPa) 33.3 f ck = 28 MPa
Column size - bc (mm) 500 b c  h c
Column size - hc (mm) 700
Column clear length - L (mm) 3100
min cover to center of longitudinal bar (mm) 50
Provided longitudinal bars
Design reinforcement strength - fyd (MPa) 339.1 f yk = 390 MPa
Longitudinal bar diameter - dbl (mm) 22
Total number of longitudinal bars - nbl 32
No. of longitudinal bars on size bc - nob 5
No. of longitudinal bars on size hc - noh 9
Axial load for the seismic design NEd (kN) 9500
Provided transverse bars
Design stirrup strength - fywd (MPa) 339.1 f ywk = 295 MPa
Transverse bar diameter - dbw (mm) 10
Transverse bar diameter at column base - dbw2 (mm) 12 from base up to floor 1
Spacing outside critical region - swo (mm) 150
Spacing within critical region - sw (mm) 100
Spacing at column base - sw2 (mm) 100 from base up to floor 1
No. of legs nb parallel to size bc 5
No. of legs nh parallel to size hc 3
Confining design
Region critical length - lc (mm) 700 = max(h c ,l cl /6,450) and if l c /h c < 3 : l c =l cr
Concrete core size - bo (mm) 390 =b c - 2cover min - d bw
Concrete core size - ho (mm) 590 =h c - 2cover min - d bw
Khoảng cách các thanh thép dọc trên cạnh b 98 = b 0 /(n ob -1)
Khoảng cách các thanh thép dọc trên cạnh h 74 = h 0 /(n oh -1)
Spacing between longitudinal restrained bars on size bc 195 = b 0 /(n h -1) for α n
Spacing between longitudinal restrained bars on size hc 148 = h 0 /(n b -1) for α n
Checking spacing between restrained bars OK ≤ 200 mm and 150mm in the corner (EC2 :5.2.3.4(3))
Checking diameter dbw outside critical region OK ≥ (6 , d bl /4)
Checking diameter dbw within critical region OK ≥ (6 , d bl /4)
Checking diameter dbw2 at column base OK ≥ (6 , d bl /4)
Checking spacing swo outside critical region OK ≤ (0,6 h c , 0,6 b c , 240 , 12 d bl )
Checking spacing sw within critical region OK ≤ (0,5 h o , 0,5 b o , 175 , 8 d bl )
Checking spacing swb at column base OK ≤ (0,5 h o , 0,5 b o , 175 , 8 d bl )
Ratio of volumn confining hoops to that of confined core r v = A bw S L bw / ( s w b o h o )
- In critical region: rv 0.0127 r v = A bw ( b o n b +h o n h ) / ( s w b o h o )
- At column base: rv2 0.0183
Checking value r v in critical region OK Following the Eurocode 8 : 0.01< r v <0.04
Checking value r v2 at column base OK Following the Eurocode 8 : 0.01< r v2 <0.04
Design confining index wd  wd = r v f yd / f cd
- In critical region: wd 0.1292
- At column base: wd2 0.1860
Checking index wd within critical region OK ≥ 0.08 (EC8)
Checking index wb2 at column base OK ≥ 0.08 (EC8)

Curvature ductability factor : μ ϕ 7.0000 following EC8 5.2.3.4(3) and 5.4.3.2.2(7)

Critical region : αs 0.7979 (1-0.5s/b o )(1-0.5s/h o )


Base of the column : αs2 0.7979
Critical region : αn 0.7638 1 – [bo /((n h – 1)ho) + ho /((n b – 1)bo)]/3
Base of the column : αn2 0.7638
Confinement effectiveness critical region : α 0.6094 α = αn x αs
Confinement effectiveness at column base : α2 0.6094 α = α n2 x α s2
Normalised design axial force  d = NEd / Acfcd 0.8143
Checking index  d = NEd / Acfcd not OK ≤ 0.65 (EC8)
Checking a wd under the condition:
- awd in critical region 0.0787
- a2wd2 at column base 0.1134
- 30 μϕν dεsy,d.(bc/b0)-0.035 0.3367
- 30 μϕν dεsy,d.(bc/b0)-0.035 at column base 0.3367
- Checking awd in critical region not OK  μ ϕ ν d ε sy,d . ( b c / b  a wd
- Checking a2wd2 at column base not OK  μ ϕ ν d ε sy,d . ( b c / b  a wd
Checking a wd under the condition:

- Checking awd in critical region 2.1    = 4 (recommended)


- Checking a2wd2 at column base 2.8    = 7 (q o = 4)

wd = rv fyd / fcd ; rv = AbwSLbw / (swboho) ; yd = fyd / Es


an = 1 – [bo /((nh – 1)ho) + ho /((nb – 1)bo)]/3 ; d ≤ 0,55 (DCH)
as = (1 - sw/2bo)(1 - sw/2ho) ; d = Ned /(bchcfcd) ; d ≤ 0,65 (DCM)

a s a n  wd  0 , 035   
   → vùng alc móng cột
30  d  yd b c / b o   
→ vùng al khác
c
Es 200000
εsy,d = fyd/Es 0.00170