Appendix

T11 T11:
Selection Table
ÖLFLEX®

Conductor Resistances and Conductor Make-up (metric)

® Conductor Resistances and Conductor Make-up metric)


Conductor Resistances: for annealed-copper-conductors in single- and multicorHFDEOHV•PP2 acc. to DIN EN 60228 (VDE 0295)
UNITRONIC®

Conductor resistance for 20 °C fRUNPLQŸ PD[LPXPvalue)


Nominal cross-section
in mm2 of metal coated copper wire of bare copper wire
Class 2 Class 5 + 6 Class 2 Class 5 + 6
0.08 250.0 243.0
0.14 142.0 138.0
0.25 82.0 79.0
0.34 59.0 57.0

0.5 36.7 40.1 36.0 39.0


ETHERLINE®

0.75 24.8 26.7 24.5 26.0


1 18.2 20.0 18.1 19.5
1.5 12.2 13.7 12.1 13.3
2.5 7.56 8.21 7.41 7.98
4 4.70 5.09 4.61 4.95
6 3.11 3.39 3.08 3.30
10 1.84 1.95 1.83 1.91
16 1.16 1.24 1.15 1.21
25 0.734 0.795 0.727 0.780
HITRONIC®

35 0.529 0.565 0.524 0.554


50 0.391 0.393 0.387 0.386
70 0.270 0.277 0.268 0.272
95 0.195 0.210 0.193 0.206
120 0.154 0.164 0.153 0.161
150 0.126 0.132 0.124 0.129
185 0.100 0.108 0.0991 0.106
240 0.0762 0.0817 0.0754 0.0801
300 0.0607 0.0654 0.0601 0.0641
400 0.0475 0.0470
500 0.0369 0.0366
EPIC®

630 0.0286 0.0283


800 0.0224 0.0221
1000 0.0177 0.0176

Examples of Conductor Make-up (metric)


SKINTOP®

Cross section Multi-Wire Multi-Wire Fine-Wire Super-Fine-Wire


in mm2 Strands Strands Strands Strands
0.14 ~ 18 x 0.10 ~ 18 x 0.1 ~ 36 x 0.07 ~ 72 x 0.05
0.25 ~ 14 x 0.15 ~ 32 x 0.10 ~ 32 x 0.1 ~ 65 x 0.07 ~ 128 x 0.05
0.34 7 x 0.25 ~ 19 x 0.15 ~ 42 x 0.10 ~ 42 x 0.1 ~ 88 x 0.07 ~ 174 x 0.05
0.38 7 x 0.27 ~ 12 x 0.20 ~ 21 x 0.15 ~ 48 x 0.1 ~ 100 x 0.07 ~ 194 x 0.05
0.5 7 x 0.30 7 x 0.30 ~ 16 x 0.20 ~ 28 x 0.15 ~ 64 x 0.1 ~ 131 x 0.07 ~ 256 x 0.05
0.75 7 x 0.37 7 x 0.37 ~ 24 x 0.20 ~ 42 x 0.15 ~ 96 x 0.1 ~ 195 x 0.07 ~ 384 x 0.05
SILVYN®

1.0 7 x 0.43 7 x 0.43 ~ 32 x 0.20 ~ 56 x 0.15 ~ 128 x 0.1 ~ 260 x 0.07 ~ 512 x 0.05
1.5 7 x 0.52 7 x 0.52 ~ 30 x 0.25 ~ 84 x 0.15 ~ 192 x 0.1 ~ 392 x 0.07 ~ 768 x 0.05
2.5 7 x 0.67 ~ 19 x 0.41 ~ 50 x 0.25 ~ 140 x 0.15 ~ 320 x 0.1 ~ 651 x 0.07 ~ 1280 x 0.05
4 7 x 0.85 ~ 19 x 0.52 ~ 56 x 0.30 ~ 224 x 0.15 ~ 512 x 0.1 ~ 1040 x 0.07
6 7 x 1.05 ~ 19 x 0.64 ~ 84 x 0.30 ~ 192 x 0.20 ~ 768 x 0.1 ~ 1560 x 0.07
10 7 x 1.35 ~ 49 x 0.51 ~ 80 x 0.40 ~ 320 x 0.20 ~ 1280 x 0.1 ~ 2600 x 0.07
16 7 x 1.70 ~ 49 x 0.65 ~ 128 x 0.40 ~ 512 x 0.20 ~ 2048 x 0.1
FLEXIMARK®

25 7 x 2.13 ~ 84 x 0.62 ~ 200 x 0.40 ~ 800 x 0.20 ~ 3200 x 0.1


35 7 x 2.52 ~ 133 x 0.58 ~ 280 x 0.40 ~ 1120 x 0.20
50 ~ 19 x 1.83 ~ 133 x 0.69 ~ 400 x 0.40 ~ 705 x 0.30
70 ~ 19 x 2.17 ~ 189 x 0.69 ~ 356 x 0.50 ~ 990 x 0.30
95 ~ 19 x 2.52 ~ 259 x 0.69 ~ 485 x 0.50 ~ 1340 x 0.30
120 ~ 37 x 2.03 ~ 336 x 0.67 ~ 614 x 0.50 ~ 1690 x 0.30
150 ~ 37 x 2.27 ~ 392 x 0.69 ~ 765 x 0.50 ~ 2123 x 0.30
185 ~ 37 x 2.52 ~ 494 x 0.69 ~ 944 x 0.50 ~ 1470 x 0.40
ACCESSORIES

240 ~ 37 x 2.87 ~ 627 x 0.70 ~ 1225 x 0.50 ~ 1905 x 0.40


300 ~ 61 x 2.50 ~ 790 x 0.70 ~ 1530 x 0.50 ~ 2385 x 0.40
400 ~ 61 x 2.89 ~ 2035 x 0.50
500 ~ 61 x 3.23 ~ 1768 x 0.60
630 ~ 91 x 2.97 ~ 2286 x 0.60
Visualisation: Multi-wire Strands Fine-wire Strands Super Fine-wire Strands

Note: Guidelines have been established for measuring conductor sizes with the European Cable Industry. In the past, conductors were normally measured by their cross-
APPENDIX

sectional area, number and diameter of individual strands or both. The new current systems for the flexible conductors centers around the maximum strand diameter
and the conductor resistance. In view of this, some cables may have less strands and a smaller diameter than listed above but still conform to BS 6360, VDE 0295,
IEC 60228 by meeting conductor resistance requirements.

 For current information see www.lappcableasia.lappgroup.com