0% found this document useful (0 votes)
114 views9 pages

KBU Data Sheet 4921210112 UK

This technical document provides specifications for split core current transformers, type KBU, for various primary current ratings ranging from 1A to 5000A. It lists the nominal voltage, isolation class, test voltages, thermal and dynamic current ratings, and operating temperature range. Standards that are referenced are also provided. Product pages within the document provide additional details for specific current transformer models, including secondary current, burden, primary current ratings, and accuracy classes.

Uploaded by

Andy Mezeta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views9 pages

KBU Data Sheet 4921210112 UK

This technical document provides specifications for split core current transformers, type KBU, for various primary current ratings ranging from 1A to 5000A. It lists the nominal voltage, isolation class, test voltages, thermal and dynamic current ratings, and operating temperature range. Standards that are referenced are also provided. Product pages within the document provide additional details for specific current transformer models, including secondary current, burden, primary current ratings, and accuracy classes.

Uploaded by

Andy Mezeta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

Technical documentation

Split core current transformers, type KBU

DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com

Document no.: 4921210112E


Data sheet

Frequency 50/60 Hz (16 2/3 to 400 Hz on request)


≤ 720 V AC
Nominal Voltage
≤ 1200 V AC for ASK 165.5, 205.5

Isolation Class E

3000 V, 1 min, 50 Hz (Nominal Voltage ≤ 720 V)


Test Voltage
6000 V, 1 min, 50 Hz (Nominal Voltage ≤ 1200 V)

Icth = 1.0 × In
Thermal Continuous Thermal Current
Icth = 1.2 × In for ASK 165.5, 205.5

Rated Short-Time Thermal Current Ith = 60 × In, 1 sec (max. 100 kA) for ASK, ASR, KBU

Rated Dynamic Current Idyn = 2.5 × Ith

Instrument Security Factor FS 5 to 15 (see product label for specific value)

Operating Temperature -5°C to 50°C

Storage Temperature -25°C to 70°C


IEC / DIN EN 61869/1+2
Standard References
DIN 42600/1+2

2 www.deif.com
www.deif.com 3
Current transformers overview

Click on a product name or check mark to jump to information page.

Page 3 4 5 6 Page
Primary Primary
KBU KBU KBU KBU
nominal nominal
23 58 812 816
current current
A A
1 1
2.5 2.5
5 5
10 10
15 15
20 20
25 25
30 30
40 40
50 50
60 60
75 75
80 80
100 100
125 125
150 150
200 200
250 3 3 3 250
300 3 3 3 300
400 3 3 3 400
500 3 3 500
600 3 3 600
750 3 3 750
800 3 3 800
1000 3 3 3 1000
1200 3 3 1200
1250 3 1250
1500 3 3 1500
1600 3 1600
1800 1800
2000 3 2000
2500 3 2500
3000 3 3000
3200 3200
4000 3 4000
5000 3 5000
6000 6000
7500 7500
Primary Primary
conductor 20×30 50×80 80×120 80×160 conductor
in mm in mm
Round Round
conductor 20 50 80 80 conductor
in mm in mm
Transform. Transform.
width 93 125 155 195 width in
in mm mm

* For the current transformers above, click-on mountings are available for fitment onto 35mm DIN-rails (DIN 50022).

4 www.deif.com
Split core current transformer KBU 23

Secondary current 5A 1A
Primary Accuracy class Accuracy class
current Burden 1 0.5 1 0.5
A VA Art.-no. Art.-no. Art.-no. Art.-no.
250 1 3
300 3.75 3 3
400 5 3 3

C1

S1 S1
B

Type KBU 23 KBU 58


L -P 3
xxxx xxxxx
xxxxx xxx xxx
A 93 125
B 106 158
C/C1 34/58 34/58
A
D 20 50
E 30 80

Primary conductor 20 × 30mm


C

Round conductor Ø 20mm


Weight 0.550-1.320kg (1.21-2.91lbs)
Security factor FS 5
DIN rail mounting Not available
Sealed shutter Not available

www.deif.com 5
Split core current transformer KBU 58

Secondary current 5A 1A
Primary Accuracy class Accuracy class
current Burden 1 0.5 1 0.5
A VA Art.-no. Art.-no. Art.-no. Art.-no.
250 1.5 3 3
300 2.5 3 3
400 2.5 3 3
2.5 3 3
500
5 3 3
2.5 3 3
600
5 3 3
2.5 3 3
750
5 3 3
2.5 3 3
800
7.5 3 3
5 3 3
1000
10 3 3
C1

S1 S1
B

Type KBU 23 KBU 58


L -P 3
xxxx xxxxx
xxxxx xxx xxx
A 93 125
B 106 158
C/C1 34/58 34/58
A
D 20 50
E 30 80

Primary conductor 50 × 80mm


C

Round conductor Ø 20mm


Weight 0.920-1.320kg (2.03-2.91lbs)
Security factor FS 5
DIN rail mounting Not available
Sealed shutter Not available

6 www.deif.com
Split core current transformer KBU 812

Secondary current 5A 1A
Primary Accuracy class Accuracy class
current Burden 1 0.5 1 0.5
A VA Art.-no. Art.-no. Art.-no. Art.-no.
250 1.5 3 3
300 2.5 3 3
400 2.5 3 3
2.5 3 3
500
5 3 3
2.5 3 3
600
5 3 3
2.5 3 3
750
5 3 3
2.5 3 3
800
7.5 3 3
5 3 3
1000
10 3 3
C1 5 3 3
1200
3 4 .0 (1.33) 10 3 3
7.5 3 3
1250
15 3 3
7.5 3 3
1500
15 3 3

7 1 .0 (2.79)

Type KBU 812 KBU 816


B
E

A 155 195
B 198 243
C/C1 34/58 64/79
D 80 80
3 6.15 (1 .4 2)

E 120 160

1 76 .0 (6 .9 2)
Primary conductor 80 × 120mm
Round conductor Ø 80mm
Weight 1.580-1.550kg (2.87-3.09lbs)
C

Security factor FS 5
DIN rail mounting Not available
Sealed shutter Not available

www.deif.com 7
Split core current transformer KBU 816

Secondary current 5A 1A
Primary Accuracy class Accuracy class
current Burden 1 0.5 1 0.5
A VA Art.-no. Art.-no. Art.-no. Art.-no.
10 3 3 3 3
1000
15 3 3
10 3 3 3 3
1200
15 3 3
10 3 3 3 3
1500
15 3 3 3 3
10 3 3 3 3
1600
15 3 3 3 3
10 3 3 3 3
2000
15 3 3 3 3
10 3 3 3 3
2500
15 3 3 3 3
15 3 3 3 3
3000
C1 30 3 3
3 4 .0 (1.33) 15 3 3 3 3
4000
30 3 3 3 3
15 3 3 3 3
5000
30 3 3 3 3

7 1 .0 (2.79)

Type KBU 812 KBU 816


A 155 195
B

B 198 243
E

C/C1 34/58 64/79


D 80 80
E 120 160
3 6.15 (1 .4 2)

Primary conductor 80 × 160mm


1 76 .0 (6 .9 2)
Round conductor Ø 80mm
Weight 1.320-3.980kg (2.91-8.77lbs)
1,000A-1,500A = FS 5
Security factor
C

1,600A-5,000A = FS 10
DIN rail mounting Not available
Sealed shutter Not available

8 www.deif.com
Current transformers Accessories for DCT

Test certificate
On request, we can provide you with a test certificate for a specific current transformer along with the CT. Please inform us when placing your order.

Sealed shutter
On request, we can supply a transparent plastic cover. The cover seals the connections on the CT in a way that leaves the type label visible. Please
check availability on each individual data sheet.

Excitation curve
On request, we can provide you with an excitation curve for a specific current transformer along with the CT. Please inform us when placing your order.

Optional frequency
Frequency range for a standard CT is 50-60Hz. On request, we can provide you with a frequency range from 16 2/3 – 400Hz. Please inform us when
placing your order.

Cast resin
Cast resin is standard for all CT’s with a nominal current >4,000A. On request, all CT’s with a nominal current <4,000A can be produced with cast
resin. Please inform us when placing your order. The min. and max. weight specification for each type refers to standard versions. The specification is
different if cast resin is ordered for CT’s <4,000A.

Mounting
Foot angle for screw mounting and busbar mounting screws with isolating protection caps are supplied along with the CT. DIN-rail mounting for tubes,
plug-ins and protection transformers is available on request for certain CT types. Please check availability on each individual data sheet.

www.deif.com 9