Design a rectangular combined footing with a central beam for supporting two columns
400x400 mm in size to carry a load of 1000kN each. Center to center distance between the
columns is 3.5m. The projection of the footing on either side of the column with respect to
center is 1m. Safe bearing capacity of the soil can be taken as 190kN/m2. Use M20 concrete
and Fe-415 steel.
Solution: Data
fck = 20Nlmm2,
fy= 415mm2,
f b (SBC)= l90 kN/m2,
Column A = 400 mm x 400 mm,
Column B = 400 mm x 400 mm,
c/c spacing of columns = 3.5,
PA = 1000 kN and PB = 1000 kN
Required: To design combined footing with central beam joining the two columns.
Ultimate loads
PuA= 1.5 x 1000 = 1500 kN, PuB = 1.5 x 1000 = 1500 kN
For uniform pressure distribution the C.G. of the footing should coincide with the C.G. of
column loads. As the footing and columns loads are symmetrical, this condition is satisfied.
15
1000 kN 1000 kN
1m 3.5 m 1m
p=173.16 kN/m2
(safe)
Design of slab:
Intensity of Upward pressure = p =173.16 kN/m2
Consider one meter width of the slab (b=1m)
Load per m run of slab at ultimate = 173.16 x 1 = 173.16 kN/m
Cantilever projection of the slab (For smaller column) =1050 - 400/2 = 850mm
Maximum ultimate moment = 173.16 x 0.8502/2 = 62.55 kN-m. (Working condition)
1m
p=173.16
kN/m2
For M20 and Fe 415, Q u max = 2.76 N/mm2
Required effective depth = √ (62.15 x1.5 x 106/(2.76 x 1000)) = 184.28 mm
Since the slab is in contact with the soil clear cover of 50 mm is assumed.
Using 20 mm diameter bars, effective cover =20/2 +50 say 75 mm
Required total depth = 184.28 + 75 = 259.4 mm. However provide 300 mm from shear
consideration as well. Provided effective depth = d = 300-75 = 225 mm
To find steel
Mu/bd2 =1.5 x 62.15 x106/1000 x 2252 = 1.84 2.76, URS
Pt=0.584 %
16
Ast = 1314 mm2
Use #20 mm diameter bar at spacing = 1000 x 314 / 1314 =238.96 mm say 230 mm c/c
Area provided =1000 x 314 / 230 = 1365 mm2. Hence safe. This steel is required for the entire
length of the footing.
Transverse reinforcement
Required A st = 0.12 bD / 100 = 0.12 x 1000 x 400/100 = 480mm2
Using 10 mm bars, spacing = 1000 x 79 / 480 = 164.58 mm
Provide distribution steel of #10 mm at 160 mm c/c
17
Point of zero shear is at the center of footing at L/2, i.e., at E
Maximum B.M. occurs at E
ME = 363.64 x 2.752 / 2 - 1000 (2.75 - 1) = -375 kN.m
18
Check the depth for Two-way Shear:
The column B can punch through the footing only if it shears against the depth of the beam along its
two opposite edges, and along the depth of the slab on the remaining two edges. The critical section
for two-way shear is taken at distance d/2 (i.e. 680/2 mm) from the face of the column. Therefore, the
critical section will be taken at a distance half the effective depth of the slab (ds/2) on the other side as
shown in Fig.
1000 kN 1000 kN
363.64 kN/m
MC=375 kN-m
0.3 - 0.3
V2=636.36 kN
V4=363.63 kN
+ -
_
+
V1=363.63 kN SFD
V3=636.36 kN
19
0.85m
5500 mm
db/2
400
D+db
Area of Reinforcement
Cantilever portion BD and AC
Length of cantilever from the face of column = 0.8 m.
Ultimate moment at the face of column = 363.64x1.5 x 0.82 / 2 = 177.53 kN-m
Mumax = 2.76 x 400 x 7252 x 10 -6 = 580.29 kN.m >177.53 kN-m
Therefore Section is singly reinforced.
20
Pt=0.248%, A st =719.2 mm2
Provide 4 - 16 mm at bottom face, Area provided = 804 mm2, pt=0.278%
Ld = 47x16 =752 mm
Curtailment: All bottom bars will be continued up to the end of cantilever for both columns. If
required two bottom bars of 2-16mm will be curtailed at a distance d (= 725 mm) from the point
of contra flexure in the portion BE as shown in figure.
Curtailment: Curtailment can be done as explained in the previous problem. However extend
all bars up to a distance ‘d’ from the point of contra flexure i.e up to 225 mm from the outer
faces of the columns. Extend 2-16mm only up to the end of the footing.
21
Steel at this section is 4 – 16 mm, Area provided = 804 mm2, pt=0.278%
τc =0.38N/mm2 (Table IS:456-2000). No shear steel is needed.
Provide minimum steel.
Using 12 mm diameter 2- legged stirrups,
Spacing = 0.87 x 415 x (2 x 113) /(0.4x400) =509.9 mm say 300 mm c/c
400x400 400x400
1 m 3.5 m 1m
Side face
2-#16 4-#25 + 2-#16 2-#16 2-#12
4-#16
2-#16
22