2. DEFINITION
RCD
Residual current:
Vector sum of the instantaneous values of current flowing in the
main circuit of an RCD.
3. STANDARDS & REFERENCES
4. ENVIRONMENTAL CONDITIONS
5. GENERAL CONSIDERATIONS
6. SELECTION of RCDs
6.1 Types of RCD
21-22 July 2011, KLCC
6. SELECTION of RCDs
6.2 Rated Residual Tripping Current /sensitivity (I∆n)
21-22 July 2011, KLCC
3 Dangerous
level
No harmful 2
effects
8. TRIPPING of RCDs
8.1 Unwanted tripping 21-22 July 2011, KLCC
G Any value Any value 0.3 0.15 0.04 0.04 Maximum break times
100ms
130ms
200ms
300ms
400ms
500ms
Overlap
Overlap = No discrimination
Gap
Gap = Discrimination
During the operation of SPD, large surge currents may flow to earth as a
result of limiting transient over-voltages in the installation.
In the particular case when an SPD is connected downstream of an
RCD, the resultant surge current to earth will be seen by the RCD as a
residual current. In this situation, the RCD can trip.
SPD 1 SPD 2
8.2 Minimizing Unwanted tripping
21-22 July 2011, KLCC
Calculation of the total leakage current from different appliances does not
follow an arithmetic sum and needs to be corrected by a factor of 0.7/0.8.
8.2 Minimizing Unwanted tripping
Impact of standing leakage current 21-22 July 2011, KLCC
Hints:
Each computer has 2 mA standing leakage current.
Factor = 1
8.2 Minimizing Unwanted tripping
21-22 July 2011, KLCC
Impact of harmonics and high frequency leakage current
High frequency leakage currents can be produced by particular
equipment, such as electronic ballasts, frequency inverters, etc.
2. INDISCRIMINATE TRIPPING
3. CONTACTS MELTED/BURNT
4. NO TRIPPING
• INSENSITIVE (Numb)
• LOW VOLTAGE (only for test button)
• DIFFERENT WAVEFORM
10. RCCB – THE SOLUTIONS (summary)
1. NUISANCE TRIPPING 21-22 July 2011, KLCC
a. Due to surges
a. Install an SPD before the RCCB
b. Choose RCCB with higher surge immunity (HI-type or S-type)
c. Install an auto-reset device
100A
40A 63A
40A 63A