Product description High-voltage pole
A new generation of FSK type breakers has
been developed to address the railway AC
market for outdoor application. As result of a
continuous improvement of former products
dedicated to the same application range, this
product line is based on proven technology
components and uses vacuum interrupting
technology.
This technology is well suited for railway The space between the insulator and
application where the operating conditions
vacuum interrupter ( ) is filled in with 0.5
are specially demanding.
bar pressure dry nitrogen N2 (or SF6 gas on
request).
3
The magnetic driven Block diagram
operating mechanism
The magnetic actuator is an ultra-modern
concept for operating mechanism
construction; storing and monitoring its
energy electrically. The result is a completely
maintenance-free drive system, which can
confidently be expected to have even longer
life times than its mechanical predecessors.
4
The logic of the processing unit takes
The control board account of priority of OFF commands and
integrates anti-pumping and self-monitoring
features.
The control board consists of two main
elements: Inputs and outputs
The power supply Several digital inputs control the circuit
The control unit breaker. Two “Off-switching” inputs are
available as well as one “Closing lock-out”
Power Supply input.
Processing unit
5
The capacitor bank Self monitoring
The capacitor stores the electrical energy A watchdog monitors if the programmable
needed for a complete autoreclosing cycle logic array is working. Additional internal
but also ensures power supply to the conditions are monitored:
electronics. The energy content is sufficient
for a buffer time of 200 s on failure of the Availability of the internal voltage
auxiliary power. Position of the end position sensors
(XOR logic)
After an autoreclosing cycle, the recharge of Voltage level of the capacitor
capacitor bank requires less than 100 W
(average value over the charging time) for If these four conditions are fulfilled, the
only a few seconds. “Ready” LED is shining, the output contact
“Ready” is closed and the output contact
The external power consumption is very low “Not Ready” is open.
when the breaker is in the “On” or “Off”
position.
The control box
End position sensors The control box is a small stainless cabinet
housing the electronic board, the capacitor,
the heating resistance, local push buttons
and optional voltage free NO/ NC contacts.
6
Technical specifications of the high voltage pole
Type designation FSK 1020 or FSK 1025
Ratings
Rated voltage 27.5 kV
Rated continuous current 1'
250 A 2'
000 A 2'
500 A
Rated frequency 50 Hz
Number of phase 1 or 2
Opening time ≤ 40 ms
Closing time ≤ 60 ms
Rated operating sequences O - 0.3 s - CO – 180 s - CO
CO - 10 s - CO
Electrical endurance 1)
• at rated current 20'
000
• at rated short circuit current 50
1)
According to vacuum interrupter datasheet
Magnetic actuator
Mechanical endurance 100’000
7
Characteristics of the control board
Power supply voltage range
Service operating voltage, low voltage range 20 … 60 V AC/DC
Service operating voltage, high voltage range 80 … 264 V AC/DC
Consumption
In normal position 4 W .. 10 W
During a charging process approx. 100 W
Recharging time
1)
Capacitor bank recharging time at minimum voltage ≤3s
1)
Capacitor bank recharging time at maximum voltage ≤2s
1)
Charging time for capacitor bank of 0.1 F
Binary inputs
Electrical isolation from the electronics 2 kV AC
Electrical isolation between the inputs 2 kV AC
Maximum input voltage 260 V AC/DC
Response range 48 to 250 V AC/DC
Current consumption ≤ 2 mA at 250V AC/DC
Protection against voltage surges Yes
Binary outputs
Electrical isolation from the electronics 2 kV AC
Electrical isolation between the inputs 2 kV AC
Maximum switching voltage 400 V DC/ 280 V AC
Maximum switching current 0.5 A AC/DC
Accessories
Five-digit operation counter 1
Electrical opening and closing push button 1+1
Mechanical indicator “Close”/“Open” 1
Electrical indicator “Ready” 1
Local/ Remote Switch (option) 1
Service conditions
Operating temperature range - 25 / +50° C
Altitude ≤ 1000 m
8
Type tests reports
Copies of following type tests reports are available on request:
• Insulation voltage
• Short-circuit breaking and making current
• Short-circuit withstand current and peak withstand current
• Capacitive current
• Temperature rise
• Measurement of the main circuit resistance
• Mechanical endurance test
Routine tests
The following routine tests are carried out in the seller’s factory:
• Construction inspection
• Mechanical operation and mechanical data test
• Measurement of the main circuit resistance
• Power frequency withstand voltage of the main, auxiliary and control circuit
Technical documentation
For each order, the following technical documentation (in English) will be provided in 2
copies:
9
Outline drawings