DOCUMENT No.

`-' A ^ft ENGINEERS ENGINEERING DESIGN BAS'


STRUCTURAL & ARCHITECT^..<AL 6987-00-16 -48-DB01
Eff ^C „ems ^ INDIA LIMITED
imzn ?E VlTh A 604 o, 10010 Jncenwn3 Rev. 1
Page 1 of 40

ENGINEERING DESIGN BASIS


DESIGN PHILOSOPHY

6.6 STRUCTURAL & ARCHITECTURAL

kLV,
I - a, 4'I E VJ t-C1 Lt ^sQ

18.11.2009 REISSUED FOR ENGINEERING


DS )Pis

0 19.06.2009 ISSUED FOR ENGINEERING PM/AG SCISD VK

A 02.03.2009 ISSUED FOR CLIENT'S COMMENTS/APPROVAL PM/AG SC/SD VK


Rev. Prepared Checked Approved
Date Purpose
No by by by
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 2 of 40

PART – I : STRUCTURAL
(FROM PAGE 3 TO 20)

PART –II : ARCHITECTURAL


(FROM PAGE 21 TO 40)

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 3 of 40

PART–I: STRUCTURAL
TABLE OF CONTENTS

S.No. Title Page No.

1.0 REFERENCED STANDARDS & PUBLICATIONS..……………………….4

2.0 GENERAL.………………………………………….……….…………….……6

3.0 MATERIALS OF CONSTRUCTION….…………………….……………..…6

4.0 DESIGN LOADS………………..….………………………… ……… …. 6

5.0 SOIL AND HYDROSTATIC PRESSURE….……….. …………………….. 9

6.0 FOUNDATION DESIGN……………………………………………………….10

7.0 FLOORING DETAILS FOR BUILDINGS………………………..………… 11

8.0 SPECIAL CONSIDERATIONS FOR RCC STRUCTURES….……….. … 11

9.0 SPECIAL CONSIDERATIONS FOR STEEL STRUCTURES… ………… 14

10.0 SPECIAL CONSIDERATIONS FOR MASONRY WORKS…… ……….... 17

11.0 DESIGN REQUIREMENTS FOR SPECIFIC APPLICATIONS…………… 17

11.1 PIPE RACK & PIPE SUPPORTS………….………………………. 17

11.2 MACHINE FOUNDATIONS.……………………………….……..… 17

12.0 SPECIFIC REQUIREMENT…………………………………………………. 18

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 4 of 40

1.0 REFERENCED STANDARDS & PUBLICATIONS


(BIS codes of Practice shall be applicable)

S.No. CODES

1. Code of practice for plain & reinforced concrete IS: 456


2. Code of practice for general construction in steel IS: 800
3. Code of practice for use of cold formed light gauge steel
structural members in general building construction IS:801
4. Code of practice for use of structural steel in overhead
transmission line towers IS:802
5. Code of practice for use of steel tubes in general
building construction IS:806
6. Indian Standard on Dimension s of Hot Rolled Steel
Beams, Columns, Channel and Angles IS: 808
7. Scheme of Symbols for Welding IS: 813
8. Covered electrodes for manual metal arc welding
of carbon and carbon manganese steel IS:814
9. Code of practice for use of metal arc welding for general
construction IS:816
10. Code of practice for design loads IS: 875
11. Common burnt clay building bricks-specification IS: 1077

12. Steel tubes for structural purposes-specifications IS: 1161


13. Technical Supply Conditions for Threaded Steel
Fasteners IS: 1367
14. Code of practice for construction of stone masonry IS: 1597
15. Fillers for expansion joints IS: 1838
16. Criteria for earthquake resistant design of IS: 1893
Structures (Part -1& 4)

17. Code of practice for design & construction of IS: 1904


Foundations in soils
18. Code of practice for structural use of unreinforced
masonry IS:1905
19. Steel for General Structural Purposes- Specification. IS: 2062
20. Recommended practice for hot dipped galvanising
on iron and steel IS:2629
21. Methods for testing uniformity of coating of
zinc coated articles IS:2633
22. Code of practice for Design and construction of Pile
foundations IS:2911
23. Code of practice for design & construction of
raft foundations IS:2950
24. Code of practice for design & construction of
machine foundations IS:2974
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 5 of 40

25. Code of practice for concrete structures for


storage of liquids IS:3370
26. Steel Chequered Plates – Specification IS: 3502
27. Code of practice for design and construction of foundation
for transmission line towers and poles IS:4091
28. Code of practice for earthquake resistant design
and construction of buildings IS:4326

29. Criteria for blast resistant design of


structures for explosions above ground IS:4991
30. Criteria for design of RCC chimneys IS: 4998
31. Method of test for determination of dynamic property
of soil IS: 5249
32. Code of practice for anti-termite measures in buildings IS: 6313
33. Code of practice for determination of bearing capacity
of shallow foundations IS: 6403
34. Code of practice for design & construction of steel
chimney IS:6533
35. Method for determination of mass of zinc coating IS: 6745
36. Code of practice for calculation of settlement of IS: 8009
foundations
37. Chlorpyrifos emulsifiable concentrates IS: 8944
38. Recommendations for metal arc welding of carbon
and carbon manganese steel IS:9595
39. Two parts polysulphide based sealants IS: 12118
40. Indian Standard on Hot Rolled Parallel Flanged Steel
sections for Beams, Columns and Bearing Piles IS:12778
41. Pulverized fuel ash-lime bricks-specification IS: 12894
42. Code of practice for ductile detailing of
reinforced concrete structures subjected
to seismic forces IS:13920
43. Control Room Safety
(a publication of Oil Industry Safety Directorate) OISD-STD-163
44. Fire Proofing in Oil and Gas Industry
(a publication of Oil Industry Safety Directorate) OISD-STD-164
45. Fire Protection System for Electrical Installations OISD-STD-173

Note The above list is suggestive and not exhaustive. Apart from these basic codes any
other related codes shall also be followed wherever required.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 6 of 40

2.0 GENERAL

2.1 This specification defines the design criteria and loads that shall be taken in to
account for the design of all industrial plant and non-plant structures and buildings for
a pipeline project. The design considerations given hereunder establish the minimum
basic requirements of reinforced concrete structures, structural steel works and
masonry structures. However, all structures shall be designed for the satisfactory
performance of the functions for which the same are to be constructed.

3.0 MATERIALS OF CONSTRUCTION

3.1 All shed type structures such as Compressor house, Ware house etc. shall be in
structural steel.

3.2 Pipe supports, cross over, access way, service platform shall completely be of steel
construction. All other buildings shall be as per Architectural Design Basis.

3.3 All buildings shall be of RCC Frame type construction with brick masonry walls.

3.4 Boundary wall shall be of Stone masonry.

3.5 Bricks for masonry works shall be of the class conforming to IS: 1077 which is locally
available.

4.0 DESIGN LOADS

4.1 These loadings shall be applicable to all structures irrespective of the material
employed for construction.

a. DEAD LOADS

The weight of all permanent construction including walls, fire proofing, floors, roofs,
partitions, stairways and fixed service and other equipments excluding their content.

b. EQUIPMENT LOADS

The empty weight of process equipment including all fixtures, platforms, ladders and
attached piping but excluding contents shall be considered. If piping weight is not
indicated separately or included in the weight of the equipment, the same shall be
taken as 10% of the weight of the equipment.

For horizontal equipments the weight on two supports shall be calculated based on
the total weight and C.G. of the equipment.

c. LIVE LOADS

Live loads shall, in general, be as per IS: 875. However, the following minimum live
loads shall be considered in the design of structures to account for maintenance and
erection as well.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 7 of 40

i. Process Building/Technological Structure (Open/Enclosed type)

Operating area - 5.0 kN/m2


(including 2.0 kN/m2 for
Piping)

Maintenance area - 7.5 kN/m2

ii. Compressor House/TG house

Operating area - 7.5 kN/m2

Maintenance area - 7.5 kN/m2 (or as specified


by machine vendor)

iii. Service Platform

Vessel/Tower - 3.0 kN/m2

Isolated platform - 2.5 kN/m2


(for valve operation)

Access way - 2.5 kN/m2

Cross over - 2.0 kN/m2

iv. Substation/Control Room

Panel floor - 10.0 kN/m2

Partitions - 1.0 kN/m2

v. Office building

Office area - 3.0 kN/m2

Lobby - 5.0 kN/m2

Exit way - 5.0 kN/m2

Partitions - 1.0 kN/m2

vi. Laboratory

Upper floors - 4.0 kN/m2

vii. Staircase

Office - 5.0 kN/m2

Substation/Control Room - 3.0 kN/m2

Laboratory - 3.0 kN/m2

Service platform - 2.5 kN/m2


Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
u Z ENGINEERS ENGINEERING DESIGN " 3lS DOCUMENT No.
ai lc^'6 INDIA LIMITED STRUCTURAL & ARCHIT-uTURAL 6987-00-I 6 -48-D B 01
Rev. 1
Page 8 of 40

vi. Walkway

Gantry girder - 3.0 kN/m2

Live load on various types of roofs shall be as per the requirements given in IS: 875.

d. OPERATING LOADS

Operating loads shall include the maximum designed equipment inventory in the
operating cycle of the plant.

e. WIND LOADS

Wind loads shall generally be as per IS: 875. The basic wind speed for all the
stations/terminals shall be taken as 44 m/sec.

Values of coefficients k1, k2, k3 shall be as:

kf (Probability factor, risk coefficient) = 1.00 for permanent structures and


= 0.90 for for temporary structures
= 0.70 for barricading structures/ Boundary
Wall

k2 (Terrain, height & structure size factor) = this shall be taken for relevant
class of structure with category 2
terrain w.r.t. actual height of the
structure

k3 (Topography factor) As per site

The design life span of all structures shall be taken as 50 years. Temporary
structures shall be designed for a design life span of 25 years. Design life span for
boundary wall/barricading structure shall be as per IS: 875.

To account for surface area of piping , platforms and other attachments fixed to
the equipment the surface area of the equipment ( vessel/column ) exposed to
wind shall be increased by 20% or as specified in the mechanical data sheet of
the equipment.

f. SEISMIC LOADS

Seismic forces shall be as per site specific seismic spectra 6987-00-16-54-DB-01 for
Seismic Zone Ill.

g. IMPACT & VIBRATORY LOADS

Structures subjected to impact or vibratory loads shall be designed as per the


provisions of IS: 875 & IS: 2974.
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 9 of 40

h. BLAST FORCES

Blast resistant control room or any other specified structure subjected to blast forces
generated due to accidental blasts from hydrocarbon ignitions shall be designed to
withstand all such forces. Design blast loads and blast resistant construction shall
conform to OISD-STD-163.

i. BUNDLE PULL

Bundle pull for different types of Exchangers shall be taken for design of their
supports unless it is made clear that bundle extractor is to be used.

Total Bundle Pull shall be considered on fixed pedestal alone.

j. OTHER LOADS

Apart from the specified live loads, any other equipment load or possible overloading
during construction/hydro-test/ maintenance/erection shall also be considered in the
design. Under hydro test condition the wind force shall be taken as 25% of normal
loading.

Design of all structures shall also consider any other relevant and consequential
load/stress imparted to the structure.

All liquid retaining/storage structures shall be designed assuming liquid up to the full
height of wall irrespective of provision of any over flow arrangement. Pressure relief
valves or similar pressure relieving devices shall not be made in underground water
retaining/storage RCC structures.

All buildings/structures shall be designed to resist the worst combination of the above
loads. However wind loads shall not be considered in combination with loads due to
maintenance cranes in workshop, comp. House etc.

5.0 SOIL AND HYDROSTATIC PRESSURE

Pressure on basement walls: - In design of basement walls and similar


approximately vertical structure below grade, provision shall be made for the lateral
pressure of adjacent soil. Due allowance shall be made for possible surcharge from
fixed or moving loads. When a portion or whole of adjacent soil is below free water
surface, computations shall be based on the weight of the soil diminished by
buoyancy (submerged weight of soil) plus full hydrostatic pressure.

Uplift on floor: - In the design of basement floor and a similar approximately


horizontal construction below grade, the upward pressure of water, if any, shall be
taken as the full hydrostatic pressure applied over the entire area. The Hydrostatic
head shall be measured from the underside of construction. Factor of safety against
uplift shall be 1.2. For the purpose of calculating downward load due to over burden;
the weight for the same shall be calculated for volume over projected plan area only.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 10 of 40

6.0 FOUNDATION DESIGN

6.1 Minimum Requirements

Foundation design shall be as per Geo-Technical Data as specified in bid document.

6.1.1 Minimum depth of foundation for all structures shall be as per Geo-Technical Data.
Factors of safety against overturning and sliding shall be as per values given in
Table-1. Component of soil backfill weight over foundation slab shall be appropriately
covered as foundation dead load. For stability checks the weight of soil as
overburden shall be as per Table-1.

6.1.2 The design ground water level shall be as per the Geo-Technical Data and the
hydrostatic pressure shall be adequately accounted for in design.

6.1.3 Allowable net bearing capacity of soil shall be based on the following settlement
criteria for dead plus imposed load conditions:

- Foundations in unit areas, utility areas


and foundations for Plant buildings. 25mm settlement.

- Non Plant buildings. 40mm settlement.

- Raft Foundations 40mm settlement

For transient loadings, e.g. wind/seismic, settlement shall not be the design criteria
and the SBC (safe bearing capacity) based on shear criteria shall be considered.

6.1.4 Permissible increase in SBC/Pile capacities (for compressive, shear and


uplift/tension) shall be as per the Geo-Technical Data.

6.1.5 Under blast (due to hydrocarbon explosion load combinations the design bearing
pressure of soil shall not exceed 2 (two) times the allowable static bearing pressure of
soil. Pile capacity shall be similarly increased in blast condition to 1.5 times the
permissible capacity under compression, tension and shear modes.

6.1.6 Grade of concrete to be used shall in general be as per the philosophy adopted for
the entire project However, minimum cement content, type of cement & any remedial
actions required for foundation due to aggressiveness of sub soil water shall be as
per the Geo-Technical Data.

6.2 Anti Termite Treatment

No anti termite treatment shall be provided inside the unit areas. All buildings shall be
provided with anti termite treatment as per IS: 8944 and IS: 6313.

6.3 Minimum Cover to Foundation Bolts

Minimum distance from the centerline of foundation/anchor bolt to edge of pedestal


shall be the maximum of the following:

i) Clear distance from the edge of the base plate/base frame to the outer edge
of the pedestal shall be minimum 50mm.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 11 of 40

ii) Clear distance from the face of pocket to the outer edge of the pedestal shall
be 100mm.

iii) Clear distance from the edge of the sleeve or anchor plate to the edge of
pedestal shall be 100mm.

6.4 Height of Pedestals

The minimum projection of pedestals supporting any steel structure/stanchion bases


shall be 300/150mm above the high point of pavement/ finished grade/finished floor
level whichever is higher, for outdoor and indoor located pedestals respectively. The
maximum projection of pedestals for staircase/ladder shall be 200mm.

6.5 Grouting & Minimum Grout Thickness

The minimum thickness of grout shall be 25 mm and not more than 50mm.

All anchor bolt sleeves/pockets and spaces under column bases, shoe plates etc.
shall be grouted with free flow, non shrink (premix type) grout with 28-day minimum
cube crushing strength of 40N/mm2. Ordinary cement sand (1:2) grout shall only be
used under the base plates of cross-overs, short pipe supports (not exceeding 1.5 m
height) and small operating platforms (not exceeding 2 m height) not supporting any
equipment.

Grouting requirement for machines and equipments are not covered here. The same
shall be governed by equipment vendor’s requirement.

7.0 FLOORING DETAILS FOR BUILDINGS & SHEDS

The specifications given hereunder shall be adopted for the non-suspended ground
floor slabs for buildings & sheds as categorised in Table-2 only.

For outdoor pavements, Design basis of Gen. Civil shall be referred.

8.0 SPECIAL CONSIDERATIONS FOR RCC STRUCTURES

8.1 General/Design Methods

a) All buildings, structures, foundations, machine/equipment foundations, liquid


retaining/storage structures, trenches, pits etc. shall be of RCC and designed
based on the following IS Codes (latest revision with all amendments issued there
to) in general and other relevant IS Codes applicable: IS: 456, 875, 1893, 1904,
2911, 2950, 2974, 3370, 4091, 4326, 4995, 4991, 4998, 5249, 6403, 8009,
13920.

b) Only limit state method as per IS: 456 shall be followed in the design unless
otherwise specified elsewhere in this document for special structures.

c) Where the specified design depth of groundwater table so warrants all


underground pits, tunnels, basements etc. (excluding appurtenances of storm
water/effluent collection system, cable trench, pipe trench) shall be of leak-proof
RCC construction using waterproofing compounds.

d) All liquid retaining/storage RCC structures shall be leak-proof and designed as


uncracked section as per IS: 3370. However, the parts of such structures not
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 12 of 40

coming in contact with the liquid shall be designed according to IS:456 except ribs
of beams of suspended floor slabs & counter forts of walls (located on the side
remote from the liquid) and roof which shall be designed as uncracked section.
No increase in permissible stresses in concrete and reinforcement shall be made
under wind or seismic conditions for such structures.

e) The walls and base slabs of liquid retaining/storage structures shall be provided
with reinforcement on both faces for thickness greater than or equal to 150mm. In
all liquid retaining structures, PVC water bars (minimum size 230mm wide, 5mm
thick) shall be provided at each construction joint.

f) Hot/cold water basin and other primary framing members of Cooling towers or
similar liquid retaining structures which remain constantly in contact with water
(stored/sprayed) shall be designed as uncracked sections.

8.2 REINFORCEMENT BARS

High Strength Deformed TMT steel bars of grade Fe 500 (with corrosion inhibitors in
concrete) conforming to IS: 1786 shall be used for all structures.

8.3 CONCRETE

Minimum grade of reinforced cement concrete to be used for different structures and
foundations shall be M30. From Durability considerations the minimum cement
content and maximum water-cement ratio shall be as under. However, the maximum
cement content shall not exceed 450 kg/m3.

For all stations/terminals

Type of Plain concrete Reinforced concrete Exposure


cement (M20) (M30) Condition
Minimum Maximum Minimum Maximum
cement water-cement cement water-
content ratio content cement ratio
(kg/m3) (kg/m3)

OPC/Fly ash
based 250 0.50 320 0.45 Severe
PPC/SRC(*)

OPC: Ordinary Portland cement, PPC: Portland Pozzalana Cement

*SRC: Sulphate Resistant Cement (if required as per soil recommendation for
respective site)

75mm thick lean concrete of grade 1:5:10 shall be provided under all RCC
foundations except under base slab of liquid retaining structures where 100 thick
concrete of mix 1:3:6 shall be used. The lean concrete shall extend 50mm beyond
the foundation for normal foundations and 75mm under liquid retaining structures.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 13 of 40

Plain Cement Concrete (PCC) of grade M15 of minimum 150mm thickness shall be
provided under all masonry wall foundations.

Plain cement concrete of grade M20 of minimum 40mm thickness shall be provided
as damp proof course at plinth level of all masonry walls and to be coated with 3mm
thick bitumen emulsion.

8.4 MINIMUM COVER TO MAIN REINFORCEMENT

The following minimum clear cover shall be provided for RCC works.

- Slab (roof & floor), Canopy, 45mm


Cantilever, Waist slab
- Beam (roof, floor & tie),lintel 45mm
- Column, Pedestal 50mm
- Retaining Wall, Basement and Pit Wall.

a) Face in contact with earth 50mm


b) Free face 45mm

- Liquid retaining structure

a) Face in contact with liquid 45mm


b) Face away from liquid 50mm
but in contact with earth

c) Free face 45mm

- Foundation slab, base slab, plinth beam 50mm


- Pile Cap

a) Bottom face 100mm


b) Top face 50mm

8.5 MINIMUM THICKNESS OF STRUCTURAL CONCRETE ELEMENTS

The following minimum thickness shall be followed:

- Footings (All types, with or without beams) 300mm


(Note: Tapered footings shall not have thickness less than 150mm at
the edges. Minimum average thickness shall not be less than 300mm)

- Pile Cap 500mm

- Basement

a) Walls 150mm

b) Base slab with beams 200mm

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 14 of 40

c) Base slab without beams 300mm

- Slab thickness in Raft foundations with beam & slab construction 150mm

- Floor/Roof Slab, Walkway, Canopy Slab 120mm

- Cable/Pipe Trench/Launder Walls & Base Slab 125mm

- Parapet 75mm

- Louvre / Fin. 100mm

- Precast Trench Cover/Precast Floor Slab 125mm

- Louvre (in contact with liquid) 125mm

- Liquid Retaining / Leak proof Structure

a) Walls 150mm

b) Base slab with beams 200mm

c) Base slab without beams 300mm

- Underground Pit

a) Walls 150mm

b) Base slab with beams 200mm

c) Base slab without beams 300mm

- Blast resistant construction AS/OISD-STD-163

9.0 SPECIAL CONSIDERATIONS FOR STEEL STRUCTURES

9.1 General/design methods

a) Design, fabrication and erection of the above work shall be carried out in accordance
with the following IS Codes as applicable to the specific structures, viz. IS: 800, 801,
802, 806, 814, 816, 875, 1893, 9178, 9595, 6533, etc. Basic consideration of
structural frame work shall primarily be stability, ease of fabrication/erection and
overall economy satisfying relevant Indian Standard Codes of Practice. Simple and
fully rigid design as per IS: 800 shall be used. Where fully rigid joints are adopted
they shall generally be confined to the major axis of the column member

b) Structural elements continuously exposed to temperatures above 2000 C shall be


designed for reduced stress as per IS:800.

c) Crane gantry girders shall generally be of welded construction and of single span
length. Chequered plate shall be used for gantry girder walkway flooring.

d) Steel staircases for main approaches to operating platforms shall have channels
provided as stringers with minimum clear width of 750mm and slope of app. 41
degree. The vertical height between successive landings shall not be less than 2.6m
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 15 of 40

nor exceed 4.0 meters. Treads shall be minimum 230mm wide made of grating (with
suitable nosing) spaced equally so as to restrict the rise to maximum 200mm.

e) Hand rails, 1000mm high, shall be provided to all walkways, platforms, staircases.
Toe plate (100mmx5mm) shall be provided for all hand railing (except for staircases).
Spacing of uprights shall be 1500mm (maximum). Two types of hand railing shall be
provided.

i) For Tech. structures, walkways, platforms (except platform around/on


circular/horizontal vessels), and staircases: Top rail, mid-rail and upright shall
be 32mm dia (NB) galvanised MS tubes.

ii) For platforms around circular vessels: Top rail shall be 32mm dia (NB)
galvanised MS tubes but mid rail and upright shall be of structural steel.

f) Electro-forged hot dip galvanised MS Gratings shall be minimum 25 deep. The


maximum size of voids in the grating shall be limited to 30mm x 100mm.The minimum
thickness of galvanising shall be 120 microns.

g) Welded connections shall be adopted as far as practicable except for the removable
members where bolted connections are required viz. (Galvanised) electrical
switchyard structures and transmission towers. Structural connections shall have
minimum two bolts of 16mm dia. unless otherwise limited by the size of members.

h) Minimum two nuts shall be used for all anchor bolts except for ladder, stair and
handrail.

i) Structural section shall be conforming to IS:808 and/or IS:12778. RHS/SHS section


conforming to IS:4923 shall be used. CHS section shall be conforming to IS:1161.

9.2 GRADE OF STEEL

Structural steel shall be of yield stress of 250 MPa conforming to grade A of IS: 2062.
RHS/SHS/CHS shall conform to Yst 310/240.

9.3 FIREPROOFING OF STEEL STRUCTURES

Fire proofing of steel structures shall be by concrete (for structures supporting


transfer line & two phase flow line above 6” diameter) and vermiculite (for other
structures), wherever required as per OISD-STD-164 and shall be done for 2 hours
fire rating as per EIL specification or as required as per TAC rules. Guniting method
of fire proofing shall be applied for equipment skirts

9.4 Limiting permissible Stresses

- Permissible stresses in structural members shall be as specified in:

IS: 800 Hot rolled sections (excluding transmission towers and


switchyard structures).
IS: 801 Cold formed light gauge sections
IS: 802 Code of practice for use of structural steel in overhead
Transmission line towers & switchyard structures
IS: 806 Tubular structures

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 16 of 40

- Permissible stresses in bolts shall be as specified in:

IS: 800 Hot rolled sections


IS: 801 Cold formed light gauge sections.
IS: 802 Transmission towers & switchyard structures.

- Permissible stresses in welds shall be as specified in:

IS: 801 Cold formed light gauge sections.


IS: 816 Metal Arc Welding

9.5 Limiting Deflection

a) The limiting permissible vertical deflection for structural steel members shall
be as specified below:

- Gantry girder for electric overhead crane : L/750


(Capacity up to 50T)
- Gantry girder for electric over head crane : L/1000
(Capacity over 50T)
- Gantry girder for manually operated crane : L/500
- Girder/beam for supporting dynamic
equipment/hoist : L/450
- Grating/Chequered plate
: L/200 or 6mm whichever
is minimum
- Purlins supporting any type of roofing : L/200
material under (dead load+live load)
or (dead load+wind load) conditions
- Other structures/structural components : As specified in
Relevant IS Codes
Where 'L' represents the span.

b) The limiting permissible horizontal deflection for multi storied steel structure/
building including flare stack shall be Height/325.

9.6 Minimum Thickness

The minimum thickness of various structural components (Hot rolled sections) shall
be as given:

a) General Construction:
Trusses, purlins, side girts & bracings 6mm
Columns, beams 7mm
Gussets in trusses & girders

i) upto and including 12m span 8mm


ii) above 12m span 10mm
Stiffeners 8mm
Base plates 10mm
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 17 of 40

Chequered plate 6mm (on plain)


Grating 3mm

Structural members exposed to marked corrosive action shall be increased in


thickness or otherwise suitably protected against corrosion.

The minimum thickness of structural components (except gratings & chequered


plates) which are directly exposed to weather and inaccessible for repainting shall be
8mm.

b) Transmission Towers & Switchyard Structures:

The minimum thickness of various structural components shall be as per IS:


802.

The minimum thickness for rolled beams and channels shall be mean flange
thickness regardless of the web thickness.

The minimum thickness of tubes shall be as specified in IS: 806.

9.7 PAINTING

Painting including shop primer to Structural Steel shall be as per painting


specification attached elsewhere.

10.0 SPECIAL CONSIDERATIONS FOR MASONRY WORKS

10.1 General

Masonry works shall be of the class which is locally available in accordance with
IS: 1077, IS: 1905, IS: 1597, IS: 12894 and other relevant IS Codes as applicable. All
external brick masonry walls shall be of minimum 230mm thickness except for fire
walls.

10.2 Cement Mortar

All masonry work shall be constructed in cement sand mortar 1:6 except half brick
partition walls which shall be constructed in 1:4 cement sand mortar with two
numbers of 6mm diameter MS bars provided at every fourth course properly
anchored with cross walls or pillars.

11.0 DESIGN REQUIREMENTS FOR SPECIFIC APPLICATIONS

11.1 PIPE RACK & PIPE SUPPORTS

Design of pipe rack & pipe supports shall be as per document no. 8-76-0020

11.2 MACHINE FOUNDATIONS

Machine foundations shall satisfy the requirements of IS: 2974 and any other
parameter as per machine vendor.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 18 of 40

12.0 SPECIFIC REQUIREMENT

Maintenance platform below Coolers shall be full RCC platform.

Sand Filling for Ring Wall foundation shall be either by river sand or crushed Stone
Sand.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 19 of 40

TABLE-1

FOUNDATION DESIGN - FACTORS OF SAFETY

Minimum Factor Of Minimum Factor Of


Safety Against Safety Against % Weight Of
Type Of Overturning Sliding Overburden Over
Structure With Wind Without With Without Projected Plan
Or Wind Or Wind Or Wind Or Area Of Footing
Seismic Seismic Seismic Seismic
All Buildings/ 1.5 2.0 1.5 1.5 100
Structures/Eqpts.
in Units
Pipe Rack 1.5 2.0 1.5 1.5 50$
(Offsite)
Flood Light Mast 1.5 - 1.5 - 50$
Retaining Wall 1.5 2.0 1.5 1.75 100
Over Head water 1.5* / 2.0 - 1.5 - 50$
Tank
Flare Supporting 1.5 - 1.5 - 50$
Structure
Blast Resistant 1.5 2.0/1.2# 1.5 1.5/1.5# 100
Structures
* Empty condition
# With blast pressure
$ In case area is paved, overburden shall be based on NGL (for area under
filling) or 600mm below HPP whichever is lower. In case of unpaved area, it
shall be w.r.t. FGL.

Minimum Factor of safety against UPLIFT shall be 1.2 for all structures. (Note: In case
of sumps, lining weight shall not be included)

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 20 of 40

TABLE – 2

FLOORING DETAILS FOR BUILDINGS & SHEDS

Flooring Type
S No Description
I II III
1(a) Sub Earth fill base compacted to 95%
Grade dry density.
1(b) Compacted layer of sand/boulder 200 THK. 200 THK. 150 THK.
packing over thoroughly compacted
Earth fill (in mm)
2(a) Strl Lean concrete 1:5:10 over sand 50 THK. 50 THK. 50 THK.
Grade layer (in mm)
Slab
Strl. non suspended slab in M20 150 THK. 150 THK. 100 THK.
Grade concrete (Reinforced with
8mm dia bars @200 c/c both ways)
over lean concrete.
2(b) R/F placement R/F R/F placed No R/F
placed in two layers required.
centrally at top &
bottom
3 Finish Floor finish As per As per As per
Arch Arch Detail Arch Detail
Detail

Type I: Plant Buildings such as Sub-Stations, Control Rooms, Pump


Houses, Utility Compressor Houses, Parking Areas, Stores,
Porches.

Type II: Ware Houses, Workshops, Cement Godowns, Fire Stations,


Process Compressor Houses.

Type III: Non Plant Buildings (viz. Administration, Laboratory, Canteen,


Time Office, Gate House, Training Centre, Guest House,
Residential buildings).

Notes:
1) Reinforcement steel shall be as per clause 8.2.

2) For Ware Houses & Work shops non suspended ground floor slabs with
above specifications shall be provided using vacuum dewatering concrete
system.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 21 of 40

PART –II : ARCHITECTURAL

CONTENTS

Title Page No.

ENGINEERING DESIGN BASIS

1.0 REFERENCED PUBLICATIONS……………………………….. 22

2.0 DESIGN PHILOSOPHY/ CRITERIA

2.1 ARCHITECTURAL DESIGN…………………………….. 22

2.2 BUILDING REQUIREMENTS…………………………… 22

2.3 BUILDING SERVICES…………………………………… 26

2.4 AESTHETICS………………………………………………27

2.5 STRUCTURAL AND CONSTRUCTION ELEMENTS…27

2.6 BUILDING ELEMENTS………………………………… 27

2.7 SCHEDULE FOR ARCHITECTURAL FINISHES……32

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 22 of 40

ENGINEERING DESIGN BASIS

1.0 REFERENCED PUBLICATIONS

1. National Building Code of India


2. Factory Law
3. Local Municipality or any other Authority’s Bye-laws as applicable.
4. TAC (Tariff Advisory Committee) Rules.
5. Bye-laws of Town & Country Planning Organisation
6. OISD Norms
7. BPE Norms
8. BIS Codes
9. Indian Electricity Rules
10. Any other applicable Law, Rules, Standard as referred in respective clause.

1.1 STANDARD SPECIFICATIONS CODES & PRACTICES

EIL Engineering design incorporates Codes and Standards as referred in the design
philosophy of respective engineering disciplines as well as applicable EIL standards
specifications.

2.0 DESIGN PHILOSOPHY/ CRITERIA

2.1 ARCHITECTURAL DESIGN

Architectural design of the buildings shall be in accordance with this design basis and
references as stated above to meet the functional requirements.

2.2 BUILDING REQUIREMENTS

2.2.1 List of buildings:

Following buildings are envisaged in this project.

2.2.1.1 Non-Plant Buildings

1. Security Barracks and Guard Houses


2. Product Ware House
3. Central Ware House
4. Guest House
5. Construction Office Building
6. Canteen Building
7. Emergency DG House
8. Health Centre
9. Administrative/Training/ Medical centre
10. Central Laboratory Building
11. Polymer Service Building
12. NCU/GCU Service Building
13. Central Workshop
14. Central Warehouse
15. Weigh Bridge
16. Chemical Storage Building
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 23 of 40

17. Gate Houses

The above list of Non Plant Building is subjected to finalization during detail
engineering

Spatial requirement for non-plant buildings. shall be finalized looking into the
functional requirements and its occupancy which shall be governed by Owner’s
specific requirement. Design shall be in accordance with Factory Act, NBC etc.

Requirement of services/utilities such as air conditioning, LAN etc. shall be finalized


as per Owner’s specific requirement.

2.2.1.2 Plant Buildings

1. Main Control Room


2. Satellite Rack Room
3 Sub Stations

The above lists of Plant Buildings are subjected to finalization during detail
engineering.

Spatial requirements of these Plant Buildings shall mainly be decided based on the
equipment/panel layout, activities to be performed in the building and consequent
occupancy pattern. Sizes of various type of spaces shall be decided based on
occupancy/ equipment/Panel layout, clearances, maintenance & safety requirements.
The objective of spatial arrangement shall be to satisfy functional requirements,
physical comfort, and safety regulations as well as aesthetics.

(a) Control Room Buildings & Satellite Rack Rooms for Process Units shall be
designed as per OISD-STD 163, TAC building bye-laws and Factory Act.
Control Room Buildings shall be centrally air-conditioned, single storied
construction, designed to fully meet the Instrumentation, Electrical, HVAC,
safety and other requirements.

Control Room Buildings shall broadly consist of Console Room, Rack Room,
EC/ PLC Room, Computer Room, UPS Room, Battery Room, Operators’
Rooms, Shift-in-Charge Rooms, Supervisor’s Office accommodation,
Instruments Calibration Room, Operators’ Check and Change Room, Toilets
(Ladies & Gents), A.C. Plant/ AHU Rooms, Clean Agent Storage Room etc.

Satellite Rack Rooms shall broadly consist of Rack Room, Room, UPS Room,
Battery Room, A.C. Plant/ AHU Rooms, Clean Agent Storage Room etc.
Operators’ Rooms, Toilets (Ladies & Gents) may be provided if required.

Requirement of Blast resistant design and construction shall be finalized


during detail engineering stage.

(b) Sub-Station buildings shall be designed as per OSID –STD 149; 173;
IEA;IER; TAC building bye-laws, Factory Acts etc. Sub Stations shall be
double storied having Cable Cellar at ground floor or single storied (having
trenches for the cables) as per the Electrical requirements and Electrical
Design Basis. Sub Station Buildings shall broadly consist of Switchgear
Room, Operator’s Room, Battery Room, Other Electrical Panels’ Room,
Pressurization Room etc. as per functional requirements and Electrical design
basis. Toilets shall be provided as per requirement.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 24 of 40

2.2.1.3 Units

1. Process buildings/ sheds of DFCU unit (plant/equipment sheds, analyzer room


etc. As required)
2. Process buildings/ sheds of PGHU unit (plant/equipment sheds, analyzer room
etc. As required)
3. Process buildings/ sheds of BzEU unit (plant/equipment sheds, analyzer room
etc. As required)
4. Process buildings/ sheds of BdEU unit (plant/equipment sheds, analyzer room
etc. As required)
5. Process buildings/ sheds of LLDPE unit (additive house, extruder house, Bagging
& palletization building, catalyst storage, teal house, storages, Analyzer room etc.
As required)
6. Process buildings/sheds of HDPE unit (additive house, bagging building, extruder
house, analyzer room, etc. As required)
7. Process buildings/ sheds of PP unit (polymerization building, catalyst/ mineral oil
storage, extruder house, bagging/palletization & bulk loading building, ware-
house, valve house, analyzer room etc. As required)
8. Process buildings/ sheds of BUTENE -1 unit (plant/equipment sheds, analyzer
room etc. As required)

The above lists of buildings/sheds are subjected to finalization during detail


engineering.

Buildings/ Sheds of Process Units shall be designed as per Factory Act & NBC
incorporating special requirements of Licensors if any.

Ventilation and day-lighting shall be ensured by means of louvers/ window &


ventilators and roof monitors. Necessary lifting devices shall be provided.

2.2.1.4 Utility Facilities

1. Buildings/ sheds for power receiving and distribution system utility package (as
required for utility package)
2. Buildings/ sheds for raw water system utility package (as required for utility
package)
3. Buildings/ sheds for DM water system utility package (as required for utility
package)
4. Buildings/ sheds for cooling water system utility package (as required for utility
package)
5. Buildings/ sheds for compressed air (instrument & plant) system utility package
(as required for utility package)
6. Buildings/ sheds for fuel gas system utility package (as required for utility
package)
7. Buildings/ sheds for Inert gas system utility package (as required for utility
package)
8. Buildings/ sheds for Steam generation system utility package (as required for
utility package)

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 25 of 40

9. Buildings/ sheds for condensate & condensate polishing system utility package
(as required for utility package)
10. Buildings/ sheds for emergency power system utility package (as required for
utility package)
11. Buildings/ sheds for utility & product distribution piping utility package (as required
for utility package)

The above lists of buildings/sheds are subjected to finalization during detail


engineering.

Buildings/ Sheds of Process Units shall be designed as per Factory Act & NBC
incorporating special requirements of Licensors if any.

Ventilation and day-lighting shall be ensured by means of louvers/ window &


ventilators and roof monitors. Necessary lifting devices shall be provided.

2.2.1.5 Offsite Facilities

1. Buildings/ sheds for tankage/ storage facility (as required for offsite package)
2. Buildings/ sheds for resin silos and bagging facility (as required for offsite
package)
3. Buildings/ sheds for effluent system (as required for offsite package)
4. Buildings/ sheds for chemical storage (as required for offsite package)
5. Buildings/ sheds for catalyst storage (as required for offsite package)
6. Buildings/ sheds for fire fighting system (as required for offsite package)
7. Buildings/ sheds for security & surveillance system (as required for offsite
package)
8. Buildings/ sheds for loading and unloading system (as required for offsite
package)

The above lists of buildings/sheds are subjected to finalization during detail


engineering.

Buildings/ Sheds of Process Units shall be designed as per Factory Act & NBC
incorporating special requirements of Licensors if any.

Ventilation and day-lighting shall be ensured by means of louvers/ window &


ventilators and roof monitors. Necessary lifting devices shall be provided.

2.2.2 Day Lighting

Established level of illumination shall be maintained for all parts of the buildings by
means of windows, ventilators etc. Provision of referenced publications like NBC part-
VIII; Section-1; IS-2440-1975; IS-3646 (part II-1996); IS-7662 (part I-1974), Factory
rule or other relevant rules etc. shall be adhered to in this regard. Openings shall be
provided with shading devices to avoid glare. For the purpose of illumination, day
lighting shall also be supplemented by artificial illumination particularly at fire-exit.

2.2.3 Ventilation

2.2.3.1 Natural Ventilation

Established level of ventilation in terms of air changes per hour shall be maintained
for all spaces as per the provision of referenced publications like State Factory rules,
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 26 of 40

NBC part-VIII Section-1, IS:3101-1975 (Industrial building), IS:3362-1975 (Residential


buildings), IS-:7662 (Part I-1974) or other relevant code/ rules. Natural ventilation
shall also be supplemented by mechanical or electrical means of ventilation in all
human occupied areas. Sufficient no. of Glazed/Louvered windows/Ventilators shall
be provided and supplemented by exhaust fans.

2.2.3.2 Mechanical ventilation

In addition to natural ventilation, if required Mechanical or electrical ventilation is


provided depending on the type of building and its use. Refer Design Basis of
Packaged Equipment for its requirement and applications.

2.2.4 Safety Requirement

Safety from fire and like emergencies shall be taken into account in building design
as per NBC-Part IV; State Factory Rules and other relevant code/ rules. The buildings
shall be provided with exits sufficient to permit safe escape of occupants in case of
emergency. The exits shall be in terms of doorway, corridors, etc. to internal/ external
staircase or to areas having access to the outside.

2.2.5 Site planning & Landscaping

Site planning of building shall take into account aspects like inter-relationship of the
buildings with the whole system, movement pattern, traffic and road net-work, safety
regulations, service network, fire safety, climatic and environmental aspects, site
conditions like site dimension, contour, drainage, noise level, view, future expansion,
visual aspects etc.

Main and service/ maintenance entrances of buildings shall be provided with


vehicular access. All exit points shall also be provided with footpath/ vehicular
access. Truck movement space in accordance with traffic pattern shall be provided
for the building as per the location of hoisting bay/loading, unloading platform. Road
network and open space around the buildings shall be designed considering
movement and functioning of Fire tenders and cranes etc.

Suitable Landscaping treatment shall also be done around the important buildings.
Such treatment shall generally consist of lawns, road side plantation and
beautification of building entrance areas. Standard landscape elements such as earth
contours, pavings, flower beds, hedges, shrubs, ground cover and ornamental trees
shall be incorporated in landscape treatment. Necessary water supply/sprinklers shall
also be provided.

2.3 BUILDING SERVICES

Following services shall be provided for all buildings as essential services.

2.3.1 Water Supply, Distribution and Drainage, Sanitary Services.

This service is essential for all human occupied buildings. The building shall have
toilet and drinking water facility and accordingly water supply, distribution and
drainage, sanitary services as per NBC- Part-IX: Section 1&2, Factory rules and or
referenced publication. Drinking water provisions shall be provided within an
enclosure separated from the toilets. Space for janitor shall be provided in the toilets.
All service pipes showing on the external wall shall be suitably concealed or shall be
provided within a shaft.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 27 of 40

2.3.2 Electrical Services

This service shall be provided as essential service for all the buildings. Electrical
services for building shall consist of electrical supply, and distributions, electrical
lighting installations, telephone network, fans, exhaust fans, lighting protection system
etc., all accessories, cabling etc. including Emergency power supply, all as defined
under Engg. Design Basis of Electrical.

2.3.3 Air Conditioning and Heating

Control Room Building, Administration Building, etc. shall be centrally air-conditioned.


Accordingly A.C. Plant/ AHU etc. of the require capacity (depending on the
requirement) shall be provided and suitably housed. Some designated rooms (as per
Electrical requirement) in the Sub Station Buildings may be required to be air-
conditioned. For this suitable window/ split/ package type units may be provided as
per requirement w.r.to the Design Basis of Packaged Equipment.

2.4 AESTHETICS

Apart from the fulfillment of functional & safety requirement, aesthetic requirement of
the building shall be taken care of in the design. Preliminary drawings indicating
Architectural scheme shall be submitted for Owner’s approval.

Architectural scheme shall be based on general principles of Aesthetics. Building


facades shall reflect such principles like symmetry, balance, proportion, rhythm, light
and shade etc.

Building Elements like canopies, overhangs & shading devices, gutters, roof
projections, parapets, door; window/ ventilator composition, External wall/ facade
shall be considered as contributory elements to aesthetics.

Architectural scheme including design of above mentioned elements shall be


subjected to Owner/ PMC approval.

Minimum two alternative Architectural scheme of buildings as desired by PMC/


Owner shall be prepared and submitted for approval.

2.5 STRUCTURAL AND CONSTRUCTION ELEMENTS

The structural system shall be as specified in Engineering Design Basis (Structural).

2.6 BUILDING ELEMENTS

2.6.1 Plinth Protection

The building shall be provided with minimum 900 mm wide (100mm high from top of
Approach Road Level) plinth protection around the building.

2.6.2 Finished Floor Level (FFL)

In general, FFL of the Building shall be determined with respect to top of approach
road or pavement. Following schedule shall be adhered to for FFL of the building:

A. Control Room Building (Buildings having false flooring):


Top Road level of Approach road + 150 mm + Height of false flooring
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 28 of 40

B. Sub Station Buildings:


(i) Top of approach Road level +300 mm (Cable Cellar floor)
(ii) Top of approach Road level +150 mm (Transformer bays) with pebbles
(iii) F.G.L. (+) approx. 1000 mm high from top of road (in case of single
storey Substation Building with trenches as per electrical requirement.

C Plant Buildings (Unit area) floors (HPP) shall be maintained as per Design
Basis of General Civil.

D. Other Buildings:
Top of approach Road level +300 mm to 450 mm and or as per functional
requirement.

Notes:

1. In case of approaches with different top levels, the highest top level of
approach road/ pavement shall be considered.

2. FFL shall be same throughout in a building.

3. FFL of external loading/unloading bays/ platforms, toilet, pantry, and kitchen


shall be 10-15 mm lower than that of the building FFL to check
ingress/spillage of water.

2.6.3 Steps/ ramps/ Stairs

Steps/ ramps shall be provided for access to the Building for pedestrian/ vehicular,
equipment entry as per relevant code. Minimum 1000 mm wide platform shall be
provided in between entrance door and steps/ramps. Following dimensions of the
steps/ ramps shall be adhered to.

A Stairs width = 1500mm minimum

B. Tread = 300 mm minimum


C. Riser = 150 mm maximum
D. Slope of Ramp = Not steeper than 1:6 or as per requirement
E. Ratio of Tread & Riser = 2 Riser + Tread= 600 to 650 mm
F. No. of risers per flight = 15 Nos.
G. Landing width = 1500. minimum

2.6.4 Walls

Following schedule shall be adhered to for wall material and thickness:

A. External, walls = 230 mm. thk. Brick wall


B. Internal partition wall = 230/115 mm thk. Brick wall depending on the
overall length and height of the wall (refer note
below)
C. Transformer Walls = 200 thk. RCC or 355 thick (including plastering)
fire walls as per Electrical requirements. (IER)
D. Concrete wall (Blast resistant) = As per structure design basis

Notes:

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 29 of 40

1. 115 mm thk. brick partition walls (with nominal steel requirement as per
structure design) shall be provided with 230 mm thk. brick pillars for stability.
2. Wherever conduits or pipes are required to be concealed within partition wall,
the wall thickness shall be increased suitably.
3. Wherever, bricks are not commonly available, suitable alternative material
shall be used after obtaining owner’s approval.

2.6.5 Doors

Doors shall be provided for access, security and safety at all entry & exits of rooms,
functional areas & the buildings. Air tight door shall be provided in pressurized area
and in gaseous protection area. Fire check doors shall be with minimum two hours
rating as per statuary requirement. Sizes of the doors shall be determined on the
basis of the following schedule:

A. Equipment, Panel area: Size of max. equipment including packing.


B. Other areas: Volume of movement through door.
C. W.C., Bath Cubicle Door: 800 mm x 2100mm (wall opening size)
D. Minimum size of other doors: 1000mm x 2100mm (wall opening)

Notes:

1. Rolling shutters shall be provided for equipment entry for Switchgear Room/
Electrical Room, A.C. Plant Room etc.
2. Motor operated Rolling Shutters shall be provided in the main equipment entry
door.

2.6.6 Windows/ ventilators

Windows/ ventilators shall be provided in all areas for natural lighting, ventilation and
visibility at working level.

For the purposes of natural ventilation, total openable area of the windows/ventilators
shall be as per Factory Act subjected to a minimum of 15% of the floor area to be
ventilated.

For the purpose of natural lighting total glass area shall be minimum 15% of the floor
area. However, in case of offices, work places etc. windows shall be provided for the
full length of walls as per approved Architectural scheme. Areas accommodating
panels/eqpts. shall be normally provided with ventilators at high level for unobstructed
distributed lighting.

Wherever due to limitation of external wall area or any other reasons, stipulated area
of window/ ventilation for ventilation cannot be provided, suitable mechanical devices
shall be provided. For Workshop/Warehouse sheds etc. with roof sheeting etc.
suitable monitor to be provided for ventilation.

Transparent roof light sheeting shall be provided in roofing of shed type structures for
day lighting.

2.6.7 Canopy/ Overhang

Canopy/overhangs shall be provided at all entries & exits for rain & sun protection.
Size of the canopy/ porch shall be decided w.r.to utility of the building and other
aesthetic. Blast proof Control Rooms shall not have any projections with outer face of
its walls except with false treatment for aesthetics of the building.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 30 of 40

2.6.8 Shading Devices

Shading devices shall be provided over all windows, openable ventilators for rain &
sun protection. These devices shall be in form of horizontal projections, vertical
projected fins or combination of both as per building facade treatment. Minimum
projection shall be 600 mm.

2.6.9 Parapet

Parapets shall be of RCC for all buildings with minimum 500 mm high for non-
approachable roof and 900 mm high for approachable roof.

2.6.10 Roof Gutter

Gutter with rain water pipes or R.C.C. shafts shall be provided for all the building for
roof water drainage. Sizing of the gutter shall be based on area to be drained and
number of outlets. Gutters shall be of RCC. For Workshop/ Warehouse shed with
precoated roof sheeting, precoated sheets gutters may be provided and for big size of
workshops/warehouse RCC shaft may be provided at the end of gutter.

2.6.11 Rain Water Pipes, Spouts

Rain water pipes shall be provided for roof water drainage. Number of rain water
pipes shall be decided on the basis of roof area, slope and rainfall intensity as per
NBC-IX Section 2. Rain water pipes shall be embedded in concrete. RCC or GI
spouts may be used for drainage of chajja/small canopies of ground floor.

2.6.12 Air Lock Lobby

This shall be provided for all entries with centrally air-conditioned spaces.

2.6.13 Emergency Exits

Emergency exits shall be provided for the building as per State Factory Rules, NBC-
Part IV and for individual functional spaces such as Console area, Electrical room etc.
Emergency exits shall be located in such a manner that escape route is direct,
unobstructed & without passing through any other functional areas to safe area.

2.6.14 Staircases

Staircases shall be provided for vertical circulation & emergency exits. Number of
staircases shall be based on building sizes more than 500 Sq.M ground covered area
shall have two stairs (NBC-Part IV). Emergency exit requirements shall be as per
safety distance requirement. At least one no. staircase/ladder shall be provided for
access to the flat roof top for maintenance.

2.6.15 Railings

Railings shall be provided in stairs, and in all unprotected openings in slabs as a


safety device. Steel railings in loading/ unloading bay of shall be of removable type.

2.6.16 False Ceiling

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 31 of 40

False ceilings shall be provided in the all air-conditioned areas for the purpose of
reducing room volume and to hide air conditioned ducting etc. and also to maintain
acoustic level inside any space.

2.6.17 False/Cavity flooring

False/ cavity flooring shall be provided to accommodate under floor cabling in


Instrumentation areas like Console Room, Rack Room, Computer Room etc. Extent
of false/ cavity flooring shall be as per Instrumentation requirements.

2.6.18 Transformer Gate

Steel gate of suitable size in front of transformer bays in substations building may be
provided as per electrical requirement.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 32 of 40

2.7 SCHEDULE FOR ARCHITECTURAL FINISHES

2.7.1 GENERAL

For the purposes of schedule of Architectural finishes, buildings are categorised into
following types. colour Scheme for all Architectural items shall be as approved by the
Owner.

Type Buildings
Type A Important buildings like Administration Building / Training / Medical
centre, Main Gate/ Guard House
Type B Control Rooms, Satellite Rack Room, Sub Stations
Type C Non plant buildings like Guest house, Canteen Building, Health
Centre, Central Laboratory Building, Gate House (other than main
gate/ guard house) etc.
Type D Non plant buildings like Service Buildings, Security Barracks,
Product Ware House, Central Ware House, Construction Office
Building, Central Workshop, Central Warehouse, NCU/GCU Service
Building, Weigh Bridge, Chemical Storage Building etc. & other non
plant buildings not categorized under any other group
Type E Utility/ storage/ Process Buildings/ Sheds like DG Shed, Pump
Houses, Compressor House, Process Building/Sheds, Cement
Godown, Storage Shed, Analyzer Room etc.

Note:

In case of conflict between licensor/ process/ safety/ statutory requirement and this
schedule of Architectural finishes, the former shall override.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 33 of 40

2.7.2 EXTERNAL FINISHES

2.7.2.1 External wall, RCC Surfaces

A. Type "A” Buildings

o Composite Aluminum Panel & structural glazing

B. Type "B” Buildings

o Sand stone cladding

C. Type "C” Buildings

o Plain cement plaster and texture coating (‘Heritage’ or


‘Spectrum’)

D. Type "D" Buildings

o Plain cement plaster and Acrylic paint

E. Type "E" Buildings

o Plain cement plaster and waterproof cement paint

2.7.3 INTERNAL FINISHES

2.7.3.1 Floor finishes:

A. Entrance Lobby, Reception , lounge, Waiting area etc :

Type-A Type-B Type-C Type-D Type-E

o Granite stone o Granite stone o Vitrified tiles o Kota stone o Kota stone

B. Office and associated areas like records/ storage, meeting/ conference room etc.:

Type-A Type-B Type-C Type-D Type-E

o Vitrified tiles o Vitrified tiles o Vitrified tiles o Ceramic Tiles o Kota stone

C. Circulation area (Corridor, passage, etc.):

Type-A Type-B Type-C Type-D Type-E

o Granite stone o Granite stone o Vitrified Tiles o Kota stone o Kota stone

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 34 of 40

D. Kitchen, Pantry & Dining hall etc. :

Type-A Type-B Type-C Type-D Type-E

o Vitrified Tiles o Vitrified Tiles o Vitrified Tiles o Ceramic Tiles o Kota stone

E. Toilet, Drinking water area etc. :

Type-A Type-B Type-C Type-D Type-E

o Granite Stone o Granite Stone o Vitrified Tiles o Ceramic Tiles o Ceramic Tiles

Note: In Sub Station building flooring of Toilet/ drinking water shall be of Ceramic
Tiles

F. Staircase.

Type-A Type-B Type-C Type-D Type-E

o Granite Stone o Granite Stone o Marble Stone o Kota Stone o Kota Stone

Note: In Sub Station building flooring of staircase shall be of Kota stone

G. Battery Room & Chemical Handling areas (All type of Buildings).:

o Chemical resistant Epoxy coating

H. Electrical Room, Pressurisation Room, AC Plant, Loading / Unloading bays,


Equipment handling areas, Storage areas, Switchgear, MCC, Ware House, Work
Shop, Process/ utility Sheds etc. (All type of buildings):

o Heavy duty cement concrete flooring.


(Vacuum dewatering flooring in large Rooms/ areas)

I. Console, Rack room , UPS Room , areas housing instrumentation equipments


requiring under-floor cabling (All type of buildings):

o Raised Access/ cavity/ false flooring :


With High pressure laminate finish

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 35 of 40

2.7.3.2 Internal wall finishes:

A. Entrance Lobby, Reception , lounge, Waiting area etc :

Type-A Type-B Type-C Type-D Type-E

o Granite stone o Granite stone o Marble stone o POP punning o Oil bound
cladding cladding cladding & Plastic distemper
emulsion paint

B. Office and associated areas like records/ storage, meeting/ conference room etc.:

Type-A Type-B Type-C Type-D Type-E

o POP punning & o POP punning & o POP punning o POP punning o Oil bound
Plastic emulsion Plastic & Plastic & Plastic distemper
paint emulsion paint emulsion paint emulsion paint

C. Circulation area (Corridor, passage, etc.) :

Type-A Type-B Type-C Type-D Type-E

o Granite stone o Granite stone o POP punning o POP punning o Oil bound
cladding up to cladding up to & Plastic & Plastic distemper
1500mm height, 1500mm emulsion paint emulsion paint
POP punning & height, POP
Plastic emulsion punning &
paint above Plastic
emulsion paint
above

Note : In Sub Station building wall finish of Circulation area shall be Oil bound
distemper

D. Kitchen, Pantry & Dining hall etc. :

Type-A Type-B Type-C Type-D Type-E


o Ceramic tile o Ceramic tile o Ceramic tile o Ceramic tile
o Ceramic tile dado dado dado dado
dado

E. Toilet, Drinking water area etc. :

Type-A Type-B Type-C Type-D Type-E


o Granite stone o Ceramic tile o Ceramic tile o Ceramic tile
o Granite stone dado dado dado dado
dado

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 36 of 40

Note: In Sub Station building cladding in Toilet etc. shall be of Ceramic Tile dado

F. Staircase.

Type-A Type-B Type-C Type-D Type-E

o Textured o Plastic o Plastic o Oil bound


o Textured coating emulsion paint emulsion paint distemper
coating

Note: In Sub Station building Staircase wall finish shall be Oil bound distemper.

G. Battery Room & Chemical Handling areas (All type of Buildings):

o Acid resistant tiles/ epoxy coating over cement plaster up to 2500 height & oil
bound distemper above 2500 height.

H. Electrical Room, AC Plant, Loading / Unloading bays, Equipment handling areas,


Storage areas, Switchgear, MCC, Ware House, Work Shop, Process/ utility
Sheds etc. (All type of buildings):

o Oil bound distemper.

I. Rack room , UPS Room (All type of buildings):

o POP punning with plastic emulsion paint

J. Console Room :

o Granite stone dado

2.7.3.3 Internal ceiling finishes:

A. Entrance Lobby, Reception , lounge, Waiting area etc :

Type-A Type-B Type-C Type-D Type-E

o Gypsum board o Aluminum o Gypsum o Gypsum board o Oil bound


panel false panel/ strip board panel panel false distemper
ceiling false ceiling false ceiling ceiling

B. Office and associated areas like records/ storage, meeting/ conference room etc.:

Type-A Type-B Type-C Type-D Type-E

o Mineral fibre o Aluminum o Mineral fibre o Mineral fibre o Oil bound


false ceiling panel/ strip false ceiling false ceiling distemper
false ceiling

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 37 of 40

C. Circulation area (Corridor, passage, etc.) :

Type-A Type-B Type-C Type-D Type-E

o Gypsum board o Aluminum o Gypsum o Gypsum o Oil bound


panel false panel/ strip board panel board panel distemper
ceiling false ceiling false ceiling false ceiling

D. Other AC areas etc., where false ceiling required :

o Gypsum board false ceiling

E. Other area not indicated above etc. :

Type-A Type-B Type-C Type-D Type-E

o POP punning & o POP punning & o POP punning & o POP punning & o Oil bound
Plastic emulsion Plastic emulsion Plastic emulsion Plastic distemper
paint paint paint emulsion paint

F. Electrical Room, AC Plant, Loading / Unloading bays, Equipment handling


areas, Storage areas, Switchgear, MCC, Ware House, Work Shop, Process/
utility Sheds etc. (All type of buildings):

o Oil bound distemper

2.7.4 DOORS

A. Entrance/ exit Doors

Type-A Type-B Type-C Type-D Type-E

o Powder coated o Powder coated o Powder o Powder coated o Pressed steel


Aluminium Aluminium coated Aluminium
glazed shutter glazed shutter Aluminium glazed shutter
glazed shutter

B. Doors in circulation area of all type of Buildings

o Glazed, powder coated Aluminum door

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 38 of 40

C. Office area doors

Type-A Type-B Type-C Type-D Type-E

o TW frame, o Powder coated o Pressed steel o Pressed steel o Pressed steel


block board TW Aluminium frame block frame block frame block
veneer finish glazed shutter board board board
flush shutter laminated laminated laminated
finish flush finish flush finish flush
shutter shutter shutter

D. All Electrical Room, A.C. Plant Room, Battery Room doors of all type of
Buildings

o Pressed steel frame with Pressed steel shutter

E. Toilet doors

Type-A Type-B Type-C Type-D Type-E

o TW frame, o TW frame, o Pressed steel o Pressed steel o Pressed steel


block board TW block board TW frame block frame block frame block
veneer finish veneer finish board board board
flush shutter flush shutter laminated laminated laminated
finish flush finish flush finish flush
shutter shutter shutter

F. Fire check/ resistant doors

Irrespective of above schedule, Fire check doors (minimum 2 hours rated)


shall be provided wherever required as per OISD/ Statutory requirements.

1. Fire check doors In Control Room / Satellite Rack Room Building

A. Main entrance/ entry to Console :


o Glazed steel Fire check door

B. Other Rooms :
o Solid type steel fire check door (with 300x300 vision panel)

2. Fire check doors In Administration Building

A. Main entrance/ entry/ circulation area :


o Glazed steel Fire check door

B. Other Rooms :

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 39 of 40

o Wooden,TW veneered fire check door (with 300x300 vision


panel)

3. Fire check doors In other Buildings

A. Main entrance/ entry/ circulation area :


o Glazed steel Fire check door

B. Other Rooms :
o Solid type steel fire check door (with 300x300 vision panel)

Rolling shutters shall be provided in equipment areas like Switchgear/ MCC


Room, Workshop, Ware House etc. where opening size for door exceeds
3000 x 3000mm. Doors/windows/ventilators shall be complete with all fittings
& fixtures for easy smooth operation & locking facility.

2.7.5 WINDOWS & VENTILATORS

Type-A Type-B Type-C Type-D Type-E

o Glazed, o Glazed, o Glazed, o Glazed, o Glazed, steel


Powder coated Powder coated Powder coated Powder coated
Aluminium Aluminium Aluminium Aluminium

2.7.6 ROOF TREATMENT

o Atactic Polypropylene modified bituminous waterproofing membrane .

2.7.8 ROOFING / CLADDING (sheds/workshop)

o Precoated, profiled colour coated galvanised steel sheet roofing/ cladding

2.7.9 SANITARY FITTINGS & FIXTURES

A. Water Closet (European type) :

Type-A Type-B Type-C Type-D Type-E

o Wall hung type, o Wall hung type, o Wall hung type, o Pedestal type, o Pedestal type,
coloured coloured coloured coloured coloured
(premium (premium (premium
luxury model) luxury model) luxury model)

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DOCUMENT No.
ENGINEERING DESIGN BASIS
STRUCTURAL & ARCHITECTURAL 6987-00-16-48-DB01
Rev. 1
Page 40 of 40

B. Wash Basins :

Type-A Type-B Type-C Type-D Type-E

o Round, o Round, o Round, o Round, o Wall hung type


coloured, with coloured, with coloured, with coloured, over
electronic electronic electronic granite counter
sensor over sensor over sensor over
granite counter granite counter granite counter
(premium (premium (premium
luxury model) luxury model) luxury model)

C. Urinals :

Type-A Type-B Type-C Type-D Type-E

o With electronic o With electronic o With electronic o Standard Wall o Standard Wall
sensor sensor sensor hung type hung type
(premium (premium (premium
luxury model) luxury model) luxury model)

D. Plumbing fixtures (stop/ bib / pillar cocks, flash valves etc.):

Type-A Type-B Type-C Type-D Type-E

o Stainless steel o Stainless steel o Stainless steel o CP Brass o CP Brass


(premium (premium (premium
luxury model) luxury model) luxury model)

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved