Isa Drts-6 Manual
Isa Drts-6 Manual
Isa Drts-6 Manual
1 SAFETY AT WORK...................................................................................................................................... 5
2 GENERAL.................................................................................................................................................... 6
3 DESCRIPTION OF THE INSTRUMENT ................................................................................................... 6
4 CONNECTION AND TEST START WITH DRTS.6 ................................................................................. 7
4.1) Connection to the mains ......................................................................................................................... 7
4.2 Power-ON ................................................................................................................................................ 7
4.3 Connection to the relay........................................................................................................................... 9
4.3.1 Hazardous situations ...................................................................................................................... 9
4.3.2 Burden............................................................................................................................................ 11
4.3.3 Current outputs............................................................................................................................. 11
4.3.4 Low current ranges: option IN1-CDG........................................................................................ 14
4.3.5 Delta connection of current outputs............................................................................................ 14
4.3.6 Voltage outputs ............................................................................................................................. 15
4.3.7 Use of the AC voltage output for the relay auxiliary supply .................................................... 18
4.3.8 Auxiliary DC voltage .................................................................................................................... 20
4.3.9 Trip inputs ..................................................................................................................................... 20
4.3.10 Counting inputs........................................................................................................................... 21
4.3.11 Auxiliary outputs ........................................................................................................................ 23
4.3.12 Low level signals ......................................................................................................................... 23
4.3.13 Optional measurement inputs ................................................................................................... 24
4.4 Connection to the PC ............................................................................................................................ 24
4.5 Execution of the test and problem solutions......................................................................................... 24
4.6 Power-off ............................................................................................................................................... 25
5 TROUBLESHOOTING................................................................................................................................ 26
5.1 Introduction............................................................................................................................................ 26
5.2 Opening the test set and first checks...................................................................................................... 26
5.3 The test set cannot be powered-on or diagnostic voltage error ............................................................. 30
5.4. Fault on the current amplifier ............................................................................................................... 32
5.4.1. Overload......................................................................................................................................... 32
5.4.2. Current amplifiers power supply error........................................................................................... 32
5.4.3. Over temperature ........................................................................................................................... 33
5.4.4. Temporary intervention ................................................................................................................. 33
5.4.5. Amplifier replacement ................................................................................................................... 34
5.5. Fault on the voltage amplifier power supply ........................................................................................ 34
5.6. Fault on the voltage amplifier............................................................................................................... 35
5.6.1. Overload......................................................................................................................................... 37
5.6.2. Counter feed................................................................................................................................... 39
5.6.3. Amplifier replacement ................................................................................................................... 39
5.7. Fault on the DC SUPPLY ..................................................................................................................... 39
5.8. Fault on trip inputs................................................................................................................................ 41
5.9. Fault on the microprocessor board ....................................................................................................... 42
5.10. Problems with upgrade or with the diagnostic.................................................................................... 43
5.10.1. Upgrade problems ........................................................................................................................ 43
5.10.2. Diagnostic problems .................................................................................................................... 44
5.11. Problems with the USB interface........................................................................................................ 44
5.12 The fault cannot be fixed ..................................................................................................................... 45
6 SPECIAL SITUATIONS .............................................................................................................................. 47
6.1 Addition of the MISU option................................................................................................................ 47
6.2 Transformation of a 125 V unit into a 300 V one ................................................................................ 48
6.3 Transformation of the interface from RS232 to USB........................................................................... 50
7 FUNCTIONAL TEST .................................................................................................................................. 52
7.1 Introduction........................................................................................................................................... 52
7.2 Voltage outputs ..................................................................................................................................... 52
Doc. MIE10156 Rev. 11 Page 4/87
1 SAFETY AT WORK
The Product hereafter described is manufactured and tested according to the specifications,
and when used for normal applications and within the normal electrical and mechanical limits
will not cause hazard to health and safety, provided that the standard engineering rules are
observed and that it is used by trained personnel only.
The operating manual is published by the Seller to be used together with the system hereafter
described. The Seller reserves the right to modify the manual without warning, for any reason
I.S.A. This includes also but not only, the adoption of more advanced technological solutions and
modified manufacturing procedures. The Seller declines any difficulties arising from difficulties
due to unknown technical difficulties. The seller declines also any responsibility in case of
modification of the instrument or of any intervention not authorized by the Seller in writing.
The Product generates voltages and currents that may be lethal to the unadvertised user. Besides, in
order to avoid any danger in case of fault inside the Product, the device under test should have the
following characteristics:
. Connection cables must use safety banana plugs;
. Connection sockets must be not accessible;
. Input circuits must have an isolation degree at least equal to the one of the product.
The connection to ground is provided through the mains supply cable; however, for added safety,
the Product should be connected to ground using the dedicated socket.
The connection to ground is provided through the mains supply cable; however, for added
safety, the Product should be connected to ground using the dedicated socket.
NOTE: on test sets after 12786, there is a circuit that verifies the connection to ground of the test
set, and warns the operator if it is not connected. After this message, the test set cannot be
operated unless a proper grounding is established. Note that the test set accepts to be supplied
phase to neutral, or phase to phase.
In case of doubt, please contact your Seller. The Seller and Manufacturer decline any and all
responsibility due to improper usage, or any usage outside the specified limits.
Doc. MIE10156 Rev. 11 Page 6/87
2 GENERAL
The DRTS.6 user's manual provides information about how to use the instrument. It informs also
about the internal design and troubleshooting messages; last, it provides a suggested spare parts
list.
Technical specifications of the DRTS.6, of the resident firmware FWH6 and of the TDMS
control software are provided in separate documents.
The document includes internal options Measurement and IO6432, and external modules AMI-150,
AMIV-33, AMI-66, AMI-99 and AMV-66.
The DRTS.6 has a basic configuration, two internal options and some external optional modules.
The basic configuration includes:
. Four voltage generators (the fourth one can be used as a standard one or to generate the zero-
sequence voltage of the other three phases);
. Six current generators;
. The auxiliary DC voltage generator;
. Eight trip inputs;
. Two inputs for high-frequency impulses;
. Four digital outputs;
. A low power signal connector for the external modules;
. The RS232 serial interface connector. From June 2004, also the USB interface connector.
Before connecting the relay, connect the DRTS.6 to the mains, by means of the power supply
cord. The earth is connected to the supply plug.
The supply voltage range is 90 to 132 and 180 to 264 V AC, sinusoidal, single phase. Please
consider that most mains stabilizer and uninterruptible power supplies generate a voltage that is a
square wave rather than sinusoidal: this is out of range for DRTS.6.
NOTE: on test sets after 12786, there is a circuit that verifies the connection to ground of the test
set, and warns the operator if it is not connected. After this message, the test set cannot be
operated unless a proper grounding is established. Note that the test set accepts to be supplied
phase to neutral, or phase to phase.
4.2 Power-ON
After power-on the test set starts a self-diagnostic procedure: digital circuits first; then, analogue
circuits. The self-diagnostic procedure is the following one.
- At power on the microprocessor programs the two XILINX’s XC5204 programmable logics. At
the end of programming the programmable logic tests itself; the microprocessor checks for correct
answer (DAN). If programming of XILINX A is not OK, lights OK and ERR turn on; if
programming of XILINX B is not OK, lights ! and ERR turn on.
- Next, the microprocessor tests the Static RAM: it writes at all locations 55 first, then AA, and
checks for no error. In case of error, it turns on lights OK; !; ERR.
- At the end of this test, all lights are turned on and off.
- Next, the microprocessor tests the speed of the Static RAM, and decides whether to add one wait
cycle. During this test all lights turn on and off from bottom to top.
- At the end of this test, all lights are turned on and off.
- Next, the microprocessor tests the Dynamic RAM. During this test all lights turn on and off from
top to bottom. In case of error, it turns on lights ON and ERR.
Doc. MIE10156 Rev. 11 Page 8/87
- At the end of this test, all lights are turned on and off.
- Last, the microprocessor tests the FLASH EPROM, with its CRC code. In case of error, it turns on
lights ON; ! and ERR.
- This is the last test of logic circuits ; next steps refer to analog circuits. The following table
summarizes logic errors.
- First test is the check of the + 5 V logic circuits supply; then + 12 V for relays and fans; then + 15
V and – 15 V for analogic circuits.
- Next step is the test of DC voltage supplies for current and voltage amplifiers.
- Next step is the test of DAC’s that generate low power signals to be fed into current and voltage
amplifiers. First test is zero voltage output; next maximum voltage; next minimum voltage. During
this test outputs are inhibited: no output is generated by the instrument.
- Other errors cause the ERR light to turn on; they are also reported to the P.C. with the
corresponding error message.
During this last session, the four LED’s blink in pairs. At the end of diagnostics, the green light OK
turns on: this confirms that the microprocessor operates correctly. If there is a fault sensed on an
amplifier (current, AC voltage, DC voltage), you have the two lights: OK and ! turned on, plus the
buzzer beeping. In this situation, you can connect your PC and start the test program: it will display
you the code message telling which one is the faulty amplifier. In order to proceed, please go to the
Troubleshooting chapter.
NOTE. Also diagnostic circuits can fail; in these instances the diagnostic fault is false. This is why
if you press OK on the diagnostic message the program allows you to continue. If the alarm is
wrong or if you do not use the corresponding feature tests can be performed at no further trouble.
In this last instance, if the diagnostic alarm is annoying, it can be skipped as follows:
- Remove the four screws on the rear; remove lids;
- Microprocessor board is the second one to the left. Looking from the bottom, there is a group of
DIP switches. Switch 1 is the rightmost. Analog diagnostic is skipped setting OFF (pushing
forwards) switch no. 7.
Doc. MIE10156 Rev. 11 Page 9/87
The following table lists a number of situations that are potentially hazardous to the user and/or to
the test set. Please consider this list, and check the situation in case of doubt.
TEST SET NOT Capacitor dividers take the case at 110 V. Ground
GROUNDED The unit is not protected against common mode noise. connection
See below for details.
Voltage (or current) The test set ground and the neutral ground are connected VN (IN)
neutral connected to to very distant points of the grid. There is a voltage connected to
ground differential between the grounds; in case of fault, there is ground
an heavy risk for the test set and for the operator. Besides,
it is likely that transient spikes occur during the test;
their value can exceed the rated isolation limits.
See below for details.
Current neutral Inside the test set there is an 1 Ohm resistor between IN Connect the
connected to VN instead and VN: it would be burned by the output current. current
of IN This, in turn, can cause the oscillation of current outputs, neutral to IN.
and cause the damage of current amplifiers.
Stand-by generator The frequency and amplitude variations and the Supply
superimposed noise have caused the damage of the front- waveform
end circuit.
Filtered mains; electronic The AC voltage can be a squared waveform rather than Supply
stabilizer sinusoidal; the test set operates at the minimum supply waveform
level, with low efficiency. Besides, the power sunk by
DRTS.6 at full power is 3680 W: this is to be considered
for a correct dimensioning.
Loss of power supply There can be a loss of control because the microprocessor Quality
while the test set was resets while energy was applied to the load. monitor
generating
Contact to a live wire The contact can be dangerous to the user or even the Test before
plant. The test set voltage outputs are protected only prior connecting
to the first test.
Current outputs in series See text: the use of mis-matching resistors is mandatory. See the
manual
Voltage outputs in See text: the use of mis-matching resistors is mandatory. See the
parallel manual
Long generation of all Possible danger of over-heating components, specially Check
currents with high ambient temperature burden and
duration
Very old relay, with Spikes as the relay switches the measuring circuits Check
heavily inductive load burdens
Doc. MIE10156 Rev. 11 Page 10/87
Of these points, the first three are very hazardous, both for the user and the test set. THESE
TYPES OF FAULT ARE NOT COVERED BY THE WARRANTY.
FRAME
MAINS V
V /2
EXTERNAL GROUND
(OPERATOR)
Capacitors shown are included in the filter. Of course their value is low, so that the current flow is
limited according to specification; however, you can feel it. Besides, there is no protection against
common mode voltages, such as ESD, that are usually discharged to the ground. The connection of
the test set to any metal frame connected to ground solves the problem.
The second hazard does not apply if the relay to be tested is not connected to the plant. If, instead,
the connection to the relay is performed by means of a test connector (or directly to terminal
blocks), the operator must be sure to interrupt the connection to the V.T. secondary and to the
ground. This is normally true; however, we experienced some instance were this was not performed.
VN (IN)
VOLTAGE REMOTE
GROUND
CONNECTION
The problem in this instance is that VN of P.T.’s (or IN of C.T.’s) is connected to ground in a point
of the grid that is far away (sometimes very far away) from the control building. Between the
ground of the test set and the ground of P.T.’s there is a voltage differential that is caused by eddy
currents; in case of ground fault, this voltage grows to lethal levels, for both the user and the test
set. Besides, high energy spikes between the two grounding points are easy to develop; these spikes
have amplitudes and energy that can exceed the rated isolation limits. Checking the error is simple:
just test with a resistance meter that there is no connection between VN and the ground.
The third hazard is easily avoided just by checking that the relay neutral connection is connected to
IN rather than VN.
4.3.2 Burden
Before executing a test with the DRTS.6 it is necessary to check that the burdens of the relay
under test are compatible with the DRTS.6 voltage and current output power. To this purpose, it is
necessary to compare the burden declared by the manufacturer to the following maximum loads.
Often the burden is expressed in terms of VA load at nominal voltage or current: it is necessary
to convert it into Ohm, with the following formulas.
V burden = (nominal voltage)^2 / VA load
I burden = VA load / (nominal current)^2
When DRTS.6 is overloaded, a circuit generates a fault signal as soon as the output has an error in
excess of 5% to 10% of the nominal output. This logic error is delayed in order to avoid faults
caused by the relay itself (for instance as metering circuits are switched). For this reason, if test
duration is very short (as during the test of first zone settings in distance relays), the overload signal
can be not sensed: in this situation, test result can be different from the nominal setting. Therefore,
if test result is very different with respect to the nominal, before proceeding test that there is no
overload, with a test duration more than 0.3 s.
Currents are connected to safety sockets (5). When an output is applied, the corresponding light (6)
turns on. Note that the unit can operate two ways:
- Mode 6 I: in this mode all currents are independently adjustable, maximum current is 15 A.
Note that if only three currents are used (I1, I2, I3) the corresponding output power is 100 VA; if
more outputs are used, maximum power decreases to 80 VA.
- Mode 3 I. In this mode current outputs are to be set in parallel: I1 to I4; I2 to I5; I3 to I6. The
program accepts currents up to 30 A, and accommodates for the correct commands to DRTS.6
and test results from DRTS.6.
The two neutral sockets are connected together. If up to three currents are generated one socket is
sufficient; if more currents are generated it is advisable to use both sockets.
Be careful as IN sockets are connected to socket VN via an 1 Ohm resistor, that would be
damaged if the current neutral is connected to VN.
Doc. MIE10156 Rev. 11 Page 12/87
The instrument can drive up to 100 VA on outputs I1, I2, I3: if any other output is generated (I4 to
I6), maximum load becomes 80 VA per phase. The corresponding maximum burdens are the
following, as a function of the maximum test current.
Special care is to be taken when evaluating the burden of the current input, as the burden of
connecting wires is to be added to the relay burden. If the relay load is 2 VA at nominal
current, the relay burden is 80 mOhm. In this case it is possible to test at 15 A only if the connection
and cabling are maximum 8 m long, with a cross section of 2.5 sq. mm at least, and if cables
are tied together, in order to minimize the reactive component.
In case it is desired to have a three-phase generator, rated 30 A and 160 VA per phase, it is possible
to select the 3I mode. In this situation, DRTS.6 output currents are to be connected in parallel: I1 to
I4; I2 to I5; I3 to I6, taking advantage of the PAI option (figure 1). The program accepts test currents
up to 30 A on DRTS.6, and takes care to drive half and half the amplifiers, and to display the total
current on the display and in the test report.
I1
PAI
I2
ZL
IN
In case it is desired to run tests at even higher currents, it is possible to connect more amplifiers in
parallel, and to perform single-phase tests. The angle between currents must be 0°; the current
amplitude must be the same. By this, current increases, power increases, but the maximum burden
decreases, as summarized in the following table.
RANGE (A) 45 60 90
N. OF OUTPUTS 3 4 6
BURDEN (Ohm) 0.12 0.088 0.059
POWER (VA) 240 320 480
Doc. MIE10156 Rev. 11 Page 13/87
In these instances, please take care of the connection and of test duration: 4 mm sockets are unable
to deliver 90 A for a long while. Use both neutral sockets in parallel, and an adequate (biggest than
possible) wire size, such that connection sockets are not damaged because of over-heating and the
burden is minimized.
If the problem is having more than 100 VA at 15 A, then it is possible to connect two amplifiers in
series (figure 2). The angle between currents must be 180°; the amplitude of two currents must be
the same.
In this instance it is possible to have up to 160 VA; however, with this connection, minor
differences of current outputs can tend to overload the amplifier, that would make it impossible to
get the desired power. To overcome this problem it is possible to balance current outputs with the
SEI option, that includes a shunt resistor that causes a maximum output current error of - 1.6%. The
following table summarizes maximum burden Z at 160 VA.
I1
22 Ohm
IN Z
22 Ohm
I2
Note that it is impossible to connect in series more than two current generators because the
neutral is in common.
Doc. MIE10156 Rev. 11 Page 14/87
In conclusion, it is always possible to parallel currents and to connect in series voltages; the
opposite, i.e. parallel connection of voltage outputs and series connection of current outputs is to be
performed with attention.
With DRTS.6 the full power of 100 VA is available only at the current of 15 A. This is good for the
test of relays with the nominal current of 5 A; if relays are rated 1 A, the available power can be not
adequate to perform the test of high burden relays. In addition to this, some relays (as CDG of GE)
have very low current settings.
The option IN1-CDG solves this problem, by means of a set of three current transformers, with the
following characteristics:
. Primaries: 12.5 A and 15 A;
. Secondaries: 0.5 A; 1 A; 2.5 A;
. Nominal power: 100 VA.
- Connections:
. Four primary side sockets (I1, I2, I3, IN);
. Three independent outputs, with one phase socket and 2 zero sockets;
. Ease of connecting outputs in star or delta configuration.
. For the single phase tests it is possible to have three times the above power, connecting current
outputs in series.
The option includes four connecting cables to DRTS.6 current outputs, 1 m long, 2.5 sq. mm cross
section. Outputs are do not have a common neutral; this eases the star or delta connection. Included
is a bridge for star connection.
The test program TDMS accepts the transformer ratio, so that currents can be programmed with
their value after the option.
We have had a fault on current outputs that has been caused by a type of connection we never heard
before. This connection can very quickly cause the fault of the test set current amplifier(s): for this
reason, we explain you in the following what is it, why does it damages the amplifiers, and how to
perform it in the way that avoids faults.
In this type of connection, the device under test has only three inputs, not four; so, only current
phase outputs are connected, and not the neutral.
I1
I2
I3
IN
Doc. MIE10156 Rev. 11 Page 15/87
The test can be started only if the three currents are equal in value, and phase shifted by 120°; else,
the test set would immediately generate an over-load fault alarm. If currents are the same, our test
sets are so good that each current closes its path on the other two, and no alarm is generated.
I1
I3 I2
The only instance where this connection could be necessary is testing differential transformer relay
protections, where one side has a Delta connection and the compensator is included in the relay. The
test with Delta connection can be performed using three SEI options.
SEI is made of four banana and plug connector, and of three 22 Ohm resistors, that have the
purpose of balancing the current load as seen by the test set. There is some current flowing into
resistors: its amount, and therefore the error on the nominal current into the load, depends upon the
load itself: the lower the load the less the error. If the load is just a short circuit, the current into SEI
resistors is negligible (less than 0.1%); with the maximum load, the current error increases to –
1.6%. This inconvenience must be accepted, against the almost sure damage of the test set.
I1
I2
I3
IN
Voltages are connected to safety sockets (10). When an output is applied, the corresponding light
(9) turns on.
Doc. MIE10156 Rev. 11 Page 16/87
Output V4 can be operated either as a fourth voltage, program controlled, or as the zero sequence
voltage of the other phases; the selection is performed in the pre-fault settings. Another selection is
the value of the zero-sequence voltage, that can be (V1+V2+V3)/3 or (V1+V2+V3)/1.73 (vectorial
sum), also program selectable. Be careful because with the latter selection the zero-sequence voltage
can be higher than 125 V (300 V with the option): in this case the instrument gives an over-load
error.
Purpose of V4 is to test relays that need an independent fourth voltage; example is synchronization
relay for the reclosure of HV lines (matched to a distance relay).
Purpose of Vo is to test relays that need the zero sequence voltage along with three phase voltages.
For this purpose also the V4 selection is applicable; however, the user should compute V4 from V1,
V2 and V3 with the above formula.
Be careful that socket VN is connected to sockets IN, while it is isolated from the zero of the
auxiliary DC supply voltage (8).
Maximum burdens are the following, as a function of the maximum test voltage.
For tests at 125 V with a burden greater than 80 VA, it is possible to connect two amplifiers in
parallel, using the PAV option (figure 3): this causes a maximum error of 0.5% on voltage applied
to the load. DO NOT PARALLEL VOLTAGE OUTPUTS WITHOUT PAV, AS THIS
COULD DAMAGE THE AMPLIFIER. The angle between voltages must be 0°; the amplitude of
two voltages must be the same. With this connection, the power at maximum voltage grows to 160
VA; maximum loads are the following:
PAV includes a selector for the case that the 300 Option is available. Before starting the test, set the
switch according to the voltage output.
V1
PAV
V2
ZL
VN
It is also possible to double the output voltage by connecting the burden between phases phase-
shifted at 180°; in this instance burdens are the following.
Doc. MIE10156 Rev. 11 Page 18/87
Note that it is impossible to connect in series more than two voltage generators because the
neutral is in common.
V1
ZL
V2
4.3.7 Use of the AC voltage output for the relay auxiliary supply
In some relays the auxiliary voltage is an AC voltage rather than a DC voltage. In this instance the
AC voltage generator can be used to feed the relay; however, this must be performed with some
care.
The first check to perform is about the power consumption. On DRTS.6 the available power is 80
VA at the maximum voltage; the power decreases linearly with the voltage. However, the
maximum relay consumption should be no more than one fifth of this power. The reason is that
with an AC supply the load is made of a rectifying bridge plus filter capacitor: in this situation, the
consumption is concentrated on the 2 ms of the voltage peak; therefore, the current is five times as
higher than the one expected.
Doc. MIE10156 Rev. 11 Page 19/87
I AC
V AC
V AC
I AC
For example, if the relay voltage is 100 V and the power consumption is 10 VA, the current sink
should be: 10 / 100 = 0.1 A. Due to the concentration of current, current peak is actually 0,5 A, that
multiplied by 100 V makes 50 VA instead of 10 VA.
Second problem, when the voltage is first applied to the relay, the filter capacitor is a short-circuit.
The test set overload signal is delayed by 60 ms to overcome transient situations; during this time,
the capacitor is loaded, at the maximum current yield of the amplifier: this could cause a fault.
Besides, at the end of 60 ms the capacitor is normally not yet charged: as a consequence, DRTS.6
signals a fault on voltage output.
To avoid it, we need to increase slowly the voltage supply, and to keep it constant during the test:
this is performed as follows.
. Go to pre-fault definition, and program a low voltage, say 5 V.
. Press Apply pre-fault values: 5 V are generated. Thanks to the low voltage, the current is limited.
. Program now 10 V, and generate them.
. Continue with 10 V steps, until you reach the desired voltage supply.
. This performed, go to fault definition, and program the same value for the voltage; then, perform
your tests, but DO NOT USE THE RESET BUTTON, AS IT TAKES TO ZERO ALL OUTPUTS,
AND THE SEQUENCE SHOULD BE REPEATED.
NOTE. Suppose that the auxiliary DC voltage generator is broken, and you have to feed the relay
auxiliary supply with a DC voltage. In this instance you can use the AC voltage output, selected at 0
Hz. In this instance, you can have the full power output, but the problem at start-up is still there, so
APPLY THE VOLTAGE SLOWLY, as explained above; else, the amplifier will signal overload, or
can be damaged.
The auxiliary DC voltage is available on safety sockets (8), and is isolated with respect to voltages
and currents. The DC voltage can be used to supply the relay under test or to polarize trip contacts.
Before test start and when the voltage is zero the output is open. If a counter-feed voltage is
erroneously connected the error is sensed and reported on the test program as counter-feed on DC
supply. The voltage must be removed for the test to continue.
The DC voltage generator can yield at maximum 100 W or 2 A: as a consequence, the maximum
load is a function of the supply voltage. The following table lists the maximum load for the most
used voltages.
V dc R MAX
(V) (Ohm)
260 680
220 490
110 120
48 24
24 12
For the DC voltage, pay attention to the input filter capacitor: this is a short circuit as the voltage is
applied. When connected to this type of load, the instrument drives 2 A for the maximum time of
0.5 s; after this, the instrument signals over-load. At 110 V the DRTS.6 can drive a capacitor of
1000 uF; bigger values can cause an overload alarm. In this instance, it can be enough to reduce the
voltage.
Trip inputs are separated in two groups, with isolated zero reference: C1-C4 and C5-C8. The
connection can be made to safety sockets (14).
The selection of input voltage clean or under voltage is performed on the healthy values of the test
program, together with other selections: debounce time and value of input voltage.
If the input is voltage clean the program selects automatically the threshold of 24 V, that is the
voltage wetting the contacts.
If the input is under voltage, select 5 V for logical inputs, or the nominal voltage of the site. In case
the 5 V level is selected with a voltage of 110 V, trip delays can be false; however, circuits will not
be damaged. If the selection is voltage clean while it is under voltage, the contact can be seen closed
Doc. MIE10156 Rev. 11 Page 21/87
while it is open. The following table summarizes the nominal voltage and the corresponding
nominal threshold.
SELECTION THRESHOLD
V V
5 4.5
24 22
48 42
> 100 57
De-bounce is the time during which the input must be confirmed before being Accepted as true; this
selection is taken into account by the program, so that trip time does not change with this parameter.
The importance of this setting is that spurious noise can be ignored with high settings; on the other
side, fast trip times cannot be measured with high settings. The default value of 500 us is normally a
good compromise. If the input is AC voltage, the program selects automatically the de-bounce delay
of 2 ms, in order to avoid stopping on the zero crossings of the input.
When the input with voltage is selected, the corresponding light (32) turns on. The state of trip
inputs is signaled by lights (15): if the contact is closed or the voltage applied the LED turns
on.
At sockets (7) are available the count inputs Imp1 and Imp2, that serve to test energy meters. The
threshold level of these inputs is the respectively same of inputs C1-C4 and of inputs C5-C8, but
there is no debounce.
Input Imp1 has the same common of C1-C4; input Imp2 has the same common of C5-C8.
The following figure shows how to perform the connection in two instances: the DRTS.6 is the
reference, or the reference is made upon a sample meter.
NOTE: as the counting input operates at high frequency, make sure that there is no bounce in
the input, as otherwise they would all be counted.
Energy meter
DRTS.6 under test
V V
Rotating
disk / led
1 I I
C
Sensor
Doc. MIE10156 Rev. 11 Page 22/87
DRTS.6
V V
V
C 1
I
C 2 I I
Sample Test
sensor sensor
NOTE: this test can be eased taking advantage of the optional SHA-6 reading head.
IMPORTANT NOTE
Some energy meters have the following internal connection (3-pin).
1 2
In this situation, there is a common point between I and V inputs: it is pin 1. This pin MUST BE
CONNECTED TO IN AND VN.
V1
3
Doc. MIE10156 Rev. 11 Page 23/87
VN
These outputs are relay, that can be operated via software; relay operation can be timed with respect
to currents and voltages. The relay under test is connected to sockets (12), either on Normal Closed
or Normal Open contact.
Outputs are voltage free, and can be polarized if necessary. The closure of the output is warned by
lights (13): contact closed = light on. Contact rating is: maximum voltage : 250 V AC; maximum
current : 5 A.
These contacts are foreseen to drive loads such as coils; to avoid EMI noise interference, contacts
are protected by a capacitor and by a MOV rated 500 V AC. However, it is good practice to drive
coils that are externally protected against voltage spikes when the coil is opened.
Low level signal outputs are available on connector (34); pin-out is listed in appendix 9. Purpose of
this output is to use external amplifiers, or to test relays connected to voltage dividers and
Rogowsky coils.
On the connector provided you should make a bridge between pins C and J: it tells the DRTS.6 to
go to this operating mode. Connect the cable before powering on the instrument: after power on the
DRTS.6 inhibits power outputs, and low level outputs become available. The control program takes
into account this selection, and allows programming the corresponding conversion coefficients.
For instance, if you program 100 A max primary current, and 7 V maximum secondary voltage, if
you generate 20 A the secondary voltage will be 7/5 = 1,4 V.
On current outputs only, the maximum secondary voltage can be selected to one tenth of the above
value, that is 0,724 V. This serves to increase the accuracy when Rogowsky coils are to be
simulated.
The same connector (34) is used to drive the external amplifiers. In this instance, the cable provided
with the amplifier includes the code of the amplifier type: control programs change accordingly.
ATTENTION BECAUSE LOW LEVEL OUTPUTS ARE ACTIVE DURING NORMAL DRTS.6
OPERATION.
Doc. MIE10156 Rev. 11 Page 24/87
Optional measurement inputs (17) are four: low and high current; low and high voltage.
Low current and voltage inputs are used to test transducer outputs, respectively with current (0-5; 4-
20 mA) or voltage (10 V) outputs.
High current and voltage inputs are used to measure currents up to 20 A, and voltages up to 200 V.
The 20 mA input is protected against over-currents: a temporary fuse opens the circuit. However,
take care not to apply 20 A to the 20 mA input.
These inputs are used only if the optional MISU board has been installed. Connect converter inputs
to DRTS.6 current and voltage outputs, and converter output to the measurement input. Start the
manual or automatic test and verify the error of the converter.
The test set is connected to the PC via the RS232 serial interface (4). The connector is a 9 way
CANON type; logic signals and their positioning follow the standard for PC (see appendix 1). From
May 2004, also the USB interface (11) is available: its operation is confirmed by light (16).
The RS232 cable provided crosses the signals, from 9 to 9 ways; the wiring schematic is provided
in appendix 2. The USB cable has lights to confirm the operation.
The DRTS.6 is connected to the PC using the serial cable provided. The RS232 serial port is
normally COM1. Connection specifications for RS232 are:
- Interface type: RS232.
- Baud rate: 57600.
- Interface protocol: BUSY/READY.
- Compatibility: PC with WINDOWS 95 or higher.
The selection of the type of interface, RS232 or USB, is performed at test start; after it, the type of
interface cannot be changed unless the test set is powered OFF.
During use, the DRTS.6 is set on a table, in horizontal position: to this purpose, the container is
provided with suitable feet. Cooling air is flowing from the rear to the bottom of the instrument: do
not impeach the free air flow, to avoid over-temperature alarms.
Power on the PC and then connect it to the DRTS.6 using the serial cable. Before executing an
automatic test, it is a good rule to start the manual X-PRO program, and to execute some tests to
check that there is no error in the connections and in parameter setting, and also that it is possible
to drive the load.
Before test start the test set checks voltage output sockets. If a voltage greater than 10 V is
detected, the PC gives a message of counter-feed on voltage outputs: this avoids connecting
test set’s output voltage to a live wire. In this instance, remove the voltage before proceeding.
SITUATION V1-V2-V3-V4 V DC
At power-on Open; protected Open; protected
Counter-feed alarm At test start, even if V = 0 Immediate
During tests; STOP not pressed Closed; not protected Closed; not protected
After RESET Open; protected Open; protected
After STOP Closed; not protected Open; protected
As a test is started, as soon as the DRTS.6 generates some output, the green ON LED turns on.
This light stays on also during the pauses between tests, if healthy parameters foresee the
generation of an output, including the DC voltage.
If the red ! LED turns on (and a buzzer is heard) during the test, it alerts about the following
problems:
. Error on a voltage output, usually an overload.
. Error on a current output, usually an overload (including the open circuit).
. Over-temperature sensed on a voltage or current amplifier.
The PC gives a message that helps selecting the type of fault.
Usually, it is sufficient to correct the load and start over again. In case of over-temperature, go
to zero with the outputs and start over again after some minute. Other faults have an internal
origin: try again, and, if it does not disappear, it is necessary to repair the instrument. Appendix 4
lists error codes, and the corresponding fault area.
Other logic errors can turn on the ERR LED of the DRTS.6. The error message explains which
kind of error has been sensed. If the error is in the connection area, check the connection cable (see
appendix 2).
When everything is OK, it is possible to proceed with the execution of the test program. The
program itself will tell the operator how to connect the relay.
The way to use TDMS and the dedicated programs is explained in the corresponding manuals.
In general, it is a good rule to save test results at the end of the test, so that they can be reloaded
and printed.
4.6 Power-off
After all tests have been performed, set all outputs to zero, remove all relay connections and
power-off the test set. Do not power off with outputs being generated, and with the relay
connected: high voltage spikes could be generated; the test set could be faulty at next power-on.
Doc. MIE10156 Rev. 11 Page 26/87
5 TROUBLESHOOTING
5.1 Introduction
Sometimes, when my ears whistle, I wonder if it is because of some of my customers being angry at
us because the test set doesn’t work: According to Murphy’s law, when it was most necessary. We
at ISA do our best efforts to filter the so-called infant mortality of electronic components prior to
delivery of all our test sets; and this after extensive testing of prototypes and pre-production units.
Yet, sometimes faults occur, because everything dies, including electronic components; so, please,
before shooting at us, see if the following instructions can serve you to fix the problem. If not, e-
mail us the problem, not forgetting to mention the unit’s serial number: our business is to
minimize your downtime. My e-mail address is:
[email protected]
Please mention in your e-mail how did the fault occur: this serves us for our continuous
improvement program. In all instances, after replacement of the faulty board or module, it should
immediately be returned to the agent or to ISA.
Last, our experience is that our test sets withstand very heavy duty cycles for long wiles, if correctly
used; most problems arise because of the problems that you have found listed in the former
paragraph: please read it!
There are many types of faults: this chapter refers to the most common ones. The message displayed
by the program (unless when the unit cannot be powered on) tells you the faulty area; so, paragraphs
are divided According to the type of fault.
. Open DRTS.6 by removing the four screws on the rear. The two metal sheets that enclose the test
set can be removed, gaining access to the inside. The machine is made of the front panel, and of two
side plates to which are screwed, above and below, some metal bars that support the guides of the
printed circuit boards. In the instrument are located the following components, left to right:
. One PASSIVE board, code 11316, with zero-power amplifiers;
. The MICR-H control board, code 31300, that includes: the microprocessor, FLASH EPROM
program memory, SRAM, DRAM, PLA, interface circuits;
. One INTE-H2 board, code 21310, that handles digital inputs, with filters and isolation circuits;
. One RELE.6 board, code 11373, with the four digital outputs;
. The CONV-6 board, code 11372, that includes the DAC’s that generate the low-power analog
signals;
. Three AMCO-6 boards, code 11374, with two current amplifiers each; boards include also their
power supply;
. Two AMTE.3 boards, code 11356 (or 11405), with two voltage amplifiers each (code 11376 or
11393 for the option 300 V);
. One voltage amplifiers supply module, code 11355 (code 11358 for the option 300 V);
. One ALIAUX low-voltage supplies board, code 11370;
. One FRONT.6 board, code 11386, with mains supply generation.
. The auxiliary DC voltage module, code 11369, is mounted on the left.
Doc. MIE10156 Rev. 11 Page 27/87
. On the front panel are also mounted some boards, with LED’s and filters.
PASS MICR INTE RELEICONV AMCO AMCO AMCO AMTE AMTE ALI V ALI FR
I1-I4 I2-I5 I3-I6 V1-V2 V3-V4 AUX END
(21) (22) (23) (24) (25) (26) (26) (26) (27) (27) (28) (29) (30)
V DC
(31)
The first check to be performed is to verify if boards are in place, fit into their guides, and if
connectors are in place. The transportation of the test set can be the cause of the problem: we have
tested that the unit withstands the specified drops and vibrations; however, we do not know if drops
have respected these limits.
If there is a connector out of its place, fit it into its position and power-on again.
If boards are out of place, it is necessary to restore them into position, and then try to power-on
again; however, in this instance, short circuits between boards may have caused the fault of some
board. To fit back the boards, or to replace a board, follow these steps.
. Unscrew the front panel by removing the two screws on the front and the four nuts on the corners,
so that it can be lowered.
. On the upper aluminum bar there is an aluminum strip that keeps in place the amplifiers: remove
it.
. In the center of the first and third bar, starting from the front, there are two rods that that, when
tightened, block cards into their place, so that they cannot vibrate during transportation. Un-tighten
them, until cards can be removed.
To restore the test set, set the board, and then repeat the same steps.
Doc. MIE10156 Rev. 11 Page 28/87
If you have just received the latest issue of the software and some function does not operate
correctly, it is possible that this is caused by the DRTS.6 resident program (firmware). In this
situation, please get in touch with your agent: he will provide you the latest revision, that you can
load using the UPGRADE program.
In some sites (like mines) the air is very much polluted of conductive dust: we once occurred a case
of a test set that did not work any more because of this. After cleaning, it recovered its operation.
Last, in order to solve problems caused by transient spikes and by wrong operations (connection to
VN rather than to IN), we have put in place two important fixes. If you have any intervention on
your test set, you should also execute the following modification, in order to avoid any such
inconvenience in the future.
The fix no. 1 is necessary for DRTS.6 with serial number less than 11530 (September 2003); the fix
no. 2 is necessary for DRTS.6 with serial number less than 11574 (December 2003). At any rate,
please check: if fixes are not there, ask us for the materials, and then apply them.
Fix no. 1: protection against spikes. It is made of a ZnO transient suppressor, rated 1 kV, and
applied between the VN socket and the ground. In the picture, the suppressor is the red component:
it is soldered to the VN (blue) socket on one side, and connected to ground on the other side by
removing the nut nearby, and screwing it with the same nut.
Doc. MIE10156 Rev. 11 Page 29/87
Fix no. 2: protection against the wrong connection of current neutral to the VN socket. It is made of
an 1 Ohm 4 W resistor, that has in parallel a diode bridge rated 8 A 800 V: if the current is applied
to VN, it passes through the bridge, and the drop across the resistor is limited, so that it does not
burn; as the load is too high, the test set signals overload. The pictures show the group prior to
mounting, and the mounting on the front panel. One side is connected to IN; the other side (no
matter which one) is connected to VN.
Doc. MIE10156 Rev. 11 Page 30/87
When the unit cannot be powered-on, first of all check the fuse, that is incorporated in the power
supply pug, into the small drawer. If the fuse is OK, the cause is most likely located in the front-end
board PWA11386, that is the rightmost one looking from the front.
The DRTS.6 power supply is split in two, each controlled by a front-end module mounted on the
front of the card. The split is the following:
. Voltage amplifiers + I3-I6;
. Microprocessor + fans; I1-I4; I2-I5; DC module.
If the test set behaves correctly at 220 V and gives problems (ERR signal; no power on) at 110 V,
the fault is on one of the two front-end modules: the front card needs to be replaced.
If the test set does not operate at any power supply, proceed as follows. On AMCO amplifiers are
located two LED’s that turn on when the amplifier is powered. The first test is to verify if only one
of the modules is failing, or both. Open the unit, power on and check for these lights.
If I3-I6 is on and the other two are OFF, also the microprocessor and fans are off (case 1).
If you see the light on the I1-I4 and I2-I5, but not on the I3-I6 amplifier, the test set starts and
communicates the diagnostic error (case 2).
In both instances, there is a risk that the fault has been caused by a fault on current amplifiers or DC
module for the first one, or by the current amplifier or voltage amplifier supply for the other one.
For this reason, proceed as follows:
. Case 1. Remove the green connector from amplifiers I1-I4 and I2-I5, and from the DC voltage
module. Power-on, and measure the voltage between pins o1 and 2 of a current amplifier connector:
take care, because they are not isolated from the mains. The voltage should be 300 V. If so, the fault
is not on the FRONT-END board, but it is on one of the amplifiers. To find out which one, connect
one at a time, until the fault comes back.
. If the power supply does not come back, it is necessary to replace the front-end board, and the
modules powered by it, because they also could be damaged.
. If no power is generated, it is better to return the test set to the agent, because the fault can be very
severe.
. Case 2. Remove the green connectors to current amplifier I3-I6 and from the voltage amplifiers.
Power-on: if the test set turns on, the fault is not on the FRONT-END board, but it is on one of the
amplifiers. To find out which one, connect one at a time, until the fault comes back.
In case of voltage diagnostic error, and also for a first monitoring of the situation, it is possible that
the fault is on the diagnostic circuit, or that there is an actual fault.
In the first instance, press OK and then try to generate: if the generation is correct, the error can be
ignored.
If instead there are faults, then the fault is likely to be actual. Also in this instance, it is possible that
one board causes a short circuit on the voltage. To verify this, proceed as follows:
. Open the test set, and remove the rear protection.
To the left, there is a small back panel, with three boards connected: the front-end, the ALIAUX,
and the power supply module.
Doc. MIE10156 Rev. 11 Page 31/87
The following picture shows the board; the table lists all voltages that should be measured on the
pins of the first connector to the left.
NOTE: O LOGIC, 0 ANALOG, 0 TEN are all joined together, and between them there should be 0
V. The 300 V+I3 voltage IS NOT ISOLATED FROM THE MAINS: TAKE CARE! It feeds all
voltages and the current I3.
A low + 5 V causes loss of control of the MICROPROCESSOR board; low or missing + 15 V and –
15 V give problems on all analog circuits; low or missing + 16 V and – 16 V cause the false
operation of AMCO amplifiers.
. Extract first all the connectors of current and voltage amplifiers, and of the DC voltage module: if
the voltage restores itself, we have found the faulty board. Without it, the diagnostic error should
not appear any more.
. If this is not enough, extract also the CONV board: also it can be the cause of the fault.
If the fault persists with all boards removed, then the power supply module needs to be replaced.
5.4.1. Overload
In this instance, prior to contacting us, please verify that the load is not too much for the test set;
please refer to the relay connection paragraph. The first check is to measure the voltage drop across
the load: if it is more than 6 V, the load is too high. Another check is to short-circuit the current
output and retry generating the current: if there is no overload message, maybe that the load is too
high. In this situation, reduce the current and try again.
In this instance, you have to know first of all that there is a protection in the power supply module
that turns it off in case of severe spikes on the power supply. This protection resets after 15 minutes
approximately only if the test set is not powered. So, with this kind of fault, turn off the test set and
turn it on after half an hour of power off.
If the error is there at power-on, the first thing is to understand if there is an actual fault or if there is
a wrong fault indication.
A: actual fault. Verify if the two LED's on AMCO are ON (as the other ones). If they are not, then
the error message is correct: it can be caused by the missing of the 300 V supply on the green
connector, or by the missing of the ENABLE signal, still on the green connector. You should have
300 V between pins 2 (negative) and 1 of the green connector, and about 12 V between pins 2 and 3
Doc. MIE10156 Rev. 11 Page 33/87
(ENABLE). If you don't, also voltage generators should be not operational, and the fault is in the
FRONT-END board.
If you have the supply but LED’s don’t turn on, then the amplifier is faulty, and should be replaced.
B: wrong fault indication. If LED's turn on, then the error signal is wrong. The fault could be on the
amplifier: check this by exchanging it with another one. If it is not in the amplifier, this signal goes
through the 20-pin flat cable to the MICR board, passing through CONV and PASSIVA. Please
check that there is no bent pin on the flat cable; then, if the error is still there, it is necessary to
exchange the MICR board.
The first problem is that the software signals only one fault: in case of severe accidents, there could
be a second fault undetected, that would pop up when the faulty amplifier is replaced. In order to
avoid wasting time, after a fault it is necessary to perform a complete diagnostic test that will unveil
all possible problems.
The following procedure allows you to detect which amplifiers are in fault, and to continue working
with the remaining current generators: if you use TDMS MANUAL control, you can use DRTS.6 to
generate three currents from the good sources.
If you have to perform an automatic test, perform it on the available current only, then shift
connections to the other phase, until all of them are tested. In order to achieve this, follow these
instructions.
. Open DRTS.6.
. Locate the AMCO amplifiers.
. Power-on the test set. On AMCO boards are located the following LED’s:
.. Two red LED’s in the center of the board. For normal operation they must be ON: if one or both is
OFF, this means that the power supply is missing, see above, or that there is a fault either to the DC
to DC converter module, or to the power MOSFET: the board is not operational, and must be
replaced;
.. Three green LED’s, that signal the selected output. The inner one corresponds to I1-I4; the second
one to I2-I5; the external one to I3-I6. There must be only one LED turned on, corresponding to the
output at which is connected; else, the switch setting is wrong.
. On units having serial number more than 12876, we use a new version of the current amplifier,
where:
.. All LED’s are of the surface mount type, and the color is red;
.. There is a sixth LED, on the centre and on the edge, signaling that the local microprocessor is OK.
If it is turned off, either an auxiliary voltage is missing, what is signaled by the PC, or the board
must be replaced.
. Remove connectors from the faulty AMCO amplifier: above, a bigger, green one, with power
connections, and a 20-way flat-cable one, with analog signals and logic control bus; below, another
14-way flat cable one, that carries auxiliary supplies.
. Protect flat-cable connectors so that pin cannot touch any conductive part.
Doc. MIE10156 Rev. 11 Page 34/87
. Power-on DRTS.6, and control that there is no other fault displayed. If there is another fault,
remove the corresponding amplifier connectors.
When there is no fault, proceed with the following diagnostic:
- Short-circuit current outputs and generate currents of 0.15; 1.5; 15 A on all available outputs: there
should be no error message;
- Generate also 1; 12,5 and 125 V on all voltage outputs, and check that there is no error;
- Generate 110 and 220 V on the DC voltage output, and check that it works;
- Close in sequence all trip inputs, C1 to C8, and check that they are detected;
- Command the closure of A1-A4, and check that they operate.
. At the end, it is possible to close the unit and operate with the other current amplifiers.
If the faulty amplifier is I1-I4 or I2-I5, you could be wishing to exchange current amplifiers so that
the first two are available. You have to know that AMCO are identical; in order to select the
different positions we use the set of DIP-switches that you can note on the board.
The selection is performed the following way:
. There are three groups of eight DIP-switches;
. The selection is performed setting ON all switches of one group, and OFF the other two groups;
. The group marked SW1, located towards the center of the board, selects I1-I4; SW2 selects I2-I5;
SW3 selects I3-I6.
To fix the problem you should replace the faulty AMCO board. To this purpose, open the unit and
proceed as follows.
. Withdraw the faulty AMCO and replace it with the new one.
. Replace connections.
. Power-on DRTS.6 and check that the fault message has disappeared, and that all outputs are
operational.
. Re-assemble the unit; do not forget to tighten the central rod, as it ensures that cards stay in place
during transportation.
. The replaced amplifiers need to be calibrated. To this purpose, use DRTS.6 user’s manual,
CALIBRATION user’s manual and CALIBRATION program.
The voltage amplifier power supply is tested at power-on, during the diagnostic procedure. The
power supply generates a number of different voltages, positive and negative, that are automatically
selected by the software to be slightly higher than the voltage output: this minimizes the power
wasted on the voltage amplifier.
The associated error codes change According to the standard voltage range of 125 V, or the optional
300 V.
. 125 V error messages: 162 (+95 V); 222 (+125 V); 223 (+ 165 V); 224 (+200 V); 163 (-95 V); 225
(-125 V); 226 (- 165 V); 227 (-200 V)
. 300 V error messages: 164 (+ 115 V); 165 (+ 210 V); 166 (+ 345 V); 167 (+ 460 V); 168 (- 115
V); 169 (- 210 V); 170 (- 345 V); 167 (- 460 V).
Doc. MIE10156 Rev. 11 Page 35/87
As these are diagnostic messages, there is a chance that the amplifier is operating correctly, and the
fault is in the diagnostic circuitry. Also, if the error is for instance in the highest range, the unit can
be used provided that the voltage output is reduced. This is why we have allowed the operator to
reset the error message: by pressing OK the test can proceed.
Next step serves to understand if the power supply is actually faulty, if the fault is in the diagnostic
circuit, or if it is caused by a voltage amplifier. The procedure is the following.
. Open DRTS.6.
. Locate the AMTE amplifier; there are two equal AMTE boards: the left one generates V1 and V2;
the right one V3 and V4.
. Remove connectors from both amplifiers: a bigger, green one, on the front; one DIP-type above;
another one, DIP-type, below.
. Protect flat-cable connectors so that pin cannot touch any conductive part.
. Power-on and check if the error message is still there.
A) ERROR MESSAGE IS STILL THERE
We have to verify if the fault is in the diagnostic circuit, so:
. Set back AMTE connectors;
. Try to generate the following voltage outputs:
- 125 V: 55 V; 75 V; 95 V; 125 V.
- 300 V: 65 V; 130 V; 220 V; 300 V.
. If there is no error message, the power supply is OK, and the fault is located in the CONV-6 board
(80% confidence level): the test set can be used with no problem, unless pressing OK on the error
message;
. If the error message is still there, please check that power supply to the module is there. To this
purpose, go to the rear of the test set: the voltage supply module is connected to a small back panel.
The back panel is protected by a plastic sheet, that is taken in place by four screws: remove them to
gain access to connector pins, that are two parallel lines to the right. Starting from the bottom, pin 1
is connected to ground; pin 4 is the negative of the 300 V supply. Power on the test set, and verify
that, with respect to pin 4, pin 5 is 12 V DC, and pin 7 is + 300 V dc (coarse). TAKE CARE AS
THESE PINS ARE NOT ISOLATED FROM THE MAINS. If pin 5 is 0 V the fault is in the front-
end board; if 300 V is missing, please check for continuity of the traces coming from the leftmost
pins, that correspond to the front-end board. If + 300 V is missing, the fault is on the front-end
board.
. If above tests are OK, the power supply is faulty. You have to remove AMTE connectors again,
and then you can operate current outputs only, until the power supply module is replaced.
B) ERROR MESSAGE IS NO MORE THERE
This means that the fault is located on an AMTE amplifier. To find out which one, connect one first
and power-on: if the fault is no more there, then the fault is in the other one; if it is there, power off
and repeat with the other AMTE amplifier.
When the faulty AMTE amplifier is located, check that the other one is operational by generating on
both outputs the voltages: 1 V; 12.5 V; 125 V (or 12.5 V; 125 V; 300 V). The test set can be used
with these voltages, until the faulty AMTE is replaced.
These faults can be displayed the first time an output is generated, even if it is zero, or only with the
load. In this latter instance, it is possible that the output is overloaded. The first check is to measure
the current sunk by the load: if it is more than 0.64 A (0.26 A above 125 V), the load is too high.
Another check is to open the voltage output and retry generating: if there is no overload message,
may be that the load is too high. In this situation, reduce the voltage and try again. If this is not the
case, you can continue working as explained in the next paragraph.
• Over temperature: 182 (V1); 183 (V2); 184 (V3); 196 (V4).
These faults are generated after a long while of use at high ambient temperature. In this instance,
leave the unit powered-on for 10 minutes, so that amplifiers cool down, then start over again. If this
is not the case, then the temperature sensing chain is faulty.
5.6.1. Overload
This fault can be displayed only with the load, or the first time an output is generated, even if it is
zero. In the first instance, that is the most common, it is possible that the output is overloaded. The
first check is to measure the current sunk by the load: if it is more than 0.64 A (0.26 A above 125
V), the load is too high. Another check is to open the voltage output and retry generating: if there is
no overload message, then the load is too high. In this situation, reduce the voltage and try again.
If this is not the case, you can perform a temporary intervention on the channel that gives the fault
error, and then replace the faulty amplifier as you get it.
. Open DRTS.6.
. If the fault is on V1 or V2, it is important to verify if the error is also on V3 or V4. To this purpose,
swap the boards and power-on. If the fault is still on V1 or V2, then also the next board is faulty;
else, if the error signal moves to V3 or V4, only the original V1 or V2 was faulty.
. If a faulty AMTE board is removed, at the subsequent power-on the test set would signal overload
on the missing voltage channels. The temporary fix to overcome this problem and keep on using the
rest of the test set depends upon the AMTE board serial number. Note that the fix serves to
remove the error signal, but the output should be checked before using it, as it could be
completely wrong. To this purpose, generate 125 V and verify that there is no DC component, and
that the AC voltage is correct. Repeat the test for the outputs of 12.3 V, 1 V and 300 V (if
available). Only after this test you can use the output: this means that the fault is in the overload
sensing circuit.
. Board no. 11356; 125 V. On the component side there are two small 3-pin male connectors,
marked JP3 and JP4. You should bridge pins 1 and 3 on both connectors (the external ones): this
inhibits the fault signal. After this, connect the connectors: the fault signal is inhibited. Before
proceeding, perform the test above described.
. Board no. 11405 (125 V) or 11396 (300 V). The temporary fix is the following.
- Remove the faulty amplifier.
- Locate the test points marked TP36, TP52 and TP47. TP36 is the test point for an
oscilloscope probe, and carries the signal zero; TP52 and TP47 are small points sot protected
by the solder resist. Of them, TP52 is the fault on V1 (V3); TP47 is the fault on V2 (V4).
Connect to TP36 the test-point of the faulty channel with a thin wire, taking care not to
cause short circuits.
Doc. MIE10156 Rev. 11 Page 38/87
After this, connect the connectors: the fault signal is inhibited. Before proceeding, perform the test
above described.
. Board no. 11376; 300 V. On the component side there are two small boards; on each is located a 3-
pin male connector, marked JP2. You should bridge pins 1 and 3 on both boards (the external ones):
this inhibits the fault signal. After this, connect the connectors: the fault signal is inhibited. Before
proceeding, perform the test above described.
. Board no. 11396 (300 V). The temporary fix is the following.
- Remove the faulty amplifier.
- Locate the test points marked TP7, TP4 and TP2. TP7 is the signal zero; TP2 is the fault on
V1 (V3); TP4 is the fault on V2 (V4). Connect to TP7 the test-point of the faulty channel.
After this, connect the connectors: the fault signal is inhibited. Before proceeding, perform the test
above described.
Doc. MIE10156 Rev. 11 Page 39/87
The counter feed is sensed by an operational amplifier that is located in the power amplifier board;
it is switched by an analog switch located on the CONV board, and it is measured by an AC to DC
converter located on the microprocessor.
The first test serves to locate the fault: either on a voltage amplifier, or on the CONV board. To this
purpose, proceed as follows.
. Open DRTS.6 as described above;
. First of all, verify that the flat cables to AMTE boards are correctly fit;
. If there is no problem on flat cables, disconnect both voltage amplifiers, protecting the connectors;
. Power-on.
If the diagnostic signal disappears, the fault is located in one of the amplifiers. Locate the faulty one
by:
. Connect an amplifier;
. Power-on and check if the fault is there;
. Repeat with the other amplifier.
If the fault does not disappear with both amplifiers removed, then it is likely to be located on the
CONV board. It is possible to replace the CONV board at the customer’s site; however, as the test
set calibration corrects the errors of the amplifiers and of the CONV components, replacing CONV
implies repeating the calibration of the test set: it is advisable to send it to ISA.
. Open DRTS.6.
. Remove connectors from the faulty amplifier.
. Withdraw the module and replace it with the new one.
. Replace connections.
. Power-on DRTS.6 and check that there is no fault message.
. Re-assemble the unit: do not forget the rod, as otherwise cards would be too loose during
transportation.
. The replaced amplifiers need to be calibrated. To this purpose, use DRTS.6 user’s manual,
CALIBRATION user’s manual and CALIBRATION program.
In case of fault on the DC supply, it is possible to perform a temporary intervention, so that the test
set can be operated.
. Open DRTS.6.
. The DC voltage supply module is located to the left, when looking from the front.
. Remove the two connectors (green and 8-pin flat cable); isolate them so that they cannot touch any
metal part.
. Power-on: the fault does not appear any more; the DC supply does not operate.
If there is no fault signal, but the DC voltage is not available, proceed as follows.
Doc. MIE10156 Rev. 11 Page 40/87
. First of all, check for the cables going to the module. There are two different types of modules (see
sketches). On module one, the 8-way flat cable comes out upwards; on module 2, the flat cable must
leave the connector on the left. On the other side, verify that the 8-way cable is fit into its
connector, leaving the board upwards. You should temporarily remove the connector, verify that all
pins are straight, and fit the connector back into position:
. Next, on module one there is a fuse, rated F3.15A: check it; if it is open, replace it and try again.
. Observe now the green connector: it has 6 screws carrying wires. The screw closest to the front is
number 6: it carries the earth connection. Power-on, and measure that between screws 4 (zero) and 5
there are 300 V DC. TAKE CARE BECAUSE THIS VOLTAGE IS CONNECTED TO THE
MAINS. If 300 V are there, the module should operate.
. On module one there is a fan. Power-on and verify if it is rotating: if not, the fault is on the
module, that should be replaced.
. If the fan is rotating (for module one), and at any rate on module two, last test is to verify if the
module is blocked by a wrong command coming from the front-end board, and that is located at
screw n. 3. Remove this wire by unscrewing it, and ISOLATE IT AS IT IS CONNECTED TO
THE MAINS. Power-on and verify if the DC voltage is generated: if so, the front-end board PWA
FLAT
CABLE UP FUSE
F3.15A
SCREWS FAN
GREEN
CONN.
PIN 6
Doc. MIE10156 Rev. 11 Page 41/87
SCREWS GREEN
CONN.
PIN 6
In this instance there is no diagnostic message: the test set does not recognize one or more trip
inputs.
. Open DRTS.6.
. Locate the input board INTE-H1, YWA11320: it is mounted on the front panel, just after the
sockets.
. There is a 14-pin flat cable that goes from connector J802 of this board to connector J802 of board
INTE-H2, YWA11310: this flat cable carries signals for C1-C4. Please check that it is correctly fit.
. If cable is OK, please check that there are no burns on inductors mounted on INTE-H1: this could
have been caused by a wrong high voltage applied to inputs. In particular, check with an Ohm meter
that there is continuity between the following points.
SOCKET C C1 C2 C3 C4
PIN 14 8 9 10 11
. If everything is OK, power-on the unit and measure the voltage between C of group 1 and C1, C2,
C3, C4: there should be – 30 V (as between the other C and C5 to C8).
. If everything is OK and closing the circuit between C and C1 the corresponding LED turns on the
fault is located on board INTE-H2, YWA11310.
. Last check: via X-PRO, select inputs with voltage (for instance 24 V). Generate 24 V on the DC
voltage generator and connect it to inputs C1 to C4: does the LED turn on? Is test stopped? If yes,
this confirms that fault is on board INTE-H2.
If a group of inputs does not trip with contact free selection, while it trips with the with voltage
selection, the corresponding 30 V measurement is missing. In this situation, open the test set and
verify first of all on the rear of the unit. Looking from the rear, there are two back panels: the one to
the left receives the auxiliary supply voltages from the ALIAUX.6 board, PWA11370: these are
marked: 0C1, 0C5, 30C1, 30C5. On these points should be soldered four wires, that go to the right
back panel, where the INTE.H6 board, PWA21310, is fit.
First of all, verify that wires are soldered. If so, measure the voltage between 0C1 and 30C1, and
also between 0C5 and 30C5: it should be 30 V DC.
If the voltage is there, there is a fault in the INTE board; if it is missing, there is a fault in the
ALIAUX.6 board.
If after power-on the test set is powered, but control LED’s are not in the standard configuration
(ON turned on; the other ones off), or if it is impossible to connect the test set to the PC, it is
possible that the fault is located in the microprocessor control board.
. Open DRTS.6.
. Locate the MICR board: it is the second leftmost, looking from the front. It is connected to another
board, PASSIVA, with the connector on the front.
. On the MICR-H board are mounted two LED’s: they are located in proximity of the rear of
DRTS.6. These LED’s should turn on as the test set is powered on, and should turn off about one
second after power-on: this confirms that the two programmable logic arrays we have on the board
have been programmed; usually, this confirms that the MICR board is operational. If LED’s don’t
turn off, at 90% of confidence the MICR board is broken, and should be replaced. The alternative
to MICR is that the + 5 V auxiliary supply is low: as a consequence, the microprocessor is on hold.
To verify the + 5 V, proceed as follows.
. The zero is the VN socket.
. + 5 V is reached as follows. On the front panel there are a number of LED's by the side of
voltage and current outputs. On the rear of the panel, these LED's are mounted on a small board.
+ 5 V is the rightmost pin of the line of LED's corresponding to voltage output.
+5V
Doc. MIE10156 Rev. 11 Page 43/87
If the voltage is less than 4.7 V this is the cause of the problem. The low voltage can be caused
by a fault of the + 5 V converter or by an overload in some amplifier. To verify this, remove all
connectors: power (green) and flat cables, to current and voltage amplifiers (boards with heat
sinks), and try again. If the + 5 V is now good, locate which one is the faulty board by connecting
an amplifier at a time until the problem comes up again; if not, then the ALIAUX auxiliary
supply board is faulty.
. If LED’s turn off, and yet there is no communication, the last test is to remove all connectors:
power (green) and flat cables from current and voltage amplifiers (boards with heat sinks). After
that, power-on: the test set should communicate. If not, the MICR board is to be replaced; else, one
of the amplifiers is the cause of the fault. Locate which amplifier by connecting an amplifier at a
time, until the problem comes up again.
NOTE. The replacement of the microprocessor board involves the loss of the calibration
parameters, that is the linearity and the phase angle. For this reason, in this situation we usually
provide the .CAL file of the test set, that should be loaded into the unit using the CALIBRATION
program. If the .CAL file is not available, if you have the suitable test meters, please refer to the
Calibration chapter; else, the test set should be returned to your agent.
If during the Upgrade the power went off, or if the DRTS.3 firmware was loaded into the DRTS.6
test set, it is possible to recover the situation as follows.
FRONT PANEL
SWITCH NO. 1
SWITCH NO. 10
Doc. MIE10156 Rev. 11 Page 44/87
BACK PANEL
If you move these switches towards the edge of the board you set them ON; otherwise they are OFF.
SWITCH 1 2 3 4 5 6 7
POSITION OFF OFF OFF X X X OFF
X = DON’T TOUCH. This is a special setting that should allow to re-load the firmware, no matter if
there are hardware faults.
SWITCH 1 2 3 4 5 6 7
*POSITION ON ON ON X X X ON
. Power-on again: the unit should perform the self-test and display no error.
The problem may be caused by some factors, and the three commons are:
Of these, the most important is to be the administrator of the PC; if you are not, the driver will not
be installed. If the software was already installed, uninstall everything, turn off the PC, turn on the
Doc. MIE10156 Rev. 11 Page 45/87
PC as administrator and install it again. Please refer also to our installation manual.
If the fault is too hard to be fixed, you have to deliver it back to your agent. We have encountered
problems caused by a poor packing of instruments that have been delivered us for calibration or
repair. In order to avoid such inconveniences, please apply the following procedure.
First of all, compile the following form, and attach it to the instrument. Please do not forget to
compile it.
With the instrument should come the mains supply cable, the RS232 and the USB interface cables
and all cables that serve to connect modules (boosters). The user’s manual originally delivered with
the test set is not necessary.
Cover the instrument itself with a polyester film, in order to protect it against dust and foam.
The instrument should be protected by anti-shock foam having a minimum thickness of 5 cm ON
ALL SIDES.
Use a new carton box as a container. On the box apply the UP and the FRAGILE labels.
In the box the instrument will be placed horizontal or standing; not upside down.
If the set is heavier than 20 kg it is better to use also a pallet: this ensures that the box will not be
packed upside down.
Last but not least, do not declare an high value for customs: this expedites clearance of the good and
lowers fees.
Doc. MIE10156 Rev. 11 Page 46/87
6 SPECIAL SITUATIONS
If the customer wishes to add the MISU option, he can ask ISA the upgrade kit, and add it by
himself, with the following instructions.
. Open DRTS.6.
. Unscrew the front panel by removing the two screws on the front and the four nuts on the corners,
so that it can be lowered.
. On the rear of front panel, between and below the sockets, stick the isolating stripes provided: this
serves to guarantee the isolation level.
. Fit the MISU board into the socket connections. Between the MISU components and the panel
leave a space of about 1 mm; do not press against the isolation stick, as they could be damaged.
Solder MISU in this position.
. On the upper aluminum bar there is an aluminum strip that keeps in place the board: remove it.
. In the center of the first and third bar, starting from the front, there are two rods that that, when
tightened, block cards into their place, so that they cannot vibrate during transportation. Un-tighten
them, until the card can be moved.
. Remove all connectors to CONV so that it is possible to withdraw it completely.
. Just after the connector is located a 2-pin jumper, marked JP2: short-circuit the two pins.
. Set back CONV and connect cables.
. Connect MISU connector to CONV connector marked J802 by the flat cable provided.
. Take care that pin 1 of MISU connector goes to PIN 1 of J802 on CONV.
4) MISU calibration.
. On MISU board there are a number of trimmers, that have already been sealed as the board is
calibrated. There is only a small adjustment to be performed, as follows.
. On the edge of the board, starting from the left, there are five trimmers: trimmers P6 and P7 are
respectively the fourth and fifth from the left: see sketch.
Doc. MIE10156 Rev. 11 Page 48/87
P6 P7
. Power-on the test set, connect it to the PC and start TDMS MANUAL control. Select the
frequency of 0 Hz.
. Connect the V1 output to the 10 V measurement input.
. Select on the software the 10 V DC measurement.
. Generate in sequence + 9 V and – 9 V. With trimmer P6, offset calibration, make the two readings
equal between them.
. After this, with trimmer P7, gain, make the readings equal to 9.000 V. Now generate again + 9 V
and – 9 V and verify that the gain correction did not alter the offset calibration; else, repeat the
procedure.
If the customer wishes to have the optional 300 V version rather than the 125 V one that he has
purchased, he can ask ISA the upgrade kit, and perform the change by himself, with the following
instructions.
. Open DRTS.6.
. Remove the voltage supply module.
. Remove connections to AMTE voltage amplifiers and remove the amplifiers.
. Remove also connections to AMCO current amplifiers I2-I5 and I3-I6, and remove amplifiers.
Mark them as they cannot be exchanged.
. Next problem is that we have to modify the position of guides for the two AMCO and AMTE 1-2,
else the two AMTE would not fit. The following is the sketch of guide positions as you will find
them, and of new guide positioning.
Doc. MIE10156 Rev. 11 Page 49/87
. The numbers below refer to hole counting starting from the rightmost. Movements are:
- AMCO 2-5: rotate the guide position from right (dotted) to left, and screw it on holes 55-56 (two
to the left);
- AMCO 3-3: move it leftwards of one hole;
- AMTE 1-2: move it leftwards of one hole.
. Now you can fit back AMCO 2-5 and 3-6, the new AMTE and the new power supply.
The test set must be instructed that the maximum voltage is 300 V rather than 125 V; this is
obtained by modifying the switch setting on MICR board.
The modification can be performed without dismounting MICR board from the test set. If you look
at the test set from below, MICR is the second one from the left. The sketch shows the location of
DIP switches.
Doc. MIE10156 Rev. 11 Page 50/87
PASS
MICR
DIP SWITCHES
10
For the switches, the ON position is towards the board edge; OFF is towards inside. The setting you
will find is the following.
SWITCH 1 2 3 4 5 6 7 8 9 10
SETTING ON ON ON ON OFF ON ON ON ON ON
Now press switch no. 4 towards the inside of the board, so that it goes to OFF position. The final
setting is the following.
SWITCH 1 2 3 4 5 6 7 8 9 10
SETTING ON ON ON OFF OFF ON ON ON ON ON
NOTE: if you do not feel safe to operate this way, you can dismount MICR to perform it. In this
instance, please consider that:
. MICR and PASS boards are screwed together: the must be removed together, this takes a certain
amount of force. Same force is to be used when fitting them back;
. On PASS is soldered a yellow/green wire that is screwed to the frame; unscrew it for the dismount;
. PASS hosts two flat cables; they must be fit prior to insert back the two boards.
Test sets after S/N 12000 have both the RS232 and the USB interface; older units have only the
RS232 interface. It is impossible to modify older units so that they have both interfaces; however, if
Doc. MIE10156 Rev. 11 Page 51/87
the customer wishes it, it is possible to modify older units so that they have the USB interface
instead of the RS232 one. In this instance, the customer can send the test set to ISA for the
modification, or can ask ISA the upgrade kit, and perform the change by himself, with the following
instructions.
The overall note is to be careful, as some operation can lead to the damage of the test set.
7 FUNCTIONAL TEST
7.1 Introduction
The DRTS.6 does not need to be calibrated, as all outputs are feedback controlled, both current and
voltage, by high stability components. It is suggested to check the unit every 3 years. To this
purpose, it is possible to use the X-PRO manual program. Following paragraphs explain the test
procedure.
In the following procedure voltages are tested with values of 1, 10, 100 V and currents at 0.1, 1, 10
A, while voltage ranges are 1, 12.5, 125 V (or 12.5, 125, 300 V) and 0.15, 1.5, 15 A. The reason is
that the multimeter changes range around 1.1: measuring at 0.15 A implies a not acceptable
measurement error.
At the end of the test, if deviations are not Acceptable it is possible to proceed as explained in next
chapter or to send the unit to the closest ISA agent.
8 DRTS.6 CALIBRATION
The calibration of all DRTS.6’s relevant parameters is performed using the TDMS CALIBRATION
program. For the description of the program itself and of the calibration procedure, please refer to
the CALIBRATION program user’s manual (MSE20098).
Doc. MIE10156 Rev. 11 Page 55/87
9 MEASUREMENT OPTION
9.1 Introduction
The Measurement option has the purpose to allow measuring currents and voltages. Input ranges
are: two low level, 20 mA DC and 10 V DC, and two high level, 20 A DC –AC and 250 V DC –
AC.
Voltages and currents to be measured are connected to the safety sockets (17) on the front panel. In
case of converters, connections are the followings.
DRTS.6
V I
IN
I= V I
(V=)
CONV.
DRTS.6 outputs are connected to converter inputs; converter output is connected to the 20 mA (10
V) metering input. The test can be performed manually, with X-PRO or automatically, with the
program TRANSDUCERS (specification MSE10059). Test details are explained in software
manuals.
In case of high rating current or voltage measurement, inputs are connected to the corresponding
sockets. Connect only one input!
Doc. MIE10156 Rev. 11 Page 56/87
10 IO6432 OPTION
10.1 Introduction
Option IO6432 has the purpose of increasing the number of digital inputs and outputs, respectively
64 and 32. These inputs and outputs add to the existing ones.
The option is installed in the rear of DRTS.6: input and output connectors are Accessible through a
window in the rear screen. Input and output characteristics are the followings.
TRIP INPUTS
- Number of inputs: 64, divided in 4 groups of 16 that are isolated among them.
- Type of input: opto-isolated circuits, with a constant current load.
- Input level: from 5 V to 130 V DC; maximum input current 3 mA. DO NOT APPLY MORE
THAN 130 V!
- Connection: 68 way connector.
- Designation of inputs. Standard inputs (on the front of DRTS.6) are numbered from C1 to C8; the
additional ones are numbered from C16 to C80. The four references are:
. COM-1: C17-C32;
. COM-2: C33-C48;
. COM-3: C49-C64;
. COM-4: C65-C80.
AUXILIARY OUTPUTS
- Number of outputs: 32, divided in 4 groups of 8, that are isolated among them.
- Type of output: MOSFET open collector.
- Output level: maximum voltage 130 V; minimum drive capability 15 mA; maximum 50 mA. DO
NOT SHORT CIRCUIT THE OUTPUT!
- Connection: 50 way connector.
- Designation of outputs. Standard outputs (on the front of DRTS.6) are numbered from A1 to A4;
the additional ones are numbered from A16 to A48. The four references are:
. RIF-1: A17-A24;
. RIF-2: A25-A32;
. RIF-3: A33-A40;
. RIF-4: A41-A48.
Appendix 7 provides the pinot configuration, and the position of mating connectors pins, with
soldering contacts, provided with the instrument.
Doc. MIE10156 Rev. 11 Page 57/87
11 GPS OPTION
11.1 Introduction
The GPS option has the purpose to allow testing the following relays:
. Distance relays connected with permissive or blocking schemes;
. Line differential.
For the test are requested two test sets in distant sites, and the possibility to simulate faults at the
meantime on both instruments. In the first instance the timing error can be in the range of some
millisecond; for the second one, the maximum timing error is 100 us.
The GPS option that can generate the synchronization impulses, that last 10 ms and have a
maximum error of 2 us between two GPS. These impulses can be generated as the seconds of the
absolute time are elapsed, with a pace selectable among 5 – 10 – 20 – 30 – 40 – 60 s. The first
impulse is generated after one to two complete periods are elapsed from the moment the
START/STOP pushbutton was pressed. If, for instance, the selection is 30 s, impulses are generated
when the absolute time is:
(hh; mm; 0”; hh; mm; 30“; hh; mm+1; 0“; hh; mm+1; 30“...).
The operators at both sites should connect first GPS to the mains by the plug (1): the 1 pps light
starts turning on, thus assuring that GPS is operational.
After this locate the antenna, that should be located in a place that allows it to receive the
synchronizing signals from 4 GPS satellites. Usually it is enough to put it outside the protections
building; if the building is armored the distance should increase. The antenna provided has a cable 6
m long, usually enough for the purpose. The user can increase the distance by an extension cable,
provided that it is made of satellite graded shielded cable, such as CT/100 or CT/167, with BNC
connectors terminations. The maximum cable length should be such not to attenuate more than 10
dB the signal at 1.5 GHz: for CT/100 this means 50 m maximum.
After the antenna is located, connect it to GPS with connector (7). The green GPS locked light (5)
turns on within 15 minutes (typically 1 minute); if not, try to press the white key by the light. If this
is not enough, the antenna should be located in another position.
Connect on the two sites the two DRTS.6 to the relays to be tested; in particular, connect relay trip
contacts to inputs C1 to C4 (see figure).
Doc. MIE10156 Rev. 11 Page 58/87
V, I V, I
TEST SETUP
Connect now GPS to DRTS.6. To this purpose, connect the black socket (8) to C5-8 common, and
the red socket (8) to C5. Connect DRTS.6 to the PC and select in Preferences the type of relay trip
contacts for C1– C4, and DC Voltage, 24 V, for C5-C8. Select also Debounce delay = 0 for C5-C8.
Note that selections for C1-C4 and C5-C8 can be different.
Select the pulse interval on switch (2): 30 s or more are a good choice, to avoid the risk to loose
synchronization during the test. It is possible now to start the test. The two operators should keep in
touch by phone, and start on the PC the test program they want to use.
Let us assume for example that the program is Z-PRO, with the Intertrip test selected. Both
operators can program the desired tests before starting the first one; then, they should press test
START on PC at approximately the same time. After this, they should press the GPS START/STOP
button (1): its light turns on, and the PULSE light (3) turns on as the first synchronization impulse is
generated; it will be applied after one to two selected periods. After this, impulses are generated at
the selected time interval.
When the two DRTS.6 sense the first pulse they execute the first test at the meantime, and provide
the first test result. Pressing test START on PC again the second test can be initiated, and so on until
all tests are over. START commands cannot be contemporary; they should be provided before the
next synchronization impulse.
Doc. MIE10156 Rev. 11 Page 59/87
1 2
GPS SYNCHRONIZER
PULSE
3
20 30
10 40
START/STOP
1 pps 5 60
4
GPS
5 PULSE INTERVAL
(seconds)
LOCKED
GPS ANTENNA
T0,5A 250V
PULSE
100-240V~ 50/60Hz 5W
8
00
12.1 Introduction
The optional amplifier AMI150 has the purpose to provide more power on current outputs, if the
power of the DRTS.6 is not enough; the software allows for the following selections.
. 9I: nine currents in all; six from DRTS.6, with ranges up to 15 A, and three from AMI-150, with
ranges up to 50 A.
. 6I: six currents in all; three from DRTS.6, with outputs in parallel so that ranges reach 30 A, and
three from AMI-150, with ranges up to 50 A.
. 3I: three currents from AMI-150, with ranges up to 50 A.
Physically, the AMI150 (see drawing) is made of a 19” container, 4 U high, with handle for ease of
transportation. All components are slide-in modules, that can be easily replaced for maintenance:
. N. 3 AMI-150 current amplifiers;
. N. 1 ALI 1K power supply.
Each amplifier has three connection sockets: one red and two black. The two black are bridged
between them, and are provided for ease of connection. The zero of the three amplifiers are
independent: the common connection is made by the metal bridge provided.
Before executing the test with the AMI150 check that the burdens of the relay under test are
compatible with the current output power. To this purpose, it is necessary to compare the burden
declared by the manufacturer to the following maximum loads.
Special care is to be taken when evaluating the burden, as the burden of connecting wires is to be
added to the relay burden. If the relay load is 2 VA at nominal current of 5 A, the relay burden
is 80 mOhm. In this case it is possible to test at 12.5 A only if the connection and cabling are
maximum 5 m long, with a cross section of 2.5 sq. mm at least, and if cables are tied together,
in order to minimize the reactive component.
For tests at 50 A, it is advisable to use connection cables with at least a cross section of 10 sq. mm.
In case it is desired to run tests at currents higher than 50 A, it is possible to connect all amplifiers in
parallel: it is possible to have 450 VA. However, the maximum load decreases to 0.02 Ohm.
If the problem is having more power at the current of 50 A or less, then connect all amplifiers in
series. In this instance it is possible to have something less than 450 VA because of minor
inaccuracies of current amplifiers in series. Considering 350 VA, maximum loads are the following.
When the output is not the maximum of the range, the maximum burden increases: at 50% of the
range the output power is three times the one available with one output. This is applicable to ranges
2.5 and 12.5 A: at 25 and 50 A range is automatically switched for outputs less than 50% of the
range. The following tables summarizes maximum burdens for the range of 2.5 A, and the
corresponding power. The table reports also the maximum voltage and the maximum error, that is
the value of 1% of the range applied to the output.
12.3.2 Power-on
Before connecting the relay, connect the AMI150 to the connector EXT. AMP. of the DRTS.6,
with the cable provided.
Then connect the DRTS.6 and AMI-150 to the mains, by means of the power supply cables
provided. The earth is connected to the supply plug. Be careful to have the earth on the supply,
as otherwise the DRTS.6 and AMI-150 would reach the voltage of 110 V (supply 220 V): this
is caused by noise suppression capacitors on mains supply.
Doc. MIE10156 Rev. 11 Page 63/87
Power on the AMI150 first, then the DRTS.6. At power on, the green light OK of AMI150 and of
DRTS.6 turn on: this confirms that the microprocessors operate correctly. At the meantime, the self
diagnostic procedure is initiated in both units. Also green lights (8) of the amplifiers will turn on.
The connection of the DRTS.6 and AMI150 to the relay under test depends upon the choice about
the AMI150 function.
With selection 3I, currents will be connected to sockets (6) of AMI150: current outputs of the
DRTS.6 are disabled, and SHOULD NOT BE CONNECTED.
All other signals (voltages, trip input, auxiliary outputs) shall be connected to the DRTS.6, as
explained in the former chapters.
With selection 9I, currents I1 – I6 will be connected to the DRTS.6, and currents I1-I3 (booster) to
the AMI150. Voltage outputs V1 to V3 are also available, while V4 is not available; all other
signals (trip input, auxiliary outputs) shall be connected to the DRTS.6, as explained in the former
chapters. Current ranges and outputs of the two units are up to 15 A for DRTS.6, and up to 50 A for
AMI-150.
With selection 6I, currents I1-I4; I2-I5; I3-I6 are paralleled on the DRTS.6, in order to have a total
of 30 A on one set, and 50 A on the other one. Voltage outputs V1 to V3 are also available, while
V4 is not available; all other signals (trip input, auxiliary outputs) shall be connected to the DRTS.6,
as explained in the former chapters.
If the red ! LED turns-on on the AMI150 and the error is on a current output, the red light (9) of
the AMI150 current amplifier in overload can turn on. Before continuing, it is necessary to press the
corresponding reset button (10).
At power off, turn off the AMI150 first; then the DRTS.6.
Doc. MIE10156 Rev. 11 Page 64/87
13.1 Introduction
The optional amplifier AMI-99 has the purpose to allow controlling nine currents at the meantime.
The unit can also be used to generate six currents rated 30 A 160 VA, by connecting in parallel the
outputs of DRTS.6. It is also possible to have three currents at 60 A 320 VA each, or one current at
180 A 720 VA.
Physically, AMI-99 (see drawing) is housed in a container that is the same as DRTS.6, 3 U high,
with handle for ease of transportation. Amplifiers are the same as those used in the DRTS.6, and
internally connected in parallel in order to have 30 A.
13.3.1 Power-on
Before connecting the relay, connect AMI-99 to the connector EXT. AMP. of DRTS.6, with the
cable provided. Connect also IN of DRTS.6 to IN of AMI-99 with the cable provided.
Then connect DRTS.6 and AMI-99 to the mains, by means of the power supply cord. The earth
is connected to the supply plug. Be careful to have the earth on the power supply cord, as
otherwise DRTS.6 and AMI-99 would reach the voltage of 110 V: this is caused by noise
suppression capacitors on mains supply.
Power on AMI-99 first, then DRTS.6. At power on, the front lights of both instruments turn on and
off as the self-diagnostic is executed; at the end of which, the OK LED’s of AMI-99 and of DRTS.6
turn on: this confirms that the microprocessors operate correctly. If DRTS.6 is powered-on first, an
error code can be displayed; in this instance, just press OK on the OK button of the P.C. display.
Before executing the test with AMI-99 check that the burdens of the relay under test are
compatible with the maximum load. To this purpose, it is necessary to compare the burden declared
by the manufacturer to the maximum load.
Special care is to be taken when evaluating the burden, as the burden of connecting wires is to be
added to relay current burden.
The connection of DRTS.6 and AMI-99 to the relay under test depends upon the choice about the
AMI-99 function.
Aside currents, all other signals (voltages, trip input, auxiliary outputs) shall be connected to
DRTS.6, as explained in the former chapters.
In this instance currents I1 – I6 will be connected to the DRTS.6, and currents I7-I9 to AMI-99.
DRTS.6 voltage outputs V1 to V3 are available, while V4 is not available. Current ranges and
outputs of the two units are independently set.
Maximum current is 15 A on DRTS.6 and 30 A on AMI-99; the maximum load is 350 mOhm for
DRTS.6 and 180 mOhm for AMI-99.
If it is necessary to perform a six phase test at 30 A, connect in parallel current outputs of DRTS.6:
maximum burden is 0.18 Ohm for all outputs.
DRTS.6
I1-I4 I7 AMI-99
I2-I5 I8
I3-I6 I9
IN IN
Paralleling of DRTS.6 outputs is easily performed using option PAI. Current outputs must be
connected in the order shown, as the program foresees this connection when computing current
outputs: maximum test current is 30 A per output.
Doc. MIE10156 Rev. 11 Page 66/87
If it is necessary to perform a three phase test at 60 A, connect in parallel current outputs of DRTS.6
to those of AMI-99: maximum power is 320 VA; burden is 0.09 Ohm for all outputs.
DRTS.6
I1-I4 I7 AMI-99
I2-I5 I8
I3-I6 I9
IN IN
Paralleling of DRTS.6 outputs is easily performed using option PAI. Current outputs must be
connected in the order shown, as the program foresees this connection when computing current
outputs.
Select 0° between currents, both on DRTS.6 and AMI-99. Connect all outputs among them and to
one end of the load; connect IN (DRTS.6) to IN (AMI-99), and to the other end of the load. The
corresponding maximum power is 760 VA; maximum load is 23 mOhm.
I2-I5 I8
I3-I6 I9
IN IN
The procedure to follow is the one explained for DRTS.6. At power off, turn off AMI-99 first; then
DRTS.6.
Doc. MIE10156 Rev. 11 Page 67/87
The option is made of a plug that fits into the mains, and that has two banana sockets for the
connection to the test set counting input. The purpose is to synchronize the outputs of two test sets
to the mains: as the synchronisation is repeated every 2 minutes, the test set stays locked to the
mains for the infinity.
The option includes a circuit that squares the sinusoidal mains waveform; the isolated output is a
square-wave with an amplitude of 18 V nominal, running at the mains frequency.
INP 2 INP 2
POWER
CABLE
MAINS
SYNCHRON. MAINS
SYNCHRON.
The outputs of the mains synchroniser have to be connected to the INP 2 sockets of both test sets.
The inputs should be selected with voltage; the voltage threshold is 5 V.
Start the program that allows performing the differential test with mains synchronisation: both test
sets will be locked to the mains. Now it is possible to apply the nominal current to both ends: as if
this is not at the meantime, just ignore the corresponding trip. This is the pre-fault situation
From this moment on, it is possible to perform any test, of the type healthy – fault – healthy: it will
be possible to explore the entire relay curve.
Doc. MIE10156 Rev. 11 Page 68/87
PIN N° SIGNAL
1 DCD
2 RXD
3 TXD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 --
DRTS.6 PC
PIN SIGN PIN SIGNAL
1 DCD 1 DCD
2 RXD 3 TXD
3 TXD 2 RXD
4 DTR 6 DSR
5 GND 5 GND
6 DSR 4 DTR
7 RTS 8 CTS
8 CTS 7 RTS
Doc. MIE10156 Rev. 11 Page 69/87
This appendix lists the suggested spare parts. The list is divided in two: main spare parts and
other spares. The separation follows the level of probability of the intervention.
N. DESCRIPTION CODE
1 FRONT.6 YWA11386
1 AMCO.6 YWA11374
1 AMTE .3 YWA11356
N. DESCRIPTION CODE
N. DESCRIPTION CODE
Error messages from the PC are listed in the following table. The table lists also the meaning of the
code, and the fault area or the cause of the fault.
1 - PARITY/FRAMING/OVERRUN CONNECTION
2 - NON-BCD CODE, LONGITUDINAL FIELD CONNECTION
3 - NON-BCD CODE, LRC FIELD CONNECTION
4 - NON-BCD CODE, ID PARAMETER FIELD CONNECTION
5 - INCORRECT LRC CONNECTION
6 - ETX PREMATURE CONNECTION
7 - ETX NOT ARRIVED CONNECTION
8 - NON-BCD CODE IN PARAMETER VALUE FIELD CONNECTION
9 - DROP IN DTR DURING TRANSMISSION CONNECTION
10 - FRAME LENGTH DOES NOT COMPLY CONNECTION
11 - ID PARAMETER CODE INCORRECT CONNECTION
12 - OVERFLOW BUFFER PARAMETERS CONNECTION
13 - UNDERFLOW BUFFER PARAMETERS CONNECTION
14 - START VALUES RECEIVED WHILE RUNNING SOFTWARE
15 - NEW VALUES RECEIVED WHILE RUNNING SOFTWARE
16 - REPEAT RECEIVED WHILE RUNNING SOFTWARE
17 - PARAMETER MEANINGLESS SOFTWARE
18 - PARAMETER VALUE OUT OF RANGE SOFTWARE
19 – NACK RECEIVED INSTEAD OF ACK SOFTWARE
20 - RECEIVED CHARACTERS DIFFERENT FROM ACK,NACK,STX SOFTWARE
21 – RECEIVE DATA FRAME TIMEOUT CONNECTION
22 – DATA FRAME READ ERROR CONNECTION
67 - IR OVERLOAD LOAD
69 - IS OVERLOAD LOAD
71 - IT OVERLOAD LOAD
75 - VR OVERLOAD LOAD
77 - VS OVERLOAD LOAD
79 - VT OVERLOAD LOAD
On connection pins provided it is possible to crimp wires with AWG size 20 to 16 (0.52 sq. mm. To
1.5 sq. mm.). BOLDED: connection of low level signals.
A
B P
C R N
S Y
D M
T Z X
E L
U W
F V K
G J
H
FRONT VIEW OF EXT. AMP. CONNECTOR
Doc. MIE10156 Rev. 11 Page 76/87
CABLE TO AMI-150
This cable connects DRTS.6 to AMI-150. DRTS.6 side: male pins; booster side: female pins.
This cable connects DRTS.6 to all other boosters. DRTS.6 side: male pins; booster side: female
pins.
2 34
1 33
36 68
35 67
2 24
1 25
27 49
26 50
17 14 15 14 13 12 10 9 6 5 6 2 3
OK
C4 C8 A4 V1 I1 I4 !
0 10 V--- 250 V~
ERR
ON
C3 C7 A3 V2 V0/V4 I2 I5
0 20 mA--- 20 A~
ANALOG INPUT
DRTS-6
C2 C6 A2 V3 I3 I6 AUTOMATIC RELAY TESTING
RS232 AND MEASUREMENT SYSTEM
VN ! IN IN
C1 C5 A1
125/300 V~ 15 A~
T16A 250V
250 V5~ A
C C
IMP1 IMP2
V~ V~ V---
250 V~ !
16
11 19 4 32 7 8 1
AMI150 PART-LIST
10 8 9 2 5
7 1
7) Fans.
8) Front panel.
9) Mains supply filter YWA11389.
10) LEDALI.6 signaling lights board YWA11385.
20) Control cards back-panel YWA11371.
21) PASSIVA printed wire board YWA31316, with connections to the back panel.
22) MICR-H YWA31300, with: microprocessor, memories, programmable logics.
24) RELE.6 YWA21373, with connectors for the amplifiers.
25) CONV-6 YWA21372, with connections to current amplifiers.
26) AMCO I7; I8; I9 YWA11374: one-phase current amplifiers.
29) ALIAUX.6 YWA11370, that generates the auxiliary DC voltage supplies.
30) FRONT.6 YWA11386, that generates two 300 V DC supplies.
31) Power supply back panel YWA11368.
49cm
N=3 64I MAS. 22µH
PASSIVA I/O6432 SUP.
68PIN EXP. AMTE.3 R_S
890 891 BPSEGN.6 MAS. 800 VR
5 891-10 LGND 18 I/O +200
0_D
810-7 810-1 120 R
9 891-4 TERRA 801 802 831 801 810-6 VS
803 -200 810-5 810-3 120 R
4 891-11 DTR 11316 21 50PIN
8 891-3 CTS 841 802 32OUT 0,5Q 10
3 891-12 TX 11346 34 MAS.
RTS MICR-H 22µH
4 7 891-2 VN
2 891-13 RX 801 810-2 BL
6 891-1 DSR 801
1 891-14 802 832 804 810-4 1Q
I/O6432 INF. 11356 27
CONN SERIALE 21300 22 VN
841
ESPANSIONE CONNETTORE CONV-6 803 20P 7cm AMTE.3 T_V4 22µH
801
800 835 +200 810-7 810-2
FEMM.
890 802 0_D 810-6
28cm VT
MISU 801 -200 810-5 120
NEUTRO_TENSIONE 23 8P 8cm 810-1 V4 R
11322 19 11372
800 20P 14cm 120
0,02/20A
10/250V
MISURA