Zig Zag Transformer - Manual Calculation
Zig Zag Transformer - Manual Calculation
33.00 kV 25.00 kA
Z0 = 0.000 Ω/Phase
R0 = 12.702 Ω/Phase
Grounding Type = Resistive
REF = 1500.00 A
1 Base MVA 1 MVA
2 C Factor 1.05
3 Rated kV 33.00 kV
4 C factor kV 34.65 kV
5 Base Ohms 1200.62 Ohms
6 Base Amps 16.66 A
7 Fault kA 25.00 kA
8 Fault kVA 1500.39 kVA
9 Fault MVA 1.50 MVA
10 Z(1)=Z(2) 0.666 p.u
11 REF 1500 A
12 I(G) 90.02 p.u. A
13 I(o) 30.01 p.u. A
14 Z(total) 0.033 p.u. Ohms
15 Z(total) - 2Z(1) -1.300 p.u. Ohms
16 In Ohms (Z0) ### Ohms/phase
17 KVA 17325 kVA
18 17 MVA