Electrical 23D.2: Bus, Behaves When

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

230.

25-5

Electrical Equipment - Course 23D.2

GENERATORS: PART 5
INFINITE BUS OPERATION

1. OBJECTIVE
The student must be able to:

1. Define an "infinite bus".

2. Explain how the current in a generator increases as


it is loaded.
3. Explain how a generator, connected to an infinite
bus, behaves when:
(a) it is supplying a .constant MW load and -its
exci ta tion is varied.

(b') its MW load is varied wi th the exci ta tion


re~aining constant.

2. INTRODUCTION
Lesson 230.22-1 dealt wi'l;h a generator operating on
no load and supplying an isolated system. This lesson
explains how a generator behaves when it is loaded onto
an infini te bus.

The next lesson explains how a generator behaves


when it is loaded onto a non-finite bus grid.

3. THE INFINITE BUS


3.1 Defini tion

By defini tion, an infinite bus has constant


voltage and frequency.
All generators, when loaded onto a power
system, will to some degree alter the system's
voltage and frequency_ However, when a small
generator is loaded on a large system, it will have
negligible effects on the vol tage and frequency and
consequently, wi th respect to the small generator,
the system behaves as an infinite bus.

August 1981 - 1 -
230.25-5

4. GENERATOR LOADED ON TO AN INFINITE BUS

4.1 Generator MW Loading Increased From Zero

When a generator is connected to an infinite


bus, its terminal voltage is the same as the infin-
ite bus voltage and therefore remains constant.
When more mechanical power is produced by the tur-
bine the generator converts this additional
mechanical power into additional active electrical
power P.
As the generator produces more active power P,
it also produces more current I a - This is explain-
ed by the relationship.
p = I3vL1a Cos 6.
It follows that as P increases (nVT is con-
stant) then I a Cos e must increase. Typically, the
magnitude of Cos e (power factor) will vary between
1.0 to 0.·8. Consequently, the magnitude of the
load current I a will increase almost in proportion
to an increase in load power P.

4.2 Generator on Constant MW Load, Excitation Varied

When a· generator is producing watts but no


vars, (1.0 pf) it is operating with optimum excita-
tion, ie, the excitation is just sufficient to
cause the generator to produce all active power and
no reactive power.

When a generator is on full load at 1.0 pf and


its excitation is varied, the flux produced by the
field also varies, see Figure 1.

A decrease in excitation will cause the gener-


ator to be underexcited for the constant MW load
and the power factor will become leading. This
effect was explained in the previous lesson.

It must be noted that reducing the excitation


will increase the load angle. Should this load
angle exceed 90° then pole slipping will result.

An increase in excitation will cause the gen-


erator to be overexcited for the constant MW load
and the power factor will become lagging. Again
this effect was explained in lessons 230.25-1 and
230.25-2.

- 2 -
230.25-5

The vector diagrams in Appendix 1 of this


lesson illustrate these effects.

Xd Infinite Bus
Constanf
Excitation
Varying Vr Voltage and
Frequency

Steam
Input Constant

Figure 1: Equivalent circuit excitation varying, MW load


constant.

4.3 Generator on Varying MW Load, Excitation Constant

FigLlre 2 shows a generator connected to an


infinite bus. The MW load is varied while the
exel tation is held constant.

Increasing the active power output from 75% of


full load at 1.0 pf, will cause IOClre current to
flow in the generator stator. This will cause more
armature reaction which will weaken the fluxes in·
the generator. The generator will become under-
excited. ie, it now has insufficient excitation for
it to operate at 1.0 pi. Consequently, the pi of
the generator will be leading and the generator
will consume vars.

Decreasing the active power output from 75%


full load at ,1.0 pf will cause less current to flow
giving less armature reaction. This will cause
less armature reaction which will strengthen the
fluxes in the generator. The generator is now
overexcited ie, the generator now has more than
enough excitation for it to operate at 1.0 pf, and
its pf will be lagging. Excessive excitation, for
a given MW load, will cause exessive production of
lagging vars.

This information is illustrated by the vector


diagram, see Appendix 2 of this lesson.

- 3 -
230.25-5

la
Xd In,finite Bus
Constant
Excitation Voltage and
Constant
Frequency

Steam
Input Varied

Figure 2: Equivalent circuit, excitation constant, MW load


varying

5. SUMMARY FOR A GENERATOR CONNECTED TO AN INFINITE BUS

(a) A generator, overexcited for a given MW load and


terminal voltage, operates at a lagging pf.
(b) A generator, underexcited for a given MW load and
terminal voltage operates at a leading pf.
(c) Increasing MW load on a generator with constant
excitation, will make the generator's power factor
become more leading.
An operator, when loading a generator, will have to
take care to ensure that adequate excitation is
provided. Failure to do this can cause the load
angle to exceed 90°. Pole slipping will result.
(d) Decreasing MW load on a generator with constant
exei tation, wi 11 make the generator I s power factor
become more lagging.
An operator, when unloading a generator, will have
to take care to ensure that excessive excitation is
not provided. Failure to observe this precaution
can give excessive fluxes which can cause excessive
prOduction of lagging vars.

- 4 -
230.25-5

ASSIGNMENT

1. By def ini ticn, what is an "inf in1 te Bus "? By defini-


ticn, what is a nnon-finite bus"?

2. A generator is supplying an infinite bus. Explain,


using labelled diagrams, why the power factor of the
generator becomes:
(a) more leading when the excitation is decreased.
( b) more lagging when the excitation is increased.
(e) I;\ore leading when the MW load is increased.
(d) more lagging when the MW load is decreased.

3. A generator has a manually controlled excitation


system. State the actions the operator must take to
ensure safe generator operation when MW loading is:
(a) increased
(b) decreased

4. A 540 MW generator is supplying a 4000 MW grid. Explain


briefly why the grid with respect to this generator,
will or will not behave as an infinite bus.

J .R.C. Cowling

- 5 -
:l30,25-5

APPENDIX 1: Vector diagram showing a generator on full load


(constant MW) with the excitation being varied.
Generator on an "infinite bus".

",
/
/ "
E
",
;'
/

Radii of
constant
/)1
--- r::
,
I
I
.excitation I
,~'!..2
I

Suffix 1 denotes excitation to give 1.0 pf at full load.


Suffix 2 denotes increased excitation giving lagging p£ at
full load,
Suffix 3 denotes reduced excitation giving leading pf at full
load.

Note the following:

( a) As the generator is on a inf ini te bus, VTl = V'l'2 =


T
( b) VIncreasing
" the excitation causes the power factor to
become more lagging.
(e) Decreasing the excitation causes the power factor to
become more leading.
(d) As the power factor becomes less than 1. a (lead or lag)
the current I a increases for the same MW load.
(e) As the excitation is increased, 0 decreases and vice
versa.

As Cos e is less than 1.0 in Suffix 2 and 3 cases, it follows


that I a 2 and I a 3 must increase in magnitude relative to I a at
unity pf.

- 1 -
230.25-5

APPENDIX 2:- Vector diagram showing a generator with its load


varying, excitation held constant. Generator on
infinite bus.

,/
,/ la,Xd
,,"""_ _';"_ _...l~ ~~~T,=VT2=VT3

.................
"
'lI.7
I
I
E3 I
I
I la, I
I
"- Constant
I
excitation la2
radius

Suffix 1 denotes excitation set to give 1.0 pf at 75% load.


Suffix 2 denotes load reduced to 50% with constant excita-
tion.
Suffix 3 denotes load increased to 100% with constant excita-
tion.

Note the following:

(a) As the generator is on an infinite bus, VT1 , - VTZ '


VT are constant.
( b) Inrlreasing the load MW causes more current l a to flow
giving a larger value of IaXd and vice versa.
( c) Increasing load MW causes the current l a to become roore
leading.
(d) Decreasing MW load causes the current l a to become more
lagging.
(e) As the load increases, 0 increases and vice versa.

- 1 -

You might also like