Protective Device Settings Report: Project: Date

The document provides settings for various protective devices including fuses, relays, and low voltage circuit breakers. It lists manufacturer, model, ratings, and pickup/trip settings for overcurrent, ground fault, and other protection functions for equipment across a transmission and distribution system. Settings are provided according to common protection curves like IEC extremely inverse to coordinate selective operation of the protective devices during faults.

Uploaded by

rian0201
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
527 views6 pages

Protective Device Settings Report: Project: Date

The document provides settings for various protective devices including fuses, relays, and low voltage circuit breakers. It lists manufacturer, model, ratings, and pickup/trip settings for overcurrent, ground fault, and other protection functions for equipment across a transmission and distribution system. Settings are provided according to common protection curves like IEC extremely inverse to coordinate selective operation of the protective devices during faults.

Uploaded by

rian0201
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Protective Device Settings Report

Project: Date: 05-23-2017

Location: Revision: Base

Contract:

Filename: C:\Users\Dougen\Desktop\GMC\E-Model_2\SLD
with Proposed Settings\SLD.OTI

Page 1 of 6
Protective Device Settings - Fuse

Fuse ID Manufacturer Model Max Voltage Speed Size Cont. Amp

TR-N1-F S&C SM-4 17 kV Slow 40E 40

TR-N2-F S&C SM-4 17 kV Slow 40E 40

N12-F S&C SM-4 17 kV Slow 100E 100

TR-FDM-F S&C SM-4 17 kV Slow 100E 100

TR-SILO-F S&C SM-4 17 kV Slow 100E 100

TR-FM-B-F S&C SM-4 17 kV Slow 200E 200

TR-G-F S&C SM-4 17 kV Slow 100E 100

TR-E-F S&C SM-4 17 kV Slow 150E 150

TR-FM-C-F S&C SM-4 17 kV Slow 150E 150

TR-FM-A-F S&C SM-4 17 kV Slow 150E 150

PP-F1 S&C SMD-2B 72.5 kV Slow 300E 300

PP-F2 S&C SMD-2B 72.5 kV Slow 300E 300

PP-F3 S&C SMD-2B 72.5 kV Slow 300E 300

* Library settings have been modified.

Page 2 of 6
Protective Device Settings - Relay
K
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam) Directional (67) Preload.
PT / Base Multip.
Device Trip Level
Relay ID Manufacturer Model Current Curve Block
CT Function Element /Stage Prim. Time Prim. Time
Setting Pickup Pickup TOC by Direction MTA Polariz. Setting Setting
Ratio Amps Delay Amps Delay
IOC

TR1-LV-R AREVA P121 500:5 Overcurrent Phase OC1 IEC - Extremely Inverse 1.000 500.000 0.150

TR1-LV-R AREVA P121 500:5 Overcurrent Ground OC1 IEC - Extremely Inverse 0.720 360.000 0.300

SPAJ
TR1-HV-R ABB 140C(SPCJ 100:5 Overcurrent Phase OC1 IEC - Extremely Inverse 1.000 100.000 0.420 20.000 2000.00 0.15 s
4D29)
SPAJ
TR1-HV-R ABB 140C(SPCJ 100:5 Overcurrent Ground OC1 IEC - Very Inverse 0.200 20.000 0.210 2.000 200.00 0.15 s
4D29)

NGCP-50/51 ABB DPU-2000R 500:5 Overcurrent Phase OC1 2.500 250.00 0.4 s

NGCP-50/51 ABB DPU-2000R 500:5 Overcurrent Ground OC1 2.500 250.00 0.4 s

FM-A-R LSIS Gipam-10 600:5 Overcurrent Phase OC1 IEC-EI 1.900 228.000 0.170 20.000 2400.00 0.04 s

FM-A-R LSIS Gipam-10 600:5 Overcurrent Ground OC1 IEC-EI 0.500 60.000 0.050

FM-C-R ABB REJ 603 200:1 Overcurrent Phase OC1 IEC - Extremely Inverse 1.150 230.000 0.230

FM-C-R ABB REJ 603 200:1 Overcurrent Ground OC1 IEC - Extremely Inverse 18.000 36.000 1.400 400.000 800.00 0.05 s Enabled

Sulzer-51P GEC TA 3220 300:5 Overcurrent Phase OC1 Definite Time 5.500 330.000 6.400 10.000 600.00 0.2 s

CAT-51P GEC TA 3220 80:5 Overcurrent Phase OC1 Definite Time 7.750 124.000 6.400 11.000 176.00 0.2 s

IEC - Extremely Inverse


ENG-R Merlin Gerin Sepam 40 300:5 Overcurrent Phase OC1 1.000 300.000 0.130
(TMS)

IEC - Extremely Inverse


ENG-R Merlin Gerin Sepam 40 300:5 Overcurrent Neutral OC1 0.200 60.000 0.130
(TMS)

FM-B-R LSIS Gipam-10 300:5 Overcurrent Phase OC1 IEC-EI 4.300 258.000 0.280

FM-B-R LSIS Gipam-10 300:5 Overcurrent Ground OC1 IEC-EI 1.000 60.000 0.060

Page 3 of 6
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device

Long Time Short-Time / Ground Inst. / Maintenance

Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)

CAT-CB LSIS AS-32E P Type Phase 1 3200 Time delay 20 10 32000 0.4 OUT 15 48000
*

GARD-LVCB Mitsubishi S Type 2000 0.8 Phase 0.8 1280 50 2 3200 0.2 IN 12 19200
*

GARD-LVCB Mitsubishi S Type 2000 0.8 Ground 0.1 200 0.3


*

AGR-L (LT
ENG-LVCB Terasaki 4000 4000 Phase 1 4000 I^2 t 5 1.5 6000 0.1 IN 10 40000
Curve)
*

AGR-L (LT
ENG-LVCB Terasaki 4000 4000 Ground 0.3 1200 3 IN
Curve)
*

AGR-L (LT
FMC-LVCB Terasaki 4000 4000 Phase 1 4000 I^2 t 5 1.5 6000 0.05 IN 14 56000
Curve)
*

AGR-L (LT
FMC-LVCB Terasaki 4000 4000 Ground 0.3 1200 3 IN
Curve)
*

FMA-LVCB LSIS AS-40E P Type Phase 1 4000 Time delay 0.5 8 32000 0.4 OUT 6 24000
*

FMA-LVCB LSIS AS-40E P Type Ground 0.8 3200 0.4 OUT


*

FMB-LVCB ABB E6H SACE PR112 5000 Phase 1 5000 3 2.6 13000 0.4 OUT 6.1 30500
*

FMB-LVCB ABB E6H SACE PR112 5000 Ground 0.2 1000 0.1 OUT
*

RMS-9
FDM-LVCB General Electric 4000 4000 Phase 0.95 3800 1 1.5 6000
(LVPCB)
*

AGR-L (LT
SILO-LVCB Terasaki 4000 4000 Phase 0.95 3800 I^2 t 0.5 2 8000 0.05 IN 6 24000
Curve)
*

AGR-L (LT
SILO-LVCB Terasaki 4000 4000 Ground 0.3 1200 3 IN
Curve)
*

4000-
Cummings-CB Mitsubishi S Type 0.8 Phase 0.8 2560 50 4 12800 0 IN 4 12800
SSC
*

4000-
Cummings-CB Mitsubishi S Type 0.8 Ground 0.2 800 0.3
SSC
*

Page 4 of 6
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device

Long Time Short-Time / Ground Inst. / Maintenance

Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)

Fixed Fixed LT
N2-LVCB Moeller AE800 800 0.8 Phase 640 6 4800
Pickup Band
*

Cummings-CB2 LSIS AS-20E N Type 1 Phase 1 2000 Time delay 16 10 20000 0.4 OUT 10 20000
*

Cummings-CB2 LSIS AS-20E N Type 1 Ground 0.6 1200 0.4 OUT


*

* Library settings have been modified.

Page 5 of 6
Protective Device Settings - Low Voltage Circuit Breaker with Thermal-Magnetic Trip Device

Breaker Thermal Magnetic (Inst.)

LVCB ID Manufacturer Trip Trip


Model Size Setting Setting
(Amps) (Amps)

N1-LVCB K Moeller 72% 720.000 3000Amps 3000.000