FB 1200
FB 1200
FB 1200
Returning Equipment
If you need to return any equipment to Remote Automation Solutions, it is your responsibility to ensure that the
equipment has been cleaned to safe levels, as defined and/or determined by applicable federal, state and/or
local law regulations or codes. You also agree to indemnify Remote Automation Solutions and hold Remote
Automation Solutions harmless from any liability or damage which Remote Automation Solutions may incur or
suffer due to your failure to ensure device cleanliness.
Grounding Equipment
Ground metal enclosures and exposed metal parts of electrical instruments in accordance with OSHA rules and
regulations as specified in Design Safety Standards for Electrical Systems, 29 CFR, Part 1910, Subpart S, dated: May
16, 1981 (OSHA rulings are in agreement with the National Electrical Code). You must also ground mechanical
or pneumatic instruments that include electrically operated devices such as lights, switches, relays, alarms, or
chart drives.
Contents
Section 1: Introduction .............................................................. 1
1.1 Safety Labels .................................................................................................................. 3
1.2 Features ........................................................................................................................ 3
1.3 FB1200 Flow Computer Models ..................................................................................... 4
1.3.1 FB1200 Flow Computer – With Sensor .............................................................. 4
1.3.2 FB1200 Flow Computer – No Sensor Version..................................................... 5
1.4 Central Processing Unit (CPU) ........................................................................................ 5
1.4.1 Memory ............................................................................................................ 5
1.5 Explosion-proof Enclosure.............................................................................................. 5
1.6 I/O ................................................................................................................................. 6
1.7 Power Options ............................................................................................................... 7
1.8 Communications ........................................................................................................... 7
1.9 Human-Machine Interface (HMI) Module ....................................................................... 8
1.10 Mobile SCADA ............................................................................................................... 8
1.11 Software Tools ............................................................................................................... 9
1.12 Base Firmware ............................................................................................................... 9
Contents iii
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
iv Contents
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Contents v
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Section 1: Introduction
This section covers the following topics:
Safety Labels
Features
FB1200 Flow Computer Models
Explosion-proof Enclosure
I/O
Power Options
Communications
Human-Machine Interface (HMI) Module
Mobile SCADA
Software Tools
Base Firmware
The Emerson FB1200 flow computer measures pressure, differential pressure, and temperature for
one or two meter runs of natural gas. This manual describes how to install and configure the
Emerson FB1200 flow computer hardware.
For information on using the FBxConnect configuration software, see the online help that
accompanies FBxConnect.
Introduction 1
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1 HMI module
2 Front end cap (cover)
3 Data plate
4 Rear end cap (cover)
5 Conduit fittings
6 Enclosure
7 Sensor module
2 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
DANGER
MAY CAUSE DEATH
WARNING
DANGER TO PERSONNEL AND EQUIPMENT
CAUTION
MAY CAUSE INJURY TO PERSONNEL OR DAMAGE EQUIPMENT
SAFETY FIRST
General instructions and safety reminders.
1.2 Features
The FB1200 flow computer includes the following key features:
Enclosure suitable for use in Class I Division 1 explosion proof and Ex d Zone 1 flame- proof
environments.
Enclosure suitable for use in Class I Division 2 non-incendive and Ex nA Zone 2 non-
sparking environments.
Integral multi-variable sensor for measurement of Pressure (P) and Differential Pressure
(DP).
Connections for customer-supplied resistance temperature detector (RTD) for
measurement of temperature (T).
Introduction 3
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Support for a second meter run through communication with a separate external
transmitter.
Base I/O consists of two on-board channels you can individually configure as either digital
input (DI), digital output (DO) or pulse input (PI) and two on-board I/O channels you can
individually configure as either analog input (AI) or analog output (AO). Optional 6-channel
expansion I/O board available.
Power from a DC power supply, or an optional lead acid battery/solar panel combination.
Serial communication options for RS-232, RS-422, and RS-485.
Ethernet.
HMI module with optional display and back light for local operator interaction.
Optional Wi-Fi® transceiver (802.11 b/g) for field technician to access the flow computer
from a laptop without physical cable connection.
Application software supports AGA3, AGA8, ISO 5167, ISO 6976, and API 21.1 calculations
in either U.S., metric, or other natural gas standard units.
4 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1.4.1 Memory
The flow computer includes both static and flash memory.
Memory Usage
The four conduit entry points are ¾ in NPT pipe threaded holes that permit entry of field conduit
for I/O and communication wiring. ATEX installations use a ¾ in NPT to M20 thread reducer.
Unused apertures shall be closed with suitable blanking elements.
Introduction 5
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
The FB1200 can operate in an unprotected outdoor environment. Wiring for I/O, communications,
and power enters the enclosure through the four conduit fittings with appropriate protective seals
and connects to the terminal plate.
The front end cap (cover) provides a viewing window for the HMI module. You can access the
terminal plate by removing the rear end cap (cover).
The FB1200 has North American certification for Class I Division 1 Groups C and D (explosion proof)
and Class I Division 2 Groups A, B, C and D (non-incendive) hazardous locations or non-hazardous
locations. See Appendix A and Appendix B for more information.
The FB1200 has European certification for EExd Zone 1 (flame proof) and EExd Zone 2 (non-
sparking) hazardous locations or non-hazardous locations. See Appendix C and Appendix D for more
information.
Details on certification information are included on the data plate screwed to the top of the
enclosure.
1.6 I/O
The flow computer comes with base I/O from both the CPU and the built-in multi-variable (MV)
sensor.
Pressure (P) input from the MV sensor, Differential pressure (DP) input from the MV
sensor, connections for temperature (T) input from a customer-supplied RTD – or - a
single Static Pressure Sensor.
Two on-board I/O channels that you can individually configure as either digital input (DI),
digital output (DO), or pulse input (PI)
Two on-board I/O channels that you can individually configure as either analog input (AI)
or analog output (AO)
An optional 6-channel expansion I/O board includes:
Four I/O channels that you can individually configure as either digital inputs (DI), digital
outputs (DO), or pulse inputs (PI)
Two I/O channels that you can individually configure as either analog inputs (AI), or analog
outputs (AO)
MV (P, DP, T) or Static Pressure Sensor MV (P, DP, T) or Static Pressure Sensor
6 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Important
Only use batteries supplied with the flow computer or sold by Emerson Remote Automation
Solutions as spare parts for this flow computer. If you substitute a battery you obtain elsewhere
you will void your certification unless it is the identical part from the same manufacturer as
that supplied with the flow computer from Emerson.
Option Usage
External DC Power
5.7 Vdc to 30 Vdc external supply (Max power at 10 watts)
Supply
1.8 Communications
The flow computer includes three serial communication ports and one Ethernet port.
The Ethernet port is an RJ-45 connector. A maximum of six concurrent TCP connections (sockets)
are supported through the Ethernet port.
The serial ports allow communication using DNP3, Modbus, BSAP, and ROC protocols.
Serial communications
COM1
Software-selectable for RS-232, RS- RS-232, RS-422, or RS-485 communication to host or
422, or RS-485 operation other devices. 4-wire used with external radio.
4-wire
Serial communications
COM2
Software-selectable for RS-232, or RS- RS-232 or RS-485 communication to host or other
485 operation devices.
2-wire
Serial communications
COM3 Software-selectable for RS-232, or RS- RS-232 or RS-485 communication to host or other
485 operation devices.
2-wire
Introduction 7
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
The HMI module includes four LEDs to provide status information. Units with the display include
four infrared (IR) buttons for operator interaction. To conserve power, the HMI module enters sleep
mode after a period of inactivity. The operator wakes up the device by holding a finger against the
front cover glass over the Hold to Wake button (the left-most button).
Note
If your flow computer does not include the LCD option (shown in Figure 1-4), you still have the
status LEDs and a single IR button for waking up the device (shown in Figure 1-5).
8 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
This capability allows an operator to potentially remain outside the hazardous location and still
communicate with the flow computer. The operator's laptop must have Wi-Fi® capability, line-of-
sight access to the HMI module, and must be loaded with FBxConnect configuration software.
Once connected, the operator can view process values, edit configuration parameters, and collect
logs.
Note
The Mobile SCADA electronics reside inside the HMI module.
Introduction 9
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
The firmware maintains the following sets of data values for logging purposes:
Indicated volume
Corrected (standard) volume
Mass
Energy
The firmware supports a fallback mode when a process variable's value is questionable. The fallback
options can be one of the following:
10 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Section 2: Installation
This section covers the following topics:
Hazardous Locations
Environmental Specifications
Required Tools
Site Considerations
General Wiring Guidelines
Removing the Front or Rear End caps
Replacing the Front or Rear End caps
Mounting the Enclosure
Grounding the Device
Terminal Plate
Power Modes
Connecting Power
The flow computer ships from the factory fully assembled, except for the optional solar panel
assembly.
For North America the FB1200 has certifications for Class I, Division 1 (Groups C & D) explosion-
proof, Class I Division 2 (Groups A, B, C & D) non-incendive, and non-hazardous locations only.
Appendix A contains special information for Class I Division 2 installations; Appendix B contains
special information for Class I Division 1 installations.
For Europe the FB1200 has certifications for Ex d Zone 1 flame-proof and for Ex nA Zone 2 non-
sparking installations and non-hazardous locations only. Appendix C contains special information
for Ex nA Zone 2 installations; Appendix D contains special information for Ex d Zone 1 installations.
All certifications are listed on the data plate located on the top of the device.
Installation 11
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Specification Range
Tool Use
3 mm hexagonal wrench For screw for M4 x 0.7 end cap retaining clamp (ATEX
required)
High-wattage soldering iron and solder For tinning ground connection wire
1/8 inch flat-head screwdriver For 5.08 mm pitch terminal block connections
1/16-inch flat head screwdriver For 3.81 mm pitch terminal block connections
12 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Ensure the installation location provides easy access to the HMI module.
If your unit includes the optional solar panel, ensure the installation location provides
sufficient space to mount the solar panel and adequate sunlight to charge the battery.
If your unit includes the optional Mobile SCADA ensure the installation location provides
line-of-sight access to the transceiver.
Installation 13
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
14 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
The 5.08 mm pitch terminal blocks accommodate wire between 28 and 12 AWG; the 3.81 mm
pitch terminal blocks accommodate wire between 28 and 14 AWG.
When making a connection, insert the bare end of the wire (approx. 1/4" max) into the
clamp adjacent to the screw and secure the screw.
To prevent shorts, ensure that no bare wire is exposed. If using stranded wire, tin the bare
end with solder to prevent flattening and improve connectivity.
Allow some slack in the wire while making terminal connections. Slack makes the wires
more manageable and helps minimize mechanical strain on the terminal blocks.
Use twisted pair, shielded and insulated cable for communication and I/O wiring to
minimize signal errors caused by electromagnetic interference (EMI), radio frequency
interference (RFI) and transients. When using shielded cable, ground all shields at only one
point in the appropriate system. This prevents circulating ground current loops that can
cause signal errors.
1 End Cap
2 Screw
3 Retaining Clamp
Installation 15
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
To loosen or tighten the screw, use a 3mm hexagonal wrench. When tightening, torque to 12 in-lbs
(1.4 N m).
Note
If you need more leverage place a long screwdriver or other appropriate tool across the two
notches in the end cap to act as a pry bar (see Figure 2-6).
Figure 2-6: Removing or Tightening the End Cap with Long Screwdriver
16 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
3. Unscrew the end cap turning it counter-clockwise until it comes off. Set it aside in a safe
location.
Figure 2-8: Front (left) and Rear (right) End Caps Removal
Important
When replacing the rear end cap, ensure wires connecting to the terminal plate do not get
crimped or caught between the end cap threads and the enclosure.
3. Screw the end cap clockwise (eight full turns) until it is tightly sealed to the enclosure.
4. Replace the retaining clamp (if required). (See Section 2.6.1)
Note
If you need more leverage place a long screwdriver or other appropriate tool across the two
notches in the end cap to act as a pry bar (see Figure 2-6).
Installation 17
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Direct mount installations use either a traditional mounting kit or a coplanar mounting kit. Indirect
mount installations use an inline mounting kit.
Only use bolts supplied with the flow computer or sold by Emerson Remote Automation Solutions
as spare parts. Refer to the figure for common flow computer assemblies with the bolt length
required for proper flow computer installation.
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
Note
For all other manifolds, contact your Emerson Local Business Partner (LBP).
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on
the head of the bolt and referencing the figure. If bolt material is not shown in the figure, contact
your local Emerson Remote Automation Solutions representative for more information.
Figure 2-10: Transmitter with Coplanar Flange and Optional Flange Adapters
18 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Figure 2-11: Transmitter with Traditional Flange and Optional Flange Adapters
1. Carbon steel bolts do not require lubrication. Stainless steel bolts are factory-coated with a
lubricant to ease installation. Do not apply any additional lubricant when installing either
type of bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See Table 2-3 for initial
torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See Table 2-3 for
final torque value.
5. Verify that the flange bolts protrude through the sensor module before applying pressure.
Table 2-3: Torque Values for the Flange and Flange Adapter Bolts
Bolt
Head markings Initial Torque Final Torque
Material
Installation 19
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1 Bolt
2 Sensor module
1 Flange
2 O-ring
3 Square PTFE-based profile
4 Round Elastomer profile
1. Whenever the flange or adapters are removed, visually inspect the O-rings.
2. Replace the O-rings if there are any signs of damage, such as nicks or cuts.
3. If the O-rings are replaced, re-torque the flange bolts and alignment screws after installation
to compensate for seating of the O-rings.
20 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
Installation 21
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
22 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Important
Never rotate the housing more than 180 degrees from its original (as-shipped) position. Over-
rotation can break electronics within the unit.
Installation 23
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
24 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1 Ground Lug
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
Once you have installed the unit, run a ground wire between the ground lug and a known good
earth ground. You route the ground wire through one of the conduit fittings.
Use stranded copper wire to earth ground, and keep the length as short as possible.
Clamp or braze the ground wire to the ground bed conductor (typically a stranded copper
AWG 0000 cable installed vertically or horizontally).
Using a high-wattage soldering iron, tin the wire ends with solder before you insert them into
the chassis ground lug.
Run the ground wire so that any routing bend in the cable has a minimum radius of 30.5 cm
(12 inches) below ground and 20.4 cm (8 inches) above ground.
For more information on grounding or if your installation uses cathodic protection, refer to Site
Considerations for Equipment Installation, Grounding, and Wiring (D301452X012).
Installation 25
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
The terminal plate’s appearance varies depending upon whether or not you have the optional 6-
channel expansion I/O board installed with 3.81 pitch connections; when it is installed there are
eight or nine connections per terminal blocks instead of six 5.08 pitch connections. Compare your
device to the pictures to see which terminal plate you have.
26 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Installation 27
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
mode when the communication period is over. A serial connection to a remote 4088B MVS can
occur in low power mode.
The local display (HMI module) with Mobile SCADA and WiFi uses additional power. You can
configure it in FBxConnect to shut down after a period of inactivity.
Table 2-4: Typical Power Usage – Low Power Mode at Room Temperature
Power
Usage
Description
(mW) at
6.1Vdc
82
Historical configuration supports maximum of:
8 averages
24 Station 1 & Station 2 history points (Group 4/Group 5)
10 User Periodic history points (Group 1)
Important
If you increase the number of history points/averages beyond any of the maximum limits in
Table 2-4, the flow computer cannot operate in low power mode and automatically runs in
standard power mode.
28 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
WiFi is active
6-channel expansion I/O board installed and enabled in the flow computer; if board installed
but disabled in FBxConnect, can remain in low power mode
Table 2-5: Typical Power Usage – Standard Power Mode at room temperature
Installation 29
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Power connections are made through conduit fittings to the terminal plate. Remove the rear end
cap for access to the terminal plate.
When power comes from an external DC supply, connect using the +DCIN and –DCIN terminals.
Use standard copper wire (#18 AWG minimum). The device supports both 12V and 24V power
supplies. It accepts DC voltage from 5.7 to 30V; the amount of power required varies depending
upon the options used.
30 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
When power comes from an internal battery pack, the battery pack plugs into one of two
connectors.
Restriction
The solar panel and lead acid battery combination cannot be used with ATEX/IECEx applications.
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
Attaching mounting hardware to the solar panel (if not attached prior to shipment).
Installation 31
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Setting the tilt angle of the panel for maximum solar exposure.
Attach aluminum tilt brackets (Item 2) to solar panel using the provided pan head screws
(Item 3), hex nuts (Item 10 in Figure 2-23), and #10 lock washers (Item 9 in Figure 2-23).
Apply Loctite 222 threadlocker sparingly to threads of hex nuts (Item 6). Attach mounting
bracket to tilt brackets using provided hex nuts (Item 6), hex bolts (Item 5), washers (Item
4), and spring lock washers (Item 7). The spring lock washer goes between the washer and
the nut. Torque to 30 in-lbs (3.4 N m).
32 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
7 5/16 flat spring lock washer (2) only one visible; placed on bolt between washer and
nut
8 mounting bracket
Restriction
The solar panel and lead acid battery combination cannot be used with ATEX/IECEx applications.
The integral mount solar panel cannot be used in a Class I Division 1 area; C1D1 solar panels must
be remote mounted with the solar panel in a safe area.
1. Apply Loctite® 380™ Black Instant Adhesive to threads of elbow pipe (Item 15 in Figure 2-20).
Attach elbow pipe (Item 15) to the flow computer conduit opening (Item 16); torque to 50 in-
lbs (5.6 N m).
3. Attach pipe (Item 14) to elbow pipe (Item 15). Torque to 50 in-lbs (5.6 N m).
4. Attach pipe cap (Item 11) to top of pipe (Item 14). Torque to 50 in-lbs (5.6 N m).
6. Attach solar panel assembly to pipe (Item 14) using U-bolt (Item 12).
7. Adjust swivel and tilt angle for maximum solar exposure (see Section 2.13.5).
Installation 33
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
34 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Restriction
Battery power is not allowed in ATEX/IECEx applications.
2. Attach solar panel assembly to pole using U-bolt (Item 12). Torque to 30 in-lbs (3.4 N m).
3. Adjust swivel and tilt angle for maximum solar exposure (see Section 2.13.5).
Installation 35
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
When power comes from a solar panel/lead acid battery combination, connect using the +SPIN and
–SPIN terminals and standard copper wire (#18 AWG minimum).
Restriction
Battery power is not allowed in ATEX/IECEx applications.
36 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
The mounting brackets allow you to adjust the solar panel for maximum solar exposure. You can
adjust the swivel of the panel by adjusting the U-bolt.
Point the solar panel surface due south (in the northern hemisphere) or due north (in the
southern hemisphere) at an angle determined by the latitude of the site. Table 2-6 shows
the angle (from horizontal) at which you should install the solar panel to maximize annual
energy output. At most latitudes, you can improve performance by reducing the angle
during the summer and increasing the angle during the winter. If no seasonal adjustments
in panel direction are needed then adjust the position for the worst-case December-
January angle.
Solar insolation is the amount of solar energy in hours received each day by an optimally
tilted panel during the worst month of the year. An insolation rating of one hour means
that the site, on average, would receive one hour of solar energy at the panel's rated power
level (1000W/m2 per day). This rating varies from less than one hour in northern Canada to
more than six hours in the Sahara Desert.
Installation 37
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
The communication ports allow you to connect either to a PC or laptop running FBxConnect
software or to other devices. If your application measures two meter runs, you’ll require a
dedicated port for communication to the external transmitter for the second meter run.
You access the three serial communication ports and the Ethernet port on the terminal plate under
the rear end cap.
You route communication cables through the conduit fittings and connect the cables on the
terminal plate.
38 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
When connecting COM1 to another device using RS-232, use a cable with configurations as shown
in Figure 2-27:
RS-232 Port
(COM1)
on FB device
RS-232 Port
on external device
RS-232 Port
(COM1)
on FB device
RS-232 Port
on external device
Installation 39
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
When connecting COM1 to another device using RS-422, use a cable with configurations as shown
in Figure 2-28:
RS-422 Port
(COM1)
on FB device
RS-422 Port
on external device
RS-422 Port
(COM1)
on FB device
RS-422 Port
on external device
40 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
When connecting COM1 to another device using RS-485, use a cable with configurations as shown
in Figure 2-29:
RS-485 Port
(COM1)
on FB device
RS-485 Port
on external device
RS-485 Port
(COM1)
on FB device
RS-485 Port
on external device
Regardless of the interface standard (RS-232, RS-422, or RS-485) you must use FBxConnect to
configure the port for proper usage.
Installation 41
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Figure 2-30: Connecting a Device to COM2 or COM3 Using RS-232 – Optional I/O present
RS-232 Port
(COM2)
on FB device
RS-232 Port
on external device
RS-232 Port
(COM3)
on FB device
RS-232 Port
on external device
42 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Figure 2-31: Connecting a Device to COM2 or COM3 Using RS-232 – No optional I/O
COM2 does not have its own GND terminal. Use either GND terminal on the COM1 terminal
block.
RS-232 Port
(COM2)
on FB device
RS-232 Port
on external device
COM3 does not have its own GND terminal. Use either GND terminal on the COM1 terminal
block.
RS-232 Port
on external device
RS-232 Port
(COM3)
on FB device
Installation 43
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
When connecting COM2 or COM3 to an RS-485 port on another device (for example, a
transmitter), use a cable with configurations as shown in Figure 2-32:
Figure 2-32: Connecting a Device to COM2 or COM3 Using RS-485 – Optional I/O present
RS-485 Port
(COM2)
on FB device
RS-485 Port
on external device
RS-485 Port
(COM3)
on FB device
RS-485 Port
on external device
44 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Figure 2-33: Connecting a Device to COM2 or COM3 Using RS-485 – No optional I/O
COM2 does not have its own GND terminal. Use either GND terminal on the COM1 terminal
block.
RS-485 Port
(COM2)
on FB device
RS-485 Port
on external device
COM3 does not have its own GND terminal. Use either GND terminal on the COM1 terminal
block.
RS-485 Port
on external device
RS-485 Port
(COM3)
on FB device
Regardless of the interface standard (RS-232 or RS-485), you must use FBxConnect to configure
the port for proper usage.
Installation 45
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1 Ethernet Port
Note
The default IP address for the Ethernet port is 192.168.1.10.
The default port is 20000.
Connect to an Ethernet switch using the appropriate Category 5 shielded patch cable.
46 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Note
If you ordered Ethernet, the unit ships with Ethernet enabled. If you need to operate the device in lower power
mode, you must disable Ethernet. Jumper J10 on the CPU module determines whether Ethernet is enabled or
Ethernet is disabled (lower power mode). See the CPU Module Field Replacement Guide (D301802X012) for
information on how to open the unit to gain access to the CPU module.
Installation 47
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Analog Inputs
Analog Outputs
Digital Inputs
Digital Outputs
Pulse Inputs
Connecting the RTD
Connecting a Rosemount 4088B Transmitter For Use in a Second Meter Run
I/O in the FB1200 flow computer comes from the integrated MVT sensor and RTD connector, the
CPU board, as well as from the optional 6-channel expansion I/O board.
Note
When using a digital output to drive an inductive load (such as a relay coil), place a suppression
diode across the load. This protects the DO from the reverse Electro-Motive Force (EMF) spike
generated when the inductive load is switched off.
Figure 3-1: Base I/O On CPU (when optional I/O also present)
expansion I/O board, there are two additional channels you can individually configure as either AIs
or AOs.
Note
No external resistor is required for a current (mA) device. You can apply a 250 ohm resistor using
analog input configuration selections in FBxConnect.
When configured as analog inputs, the channels have the following characteristics:
0 to 4 as follows:
0 to 21 mA range (@24Vdc), or 0 to 5.25V
1 or 2 non-isolated channels on CPU board
Externally powered
(AIAO1 and AIAO2) always present. You can
Factory calibrated (re-calibration is
Analog configure one, both, or neither as AIs.
unnecessary for at least 3 years)
Input (AI) 1 or 2 additional non-isolated channels on
Signal conditioning
optional 6-channel expansion I/O board
When you configure a channel as an AI it
(AIAO3 and AIAO4). If present you can
cannot be used as an AO
configure one, both, or neither as AIs.
3.1.1 AI Wiring
Wire analog inputs as shown below:
Figure 3-4: 4-20 mA Analog Input (AI) Wiring (Base I/O when Optional I/O Module also
present)
Note: Analog input wiring for AIAO2 shown. AIAO1 and AIAO2 share same GND terminal.
Figure 3-5: 1-5 V Analog Input (AI) Wiring (Base I/O when optional I/O also present)
Note: Analog input wiring for AIAO2 shown. AIAO1 and AIAO2 share same GND terminal.
Figure 3-6: Analog Input (AI) Wiring (Base I/O when Optional I/O Module not present)
Figure 3-7: 4-20 mA Analog Input (AI) Wiring – (Optional 6-channel expansion I/O board)
Note: Analog input wiring for AIAO3 shown. AIAO3 and AIAO4 share same GND terminal.
Figure 3-8: 1-5 V Analog Input (AI) Wiring (Optional 6-channel expansion I/O board)
Note: Analog input wiring for AIAO3 shown. AIAO3 and AIAO4 share same GND terminal.
When configured as analog outputs, the channels have the following characteristics:
3.2.1 AO Wiring
Wire analog outputs as shown:
Figure 3-9: Analog Output (AO) Wiring – (Base I/O – when optional I/O also present)
Note: Analog output wiring for AIAO1 shown. AIAO1 and AIAO2 share same GND terminal.
Figure 3-10: Analog Output (AO) Wiring – (Base I/O – when optional I/O not present)
Figure 3-11: Analog Output (AO) Wiring (Optional 6-channel expansion I/O board)
Note: Analog input wiring for AIAO4 shown. AIAO3 and AIAO4 share same GND terminal.
When configured as digital inputs, the channels have the following characteristics:
0 to 6 as follows:
Circuit protection
1 or 2 non-isolated channels on CPU board
30ms input filtering
(PI/DI/DO1 and PI/DI/DO2). Two always
Maximum input frequency of 10 Hz
present; you can configure one, both, or
Selectable current source of 66 μA or 2 mA
Digital neither as DIs.
Either externally driven or internally driven
Input (DI) 1 to 4 additional non-isolated channels on
and pulled to ground by dry contact
optional 6-channel expansion I/O board
closures or open collector devices
(PI/DI/DO3 through PI/DI/DO6). If present
When a channel is configured as a DI it
you can con- figure one, two, three, four or
cannot be used as a DO or PI channel
none as DIs.
3.3.1 DI Wiring
The diagrams below show how to wire digital inputs.
Figure 3-12: Digital Input (DI) Wiring - (Base I/O -when optional I/O also present)
Note: Digital input wiring for DIDO1 shown. DIDO1 and DIDO2 share same GND terminal.
Figure 3-13: Digital Input (DI) Wiring - (Base I/O -when optional I/O not present)
Figure 3-14: Digital Input (DI) Wiring - (Optional 6-channel expansion I/O board)
Note: Digital input wiring for DIDO6 shown. DIDO5 and DIDO6 share same GND terminal. DIDO3 and
DIDO4 share a different GND terminal.
Note
When using a digital output to drive an inductive load (such as a relay coil), place a suppression
diode across the load. This protects the DO from the reverse Electro-Motive Force (EMF) spike
generated when the inductive load is switched off.
When configured as digital outputs, the channels have the following characteristics:
3.4.1 DO Wiring
The diagrams below show how to wire digital outputs.
Figure 3-15: Digital Output (DO) Wiring - (Base I/O - optional I/O also present)
Note: Digital output wiring for DIDO2 shown. DIDO1 and DIDO2 share same GND terminal.
Figure 3-16: Digital Output (DO) Wiring - (Base I/O - optional I/O not present)
Figure 3-17: Digital Output (DO) Wiring - (Optional 6-channel mixed I/O board)
Note: Digital output wiring for DIDO4 shown. DIDO3 and DIDO4 share same GND terminal. DIDO5 and
DIDO6 share a different GND terminal.
When configured as pulse inputs, the PI channels have the following characteristics:
3.5.1 PI Wiring
The diagrams below show how to wire the pulse inputs.
Figure 3-18: Pulse Input (PI) Wiring - (Base I/O - when optional I/O also present)
Note: Pulse input wiring for PIDIDO shown. PIDIDO1 and PIDIDO2 share same GND terminal.
Figure 3-19: Pulse Input (PI) Wiring - (Base I/O - when optional I/O not present)
RTD connections reside on the terminal plate under the rear end cap. The flow computer supports
2-wire, 3-wire, and 4-wire operation. Route the RTD cable through the conduit fittings and connect
them on the terminal plate (as shown on Figure 3-21 and Figure 3-22).
Note
The device defaults to the 4-wire RTD configuration; you can change this setting in FBxConnect.
Figure 3-21: Wiring for 2-Wire, 3-Wire, and 4-Wire RTD (Units with Optional I/O)
Figure 3-22: Wiring for 2-Wire, 3-Wire, and 4-Wire RTD (Units without Optional I/O)
See the Rosemount™ 4088 Multivarible™ Transmitter Reference Manual (00809-0100-4088, Rev
CB, Feb. 2017) for details on installing the 4088B.
1. Using twisted pair wire, connect the RS-485 terminals for COM3 to the RS-485 terminals on
the 4088B as shown in the graphic.
2. Set switches on the 4088B for bus termination, or use a 120 ohm resistor.
3. Use FBxConnect software to configure COM3 for RS-485. In particular, enable termination
for the port.
Section 4: Operation
This section covers the following topics:
This section describes day-to-day operation of the flow computer including how to turn it on and
off and how to communicate with it.
2. Terminal block TB1 includes connections for DC power (+DCIN, -DCIN) and solar power
(+SPIN, -SPIN). Battery power (which is also used with solar power) has its own internal
connections.
Plug in TB1 to activate DC or solar power. If your device uses an internal battery and
it is not connected, connect it as discussed in 2.12.3 Connecting Battery Power.
Unplug TB1 to deactivate DC or solar power. If your device uses an internal battery,
disconnect the main battery.
This turns on (or shuts OFF) power from either an external power supply or the battery
pack/solar panel.
Note
When you turn power on, the backlight on the HMI module lights, momentarily turns off and then
remains lit while the INPUT LED blinks. After approximately one minute the initialization process
finishes and the HMI starts to display live data.
Operation 69
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1. Decide how the SCADA host should communicates with the flow computer. This could be
through connection with one of the communication ports. A serial port connection could
be a cable directly connected to the SCADA host or there could be intermediate
connections through a radio or modem. An Ethernet port connection must be through an
Ethernet switch with an appropriate Category 5 shielded patch cable.
2. Decide which communication protocol you will use. This could be DNP3, ROC, or BSAP.
See these documents for more information:
Emerson FB Flow Computer DNP3 Protocol Specifications Manual (D301806X012)
ROC Protocol Specifications Manual (for Emerson FBx-series) (D301828X012)
FB1x00/FB2x00 BSAP Communication Guide (D301808X012)
3. Provide the SCADA host with information about the various parameters it needs to extract
from the application running in the flow computer. Typically, the SCADA host software
includes a utility that allows you to identify this information so it can be incorporated into the
database at the SCADA host.
4. Using whatever human-machine interface (HMI) tools exist for the SCADA host, create
graphical displays or reports that include the parameters from the application required for
successful operator interaction (setpoints, flow variables and so on).
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
1. Connect a cable between a serial port (or serial/USB adapter) on your laptop and port COM2
on the flow computer.
2. Launch Field Tools and add a new serial connection for this device; this launches FBxConnect
configuration software. (If you already have an existing saved serial connection for this
device in Field Tools, just double-click on it in the Connections list.)
3. Log into the flow computer if prompted.
4. Use the FBxConnect configuration software to view or change any desired parameters.
5. When finished, log off the flow computer and disconnect the cable from its serial port.
You must know a valid username/password combination for the flow computer.
70 Operation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
1. Connect a Category 5 shielded cable between an Ethernet port on your laptop and an
Ethernet switch for your network.
2. Connect a Category 5 shielded cable between your Ethernet switch and the Ethernet port
on the flow computer.
3. Launch Field Tools and add an IP connection for the device then click Connect to start the
FBxConnect software. (If you already have an existing saved IP connection for this device in
Field Tools, just double-click on it in the Connections list.)
4. Log into the flow computer if prompted.
5. Use the FBxConnect software to view/change any desired parameters.
6. When finished, log off from the flow computer and disconnect the cable.
WARNING
Ensure that you and your laptop PC are in a non-hazardous area.
1. Launch Field Tools software and add a new wireless connection. (If you already have a saved
wireless connection for this device in Field Tools, just double-click on it in the Connections
list and skip to Step 4.)
2. Select the wireless network to which the flow computer belongs and enter the appropriate
security key.
3. Click Connect to start the FBxConnect software.
4. Log into the flow computer if prompted.
5. Use the FBxConnect software to view or change any desired parameters.
Operation 71
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
6. When finished, log off the flow computer and disconnect from the wireless network.
Note: If the device is configured to require logins to view data, you must know a valid
username/password combination for the flow computer.
1. Go to the front of the flow computer and touch your finger on the glass above the Hold to
Wake button until the display lights up. (This may take several seconds.)
72 Operation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Note
When using the IR buttons, aim your finger at the round spot just below the arrow.
Operation 73
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
Button Use to
UP or DOWN buttons
Data Entry Mode
Tap (UP) once to move the cursor to the previous character in the list or
(DOWN) once to move the cursor to the next character in the list.Hold
(UP) or (DOWN) to scroll more quickly through the character list.
Symbol(s) representing the status of a value may appear in the upper right of the display, next to
the description. Multiple symbols may be shown. If there are no data quality issues, no symbols will
be shown.
Table 4-2: Symbols on Display
Symbol Explanation
Alarm - The parameter value shown is in an alarm state (High Alarm, Low Alarm, etc.)
Override - The parameter value shown is in override mode (i.e. a user entered fixed
value)
Unverified - For parameter values that require additional validation (beyond simple
database min/max range checking, the parameter value shown has not yet been
validated by the firmware).
74 Operation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
In order to maintain hazardous location certifications, you can only replace components in the field
with the exact same part so that the model string on the data plate remains correct. This means
you cannot add any hardware not reflected in the model string or upgrade a hardware component
to a newer version; any such upgrades are prohibited and void the hazardous location certification.
This chapter describes the service tasks that everyone needs to know such as replacing batteries or
installing a firmware upgrade. For other field replacements, see the appropriate field replacement
guides for that component.
Any replacement not covered in this chapter or in the field replacement guides (such as adding or
upgrading hardware or replacing sensors) can only be performed at an Emerson-authorized repair
facility.
Important
Only use batteries supplied with the flow computer or sold by Emerson Remote Automation
Solutions as spare parts for this flow computer. If you substitute a battery you obtain elsewhere you
will void your certification unless it is the identical part from the same manufacturer as that
supplied with the flow computer from Emerson.
1 Input LED
2 Link LED
3 Status LED
4 Alarm LED
Off No power
DANGER
EXPLOSION HAZARD: Never remove end cap(s) in a hazardous location. Removing end cap(s) in a
hazardous location could result in an explosion.
Clears memory (SRAM). The SRAM 1. Press and hold the A button.
memory holds current data values and 2. While continuing to hold the A
pending alarm messages. If unit has button, move the SYSTEM RESET
unexpectedly stopped operating, you can switch either up or down to initiate a
A
depress this button on power- up to clear reset.
that information from memory (hard 3. Release the A button. The system
reset). Try this if a SYSTEM RESET alone clears SRAM during the power up
does not work. sequence.
DANGER
Ensure the flow computer is in a non-hazardous area. Never remove/replace the HMI module in a
hazardous area.
Important
The HMI module includes the WiFi transceiver; once you remove the HMI module; WiFi
communication with the flow computer ceases.
1. Remove the retaining clamp from the front end cap (if present). (See Section 2.6.1.)
2. Unscrew the front end cap.
3. Loosen the four captive fastening screws on the HMI module.
4. Grasp the HMI module and remove it by gently pulling it straight out.
5. To replace the HMI module, line up the printed circuit board (PCB) with the slot on the back
and gently press it back on. Tighten the four captive fastening screws.
6. Replace the front end cap. Screw the end cap clockwise (eight full turns) until it is tightly
sealed to the enclosure. Replace the retaining clamp, if applicable (see Section 2.6.1).
The device provides two battery connectors, enabling you to hot-swap the battery pack in a non-
hazardous location. Slide out the first battery pack (leaving it connected), attach the new battery to
the second (available) connector (so both batteries are connected), and then disconnect the old
battery pack.
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area is
known to be non-hazardous.
DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division 1
or Class I, Division 2.
DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.
WARNING
There are no user-serviceable parts inside the battery pack. Do not open the battery pack as you
may damage the battery pack or injure yourself.
Restriction
Battery packs cannot be used with ATEX or IECEx applications.
1. Remove the retaining clamp from the front end cap (if present). (See Section 2.6.1.)
2. Remove the front end cap.
3. Loosen the two bottom captive fastening screws on the HMI module. Leave the two top
screws connected to the battery pack.
4. Grasp the HMI module and gently pull it and the battery pack out of the enclosure, leaving
the battery still connected.
5. Connect the new battery to the open connector. Route the wires so they are in the recessed
area. Make sure the wires won’t get caught in the end cap threads.
6. Disconnect the old battery pack’s connector from the unit and set the old battery pack aside.
7. Slide the new battery pack into the unit.
8. Loosen the top captive fastening screws on the HMI module to separate it from the old
battery pack.
9. Align the HMI module with the new battery pack and the tab on the CPU carrier board
(bezel). Gently press the assembly on, being careful not to pinch the battery wires.
Tighten all four screws.
10. Replace the front end cap. Screw the end cap clockwise (eight full turns) until it is tightly
sealed to the enclosure. Replace the retaining clamp, if applicable (see Section 2.6.1).
Important
If the unit is ever powered down without the SRAM battery installed, SRAM data is lost. Always back
up your data before you remove the SRAM battery if you know that main power will also be off.
Important
Replacement SRAM backup batteries must be Rayovac® Model BR2335.
DANGER
Ensure the flow computer is in a non-hazardous area. Never remove the end cap in a hazardous
area.
DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area is
known to be non-hazardous.
DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division 1
or Class I, Division 2.
DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.
1. Remove the retaining clamp from the front end cap (if present). (See Section 2.6.1.)
2. Remove the front end cap.
3. Remove the HMI module.
4. Grasp the coin cell battery and remove it from its slot.
5. Insert the new coin cell battery in the slot. The positive side (+) must be on top.
6. Replace the HMI module.
7. Replace the front end cap. Screw the end cap clockwise (eight full turns) until it is tightly
sealed to the enclosure. Replace the retaining clamp, if applicable (see Section 2.6.1).
You must know a valid username/password combination for the flow computer to complete this
process.
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
1. Launch Field Tools and use FBxConnect to connect to the flow computer.
2. Click the Services tab, then click Firmware Update.
3. Click Configuration Save to save the flow computer’s configuration.
4. Click History Collection to save the historical data contained in the flow computer.
5. Click Firmware Update.
6. In the Firmware Update dialog box, click Browse and navigate to the zip file containing your
new system firmware. The grid updates with details of the firmware version currently in the
device, and the firmware version in the zip file.
7. Select the checkbox in the Selected column to choose the firmware. If you are downloading
the same version that is already installed on the device, select Download Even If
Unchanged.
8. Click Start to begin the firmware download. Allow the download to proceed to completion. If
you choose to cancel the firmware download before it completes, the system restores the
current version already in the device.
DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area is
known to be non-hazardous.
DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division 1
or Class I, Division 2.
DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.
Figure A-1: Data Plate (NO BATTERY) – Class I Division 2 Non-incendive (UL)
Figure A-2: Data Plate (LEAD ACID BATTERY) – Class I Division 2 Non-incendive (UL)
DANGER
Though the Emerson FB1200 flow computer has a local port for local interrogation, it should
not be accessed with the cover removed in a Class I Division 1 area unless it has first been
verified that no flammable concentrations exist in that area. The local port may be wired
through a conduit, using seals, to an unclassified or Division 2 area.
3. All communication ports terminate on the terminal plate within the enclosure. Wiring to the
connectors is unrated. No connections may be made to communication ports unless the
user ensures that the area is known to be nonhazardous. Connections to the "Local Port" are
temporary and must be short in duration to ensure that flammable concentrations do not
accumulate while it is in use.
4. An RTD may be supplied with the Emerson FB1200 flow computer. Connection to the RTD is
approved as a non-incendive circuit.
Note
A bendable RTD (with a plastic bushing, as utilized in Division 2 installations) may not be
used in a Division 1 area as it renders the area non-explosion proof. Use an RTD connection
head and explosion-proof conduit for Division 1 installations.
5. I/O connections are unrated and must be wired using wiring methods as specified in Article
501-4(b) of the National Electrical Code (NEC), NFPA 70 for installations in the United States, or
as specified in Section 18-152 of the Canadian Electrical Code for installation in Canada.
DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area is
known to be non-hazardous.
DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division 1
or Class I, Division 2.
DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.
DANGER
The area must be known to be non-hazardous before servicing the unit and before installing or
removing I/O wiring.
Figure B-1: Data Plate (NO BATTERY) – Class I Division 1 Explosion Proof (UL)
Figure B-2: Data Plate (LEAD ACID BATTERY) – Class I Division 1 Explosion Proof (UL)
Provision shall be made to prevent the rated voltage being exceeded by the transient
disturbances of more than 140% of the peak rated voltage.
Lead Acid Battery, and Solar Panel options are not for use in ATEX/ IECEx applications.
Impact Tests on Display conducted based on Group II values for low risk of mechanical
danger, per Table 13 of IEC 60079-0 6th Edition. Install in an area where risk of impact is
low.
For Zone 2 installation care should be taken that the flow computer be installed and used
in such a way that the danger of electrostatic charges is excluded.
This device was evaluated according to the following standards:
Index 97
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1. Contact your authorized sales and service representative for any maintenance or repair
beyond the maintenance of the FB1200 flow computer. Do not alter or disassemble any of
the flameproof joints of the FB1200 flow computer.
2. The Scalable Pressure Transmitter Model 4088 and 215 provided with the FB1200 flow
computer contains a thin wall diaphragm. Installation, maintenance, and use shall take into
account the environmental conditions to which the diaphragm will be subjected. The
manufacturer's instructions for installation and maintenance shall be followed in detail to
assure safety during its expected lifetime.
Index
Index 99
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
1-2. FB1200 Flow Computer – MV or Static Pressure 2-35. Ethernet Jumper ......................................... 47
Version ............................................................... 4 3-1. Base I/O On CPU (when optional I/O also
1-3. FB1200 Flow Computer – No Sensor Version ... 5 present) ........................................................... 50
1-4. HMI Module with LCD ..................................... 8 3-2. Base I/O On CPU (No optional I/O present).... 51
1-5. HMI Module without LCD ................................ 8 3-3. Optional 6-channel expansion I/O board ....... 52
2-1. FB1200 Dimensions – MVT Version ............... 13 3-4. 4-20 mA Analog Input (AI) Wiring (Base I/O
2-2. FB1200 Dimensions – No Sensor Version ....... 14 when Optional I/O Module also present) .......... 53
2-3. Front End Cap with Retaining Clamp Fitted .... 15 3-5. 1-5 V Analog Input (AI) Wiring (Base I/O when
2-4. Retaining Clamp in Place ............................... 16 optional I/O also present)................................. 54
2-5. Retaining Clamp and Screw ........................... 16 3-6. Analog Input (AI) Wiring (Base I/O when
2-6. Removing or Tightening the End Cap with Long Optional I/O Module not present) .................... 54
Screwdriver ...................................................... 16 3-7. 4-20 mA Analog Input (AI) Wiring – (Optional 6-
2-7. Front (left) and Rear (right) End Caps ............. 17 channel expansion I/O board) .......................... 55
2-8. Front (left) and Rear (right) End Caps Removal 3-8. 1-5 V Analog Input (AI) Wiring (Optional 6-
......................................................................... 17 channel expansion I/O board) .......................... 55
2-9. Transmitter with Coplanar Flange .................. 18 3-9. Analog Output (AO) Wiring – (Base I/O – when
2-10. Transmitter with Coplanar Flange and optional I/O also present)................................. 56
Optional Flange Adapters ................................. 18 3-10. Analog Output (AO) Wiring – (Base I/O – when
2-11. Transmitter with Traditional Flange and optional I/O not present) ................................. 57
Optional Flange Adapters ................................. 19 3-11. Analog Output (AO) Wiring (Optional 6-
2-12. Proper Bolt Installation ................................ 20 channel expansion I/O board) .......................... 57
2-13. O-rings with Flange Adapters ...................... 20 3-12. Digital Input (DI) Wiring - (Base I/O -when
2-14. Traditional Flange Mounting Kit................... 21 optional I/O also present)................................. 58
2-15. Coplanar Mounting Kit ................................ 22 3-13. Digital Input (DI) Wiring - (Base I/O -when
2-16. Inline Mounting Kit ...................................... 23 optional I/O not present) ................................. 59
2-17. Housing Rotation Set Screw (1 each side) .... 24 3-14. Digital Input (DI) Wiring - (Optional 6-channel
2-18. Ground Lug ................................................. 25 expansion I/O board) ....................................... 59
2-19. Terminal Plate ............................................. 26 3-15. Digital Output (DO) Wiring - (Base I/O -
2-20. DC Power Connections ................................ 30 optional I/O also present)................................. 61
2-21. Connecting the Battery Pack ....................... 31 3-16. Digital Output (DO) Wiring - (Base I/O -
2-22. Attaching Mounting Hardware to the Solar optional I/O not present) ................................. 62
Panel ................................................................ 32 3-17. Digital Output (DO) Wiring - (Optional 6-
2-23. Integral mounted solar panel....................... 34 channel mixed I/O board .................................. 62
2-24. Solar panel remote mounted (pole mounted) 3-18. Pulse Input (PI) Wiring - (Base I/O - when
......................................................................... 35 optional I/O also present)................................. 63
2-25. Wiring Solar Power ...................................... 36 3-19. Pulse Input (PI) Wiring - (Base I/O - when
2-26. Adjusting Solar Panel Tilt Angle ................... 37 optional I/O not present) ................................. 64
2-27. Connecting a Device to COM1 Using RS-23239 3-20. Pulse Input (PI) Wiring - (Optional I/O Board)
2-28. Connecting a Device to COM1 Using RS-42240 ........................................................................ 64
2-29. Connecting a Device to COM1 Using RS-48541 3-21. Wiring for 2-Wire, 3-Wire, and 4-Wire RTD
2-30. Connecting a Device to COM2 or COM3 Using (Units with Optional I/O) .................................. 65
RS-232 – Optional I/O present .......................... 42 3-22. Wiring for 2-Wire, 3-Wire, and 4-Wire RTD
2-31. Connecting a Device to COM2 or COM3 Using (Units without Optional I/O)............................. 66
RS-232 – No optional I/O .................................. 43 3-23. Connecting a 4088B Transmitter for a Second
2-32. Connecting a Device to COM2 or COM3 Using Meter Run ........................................................ 67
RS-485 – Optional I/O present .......................... 44 4-1. Waking up the Display .................................. 72
2-33. Connecting a Device to COM2 or COM3 Using 4-2. Infrared (IR) Button Location......................... 73
RS-485 – No optional I/O .................................. 45 5-1. FB1200 Flow Computer Components ........... 76
2-34. Location of Ethernet Port ............................. 46 5-2. LED Locations ............................................... 77
100 Index
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
G O
Grounding ............................................................... 25 Operation ............................................................... 69
O-rings .................................................................... 20
H
P
Hazardous locations................................................. 11
ATEX Zone 1 ......................................................... 97 Ports
ATEX Zone 2 ......................................................... 95 connecting .......................................................... 38
Class I Division 1 ................................................... 91 Power
Class I Division 2 ................................................... 87 connecting .......................................................... 30
HMI module ......................................................... 8, 72 options .................................................................. 7
replacing .............................................................. 80 turning ON or OFF ............................................... 69
symbols on display ............................................... 74 Pulse Inputs ............................................................ 63
Housing R
rotating ................................................................ 23
Resetting the flow computer ................................... 79
I Returning the unit for repairs .................................. 76
I/O Rotating the housing............................................... 23
configuration and wiring ...................................... 49 RTD
options................................................................... 6 connecting .......................................................... 65
Indirect mounting .................................................... 22 Run 2 transmitter
Inline mounting kit .................................................. 23 connecting .......................................................... 67
Installation ............................................................... 11 S
L Safety Labels ............................................................. 3
LCD Screen Saver Mode .................................................. 72
communicating using .......................................... 72 Second meter run
replacing .............................................................. 80 connections for ................................................... 67
Index 101
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
102 Index
FB1200 Flow Computer Instruction Manual