Caution !
Our products are mainly custom made and are intended especially for
professional application and testing in substations.
Special attention is paid to safety against accidental contact and error free data
transmission, also in EMC burdened environment.
Current information regarding our products may be found in the Internet under:
www.siprotec.com
GENERAL INSTRUCTIONS....................................................................................................................5
1 COMMUNICATION CABLE FOR THE OPERATION OF PROTECTION DEVICES WITH PC.....6
1.1 7XV5100 Serial RS232-communication cable (wire / FO) ................................................6
1.1.1 7XV5100-0/BB PC/PG 25-pole to the protection device 25-pole ......................................6
1.1.2 7XV5100-1 PG 750 to protection device 25-pole ..............................................................6
1.1.3 7XV5100-2 PC / PG to protection device 25-pole ............................................................6
1.1.4 7XV5100-3 PG 750 (COM2) to Plotter 1604.....................................................................7
1.1.5 7XV5100-4 (/BB) PC/PG 9-pole to protection device 9-pole (DIGSI-cable) .....................7
1.1.5.1 7XV5100-4 (/BB) Additional applications ...........................................................................8
1.1.5.2 7XV5100-8H 9/25-pol. Adapter for cable 7XV5100-4........................................................8
1.1.6 7XV5100-4A PC/PG 9-pole to the local interface of the channel switch 7XV5500 ..........8
1.1.7 7XV5100-5 PC / PG 25-pol. to protection device 9-pole ..................................................9
1.1.8 7XV5100-6 Serial RS232 cable with galvanic separation via FO cable ............................9
2 RS485-BUS SYSTEM FOR DIGSI- / IEC- / VDEW-COMMUNICATION ......................................10
2.1 RS485-Bus with 9-pole Sub-D plug...................................................................................10
2.1.1 7XV5103-0AAxx Y-Bus cable for RS485-Bus with 9-pole plug .......................................10
2.1.2 7XV5103-1AAxx Extension bus cable for RS485-Bus with 9-pole plug ..........................11
2.1.3 7XV5103-2AA00 adapter cable for devices with RS485-bus on terminals .....................11
2.1.4 7XV5103-7AAxx RS485 adapter cable from the RTD-Box to SIPROTEC 4 ...................11
2.2 RS485-Bus system with RJ45-plug...................................................................................12
2.2.1 7XV5103-2BA00 Adapter cable for devices with RS485-Bus on 9-pol. Sub-D plug .......13
2.2.2 7XV5103-2CA00 Adapter cable for devices with RS485-Bus on 8-pol. RJ45 plug.........13
2.2.3 7XV5103-5BA00 RS485-Terminator with RJ45 plug.......................................................13
2.2.4 7KE6000-8GDxx Ethernet patch cable CAT5 with RJ45 plugs .......................................13
3 BUS CABLE FOR TIME SYNCHRONISATION OF SIPROTEC PROTECTION DEVICES ........14
3.1 7XV5104 Bus cable for synchronization for standard time only ...................................14
3.1.1 7XV5104-0AAxx Y-Bus cable for standard time only ......................................................14
3.1.2 XV5104-1AA10 Extension cable for standard time only ..................................................15
3.1.3 7XV5104-2AA00 Adapter cable with open ends for standard time only..........................15
3.1.4 7XV5104-3AA00 T-Adapter cable (2 Busses) for standard time only .............................15
3.2 7XV5105 Bus cable for synchronization for standard time and second puls ..............15
3.2.1 7XV5105-0AAxx Y-Bus cable for standard time and second puls...................................16
3.2.2 7XV5105-1AA10 Extension cable for standard time and second puls ............................16
3.2.3 7XV5105-2AA00 Adapter cable with open ends for standard time and second puls ......16
4 CABLE FOR CONVERTER 7XV5700 (RS232 - RS485)..............................................................17
4.1 7XV5700 RS232-interface to the PC ..................................................................................17
4.1.1 7XV5100-2 RS232-cable from 7XV5700 to PC ...............................................................17
4.2 7XV5700 RS485-Bus-Interface...........................................................................................17
4.2.1 7XV5100-7/BB RS485-cable from 7XV5700 to the first protection device with terminals17
4.2.2 7XV5100-7B RS485-cable from 7XV5700 to protection device with 9-pole RS485 plug.18
5 7XV5710 CONVERTER CABLE USB 2.0 TO RS485 WITH SUB-D PLUG................................18
Additionally, we point out that the content of this product documentation is not part of or
modifies any previous or existing agreement, promise, or legal relationship.
All obligations by Siemens result from the respective purchase order which also includes
the complete and exclusively valid warranty provision. The contractual warranty
regulations are neither extended nor limited by the statements in this document
Liability Statement
We have compared the text of this manual with the hardware and software described.
Omissions and deviations cannot be ruled out; we accept no liability for lack of total
conformity.
The information in this manual is checked periodically, and necessary corrections will
be included in future editions. We appreciate any suggested improvements.
We reserve the right to make technical improvements without notice. Any suggestions
for improvements are welcome.
Note !
This brochure also contains descriptions of products that have been discontinued, or
are only to be used for testing purposes or as commissioning aids, and are not
distributed by Siemens AG.
There will be no liability or guarantees for damages of any kind, caused by the
reproduction or re-fitting of the described products,
Copyright
In the case of cable 7XV5100-0 Version /BB the shielding was changed. The cable shield is
no longer connected with “GND”, but has plug housings at both ends.
* for Starcoupler
With this cable and the 9/25-pole adapter 7XV5100-8H, protection devices with 25-pole
interfaces can also be connected.
If this 9/25-pole adapter is connected with the 9-pole male plug of the cable 7XV5100-4
(/BB), protection devices with a 25-pole service interface can also be connected to the PC or
notebook with this cable.
Channel switch
Notebook / PC 7XV5100-4A Local interface
9pol. female Length 3m 9pol. male
1 1
2 RxD 2
3 TxD 3
4 4
5 GND 5
6 6
7 7
8 8
Note: The baud rate and the data format of all devices connected to the bus must be
set the same. The devices addresses (1-254) must differ.
SIEMENS SIEMENS
SIEMENS SIPROTEC SIEMENS SIPROTEC
RUN RUN
RUN ERROR RUN ERROR
ERROR ERROR
Anr. L1
L1 402,1A Max450.1A Anr. L2 L1 402,1A Max450.1A
L2 402,1A Max450.1A Anr. L3 L2 402,1A Max450.1A
L3 402,1A Max450.1A Anr. Erde L3 402,1A Max450.1A
Anr. L1 Anr. L1
E 00.0A Automat E 00.0A Anr. L2 Anr. L2
Anr. L1 Aus L1
Anr. L2 Aus L2
Anr. L3 Aus L3
Anr. Er de Aus Erde
Automat
Adapter cable
7XV5103-2AA00
S2 S2 B1
C C
S2
B A B A
S2
RS485 S1 B3 S1 B3 S1 B3 S1 B3 ST
Master
Y-Bus cable RS485 Y-Bus cable RS485 Y-Bus cable RS485 Y-Bus cable RS485 RS485-Terminator
7XV5103-0AAxx 7XV5103-0AAxx 7XV5103-0AAxx 7XV5103-0AAxx 7XV5103-5AA00
7XV5103-1AAxx
RS485 Extension cable
--> Master Slave -->
9pol. male Length 10 / 20 / 30 / 40 / 50 m 9pol. female
3 A 3
3+8 twisted pair
8 B 8
Housing Shield Housing
RTD-Box
7XV5662-xAD10 SIPROTEC 4 Device
4x wire end ferrule SUB-D
Terminator 120 Ohm
A' 9pol. male
A = Pin 3 Length 5 / 25 / 50 m 3
A
B = Pin 8 3+8 twisted pair 8
B
Shield Housing
B'
In the case of the serial bus system with RJ45 sockets on the device, the bus connection is
established with cost-effective, double-screened CAT 5 patch cables. This technology is
used in the case of redundant IEC 60870-5-103 system interfaces on the device. The
connection of the individual devices to the two redundant busses is in each case done via
two special Y adapter cables. The busses each terminate at a RJ45 bus termination plug
with integrated 120 Ohm resistance.
For the connection of SIPROTEC-devices with 9-pole sub-D plugs, or for connection to the
bus system with 9-pole sub-D plugs, a special adapter is available (see catalog sheet).
These cables are not suitable for PROFIBUS.
Note: The baud rate and the data format of all devices connected to the bus must be set the
same. The device addresses (1-254) must be different.
7SA522
7SJ6x 7SJ6x 7SJ6x 7SD522
7SJ62/63
Master Master
RTU 1 RTU 2
C C C C
B A B A B A B A
To RS485-Bus
Patch cable Y-Adapter cable 7XV5103-2CA00
1* For connect SIPROTEC 4 devices with RJ45 interface plug
B* on an RS485-Bus with patch cables
2* Length 0,3 m
A*
4*
X* To SIPROTEC 4
RS485 with RJ45
5*
Y*
1 A/A* and B/B* for RS485 data 1
B B
2 1+2 twisted pair 2
A A
4 4
X X
5 4+5 twisted pair 5
Y Y
Housing Shield Housing
1
B
R=120 Ohm
P= 0,25W
2
A
RJ45-Stecker
8-pol. Stift
Only double-screened CAT 5 patch cables, SFTP 1:1 connection (e.g. 7KE6000) may be
used as bus cables. The maximum bus length may not exceed 800m.
X1 X2
+Vin -Vin
+O C3 -OC3
+O C2 -OC2
RUN
R1 R2 1 2 1 2
0V 24V/ 6W +O C1 -OC1
BI 2
K2
7XV5810-0BA00 CLK DEF
C1-C 3
Weitbereichsnetzteil Sync-Transceiver
SERIES: A4-K7-655430 7XV5654-0BA00/BB
CE 5
RCV 1
RCV 2
60-230V AC IRIG B / III I IIII IIII IIII III III III UH 24 -25 0V D C / 6W
DCF77-In 10 0-2 30 V AC / 15 VA
CE 5 FL1 50 / 6 0 Hz
UH UH
2 1 N /L - L1 /L+ 2 1 N /L - L1 /L+
GPS-In
FL1
T-Adapter
C S2 S3 7XV5104-3AA00 C S2 C S2
B A B A B A
Plug Sub-D
1 3 8 4 9pol. male
Plug Sub-D Plug Sub-D
9pol. female 9pol. female
1 24 V (Time) 24 V (Time) 1
3 GND (Time) 1+3 twisted pair 1+3 twisted pair GND (Time) 3
1 24 V (Time) 1
Housing Housing
1 24 V (Time) 1
Housing Housing
3.2.3 7XV5105-2AA00 Adapter cable with open ends for standard time
and second puls
The 4-core adapter cable with open ends enables the connection of the bus to radio
controlled clocks with connection terminals.
7XV5105-2AA00 Adapter cable
open ends with Length 0,3 m for standard time and second puls Plug Sub-D
2x wire end ferrule 9pol. female
8 24 V (Puls) 8
1 24 V (Time) 1
Shield Housing
If further devices (maximally 31) are to be connected, the RS485-Bus can be extended with
the Y bus cables 7XV5103-0AAxx and a standard 9-pole "Gender Changer" (socket, socket)
(also see 7XV5103-xx).
To 7XV5700 Prot. device
RS 485-Interface 7XV5100-7B
25pol. male Length 1m 9-pol. male
B
10 8
11
19 A
21 3
22
23
GND
Housing 5
13
25
NOTE! The mode of operation in the RS485-converter is set with the jumpers in the 25-pole
plug of the cables 7XV5100-7.
390
Length 1,8 m
3
A 10
Plug USB
Plug Sub-D
220
USB-A S1
9-pol. male
B 8
B 10
100k
390
TTL 5
A
1 DCD 8
2 RxD 3
3 TxD 2
4 DTR 20
5 GND 7
6 DSR 6
7 RTS 4
8 CTS 5
9 RI 22
Housing Housing
Notebook / PC Modem
9-pol. female Max. length 3m 9-pol. male
1 < DCD 1
2 < RxD 2
3 TxD > 3
4 DTR > 4
5 GND 5
6 < DSR 6
7 RTS > 7
8 < CTS 8
9 < RI 9
Housing Housing
Note: A galvanic separation between modem and protection device via RS232-FO
converter e.g. 7XV5101 or 7XV5652-0BA00 is strongly recommended.
With this cable and the 9/25-pole adapter 7XV5100-8H, protection devices with 25-pole
interface can also be connected.
With this cable and the 9/25-pole adapter 7XV5100-8H, protection devices with 25-pole
interface can also be connected.
6.2.3 Substation modem 25-pol. to Prot. device with 25-pol. front interface
The RS232 – FO plug modules are supplied in Sub-D plug housings and may be plugged
directly onto the interface of the corresponding devices. If the plug modules are applied
correctly, no additional settings need to be made.
The quiescent state of the optical interface is generally light OFF. Data transmission takes
place full-duplex and is transparent up to 115 kBaud. The optical interface with FSMA plug
operates at 850nm and has a typical reach of 1500m with 62,5µm fibre optic cable.
The various versions have the following differences: number of pins (9 or 25-pole), the plug
design (male or socket) and the auxiliary voltage supply (pin 9 or power supply plug). More
information regarding application and type can be found in the following individual
descriptions, the technical data and the order information.
A standard mouse adapter (9-pole male to 25-pole socket) can be used between the modem
and the plug module in the case of a modem with a 9-pole connection.
The module obtains its power (5V) from an external power supply via a binding socket
(contained in the scope of delivery).
The plug allocation DCE/DTE may be converted for applications after opening of the
housing. The default setting is DTE and quiescent state light OFF. The quiescent state of the
light cannot be changed.
For a notebook with a 9-pole connection, a standard mouse adapter (9-pole male to 25-pole
socket) can be used between modem and plug module.
The module obtains its power via the interface of the active channel switch (Pin 9), and
accordingly does not require additional power supply. The default setting is DTE and
quiescent state light OFF. The quiescent state of the light cannot be changed.
The RS232 signals are transparently converted into light signals. The control wires are
bypassed and are not supported.
The module obtains its power via a cable from the keyboard DIN interface or the mouse DIN
interface of the notebook.
The default setting is DTE and quiescent state light OFF. The quiescent state of the light
cannot be changed.
7XV5101- 0A 0B 1A 1B 3A 3C
Housing: Plastics , metal-plated X X X X X X
Dimensions 58 x 53 x 17 X X X X
Dimensions 72 x 32 x 17 X X
Power supply +5V via pin 9 X 1) X 1) X
+5V via female connector 2) X 2) X
Plug-in PSU 220V/50Hz (included in delivery) X X
via keyboard connector of the notebook X
Electrical V.24 / RS232 DCE (steady light OFF) X X
interfaces
V.24 / RS232 DTE (steady light OFF) X X X
DTE / DCE switchable X X X X
Assignment: 2 TxD, 3 RxD, 5 GND X
Assignment: 3 TxD, 2 RxD, 5 GND
Assignment: 2 TxD, 3 RxD, 7 GND X X
Assignment: 2 RxD, 3 TxD, 7 GND X X
Assignment: 9 +5V X X X X X
Bridge contact: 4-5, 6-8-20 (25-pin) X X X X
Bridge contact: 7-8, 1-4-6 (9-pin) X X
Optical Plug-in connection FSMA black = transmit X X X X
interfaces blue = receive
Plug-in connection FSMA T = transmit X X
R = receive
Optical Power 27µW (-5,7dBm)* X X X X X X
Sensitivity 1µW (-30dBm)* X X X X X X
Optical Budget 7dB (+3dB Res.)* X X X X X X
Wavelength 850nm X X X X X X
Transmission Distance 1500m / 62,5µm X X X X X X
800m / 50µm
* Valid for 62,5µm glass fibre cable
1) Only for 7XV5101-xB (not for 7XV5101-xB /B)
2) Pin 9 may not be allocated
1m
Power Supply
2
1
T R
1 = +5V
2 = Gnd
7XV5101-0A
7XV5101-3A
7SA500 1)
7SA501 1)
7SJ511
7SJ512
Elbow plug 7XV5101-8A
7SD502
angled to long edge
7SD503
of the front connector
7SV51
7VK51
7XV5101-0A