0% found this document useful (0 votes)
229 views4 pages

Condensate Calculator

This document contains an HVAC condensate calculator. It provides input conditions such as average daily temperature and humidity, and calculates output conditions including specific humidity and condensate generation rates. The calculator determines that a 1-ton HVAC system operating at 10% outside air would generate approximately 2.4 gallons of condensate per day.

Uploaded by

Anish Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
229 views4 pages

Condensate Calculator

This document contains an HVAC condensate calculator. It provides input conditions such as average daily temperature and humidity, and calculates output conditions including specific humidity and condensate generation rates. The calculator determines that a 1-ton HVAC system operating at 10% outside air would generate approximately 2.4 gallons of condensate per day.

Uploaded by

Anish Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

HVAC CONDENSATE CALCULATOR

Input Conditions Output Conditions

Avg DailyTemp 96.8 Temp 73.4


Avg Daily % RH 61.3 % RH 60

SH in gr/ft3 11.02 SH in gr/ft3 5.46

Difference in Specific Humidity gr/ft3 5.56

Percentage of Outside Air 10%

Tonnage of System 1
Note: Assumption is 350 ft per minute per ton
3

Gallons per Minute 0.00

Gallons per Hour 0.10

Gallons per Day 2.4


Temperature Grains
30 1.9

grains per ft3


40 2.9 25.0
50 4.1
60 5.7
70 8.0
80 10.9 20.0
90 14.7 f(x) = 0.0032916667x^2
100 19.7

Source: Jackson State University


15.0

10.0

5.0

0.0
20 30 40 50 60
Temp (
0.0032916667x^2 - 0.1823214286x + 4.7029761905

0 50 60 70 80 90 100 110
Temp (deg Fo)

You might also like