Electrical System Design of A 185 Square Meter Single-Dwelling Unit

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 20

TECHNOLOGICAL INSTITUTE OF THE PHILIPPINES

938 Aurora Blvd., Cubao, Quezon City


COLLEGE OF ENGINEERING AND ARCHITECTURE

Title Page

ELECTRONICS ENGINEERING DEPARTMENT

EE 503 – Electrical System Design

“ELECTRICAL SYSTEM DESIGN OF


A 185 SQUARE METER SINGLE-
DWELLING UNIT”

Submitted By:

Torres, Mark Christian G.


EE51FC1

Submitted To:

Engr. William B. Laboguin


Instructor

August 26, 2017


TABLE OF CONTENTS

Title Page................................................................................................................................... 1

Table Of Contents ..................................................................................................................... 2

Design Criteria .......................................................................................................................... 3

Optional Calculation ................................................................................................................. 5

Attachments .............................................................................................................................. 8

Assigned Floor Plan Layout .................................................................................................... 9

Conductor Ampacity Table ................................................................................................... 11

Conduit Table ....................................................................................................................... 12

Other Tables Used In The Calculation & Design .................................................................. 15

Electrical Plan Layout ............................................................................................................ 20

2|Page
DESIGN CRITERIA

3|Page
4|Page
OPTIONAL
CALCULATION

5|Page
ELECTRICAL SYSTEM DESIGN LOAD SCHEDULE (Optional Calculation)

The dwelling has a floor area of 185 square meters. It has typical household appliances
including two electrical ranges (4kW and 5kW), one 2-Hp, two 1-Hp air conditioning units, one
1-Hp water pump and one water heater (3.5kW).

Air Conditioning Loads:


Two 2-Hp master bedroom air-conditioning unit
12A x 230V x 2 = 5520 VA
Two 1-Hp room air-conditioning unit
8A x 230V x 2 = 3680 VA
Subtotal Load 9200 VA
Other Loads:
Lighting and Convenience Receptacle Load:
185 sq. m x 24 volt-amperes per sq. m = 4440 VA
Three units of small appliances load
1500 VA x 3 = 4500 VA
One unit of laundry
1500 VA x 1 = 1500 VA
One 5.5-kW electrical range
5500 VA x 1 = 5500 VA
One 5-kW Clothes Dryer
5000 VA x 1 = 5000 VA
One 1.5-Hp Booster Pump
10 A x 230 x 1 = 2300 VA
One 4-kW oven
4000 VA x 1 = 4000 VA
One 3.5-kW water heater
3500 VA x 1 = 3500 VA
Total net computed 30740 VA

Application of Demand Factor:


First 10000 VA @100% demand factor
10000 VA x 1.0 D.F = 10000 VA

Remaining load @40% demand factor


30740 VA – 10000 VA = 20740 VA
20740 VA x 0.40 D.F = 8296 VA
Subtotal D.F 18296 VA
Total loads:
Air Conditioning Loads = 9200 VA
Other Loads = 18296 VA
6|Page
Total net computed 27496 VA
Circuit Requirement:
Use ten 15-ampere 2-wire branch circuits and one 20-ampere 2-wire branch circuit.
Service entrance conductor:
Total full load current
27496 VA / 230 V = 120 Amperes
Use 2-38 sq. mm THHN wire and use 14 sq. mm equipment grounding.
Service equipment:
Inverse time circuit breaker
[(27496 VA) + (2760 VA x 1.5)] / 230 V = 138 Amperes
Use one 150-ampere trip, Single-phase MCCB circuit breaker

7|Page
ATTACHMENTS

8|Page
ASSIGNED FLOOR
PLAN LAYOUT

9|Page
10 | P a g e
CONDUCTOR
AMPACITY TABLE

11 | P a g e
12 | P a g e
CONDUIT TABLE

13 | P a g e
14 | P a g e
OTHER TABLES
USED IN THE
CALCULATION &
DESIGN

15 | P a g e
16 | P a g e
17 | P a g e
18 | P a g e
19 | P a g e
ELECTRICAL PLAN
LAYOUT

20 | P a g e