Clean Room
Clean Room
Clean Room
NOTES
Areas: Clean room and air lock. However panels are to be provided for the Kitchen as also walkable ceiling
1
for the kitchen shall also form part of the scope of works.
Scope of work includes clean room panels, return air riser panels, all accessories like trims, flashings, covings,
2 sealnts at all horizontal and vertical juntions and openings. Scope of work also includes all fenestrations, light
fittings, HVAC work, walkable false ceiling incl provision for making trap doors, dummy single skin sheets
3 from
CLASS false ceiling level
= CLASS 10000to bottom of true ceiling etc.
4 Rate to include supply, installation and 3rd party VALIDATION
5 Rate to include all taxes
Please note that the quantites mentioned are indicative. The contractors are expected to visit the site and
6 study the drawings and make their own computation of the quantites.
Rate Amount
S. no. Item Description Qnty. Unit
( Rs. ) ( Rs. )
1 CLEAN ROOM PANELS
Sandwich wall panel - Providing and fixing in place
sandwich type panel of minimum thickness 60mm,
wiith PUF insulation for clean room along with panel
sheet thickness 0.5 mm precoated. Rate to include
finishing all ends properly with reqd. trims, beadings, 28.00 sqm.
sealant, PVC covings; making openings for windows,
doors as reqd., making provision reqd. for clean room
false ceiling fixing etc. Rate to include sealing all joints
with other surfaces using covings, sealants as reqd.
3 DOOR - CASE 1
4 DOOR - CASE 2
Supplying and fixing door in sandwich panel. Case 2
clean room on both sides of panel.Specifications
same as mentioned above except that the door frame to
be equal in width to the wall thickness as the case may
be so that no wall jamb is visible.
5 WINDOW - CASE 1
Supplying and fixing Clean room windows in sandwich
panel. Case 1 clean room on 1 side of the panel.
Providing and fixing in place double glazed assembly
in sandwich panel . Fixed glazing to have 6mm glass
on either sides flushed with the panel edges so that the
air gap in center is equal to the panel thickness ; air gap
to be provided with suitable dessicant. Window frame
to be equal in width to the panel jamb to allow for a
future clean room on the other side. All joints etc. to be
fully sealed between window frame / wall / sandwich
panel as per clean room standards.
1500(W)x1200(H) double fixed glass 2.00 no.
6 WINDOW - CASE 2
Supplying and fixing double glazing in sandwich panel.
Case 2 clean room on both sides of the panel. QRO sqm
Specifications same as above.
11 VALIDATION
Validation - Validation of clean room from 3rd party
agency. The credentials and background of the thrid
party validating agency to be submitted to the
architects for approval prior to their engagement. Rate L.S
to include submission of forms etc., follow up ,
submitting a time line to client for completion of
process of validation etc. all complete. 100,000.00